{{Adams
#REDIRECT [[IR 05000509/2006021]]
| number = ML20132D680
| issue date = 07/09/1985
| title = Notice of Violation from Insp on 850509-0621
| author name = Little W
| author affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
| addressee name =
| addressee affiliation =
| docket = 05000456, 05000457
| license number =
| contact person =
| document report number = 50-456-85-23, 50-457-85-24, NUDOCS 8508010333
| package number = ML20132D670
| document type = NOTICE OF VIOLATION OF A REGULATION, TEXT-INSPECTION & AUDIT & I&E CIRCULARS
| page count = 1
}}
See also: [[see also::IR 05000509/2006021]]
 
=Text=
{{#Wiki_filter:-
    ,      o
i
                                            Appendix
                                      NOTICE OF VIOLATION
      Comonwealth Edison Company                                      Docket No. 50-456
                                                                      Docket No. 50-457
      As a result of the inspection conducted on May 9 through June 21, 1985, and in
      accordance with the General Policy and Procedures for NRC Enforcement Actions
      (10 CFR Part 2, Appendix C), the following violation was identified:
            10 CFR 50, Appendix B, Criterion XIII, states in part, that measures shall
            be established to control the storage and preservation of material and
            equipment to prevent damage or deterioration. The Commonwealth Edison
            Company Quality Assurance Program contains in Quality Requirement (QR)
            2.0 a commitment to Regulatory Guide 1.39, Revision 2.
            Regulatory Guide 1.39, Revision 2, endorses the requirements of ANSI
            N45.2.3-1973, " Housekeeping During the Construction Phase of Nuclear
            Power Plants". ANSI N45.2.3, Section 3.2.1, requires that scrap and
            excess materials shall be collected and disposed of in accordance with
            specified requirements. Such excess material shall not be allowed to
            accumulate and create conditions that will adversely affect quality.
            Contrary to the above:
            a.  Nails, washers, bolts, screws, wire, metal brackets and a grinding
                  wheel were found in cable trays which had installed cable,
            b.  The upper cable spreading room was noted as having debris in cable
                  trays and empty aerosol cans which had contained a highly flammable
                  liquid.
            c.  High strength bolting material, (A490 and A325 galvanized bolts,
                  which cannot be reused per the AISC Code) were found laying in
                  various work areas of the plant, not controlled or stored in a
                  material staging area.
            This is a Severity Level IV Violation (Supplement II).
      Pursuant to the provisions of 10 CFR 2.201, you are required to submit to this
      office within thirty days of the date of this Notice a written statement or
      explanation in reply, including for each item of noncompliance: (1) corrective
      action taken and the results achieved; (2) corrective action to be taken to
      avoid further noncompliance; and (3) the date when full compliance will be
      achieved. Consideration may be given to extending your response time for good
      cause shown.
        1kbr
      Datef~
                                                            ffMA
                                                            W. 5. Little( Director "
                                                            Braidwood Project
                                                                                -
                8508010333 850711
                PDR    ADOCK 05000456