Line 6: | Line 6: | ||
| number = ML19246A778 | | number = ML19246A778 | ||
| issue date = 07/02/1979 | | issue date = 07/02/1979 | ||
| title = | | title = LER 79-040/03X-1 on 790326:discovered Nonconservative Output of Upper/Lower Flux Signal Summing Amplifier in Overpower Delta T Protection Circuitry.Caused by Instrument Drift.Summing Amplifier Card Replaced & Delta T Recalibr | ||
| author name = Cartwright W | | author name = Cartwright W | ||
| author affiliation = VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.) | | author affiliation = VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.) | ||
Line 21: | Line 21: | ||
| number = ML19246A777 | | number = ML19246A777 | ||
| issue date = 07/02/1979 | | issue date = 07/02/1979 | ||
| title = | | title = LER 79-030/03X-1 on 790308:nonconservative Gain Setting on delta-flux Signal Feeding Overpower Delta T Protection Circuitry Observed.Caused by Improper Setting of delta-flux Gain.Signal Recalibr | ||
| author name = Cartwright W | | author name = Cartwright W | ||
| author affiliation = VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.) | | author affiliation = VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.) | ||
Line 36: | Line 36: | ||
| number = ML19246A776 | | number = ML19246A776 | ||
| issue date = 07/02/1979 | | issue date = 07/02/1979 | ||
| title = | | title = LER 78-090/03X-1 on 780919:during Critical Steady State Operation,Axial Flux Difference Deviated More than -5% from Target.Caused by Rapid Load Reduction Necessitated by Clogging Strainer.Pumps Shifted | ||
| author name = Cartwright W | | author name = Cartwright W | ||
| author affiliation = VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.) | | author affiliation = VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.) |
Latest revision as of 22:37, 23 January 2020
Date released: 09/17/2019 | Download: ML19246A775 |
---|---|
ML19246A778 | |
Person / Time | |
---|---|
Site: | North Anna |
Issue date: | 07/02/1979 |
From: | Cartwright W VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.) |
To: | NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
References | |
Download: ML19246A778 (2) | |
ML19246A777 | |
Person / Time | |
---|---|
Site: | North Anna |
Issue date: | 07/02/1979 |
From: | Cartwright W VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.) |
To: | NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
References | |
Download: ML19246A777 (2) | |
ML19246A776 | |
Person / Time | |
---|---|
Site: | North Anna |
Issue date: | 07/02/1979 |
From: | Cartwright W VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.) |
To: | NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
References | |
Download: ML19246A776 (3) | |
ML19246A774 | |
Person / Time | |
---|---|
Site: | North Anna |
Issue date: | 07/02/1979 |
From: | Stallings C VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.) |
To: | OREILLY J P NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
References | |
Download: ML19246A774 (1) | |