ML18115A228: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
 
(Created page by program invented by StriderTol)
 
Line 15: Line 15:


=Text=
=Text=
{{#Wiki_filter:DRAFT - UNCERTIFIED INFORMATIONDRAFT UNCERTIFIED INFORMATION 1 of 5QuestionRAI B.1.43-2 (Closed Treated Water Systems)BackgroundFor the "detection of aging effects" program element, Section 4.13 of RBS-EP-15-00007 states that the WaterChemistry - Closed Treated Water Systems program manages the effects of aging in an environment oftreated water. For the vacuum release accumulators in LRA Table 3.3.2-3 (TK1A and TK1B on drawing PID-09-10F), the internal environment is listed as treated water with the aging management program listed asWater Chemistry Control - Closed Treated Water Systems.IssueBased on the information shown on drawing PID-09-10F, "System 118 Service Water Normal," theaccumulators and portions of the associated piping do not appear to have an internal environment of treatedwater because these components are supplied by the compressed air system. It is not clear to the staffwhether these components have a treated water internal environment and whether the aging affects for thesecomponents will be managed by the Water Chemistry Control - Closed Treated Water Systems program aslisted in LRA Table 3.3.2-3.In addition, based on information in Standby Service Water Quarterly Valve Operability Test procedures (STP-256-6305 and STP-256-6306 for valves SOV-522A, B, C, D and SOV-523A, B, C, D), air is periodicallyintroduced into portions of the piping as part of the vacuum release solenoid valve function verification. Basedon the piping configurations in various isometric drawings, it appears that air cannot be vented in someportions of the associated piping, between the check valves and the treated water source. Consequently,there will be an air water interface in a portion of the pipe, with the air being periodically replenished, similar tothe situation in NRC Information Notice 2013 06, "Corrosion in Fire Protection Piping Due to Air and WaterInteraction.It is not clear to the staff that the Water Chemistry Control - Closed Treated Water Systemsprogram activities account for this situation.Request 1.Clarify the information provided in LRA Table 3.3.2-3 (TK1A and TK1B on drawing PID-09-10F), withregard to the internal environment of the vacuum release accumulators and portions of the associatedpiping, and whether aging effects of these components will be managed by the Water ChemistryControl - Closed Treated Water Systems program.
{{#Wiki_filter:DRAFT - UNCERTIFIED INFORMATION Question RAI B.1.43-2 (Closed Treated Water Systems)
2.Provide additional information to show that the activities in the Water Chemistry Control - ClosedTreated Water Systems adequately account for the potential air-water interface in the portions of thepiping that cannot be vented between the check valves and the treated water source (associated withSOV-522A, B, C, D, and SOV 523A, B, C, D).ResponseA previous response to RAI B.1.43-2 was submitted in letter RBG-47834, dated March 8, 2018.The following response is the same as the response in letter RBG-47834 except additionalinformation has been provided regarding the internal environments associated with the auxiliarybuilding vacuum release piping and valves. In addition, a change is made to LRA Table 3.3.2-18-11. The following response supersedes the previous response submitted in letter RBG-DRAFT - UNCERTIFIED INFORMATIONDRAFT UNCERTIFIED INFORMATION 2 of 547834.1.LRA Table 3.3.2-3 vacuum release accumulators (TK1A and TK1B on drawing PID-09-10F) containinstrument air. The LRA is revised to identify that the Compressed Air Monitoring Program managesthe aging effects for the internal surfaces of the vacuum release accumulators and associated piping.
 
2.Normally closed SOV-522A, B, C, and D are located downstream of the two instrument airaccumulators. If necessary, the service water system in the containment relies on this instrument air torelease a vacuum in the system piping.Normally closed SOV-523A, B, C, and D are not associated with accumulators containing instrumentair. If necessary to release system vacuum, the valves open to admit air from the auxiliary building intothe service water system.The RAI Issue discussion refers to NRC Information Notice 2013-06, "Corrosion in Fire ProtectionPiping Due to Air and Water Interaction". This information notice discusses fire water systems whichmay contain highly oxygenated, raw, untreated water. The RBS service water system containsdemineralized water treated with sodium nitrite and molybdate as corrosion inhibitors. Because of thispiping internal environment, significant corrosion is not expected.To confirm the insignificance of corrosion in the subject piping, inspections will verify that unacceptabledegradation is not occurring. For the portions of the containment piping that cannot be vented betweenthe check valves and the treated water source, the One-Time Inspection Program will perform avolumetric inspection of a piping segment associated with SOV-522A, B, C, or D.The auxiliary building piping between the solenoid valves (SOV-523A, B, C, and D) and the rest of theservice water system is exposed to treated water internally. A vacuum would only be created in theservice water piping under emergency conditions and air would not be drawn into the auxiliary buildingpiping during valve stroke testing. Unlike with the similar containment building piping, there are no airaccumulators supplying the auxiliary building piping. Thus, there is no motive force for air to enter theauxiliary building service water piping during valve stroke testing. Nevertheless, for conservatism, theauxiliary building piping is included in the Table 3.3.2-3 line item, below, for carbon steel pipingexposed to treated water and the One-Time Inspection Program will perform a volumetric inspection ofa piping segment associated with SOV-523A, B, C, or D.Normally closed SOV-523A, B, C, and D have stainless steel valve bodies. Since portions of thestainless steel valve bodies exposed to an air-indoor internal environment are not susceptible to agingeffects, the LRA Table 3.3.2-3 line item for stainless steel valve body exposed to a treated waterinternal environment is sufficient to address aging effects for the valves.The carbon steel piping out-board of valves SOV-523A, B, C, and D is highlighted in yellow on LRAdrawing PID-09-10F, which indicates it is evaluated in LRA Section 2.3.3.18, "Auxiliary Systems in DRAFT - UNCERTIFIED INFORMATIONDRAFT UNCERTIFIED INFORMATION 3 of 5Scope for 10 CFR 54.4(a)(2).A line item is added to Table 3.3.2-18-11, "Service Water - StandbySystem, Nonsafety-Related Components Affecting Safety-Related Systems," to provide agingmanagement review results for this piping.The changes to LRA Table 3.3.2-3 and the associated notes, Table 3.3.2-18-11, Table 3.3.1, Section A.1.32,and B.1.32 follow with additions underlined.
===Background===
Table 3.3.2
For the detection of aging effects program element, Section 4.13 of RBS-EP-15-00007 states that the Water Chemistry - Closed Treated Water Systems program manages the effects of aging in an environment of treated water. For the vacuum release accumulators in LRA Table 3.3.2-3 (TK1A and TK1B on drawing PID-09-10F), the internal environment is listed as treated water with the aging management program listed as Water Chemistry Control - Closed Treated Water Systems.
-3: ServiceWater SystemComponentTypeIntendedFunction MaterialEnviron-mentAgingEffectRequiringManagementAgingManagementPrograms NUREG-1801ItemTable1 ItemNot esAccumulatorPressure boundary CarbonsteelCondensation (int)Loss of materialCompressedAir MonitoringVII.D.A-263.3.1-55 BPipingPressure boundary CarbonsteelCondens-ation (int)Loss of materialCompressedAir MonitoringVII.D.A-263.3.1-55 BPipingPressure boundary CarbonsteelTreatedwater (int)Loss of materialOne-TimeInspectionVII.C2.AP-2023.3.1-45 A, 309Notes for Tables 3.3.2-1 through 3.3.2-18-26Plant-Specific Notes309. The One-Time Inspection Program will confirm the insignificance of corrosion for service water systemcontainment and auxiliary building vacuum release piping that may have an air/water interface. The One-TimeInspection Program will use NDE techniques to inspect this piping for loss of material.Table 3.3.2-18-11:   Service Water - Standby System, Nonsafety-Related Components Affecting Safety-RelatedSystemsComponentTypeIntendedFunction MaterialEnvironmentAging EffectRequiringManagementAgingManagementProgramNUREG-1801 ItemTable 1ItemNotesPipingPressure boundary CarbonsteelAir -indoor (int)Loss of materialExternalSurfacesMonitoring V.D2.E-293.2.1-44 E DRAFT - UNCERTIFIED INFORMATIONDRAFT UNCERTIFIED INFORMATION 4 of 5Table 3.3.1: Auxiliary SystemsItemNumberComponentAging Effect/MechanismAgingManagementProgramsFurtherEvaluationRecommendedDiscussion3.3.1-45Steel piping,pipingcomponents,and pipingelements;tanksexposed toclosed-cyclecooling waterLoss of materialdue to general,pitting, and crevicecorrosionChapter XI.M21A,"Closed TreatedWater Systems" NoConsistent with NUREG-1801. Loss of materialfor steel componentsexposed to closed-cyclecooling water ismanaged by the WaterChemistry Control -Closed Treated WaterSystems Program.The One-TimeInspection Program willconfirm theinsignificance ofcorrosion for servicewater systemcontainment andauxiliary buildingvacuum release pipingthat may have anair/water interface. TheOne-Time InspectionProgram will use NDEtechniques to inspectthis piping for loss ofmaterial.
Issue Based on the information shown on drawing PID-09-10F, System 118 Service Water Normal, the accumulators and portions of the associated piping do not appear to have an internal environment of treated water because these components are supplied by the compressed air system. It is not clear to the staff whether these components have a treated water internal environment and whether the aging affects for these components will be managed by the Water Chemistry Control - Closed Treated Water Systems program as listed in LRA Table 3.3.2-3.
DRAFT - UNCERTIFIED INFORMATIONDRAFT UNCERTIFIED INFORMATION 5 of 5A.1.32 One-Time InspectionThe program will include activities to verify effectiveness of aging management programs and activities toconfirm the insignificance of aging effects as described below.A representative sample of service watersystem containment and auxiliary buildingvacuum release piping that cannot bevented between the check valves and thetreated water source.One-time inspection will confirm that loss ofmaterial is not occurring or is occurring so slowlythat the aging effect will not affect the componentintended function during the period of extendedoperation.Inspections will be performed within the 10 years prior to the period of extended operation.B.1.32 ONE-TIME INSPECTIONThe program will include activities to verify effectiveness of aging management programs and activities toconfirm the insignificance of aging effects as described below.A representative sample of service watersystem containment and auxiliary buildingvacuum release piping that cannot bevented between the check valves and thetreated water source.One-time inspection will confirm that loss ofmaterial is not occurring or is occurring so slowlythat the aging effect will not affect the componentintended function during the period of extendedoperation.Inspections will be performed within the 10 years prior to the period of extended operation.}}
In addition, based on information in Standby Service Water Quarterly Valve Operability Test procedures (STP-256-6305 and STP-256-6306 for valves SOV-522A, B, C, D and SOV-523A, B, C, D), air is periodically introduced into portions of the piping as part of the vacuum release solenoid valve function verification. Based on the piping configurations in various isometric drawings, it appears that air cannot be vented in some portions of the associated piping, between the check valves and the treated water source. Consequently, there will be an air water interface in a portion of the pipe, with the air being periodically replenished, similar to the situation in NRC Information Notice 2013 06, Corrosion in Fire Protection Piping Due to Air and Water Interaction. It is not clear to the staff that the Water Chemistry Control - Closed Treated Water Systems program activities account for this situation.
Request
: 1.       Clarify the information provided in LRA Table 3.3.2-3 (TK1A and TK1B on drawing PID-09-10F), with regard to the internal environment of the vacuum release accumulators and portions of the associated piping, and whether aging effects of these components will be managed by the Water Chemistry Control - Closed Treated Water Systems program.
: 2.       Provide additional information to show that the activities in the Water Chemistry Control - Closed Treated Water Systems adequately account for the potential air-water interface in the portions of the piping that cannot be vented between the check valves and the treated water source (associated with SOV-522A, B, C, D, and SOV 523A, B, C, D).
 
===Response===
A previous response to RAI B.1.43-2 was submitted in letter RBG-47834, dated March 8, 2018.
The following response is the same as the response in letter RBG-47834 except additional information has been provided regarding the internal environments associated with the auxiliary building vacuum release piping and valves. In addition, a change is made to LRA Table 3.3.2-18-11. The following response supersedes the previous response submitted in letter RBG-DRAFT UNCERTIFIED INFORMATION 1 of 5
 
DRAFT - UNCERTIFIED INFORMATION 47834.
: 1. LRA Table 3.3.2-3 vacuum release accumulators (TK1A and TK1B on drawing PID-09-10F) contain instrument air. The LRA is revised to identify that the Compressed Air Monitoring Program manages the aging effects for the internal surfaces of the vacuum release accumulators and associated piping.
: 2. Normally closed SOV-522A, B, C, and D are located downstream of the two instrument air accumulators. If necessary, the service water system in the containment relies on this instrument air to release a vacuum in the system piping.
Normally closed SOV-523A, B, C, and D are not associated with accumulators containing instrument air. If necessary to release system vacuum, the valves open to admit air from the auxiliary building into the service water system.
The RAI Issue discussion refers to NRC Information Notice 2013-06, Corrosion in Fire Protection Piping Due to Air and Water Interaction. This information notice discusses fire water systems which may contain highly oxygenated, raw, untreated water. The RBS service water system contains demineralized water treated with sodium nitrite and molybdate as corrosion inhibitors. Because of this piping internal environment, significant corrosion is not expected.
To confirm the insignificance of corrosion in the subject piping, inspections will verify that unacceptable degradation is not occurring. For the portions of the containment piping that cannot be vented between the check valves and the treated water source, the One-Time Inspection Program will perform a volumetric inspection of a piping segment associated with SOV-522A, B, C, or D.
The auxiliary building piping between the solenoid valves (SOV-523A, B, C, and D) and the rest of the service water system is exposed to treated water internally. A vacuum would only be created in the service water piping under emergency conditions and air would not be drawn into the auxiliary building piping during valve stroke testing. Unlike with the similar containment building piping, there are no air accumulators supplying the auxiliary building piping. Thus, there is no motive force for air to enter the auxiliary building service water piping during valve stroke testing. Nevertheless, for conservatism, the auxiliary building piping is included in the Table 3.3.2-3 line item, below, for carbon steel piping exposed to treated water and the One-Time Inspection Program will perform a volumetric inspection of a piping segment associated with SOV-523A, B, C, or D.
Normally closed SOV-523A, B, C, and D have stainless steel valve bodies. Since portions of the stainless steel valve bodies exposed to an air-indoor internal environment are not susceptible to aging effects, the LRA Table 3.3.2-3 line item for stainless steel valve body exposed to a treated water internal environment is sufficient to address aging effects for the valves.
The carbon steel piping out-board of valves SOV-523A, B, C, and D is highlighted in yellow on LRA drawing PID-09-10F, which indicates it is evaluated in LRA Section 2.3.3.18, Auxiliary Systems in DRAFT UNCERTIFIED INFORMATION 2 of 5
 
DRAFT - UNCERTIFIED INFORMATION Scope for 10 CFR 54.4(a)(2). A line item is added to Table 3.3.2-18-11, Service Water - Standby System, Nonsafety-Related Components Affecting Safety-Related Systems, to provide aging management review results for this piping.
The changes to LRA Table 3.3.2-3 and the associated notes, Table 3.3.2-18-11, Table 3.3.1, Section A.1.32, and B.1.32 follow with additions underlined.
Table 3.3.2-3: Service Water System Aging Effect        Aging        NUREG-Component      Intended                Environ-       Requiring      Management        1801    Table  Not Type      Function    Material      ment      Management        Programs        Item    1 Item  es Accumulator    Pressure    Carbon      Condens      Loss of material Compressed      VII.D.A-26 3.3.1-55 B boundary   steel      ation (int)                   Air Monitoring Piping          Pressure    Carbon      Condens- Loss of material Compressed          VII.D.A-26 3.3.1-55 B boundary   steel      ation (int)                   Air Monitoring Piping          Pressure    Carbon      Treated      Loss of material One-Time        VII.C2.AP- 3.3.1-45 A, boundary    steel      water                        Inspection      202                309 (int)
Notes for Tables 3.3.2-1 through 3.3.2-18-26 Plant-Specific Notes 309. The One-Time Inspection Program will confirm the insignificance of corrosion for service water system containment and auxiliary building vacuum release piping that may have an air/water interface. The One-Time Inspection Program will use NDE techniques to inspect this piping for loss of material.
Table 3.3.2-18-11: Service Water - Standby System, Nonsafety-Related Components Affecting Safety-Related Systems Aging Effect        Aging Component      Intended              Environ        Requiring      Management      NUREG-     Table 1 Type        Function  Material      ment        Management        Program      1801 Item    Item    Notes Piping            Pressure  Carbon    Air -         Loss of material External        V.D2.E-29  3.2.1-44 E boundary  steel      indoor                        Surfaces (int)                          Monitoring DRAFT UNCERTIFIED INFORMATION 3 of 5
 
DRAFT - UNCERTIFIED INFORMATION Table 3.3.1: Auxiliary Systems Aging          Further Item                        Aging Effect/       Management      Evaluation Number      Component          Mechanism          Programs      Recommended        Discussion 3.3.1-45    Steel piping, Loss of material    Chapter XI.M21A, No            Consistent with NUREG-piping        due to general,      "Closed Treated                1801. Loss of material components,    pitting, and crevice Water Systems"                for steel components and piping    corrosion                                          exposed to closed-cycle elements;                                                          cooling water is tanks                                                              managed by the Water exposed to                                                        Chemistry Control -
closed-cycle                                                      Closed Treated Water cooling water                                                      Systems Program.
The One-Time Inspection Program will confirm the insignificance of corrosion for service water system containment and auxiliary building vacuum release piping that may have an air/water interface. The One-Time Inspection Program will use NDE techniques to inspect this piping for loss of material.
DRAFT UNCERTIFIED INFORMATION 4 of 5
 
DRAFT - UNCERTIFIED INFORMATION A.1.32 One-Time Inspection The program will include activities to verify effectiveness of aging management programs and activities to confirm the insignificance of aging effects as described below.
A representative sample of service water        One-time inspection will confirm that loss of system containment and auxiliary building        material is not occurring or is occurring so slowly vacuum release piping that cannot be            that the aging effect will not affect the component vented between the check valves and the          intended function during the period of extended treated water source.                           operation.
Inspections will be performed within the 10 years prior to the period of extended operation.
B.1.32 ONE-TIME INSPECTION The program will include activities to verify effectiveness of aging management programs and activities to confirm the insignificance of aging effects as described below.
A representative sample of service water        One-time inspection will confirm that loss of system containment and auxiliary building        material is not occurring or is occurring so slowly vacuum release piping that cannot be            that the aging effect will not affect the component vented between the check valves and the          intended function during the period of extended treated water source.                            operation.
Inspections will be performed within the 10 years prior to the period of extended operation.
DRAFT UNCERTIFIED INFORMATION 5 of 5}}

Latest revision as of 07:43, 21 October 2019

Draft Response on RBS LRA RAI B.1.43-2 Closed Treated Water Systems
ML18115A228
Person / Time
Issue date: 04/25/2018
From: Wong A
NRC/NRR/DMLR/MRPB
To:
Wong A, NRR-DMLR 415-3081
References
Download: ML18115A228 (5)


Text

DRAFT - UNCERTIFIED INFORMATION Question RAI B.1.43-2 (Closed Treated Water Systems)

Background

For the detection of aging effects program element, Section 4.13 of RBS-EP-15-00007 states that the Water Chemistry - Closed Treated Water Systems program manages the effects of aging in an environment of treated water. For the vacuum release accumulators in LRA Table 3.3.2-3 (TK1A and TK1B on drawing PID-09-10F), the internal environment is listed as treated water with the aging management program listed as Water Chemistry Control - Closed Treated Water Systems.

Issue Based on the information shown on drawing PID-09-10F, System 118 Service Water Normal, the accumulators and portions of the associated piping do not appear to have an internal environment of treated water because these components are supplied by the compressed air system. It is not clear to the staff whether these components have a treated water internal environment and whether the aging affects for these components will be managed by the Water Chemistry Control - Closed Treated Water Systems program as listed in LRA Table 3.3.2-3.

In addition, based on information in Standby Service Water Quarterly Valve Operability Test procedures (STP-256-6305 and STP-256-6306 for valves SOV-522A, B, C, D and SOV-523A, B, C, D), air is periodically introduced into portions of the piping as part of the vacuum release solenoid valve function verification. Based on the piping configurations in various isometric drawings, it appears that air cannot be vented in some portions of the associated piping, between the check valves and the treated water source. Consequently, there will be an air water interface in a portion of the pipe, with the air being periodically replenished, similar to the situation in NRC Information Notice 2013 06, Corrosion in Fire Protection Piping Due to Air and Water Interaction. It is not clear to the staff that the Water Chemistry Control - Closed Treated Water Systems program activities account for this situation.

Request

1. Clarify the information provided in LRA Table 3.3.2-3 (TK1A and TK1B on drawing PID-09-10F), with regard to the internal environment of the vacuum release accumulators and portions of the associated piping, and whether aging effects of these components will be managed by the Water Chemistry Control - Closed Treated Water Systems program.
2. Provide additional information to show that the activities in the Water Chemistry Control - Closed Treated Water Systems adequately account for the potential air-water interface in the portions of the piping that cannot be vented between the check valves and the treated water source (associated with SOV-522A, B, C, D, and SOV 523A, B, C, D).

Response

A previous response to RAI B.1.43-2 was submitted in letter RBG-47834, dated March 8, 2018.

The following response is the same as the response in letter RBG-47834 except additional information has been provided regarding the internal environments associated with the auxiliary building vacuum release piping and valves. In addition, a change is made to LRA Table 3.3.2-18-11. The following response supersedes the previous response submitted in letter RBG-DRAFT UNCERTIFIED INFORMATION 1 of 5

DRAFT - UNCERTIFIED INFORMATION 47834.

1. LRA Table 3.3.2-3 vacuum release accumulators (TK1A and TK1B on drawing PID-09-10F) contain instrument air. The LRA is revised to identify that the Compressed Air Monitoring Program manages the aging effects for the internal surfaces of the vacuum release accumulators and associated piping.
2. Normally closed SOV-522A, B, C, and D are located downstream of the two instrument air accumulators. If necessary, the service water system in the containment relies on this instrument air to release a vacuum in the system piping.

Normally closed SOV-523A, B, C, and D are not associated with accumulators containing instrument air. If necessary to release system vacuum, the valves open to admit air from the auxiliary building into the service water system.

The RAI Issue discussion refers to NRC Information Notice 2013-06, Corrosion in Fire Protection Piping Due to Air and Water Interaction. This information notice discusses fire water systems which may contain highly oxygenated, raw, untreated water. The RBS service water system contains demineralized water treated with sodium nitrite and molybdate as corrosion inhibitors. Because of this piping internal environment, significant corrosion is not expected.

To confirm the insignificance of corrosion in the subject piping, inspections will verify that unacceptable degradation is not occurring. For the portions of the containment piping that cannot be vented between the check valves and the treated water source, the One-Time Inspection Program will perform a volumetric inspection of a piping segment associated with SOV-522A, B, C, or D.

The auxiliary building piping between the solenoid valves (SOV-523A, B, C, and D) and the rest of the service water system is exposed to treated water internally. A vacuum would only be created in the service water piping under emergency conditions and air would not be drawn into the auxiliary building piping during valve stroke testing. Unlike with the similar containment building piping, there are no air accumulators supplying the auxiliary building piping. Thus, there is no motive force for air to enter the auxiliary building service water piping during valve stroke testing. Nevertheless, for conservatism, the auxiliary building piping is included in the Table 3.3.2-3 line item, below, for carbon steel piping exposed to treated water and the One-Time Inspection Program will perform a volumetric inspection of a piping segment associated with SOV-523A, B, C, or D.

Normally closed SOV-523A, B, C, and D have stainless steel valve bodies. Since portions of the stainless steel valve bodies exposed to an air-indoor internal environment are not susceptible to aging effects, the LRA Table 3.3.2-3 line item for stainless steel valve body exposed to a treated water internal environment is sufficient to address aging effects for the valves.

The carbon steel piping out-board of valves SOV-523A, B, C, and D is highlighted in yellow on LRA drawing PID-09-10F, which indicates it is evaluated in LRA Section 2.3.3.18, Auxiliary Systems in DRAFT UNCERTIFIED INFORMATION 2 of 5

DRAFT - UNCERTIFIED INFORMATION Scope for 10 CFR 54.4(a)(2). A line item is added to Table 3.3.2-18-11, Service Water - Standby System, Nonsafety-Related Components Affecting Safety-Related Systems, to provide aging management review results for this piping.

The changes to LRA Table 3.3.2-3 and the associated notes, Table 3.3.2-18-11, Table 3.3.1, Section A.1.32, and B.1.32 follow with additions underlined.

Table 3.3.2-3: Service Water System Aging Effect Aging NUREG-Component Intended Environ- Requiring Management 1801 Table Not Type Function Material ment Management Programs Item 1 Item es Accumulator Pressure Carbon Condens Loss of material Compressed VII.D.A-26 3.3.1-55 B boundary steel ation (int) Air Monitoring Piping Pressure Carbon Condens- Loss of material Compressed VII.D.A-26 3.3.1-55 B boundary steel ation (int) Air Monitoring Piping Pressure Carbon Treated Loss of material One-Time VII.C2.AP- 3.3.1-45 A, boundary steel water Inspection 202 309 (int)

Notes for Tables 3.3.2-1 through 3.3.2-18-26 Plant-Specific Notes 309. The One-Time Inspection Program will confirm the insignificance of corrosion for service water system containment and auxiliary building vacuum release piping that may have an air/water interface. The One-Time Inspection Program will use NDE techniques to inspect this piping for loss of material.

Table 3.3.2-18-11: Service Water - Standby System, Nonsafety-Related Components Affecting Safety-Related Systems Aging Effect Aging Component Intended Environ Requiring Management NUREG- Table 1 Type Function Material ment Management Program 1801 Item Item Notes Piping Pressure Carbon Air - Loss of material External V.D2.E-29 3.2.1-44 E boundary steel indoor Surfaces (int) Monitoring DRAFT UNCERTIFIED INFORMATION 3 of 5

DRAFT - UNCERTIFIED INFORMATION Table 3.3.1: Auxiliary Systems Aging Further Item Aging Effect/ Management Evaluation Number Component Mechanism Programs Recommended Discussion 3.3.1-45 Steel piping, Loss of material Chapter XI.M21A, No Consistent with NUREG-piping due to general, "Closed Treated 1801. Loss of material components, pitting, and crevice Water Systems" for steel components and piping corrosion exposed to closed-cycle elements; cooling water is tanks managed by the Water exposed to Chemistry Control -

closed-cycle Closed Treated Water cooling water Systems Program.

The One-Time Inspection Program will confirm the insignificance of corrosion for service water system containment and auxiliary building vacuum release piping that may have an air/water interface. The One-Time Inspection Program will use NDE techniques to inspect this piping for loss of material.

DRAFT UNCERTIFIED INFORMATION 4 of 5

DRAFT - UNCERTIFIED INFORMATION A.1.32 One-Time Inspection The program will include activities to verify effectiveness of aging management programs and activities to confirm the insignificance of aging effects as described below.

A representative sample of service water One-time inspection will confirm that loss of system containment and auxiliary building material is not occurring or is occurring so slowly vacuum release piping that cannot be that the aging effect will not affect the component vented between the check valves and the intended function during the period of extended treated water source. operation.

Inspections will be performed within the 10 years prior to the period of extended operation.

B.1.32 ONE-TIME INSPECTION The program will include activities to verify effectiveness of aging management programs and activities to confirm the insignificance of aging effects as described below.

A representative sample of service water One-time inspection will confirm that loss of system containment and auxiliary building material is not occurring or is occurring so slowly vacuum release piping that cannot be that the aging effect will not affect the component vented between the check valves and the intended function during the period of extended treated water source. operation.

Inspections will be performed within the 10 years prior to the period of extended operation.

DRAFT UNCERTIFIED INFORMATION 5 of 5