SIGNATURE OF PRINCIPAL EXECUTIVE TYPED OR PRINTED OFFICER OR AUTHORIZED AGENT AREA NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)EPA Form 3320-1 PAGE OF PERMIT NUMBER LA0042731 Al No.: 2889 DEQA LOU ISIANA OFFICE OF ENVIRONMENTAL SERVICES Water Discharge Permit Pursuant to the Clean Water Act, as amended (33 U.S.C. 1251 et seM.), and the Louisiana Environmental Quality Act, as amended (La. R. S. 30:2001 et seq.), rules and regulations effective or promulgated under the authority of said Acts, and in reliance on statements and representations heretofore made in the application, a Louisiana Pollutant Discharge Elimination System permit is issued authorizing Entergy Operations, Inc.River Bend Station 5485 U. S. Highway 61 St. Francisville, LA 70775 Type Facility: steam electric generating facility Location: 5485 U. S. Highway 61 in St. Francisville West Feliciana Parish Receiving Waters: Mississippi River (Outfalls 001, 101, 201, 301, 401, 501, 601, 006, 007) and Grant's Bayou (Outfalls 002, 003, 004, 104, 005, 007) (070201)to discharge in accordance with effluent limitations, monitoring requirements, and other conditions set forth in Parts I, II, and III attached hereto.This permit shall become effective on 2 &//This permit and the authorization to discharge shall expire five (5) years from the effective date of the permit.onsued on Sam L. Phillips Assistant Secretary GAL VEZ BUILDING
SIGNATURE OF PRINCIPAL EXECUTIVE TYPED OR PRINTED OFFICER OR AUTHORIZED AGENT AREA NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)EPA Form 3320-1 PAGE OF PERMIT NUMBER LA0042731 Al No.: 2889 DEQA LOU ISIANA OFFICE OF ENVIRONMENTAL SERVICES Water Discharge Permit Pursuant to the Clean Water Act, as amended (33 U.S.C. 1251 et seM.), and the Louisiana Environmental Quality Act, as amended (La. R. S. 30:2001 et seq.), rules and regulations effective or promulgated under the authority of said Acts, and in reliance on statements and representations heretofore made in the application, a Louisiana Pollutant Discharge Elimination System permit is issued authorizing Entergy Operations, Inc.River Bend Station 5485 U. S. Highway 61 St. Francisville, LA 70775 Type Facility: steam electric generating facility Location: 5485 U. S. Highway 61 in St. Francisville West Feliciana Parish Receiving Waters: Mississippi River (Outfalls 001, 101, 201, 301, 401, 501, 601, 006, 007) and Grant's Bayou (Outfalls 002, 003, 004, 104, 005, 007) (070201)to discharge in accordance with effluent limitations, monitoring requirements, and other conditions set forth in Parts I, II, and III attached hereto.This permit shall become effective on 2 &//This permit and the authorization to discharge shall expire five (5) years from the effective date of the permit.onsued on Sam L. Phillips Assistant Secretary GAL VEZ BUILDING
* 602 N. FIFTH STREET P.O. BOX 4313
* 602 N. FIFTH STREET P.O. BOX 4313
* BA TON ROUGE, LA 70821-4313*  
* BA TON ROUGE, LA 70821-4313*
(225) 219-3181 PART I Page 2 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 001, the continuous discharge of cooling tower blowdown, previously monitored effluent from Internal Outfalls 101, 201, 301, 401, 501, and 601, and previously monitored hydrostatic test wastewater from Outfall 007.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)Monitoring Requirements STORET Monthly Code Average Daily Monthly Daily Measurement Maximum Average Maximum Frequency Flow-MGD Temperature (OF) (*1)Free Available Chlorine (*2)Total Chromium Total Zinc pH Minimum/Maximum Values (standard units)WHOLE EFFLUENT (ACUTE)TOXICITY TESTING (*4) (*5)50050 00011 50064 01034 01092 00400 Report 0.63 Report 1.64 105 0.2 0.2 1.0 6.0 (*3)(Min)110 0.5 0.2 1.0 9.0 (*3)(Max)Continuous Continuous 1/week 1/year 1/week 1/week Sample Type Recorder Recorder Grab Grab Grab Grab STORET Code NOEC, Pass/Fail  
(225) 219-3181 PART I Page 2 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 001, the continuous discharge of cooling tower blowdown, previously monitored effluent from Internal Outfalls 101, 201, 301, 401, 501, and 601, and previously monitored hydrostatic test wastewater from Outfall 007.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)Monitoring Requirements STORET Monthly Code Average Daily Monthly Daily Measurement Maximum Average Maximum Frequency Flow-MGD Temperature (OF) (*1)Free Available Chlorine (*2)Total Chromium Total Zinc pH Minimum/Maximum Values (standard units)WHOLE EFFLUENT (ACUTE)TOXICITY TESTING (*4) (*5)50050 00011 50064 01034 01092 00400 Report 0.63 Report 1.64 105 0.2 0.2 1.0 6.0 (*3)(Min)110 0.5 0.2 1.0 9.0 (*3)(Max)Continuous Continuous 1/week 1/year 1/week 1/week Sample Type Recorder Recorder Grab Grab Grab Grab STORET Code NOEC, Pass/Fail
[0/1], TEM6C Lethality, Static Renewal, 48-Hour Acute, Pimephales promelas NOEC, Value [%], TOM6C Lethality, Static Renewal, 48-Hour Acute, Pimephales promelas NOEC, Value [%], TQM6C Coefficient of Variation, Static Renewal, 48-Hour Acute, Pimeohales oromelas (Percent %, UNLESS STATED)Monthly Avg 48-Hour Minimum Minimum Maximum Report Report ---Report Report ---Report Measurement Frequency  
[0/1], TEM6C Lethality, Static Renewal, 48-Hour Acute, Pimephales promelas NOEC, Value [%], TOM6C Lethality, Static Renewal, 48-Hour Acute, Pimephales promelas NOEC, Value [%], TQM6C Coefficient of Variation, Static Renewal, 48-Hour Acute, Pimeohales oromelas (Percent %, UNLESS STATED)Monthly Avg 48-Hour Minimum Minimum Maximum Report Report ---Report Report ---Report Measurement Frequency
(*4)Sample Type 1/year 1/year 1/year 24-hr. Composite 24-hr. Composite 24-hr. Composite PART I EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (Outfall 001 continued)
(*4)Sample Type 1/year 1/year 1/year 24-hr. Composite 24-hr. Composite 24-hr. Composite PART I EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (Outfall 001 continued)
Page 3 of 17 Permit No. LA0042731 AI No. 2889 Monitoring Requirements Measurement Sample Frequency  
Page 3 of 17 Permit No. LA0042731 AI No. 2889 Monitoring Requirements Measurement Sample Frequency
(*4) Type Effluent Characteristic WHOLE EFFLUENT (ACUTE)TOXICITY TESTING Discharge Limitations Other units (Percent %, UNLESS STATED)Monthly Avg 48-Hour Minimum Minimum Maximum STORET Code NOEC, Pass/Fail  
(*4) Type Effluent Characteristic WHOLE EFFLUENT (ACUTE)TOXICITY TESTING Discharge Limitations Other units (Percent %, UNLESS STATED)Monthly Avg 48-Hour Minimum Minimum Maximum STORET Code NOEC, Pass/Fail
[0/1], TEM3D Lethality, Static Renewal, 48-Hour Acute, Daphnia pulex NOEC, Value [%], TOM3D Lethality, Static Renewal, 48-Hour Acute Daohnia pulex NOEC, Value [%], TQM3D Coefficient of Variation, Static Renewal, 48-Hour Acute Daphnia ulex Report Report ---Report Report Report 1/year 1/year 1/year 24-hr. Composite 24-hr. Composite 24-hr. Composite There shall be no discharge of floating solids or visible foam in other than trace amounts, nor of free oil or other oil materials, nor of toxic materials in quantities such as to cause acute toxicity to aquatic organisms.
[0/1], TEM3D Lethality, Static Renewal, 48-Hour Acute, Daphnia pulex NOEC, Value [%], TOM3D Lethality, Static Renewal, 48-Hour Acute Daohnia pulex NOEC, Value [%], TQM3D Coefficient of Variation, Static Renewal, 48-Hour Acute Daphnia ulex Report Report ---Report Report Report 1/year 1/year 1/year 24-hr. Composite 24-hr. Composite 24-hr. Composite There shall be no discharge of floating solids or visible foam in other than trace amounts, nor of free oil or other oil materials, nor of toxic materials in quantities such as to cause acute toxicity to aquatic organisms.
Furthermore, there shall be no visible sheen or stains attributable to this discharge.
Furthermore, there shall be no visible sheen or stains attributable to this discharge.
Line 56: Line 56:
PART I Page 4 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
PART I Page 4 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 101, the intermittent discharge of low level radioactive low volume wastewater from the liquid radwaste wastewater system (LWS) which includes equipment and building floor drain sumps, equipment washing, personnel decontamination, laboratory drains, filter press effluent, RO unit wastewater, other low volume wastewater sources as defined in 40 CFR 423 and maintenance wastewaters.
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 101, the intermittent discharge of low level radioactive low volume wastewater from the liquid radwaste wastewater system (LWS) which includes equipment and building floor drain sumps, equipment washing, personnel decontamination, laboratory drains, filter press effluent, RO unit wastewater, other low volume wastewater sources as defined in 40 CFR 423 and maintenance wastewaters.
During maintenance activities, Internal Outfall 101 may be discharged via the cooling tower flume rather than the common discharge header. (*2)Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency  
During maintenance activities, Internal Outfall 101 may be discharged via the cooling tower flume rather than the common discharge header. (*2)Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency
(*1) Type Flow-MGD TSS Oil & Grease 50050 Report 00530 ---03582 ---Report ------ 30--- 15 100 20 1/month 1/month 1/month Estimate Grab Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
(*1) Type Flow-MGD TSS Oil & Grease 50050 Report 00530 ---03582 ---Report ------ 30--- 15 100 20 1/month 1/month 1/month Estimate Grab Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
Internal Outfall 101, at the point of discharge from the Radwaste Building prior to combining with other wastestreams and the waters of Final Outfall 001.FOOTNOTE(S):
Internal Outfall 101, at the point of discharge from the Radwaste Building prior to combining with other wastestreams and the waters of Final Outfall 001.FOOTNOTE(S):
Line 62: Line 62:
(*2) The permittee shall monitor all low volume wastewater sources that contribute to Outfall 101 from various locations on the property once per month when discharging.
(*2) The permittee shall monitor all low volume wastewater sources that contribute to Outfall 101 from various locations on the property once per month when discharging.
PART I Page 5 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
PART I Page 5 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 201, the intermittent discharge of treated sanitary wastewater; also, during maintenance activities, sanitary wastewater may be combined with previously monitored hydrostatic test wastewater, wastewater from floor drains of the control building and the diesel generator oil/water separator (and other low volume wastewaters as defined in 40 CFR 423), and maintenance wastewaters and may be routed to Outfall 002 (*4).Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency  
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 201, the intermittent discharge of treated sanitary wastewater; also, during maintenance activities, sanitary wastewater may be combined with previously monitored hydrostatic test wastewater, wastewater from floor drains of the control building and the diesel generator oil/water separator (and other low volume wastewaters as defined in 40 CFR 423), and maintenance wastewaters and may be routed to Outfall 002 (*4).Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency
(*1) Type Flow-MGD BODs TSS Fecal Coliform colonies/100 ml (*2)50050 00310 00530 Report Report 30 30 45 45 400 1/quarter 1/quarter 1/quarter 1/quarter Estimate Grab'Grab Grab 74055 ---200 In addition to the above monitoring requirements, the following limitations and monitoring frequencies are applicable during maintenance activities:
(*1) Type Flow-MGD BODs TSS Fecal Coliform colonies/100 ml (*2)50050 00310 00530 Report Report 30 30 45 45 400 1/quarter 1/quarter 1/quarter 1/quarter Estimate Grab'Grab Grab 74055 ---200 In addition to the above monitoring requirements, the following limitations and monitoring frequencies are applicable during maintenance activities:
Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency  
Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency
(*3) Type Flow-MGD TSS Oil & Grease 50050 00530 03582 Report Report ------ 30--- 15 45 20 1/week 1/week 1/week Estimate Grab Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
(*3) Type Flow-MGD TSS Oil & Grease 50050 00530 03582 Report Report ------ 30--- 15 45 20 1/week 1/week 1/week Estimate Grab Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
Internal Outfall 201, at the point of discharge from the sewage treatment plant prior to combining with the waters of Final Outfall 001 or Final Outfall 002.FOOTNOTE(S):
Internal Outfall 201, at the point of discharge from the sewage treatment plant prior to combining with the waters of Final Outfall 001 or Final Outfall 002.FOOTNOTE(S):
Line 76: Line 76:
PART I Page 7 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
PART I Page 7 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 301, the intermittent discharge of mobile metal cleaning wastewater generated from cleaning processes of internal components of plant equipment.
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 301, the intermittent discharge of mobile metal cleaning wastewater generated from cleaning processes of internal components of plant equipment.
Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency  
Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency
(*1) Type Flow-MGD 50050 Report Report 1-- l/week Estimate TSS 00530 --- 30 100 I/week Grab Oil & Grease 03582 15 20 I/week Grab Total Copper 01042 --- 1.0 1.0 1/week Grab Total Iron 01045 ...... 1.0 1.0 I/week Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
(*1) Type Flow-MGD 50050 Report Report 1-- l/week Estimate TSS 00530 --- 30 100 I/week Grab Oil & Grease 03582 15 20 I/week Grab Total Copper 01042 --- 1.0 1.0 1/week Grab Total Iron 01045 ...... 1.0 1.0 I/week Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
Internal Outfall 301, at the point of discharge of metal cleaning wastewaters prior to combining with other waters and the waters of Final Outfall 001.FOOTNOTE(S):
Internal Outfall 301, at the point of discharge of metal cleaning wastewaters prior to combining with other waters and the waters of Final Outfall 001.FOOTNOTE(S):
(*1) When discharging.
(*1) When discharging.
PART I Page 8 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
PART I Page 8 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 401, the intermittent discharge of previously monitored hydrostatic test wastewater and low volume wastewater treatment systems to Final Outfall 001 via the common header. The low volume waste management systems receive effluent from the following sources, including but not limited to: ion exchange resin backwash and regeneration, auxiliary boiler blowdown, floor washdown, equipment washing, personnel decontamination, laboratory drains, filter press, and maintenance wastewaters and other low volume wastewater sources as defined in 40 CFR 423. During maintenance activities, Internal Outfall 401 may be discharged via the cooling tower flume rather than the common discharge header. During maintenance activities, reverse osmosis reject water from the makeup water polishing system may be discharged via Outfall 401 rather than Outfall 003.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency  
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 401, the intermittent discharge of previously monitored hydrostatic test wastewater and low volume wastewater treatment systems to Final Outfall 001 via the common header. The low volume waste management systems receive effluent from the following sources, including but not limited to: ion exchange resin backwash and regeneration, auxiliary boiler blowdown, floor washdown, equipment washing, personnel decontamination, laboratory drains, filter press, and maintenance wastewaters and other low volume wastewater sources as defined in 40 CFR 423. During maintenance activities, Internal Outfall 401 may be discharged via the cooling tower flume rather than the common discharge header. During maintenance activities, reverse osmosis reject water from the makeup water polishing system may be discharged via Outfall 401 rather than Outfall 003.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency
(*1) Type Flow-MGD 50050 Report Report 1-- -/month Estimate TSS 00530 --- 30 100 1/month Grab Oil & Grease 03582 --- 15 20 I/month Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
(*1) Type Flow-MGD 50050 Report Report 1-- -/month Estimate TSS 00530 --- 30 100 1/month Grab Oil & Grease 03582 --- 15 20 I/month Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
Internal Outfall 401, at the makeup water pump house off one of the two discharge pumps, after filtration prior to combining with other wastestreams and the waters of Final Outfall 001.FOOTNOTE(S):
Internal Outfall 401, at the makeup water pump house off one of the two discharge pumps, after filtration prior to combining with other wastestreams and the waters of Final Outfall 001.FOOTNOTE(S):
(*1) When discharging.
(*1) When discharging.
PART I Page 9 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
PART I Page 9 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 501, the intermittent discharge of low volume wastewaters including but not limited to wastewaters from the mobile standby service water reverse osmosis filtration unit and standby cooling tower reject.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency  
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 501, the intermittent discharge of low volume wastewaters including but not limited to wastewaters from the mobile standby service water reverse osmosis filtration unit and standby cooling tower reject.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency
(*1) Type Flow-MGD 50050 Report Report 1-- -/month Estimate TSS 00530 --- 30 100 1/month Grab Oil & Grease 03582 --- 15 20 1/month Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
(*1) Type Flow-MGD 50050 Report Report 1-- -/month Estimate TSS 00530 --- 30 100 1/month Grab Oil & Grease 03582 --- 15 20 1/month Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
Internal Outfall 501, at the northwest end of the flume at the point of discharge of low volume wastewater prior to combining with other wastestreams and the waters of Final Outfall 001.FOOTNOTE(S):
Internal Outfall 501, at the northwest end of the flume at the point of discharge of low volume wastewater prior to combining with other wastestreams and the waters of Final Outfall 001.FOOTNOTE(S):
(*1) When discharging.
(*1) When discharging.
PART I Page 10 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
PART I Page 10 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 601, the intermittent discharge of low volume wastewater including but not limited to wastewaters from the filter backwash from service water polishing and feed-and-bleed from the service water system.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency  
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 601, the intermittent discharge of low volume wastewater including but not limited to wastewaters from the filter backwash from service water polishing and feed-and-bleed from the service water system.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency
(*1) Type Flow-MGD 50050 Report Report --- --- 1/month Estimate TSS 00530 --- --- 30 100 1/month Grab Oil & Grease 03582 --- --- 15 20 I/month Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
(*1) Type Flow-MGD 50050 Report Report --- --- 1/month Estimate TSS 00530 --- --- 30 100 1/month Grab Oil & Grease 03582 --- --- 15 20 I/month Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
Internal Outfall 601, at the southeast end of the flume at the point of discharge of low volume wastewater prior to combining with other wastestreams and the waters of Final Outfall 001.FOOTNOTE(Sa):
Internal Outfall 601, at the southeast end of the flume at the point of discharge of low volume wastewater prior to combining with other wastestreams and the waters of Final Outfall 001.FOOTNOTE(Sa):
Line 97: Line 97:
PART I Page 11 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
PART I Page 11 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 002, the intermittent discharge of stormwater runoff from the industrial materials storage area, low-level storage building and sewage treatment plant area; air conditioning condensate, potable water, and previously monitored hydrostatic test wastewater.
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 002, the intermittent discharge of stormwater runoff from the industrial materials storage area, low-level storage building and sewage treatment plant area; air conditioning condensate, potable water, and previously monitored hydrostatic test wastewater.
During periods of maintenance activities, previously monitored treated wastewater from Internal Outfall 201 may be discharged through Outfall 002.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency  
During periods of maintenance activities, previously monitored treated wastewater from Internal Outfall 201 may be discharged through Outfall 002.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency
(*1) Type Flow-MGD TOC Oil & Grease pH Minimum/Maximum Values (standard units)50050 00680 03582 00400--- Report ---50 1/quarter 1/quarter 1/quarter I/quarter Estimate Grab Grab Grab--- --- 15--- 6.0 (*2) 9.0 (*2)(Min) (Max)There shall be no discharge of floating solids or visible foam in other than trace amounts, nor of free oil or other oil materials, nor of toxic materials in quantities such as to cause acute toxicity to aquatic organisms.
(*1) Type Flow-MGD TOC Oil & Grease pH Minimum/Maximum Values (standard units)50050 00680 03582 00400--- Report ---50 1/quarter 1/quarter 1/quarter I/quarter Estimate Grab Grab Grab--- --- 15--- 6.0 (*2) 9.0 (*2)(Min) (Max)There shall be no discharge of floating solids or visible foam in other than trace amounts, nor of free oil or other oil materials, nor of toxic materials in quantities such as to cause acute toxicity to aquatic organisms.
Furthermore, there shall be no visible sheen or stains attributable to this discharge.
Furthermore, there shall be no visible sheen or stains attributable to this discharge.
Line 105: Line 105:
(*2) The permittee shall report on the Discharge Monitoring Reports both the minimum and maximum instantaneous pH values measured.
(*2) The permittee shall report on the Discharge Monitoring Reports both the minimum and maximum instantaneous pH values measured.
PART I Page 12 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
PART I Page 12 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 003, the intermittent discharge of stormwater runoff from the reactor building, turbine building, services building, clarifiers, main transformer yard and auxiliary transformer yard; maintenance wastewaters including but not limited to flushing of piping systems and vessels (including Fire Protection Water Supply System and Automatic Sprinkler System); low volume wastewaters including but not limited to reverse osmosis reject water from the standby service water polishing system, effluent from floor drains within power plant buildings (domestic potable water, well water, reject mobile reverse osmosis and fire suppression water treated in the fire pump house oil/water separator), air compressor condensate, and reverse osmosis reject water from makeup water polishing system; air conditioning condensate, previously monitored hydrostatic test wastewater, and de minimis quantities of cooling tower drift/mist  
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 003, the intermittent discharge of stormwater runoff from the reactor building, turbine building, services building, clarifiers, main transformer yard and auxiliary transformer yard; maintenance wastewaters including but not limited to flushing of piping systems and vessels (including Fire Protection Water Supply System and Automatic Sprinkler System); low volume wastewaters including but not limited to reverse osmosis reject water from the standby service water polishing system, effluent from floor drains within power plant buildings (domestic potable water, well water, reject mobile reverse osmosis and fire suppression water treated in the fire pump house oil/water separator), air compressor condensate, and reverse osmosis reject water from makeup water polishing system; air conditioning condensate, previously monitored hydrostatic test wastewater, and de minimis quantities of cooling tower drift/mist
(*5).Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Flow-MGD TOC Oil & Grease TSS pH Minimum/Maximum Values (standard units)Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency  
(*5).Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Flow-MGD TOC Oil & Grease TSS pH Minimum/Maximum Values (standard units)Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency
(*1) Type I/quarter  
(*1) Type I/quarter
(*2) Estimate I/quarter Grab 1/quarter  
(*2) Estimate I/quarter Grab 1/quarter
(*2) Grab 1/month (*3) Grab 1/quarter  
(*2) Grab 1/month (*3) Grab 1/quarter
(*2) Grab 50050 00680 03582 00530 00400 Report ---50 15... .100--- 6.0 (*2) 9.0 (*4)(Min) (Max)There shall be no discharge of floating solids or visible foam in other than trace amounts, nor of free oil or other oil materials, nor of toxic materials in quantities such as to cause acute toxicity to aquatic organisms.
(*2) Grab 50050 00680 03582 00530 00400 Report ---50 15... .100--- 6.0 (*2) 9.0 (*4)(Min) (Max)There shall be no discharge of floating solids or visible foam in other than trace amounts, nor of free oil or other oil materials, nor of toxic materials in quantities such as to cause acute toxicity to aquatic organisms.
Furthermore, there shall be no visible sheen or stains attributable to this discharge.
Furthermore, there shall be no visible sheen or stains attributable to this discharge.
Line 116: Line 116:
(*1) When discharging.
(*1) When discharging.
(*2) Sampling shall be monthly when discharging low volume wastewaters.
(*2) Sampling shall be monthly when discharging low volume wastewaters.
(*3) When discharging low volume wastewater, total suspended solids shall be monitored and reported as required above.(*4) The permittee shall report on the Discharge Monitoring Reports both the minimum and maximum instantaneous pH values measured.(*5) Discharge Monitoring Reports must be submitted for BOTH operational scenarios:  
(*3) When discharging low volume wastewater, total suspended solids shall be monitored and reported as required above.(*4) The permittee shall report on the Discharge Monitoring Reports both the minimum and maximum instantaneous pH values measured.(*5) Discharge Monitoring Reports must be submitted for BOTH operational scenarios:
(1) discharges which do not include low volume wastewaters; and (2) discharges which include low volume wastewaters.
(1) discharges which do not include low volume wastewaters; and (2) discharges which include low volume wastewaters.
If either scenario does not discharge within the monitoring period, mark "no discharge" on the top right hand corner of the DMR for that operational scenario.
If either scenario does not discharge within the monitoring period, mark "no discharge" on the top right hand corner of the DMR for that operational scenario.
PART I Page 13 of 17 Permit No. LA0042731 Al No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
PART I Page 13 of 17 Permit No. LA0042731 Al No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 004, the intermittent discharge of stormwater runoff from the office areas, warehouse areas, materials storage areas, and equipment/vehicle maintenance areas; maintenance wastewaters including but not limited to flushing of piping systems and vessels (fire protection water supply system and automatic sprinkler system, etc.); air conditioning condensate, potable water, previously monitored hydrostatic test wastewater, and previously monitored effluent from Internal Outfall 104 Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency  
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 004, the intermittent discharge of stormwater runoff from the office areas, warehouse areas, materials storage areas, and equipment/vehicle maintenance areas; maintenance wastewaters including but not limited to flushing of piping systems and vessels (fire protection water supply system and automatic sprinkler system, etc.); air conditioning condensate, potable water, previously monitored hydrostatic test wastewater, and previously monitored effluent from Internal Outfall 104 Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency
(*1) Type Flow-MGD TOC Oil & Grease pH Minimum/Maximum Values (standard units)50050 00680 03582 00400--- Report ......---.-.-.-.-
(*1) Type Flow-MGD TOC Oil & Grease pH Minimum/Maximum Values (standard units)50050 00680 03582 00400--- Report ......---.-.-.-.-
50---.-.-.-.-
50---.-.-.-.-
Line 131: Line 131:
PART I Page 14 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
PART I Page 14 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 104, the intermittent discharge of exterior vehicle washwater.
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 104, the intermittent discharge of exterior vehicle washwater.
Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency  
Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency
(*1) Type Flow-MGD 50050 Report Report ---.-- 1/quarter Estimate COD 00340 ...... ...-300 1/quarter Grab TSS 00530 ---...---
(*1) Type Flow-MGD 50050 Report Report ---.-- 1/quarter Estimate COD 00340 ...... ...-300 1/quarter Grab TSS 00530 ---...---
45 1/quarter Grab Oil & Grease 03582 ...... ... 15 1/quarter Grab pH Minimum/Maximum Values 00400 --- 6.0 (*2) 9.0 (*2) 1/quarter Grab (standard units) (Min) (Max)Soaps and/or Detergents  
45 1/quarter Grab Oil & Grease 03582 ...... ... 15 1/quarter Grab pH Minimum/Maximum Values 00400 --- 6.0 (*2) 9.0 (*2) 1/quarter Grab (standard units) (Min) (Max)Soaps and/or Detergents
(*3) --- ...--- Report --- 1/quarter Inventory Calculation Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
(*3) --- ...--- Report --- 1/quarter Inventory Calculation Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
Internal Outfall 104, at the point of discharge from the area where vehicles will be washed prior to combining with the waters of Final Outfall 004.FOOTNOTE(S):
Internal Outfall 104, at the point of discharge from the area where vehicles will be washed prior to combining with the waters of Final Outfall 004.FOOTNOTE(S):
Line 142: Line 142:
PART I Page 15 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
PART I Page 15 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 005, the intermittent discharge of stormwater runoff from the cooling tower yard, air conditioning condensate, previously monitored hydrostatic test wastewater, and de minimis quantities of cooling tower drift/mist.
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 005, the intermittent discharge of stormwater runoff from the cooling tower yard, air conditioning condensate, previously monitored hydrostatic test wastewater, and de minimis quantities of cooling tower drift/mist.
Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency  
Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency
(*1) Type Flow-MGD 50050 --- Report 1..... I/quarter Estimate TOC 00680 ...... ...-50 1/quarter Grab Oil & Grease 03582 ...... ...-15 1/quarter Grab pH Minimum/Maximum Values 00400 --- 6.0 (*2) 9.0 (*2) 1/quarter Grab (standard units) (Min) (Max)There shall be no discharge of floating solids or visible foam in other than trace amounts, nor of free oil or other oil materials, nor of toxic materials in quantities such as to cause acute toxicity to aquatic organisms.
(*1) Type Flow-MGD 50050 --- Report 1..... I/quarter Estimate TOC 00680 ...... ...-50 1/quarter Grab Oil & Grease 03582 ...... ...-15 1/quarter Grab pH Minimum/Maximum Values 00400 --- 6.0 (*2) 9.0 (*2) 1/quarter Grab (standard units) (Min) (Max)There shall be no discharge of floating solids or visible foam in other than trace amounts, nor of free oil or other oil materials, nor of toxic materials in quantities such as to cause acute toxicity to aquatic organisms.
Furthermore, there shall be no visible sheen or stains attributable to this discharge.
Furthermore, there shall be no visible sheen or stains attributable to this discharge.
Line 151: Line 151:
PART I Page 16 of 17 Permit No. LA0042731 Al No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
PART I Page 16 of 17 Permit No. LA0042731 Al No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 006, the intermittent discharge of clarifier underflow.
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 006, the intermittent discharge of clarifier underflow.
Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitorinq Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency  
Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitorinq Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency
(*1) Type Flow-MGD 50050 --- Report 1-- l/day Estimate COAGULANTS The quantity and types of all coagulants (clarifying agents) used in the intake raw river water treatment clarification system during the sampling month shall be recorded.
(*1) Type Flow-MGD 50050 --- Report 1-- l/day Estimate COAGULANTS The quantity and types of all coagulants (clarifying agents) used in the intake raw river water treatment clarification system during the sampling month shall be recorded.
Records of the quantity and type of coagulants used shall be retained for three (3) years. No DMR reporting shall be required.Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
Records of the quantity and type of coagulants used shall be retained for three (3) years. No DMR reporting shall be required.Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):
Line 158: Line 158:
(*1) When discharging.
(*1) When discharging.
PART I Page 17 of 17 Permit No. LA0042731 Al No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
PART I Page 17 of 17 Permit No. LA0042731 Al No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 007, the discharge of hydrostatic test wastewater Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic  
During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 007, the discharge of hydrostatic test wastewater Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic
(*1) Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average(*2)
(*1) Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average(*2)
Maximum(*3)Average Maximum(*3)
Maximum(*3)Average Maximum(*3)
Line 180: Line 180:
VOLATILE COMPOUNDS Acrolein Acrylonitrile Benzene Bromoform Carbon Tetrachloride Chlorobenzene Chlorodibromomethane Chloroethane 2-Chloroethylvinylether Chloroform 1,2-Dichlorobenzene 1,3-Dichlorobenzene 1,4-Dichlorobenzene Dichlorobromomethane 1,1 -Dichloroethane 1,2-Dichloroethane 1,1 -Dichloroethylene 1,2-Dichloropropane 1,3-Dichloropropylene Ethylbenzene Methyl Bromide [Bromomethane]
VOLATILE COMPOUNDS Acrolein Acrylonitrile Benzene Bromoform Carbon Tetrachloride Chlorobenzene Chlorodibromomethane Chloroethane 2-Chloroethylvinylether Chloroform 1,2-Dichlorobenzene 1,3-Dichlorobenzene 1,4-Dichlorobenzene Dichlorobromomethane 1,1 -Dichloroethane 1,2-Dichloroethane 1,1 -Dichloroethylene 1,2-Dichloropropane 1,3-Dichloropropylene Ethylbenzene Methyl Bromide [Bromomethane]
Methyl Chloride [Chloromethane]
Methyl Chloride [Chloromethane]
Methylene Chloride 1,1,2,2-Tetrachloroethane Tetrachloroethylene Toluene 1,2-trans-Dichloroethylene 1,1,1 -Trichloroethane 1,1,2-Trichloroethane Trichloroethylene Vinyl Chloride MOL (iggL)50 20 10 10 2 10 10 50 10 10 10 10 10 10 10 10 10 10 10 10 50 50 20 10 10 10 10 10 10 10 10 MOL (WWg/L)10 10 10 50 50 20 50 10 5 10 10 MOL (gg/L)10 10 10 ACID COMPOUNDS 2-Chlorophenol 2,4-Dichlorophenol 2,4-Dimethylphenol 4,6-Dinitro-o-Cresol  
Methylene Chloride 1,1,2,2-Tetrachloroethane Tetrachloroethylene Toluene 1,2-trans-Dichloroethylene 1,1,1 -Trichloroethane 1,1,2-Trichloroethane Trichloroethylene Vinyl Chloride MOL (iggL)50 20 10 10 2 10 10 50 10 10 10 10 10 10 10 10 10 10 10 10 50 50 20 10 10 10 10 10 10 10 10 MOL (WWg/L)10 10 10 50 50 20 50 10 5 10 10 MOL (gg/L)10 10 10 ACID COMPOUNDS 2-Chlorophenol 2,4-Dichlorophenol 2,4-Dimethylphenol 4,6-Dinitro-o-Cresol
[2-Methyl-4,6-Dinitrophenol]
[2-Methyl-4,6-Dinitrophenol]
2,4-Dinitrophenol 2-Nitrophenol 4-Nitrophenol p-Chloro-m-Cresol  
2,4-Dinitrophenol 2-Nitrophenol 4-Nitrophenol p-Chloro-m-Cresol
[4-Chloro-3-Methylphenol]
[4-Chloro-3-Methylphenol]
Pentachlorophenol Phenol 2,4,6-Trichlorophenol BASE/NEUTRAL COMPOUNDS Acenaphthene Acenaphthylene Anthracene Part II Page 4 of 20 Permit No. LA0042731 AI No. 2889 OTHER REQUIREMENTS (continued)
Pentachlorophenol Phenol 2,4,6-Trichlorophenol BASE/NEUTRAL COMPOUNDS Acenaphthene Acenaphthylene Anthracene Part II Page 4 of 20 Permit No. LA0042731 AI No. 2889 OTHER REQUIREMENTS (continued)
Line 189: Line 189:
Ether 10 Bis(2-chloroisopropyl)
Ether 10 Bis(2-chloroisopropyl)
Ether 10 Bis(2-ethylhexyl)
Ether 10 Bis(2-ethylhexyl)
Phthalate 10 4-Bromophenyl Phenyl Ether 10 Butylbenzyl Phthalate 10 2-Chloronapthalene 10 4-Chlorophenyl Phenyl Ether 10 Chrysene 5 Dibenzo(a,h)anthracene 5 3,3'-Dichlorobenzidine 5 Diethyl Phthalate 10 Dimethyl Phthalate 10 Di-n-Butyl Phthalate 10 2,4-Dinitrotoluene 10 2,6-Dinitrotoluene 10 Di-n-octyl Phthalate 10 1,2-Diphenylhydrazine 20 Fluoranthene 10 Fluorene 10 Hexachlorobenzene 5 Hexachlorobutadiene 10 Hexachlorocyclopentadiene 10 Hexachloroethane 20 Indeno(1,2,3-cd)pyrene  
Phthalate 10 4-Bromophenyl Phenyl Ether 10 Butylbenzyl Phthalate 10 2-Chloronapthalene 10 4-Chlorophenyl Phenyl Ether 10 Chrysene 5 Dibenzo(a,h)anthracene 5 3,3'-Dichlorobenzidine 5 Diethyl Phthalate 10 Dimethyl Phthalate 10 Di-n-Butyl Phthalate 10 2,4-Dinitrotoluene 10 2,6-Dinitrotoluene 10 Di-n-octyl Phthalate 10 1,2-Diphenylhydrazine 20 Fluoranthene 10 Fluorene 10 Hexachlorobenzene 5 Hexachlorobutadiene 10 Hexachlorocyclopentadiene 10 Hexachloroethane 20 Indeno(1,2,3-cd)pyrene
[2,3-o-Phenylene Pyrene] 5 Isophorone 10 Naphthalene 10 Nitrobenzene 10 n-Nitrosodimethylamine 50 n-Nitrosodi-n-Propylamine 20 n-Nitrosodiphenylamine 20 Phenanthrene 10 Pyrene 10 1,2,4-Trichlorobenzene 10 PESTICIDES MOL (1ýg/L)Aldrin 0.01 Alpha-BHC 0.05 Beta-BHC 0.05 Gamma-BHC  
[2,3-o-Phenylene Pyrene] 5 Isophorone 10 Naphthalene 10 Nitrobenzene 10 n-Nitrosodimethylamine 50 n-Nitrosodi-n-Propylamine 20 n-Nitrosodiphenylamine 20 Phenanthrene 10 Pyrene 10 1,2,4-Trichlorobenzene 10 PESTICIDES MOL (1ýg/L)Aldrin 0.01 Alpha-BHC 0.05 Beta-BHC 0.05 Gamma-BHC
[Lindane]
[Lindane]
0.05 Delta-BHC 0.05 Chlordane 0.2 4,4'-DDT 0.02 4,4'-DDE [p,p-DDX]
0.05 Delta-BHC 0.05 Chlordane 0.2 4,4'-DDT 0.02 4,4'-DDE [p,p-DDX]
0.1 Part II Page 5 of 20 Permit No. LA0042731 Al No. 2889 OTHER REQUIREMENTS (continued) 4,4'-DDD [p,p-TDE]  
0.1 Part II Page 5 of 20 Permit No. LA0042731 Al No. 2889 OTHER REQUIREMENTS (continued) 4,4'-DDD [p,p-TDE]
 
0.1 Dieldrin 0.02 Alpha-Endosulfan 0.01 Beta-Endosulfan 0.02 Endosulfan Sulfate 0.1 Endrin 0.02 Endrin Aldehyde 0.1 Heptachlor 0.01 Heptachlor Epoxide [BHC-Hexachlorocyclohexane]
===0.1 Dieldrin===
0.02 Alpha-Endosulfan 0.01 Beta-Endosulfan 0.02 Endosulfan Sulfate 0.1 Endrin 0.02 Endrin Aldehyde 0.1 Heptachlor 0.01 Heptachlor Epoxide [BHC-Hexachlorocyclohexane]
0.01 PCB-1242 0.2'PCB-1254 0.2 PCB-1221 0.2 PCB-1232 0.2 PCB-1248 0.2 PCB-1260 0.2 PCB-1016 0.2 Toxaphene 0.3 The permittee may develop an effluent specific method detection limit (MDL) in accordance with Appendix B to 40 CFR Part 136 (See LAC 33:IX.4901).
0.01 PCB-1242 0.2'PCB-1254 0.2 PCB-1221 0.2 PCB-1232 0.2 PCB-1248 0.2 PCB-1260 0.2 PCB-1016 0.2 Toxaphene 0.3 The permittee may develop an effluent specific method detection limit (MDL) in accordance with Appendix B to 40 CFR Part 136 (See LAC 33:IX.4901).
For any pollutant for which the permittee determines an effluent specific MDL, the permittee shall send to this Office a report containing QA/QC documentation, analytical results, and calculations necessary to demonstrate that the effluent specific MDL was correctly calculated.
For any pollutant for which the permittee determines an effluent specific MDL, the permittee shall send to this Office a report containing QA/QC documentation, analytical results, and calculations necessary to demonstrate that the effluent specific MDL was correctly calculated.

Revision as of 10:30, 30 April 2019

LPDES (#LA0042731) Permit Renewal
ML11276A006
Person / Time
Site:  Entergy icon.png
Issue date: 09/27/2011
From: Spell W H
Entergy Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
ENV-L-11-031, LA004273, RBG-47178, G1.11.7, G9.5
Download: ML11276A006 (62)


Text

~Entergy Entergy Operations, Inc.5485 U.S. Highway 61 St. Francisville, LA 70775 September 27, 2011 U.S. Nuclear Regulatory Commission Document Control Desk OWFN-P I-17 11555 Rockville Pike Rockville, MD 20852-2738

Subject:

LPDES (# LA004273 1) Permit Renewal River Bend Station -Unit 1 License No. NPF-47 Docket No. 50-458 File No.: GI.11.7, G9.5 RBG-47178 ENV-L-1 1-031 Ladies and Gentlemen:

Enclosed is a copy of the revised Louisiana Pollutant Discharge Elimination System (LPDES)permit effective October 1, 2011, provided as required by Section 3.2 of Appendix B, Environmental Protection Plan (Nonradiological), to Facility Operating License NPF-47.Please contact me at 225-381-3701 if you have any questions.

Sincerely, William H. Spell Senior Environmental Specialist WHS/Ibw Enclosure COL)ý'kJ 40C LPDES (# LA004273 1) Permit Renewal River Bend Station -Unit 1 License No. NPF-47 Docket No. 50-458 Bcc: Document Control (R-GSB-10) (No Enclosure)

Patrick J. Donahue (pdonahu) (No Enclosure) 2 LR6c- o BOBBY JINDAL PEGGY M. HATCH GOVERNOR SECRETARY c'tate of louigtana DEPARTMENT OF ENVIRONMENTAL QUALITY ENVIRONMENTAL SERVICES SEP 01 2011 CERTIFIED MAIL 7005 1820 0002 2086 6520 -RETURN RECEIPT REQUEST File No.: LA0042731 Al No.: 2889 ctivity No -PER20100002 Mr. William H. Spell, HP/Chem Specialist Entergy Operations, Inc. 2011 River Bend Station 5485 U. S. Highway 61 ENVIRONMENTAL St. Francisville, LA 70775 SERVICES RE: Louisiana Pollutant Discharge Elimination System (LPDES) permit to discharge cooling tower blowdown, low volume wastewaters, maintenance wastewaters, clarifier underflow, treated sanitary wastewater, hydrostatic test wastewater, and metal cleaning wastewater to the Mississippi River (via Outfalls 001, 101, 201, 301, 401, 501, 601, 006, and 007) and stormwater runoff, vehicle washwater, air conditioning condensate, cooling tower drift, low volume wastewaters, hydrostatic test wastewater, and maintenance wastewaters to Grant's Bayou, thence to Alligator Bayou, thence to Thompson Creek (via Outfalls 002,003,004, 104, 005, and 007) from an existing steam electric generating facility located at 5485 U. S.Highway 61 in St. Francisville, West Feliciana Parish.

Dear Mr. Spell:

This Office has not received any comments from either the general public or from Entergy Operations, Inc. in response to the public notice published in the Office of Environmental Services Public Notice Mailing List on June 24, 2011, and the St. Francisville Democrat on June 29, 2011.Please note that footnote (*4), Part 1, Page 6 of 17 has been changed to clarify that discharge monitoring reports must be submitted for both Outfall 201 operational scenarios.

Pursuant to the Clean Water Act (33 U.S.C. 1251 et seq.), and the Louisiana Environmental Quality Act (La. R.S. 30:2001, et seq.), the attached LPDES permit has been issued. Provisions of this permit may be appealed in writing pursuant to La. R.S. 30: 2024(A) within 30 days from receipt of the permit.A request for hearing must be sent to the following:

Louisiana Department of Environmental Quality Office of the Secretary Attention:

Hearings Clerk, Legal Division Post Office Box 4302 Baton Rouge, Louisiana 70821-4302 Upon the effective date this permit shall replace the previously effective LPDES permit, LA004273 1.Post Office Box 4313 -Baton Rouge, Louisiana 70821-4313

  • Phone 225-219-3181
  • Fax 225-219-3309 www.deq.louisiana.gov Entergy Operations, Inc.RE: LA0042731, Al No. 2889 Page 2 Monitoring results should be reported on a Discharge Monitoring Report (DMR) form per the schedule specified.

A copy of the form to be used is attached for your convenience.

Pursuant to LAC 33:IX.1309.I, LAC 33:IX.6509.A.1, and LAC 33:1.1701, you must pay any outstanding fees to the Department.

Therefore, you are encouraged to verify your facility's fee status by contacting LDEQ's Office of Management and Finance, Financial Services Division at (225) 219-3863. Any outstanding fees must be remitted via a check to the Louisiana Department of Environmental Quality within thirty (30) days after the effective date of your permit. Failure to pay the full amount due in the manner and time prescribed could result in applicable enforcement actions as prescribed in the Environmental Quality Act, including, but not limited to revocation or suspension of the applicable permit, and/or a civil penalty against you.Should you have any questions concerning any part of the permit, please feel free to contact Lisa Kemp of the Office of Environmental Services at the address on the first page or by telephone at (225)219-3195.

To ensure that all future correspondence regarding this facility is properly filed into the Department's Electronic Document Management System, please reference your Agency Interest (AI)number 2889 and LPDES permit number LA0042731 on all future correspondence to this Department.

Sincerely, Sam L. Phillips Assistant Secretary lwk Attachment(s):

final permit and DMR c: 1O-W File ec: Lisa Kemp Angela Marse Bruce Fielding Water Permits Division Public Health Chief Engineer Office of Public Health Department of Health and Hospitals Evelyn Rosborough (6WQ-CA)U.S. EPA, Region VI Permit Compliance Unit Capital Regional Office Office of Environmental Compliance PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)

NAME ADDRESS NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES)DISCHARGE MONITORING REPORT (DMR)-UPERMITNUMBER 1 1 DISCHARGE NUMBER Form Approved.OMB No. 2040-0004 FACILITY LOCATION MONITORI FROM _IL~INGPERIOD I-=YEAR IMO DAY I Check here if No Discharge TO [ LNOTE: Read Instructions before completing this form PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO. FREQUENCY SAMPLE EX OF ANALYSIS TYPE VALUE VALUE UNITS VALUE VALUE VALUE UNITS SAMPLE MEASUREMENT PERMIT REQUIREMENT SAMPLE MEASUREMENT PERMIT REQUIREMENT SAMPLE MEASUREMENT PERMIT REQUIREMENT SAMPLE MEASUREMENT PERMIT REQUIREMENT SAMPLE MEASUREMENT PERMIT REQUIREMENT SAMPLE MEASUREMENT PERMIT REQUIREMENT SAMPLE MEASUREMENT PERMIT REQUIREMENT NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I CERTIFYUNDER PENALTYOF LAWTHATTHIS DOCUMENrANDALLATrACHMENTS WERE PREPARED TELEPHONE DATE UNDER MY DIRECTION OR SUPERVISION IN ACCORDANCE WITH A SYSTEM DESIGNED TO ASSURE THAT QUALIFIED PERSONNEL PROPERLY GATHER AND EVALUATE THE INFORMATION SUBMITTED.

BASED ON MY INQUIRY OF THE PERSON OR PERSONS WHO MANAGE THE SYSTEM. OR THOSE PERSONS DIRECTLY RESPONSIBLE FOR GATHERING THE INFORMATION, THE INFORMATION SUBMITTED IS, tO THE BEST OF MY KNOWLEDGE AND BELIEF. TRUE. ACCURATE, AND COMPLETE.I AM AWARE THAT THERE ARE SIGNIFICANT PENALTIES FOR SUBMITTING FALSE INFORMATION.

D INCLUDING THE POSSIBILITY OF FINE AND IMPRISONMENT FOR KNOWING VIOLATIONS.

SIGNATURE OF PRINCIPAL EXECUTIVE TYPED OR PRINTED OFFICER OR AUTHORIZED AGENT AREA NUMBER YEAR MO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)EPA Form 3320-1 PAGE OF PERMIT NUMBER LA0042731 Al No.: 2889 DEQA LOU ISIANA OFFICE OF ENVIRONMENTAL SERVICES Water Discharge Permit Pursuant to the Clean Water Act, as amended (33 U.S.C. 1251 et seM.), and the Louisiana Environmental Quality Act, as amended (La. R. S. 30:2001 et seq.), rules and regulations effective or promulgated under the authority of said Acts, and in reliance on statements and representations heretofore made in the application, a Louisiana Pollutant Discharge Elimination System permit is issued authorizing Entergy Operations, Inc.River Bend Station 5485 U. S. Highway 61 St. Francisville, LA 70775 Type Facility: steam electric generating facility Location: 5485 U. S. Highway 61 in St. Francisville West Feliciana Parish Receiving Waters: Mississippi River (Outfalls 001, 101, 201, 301, 401, 501, 601, 006, 007) and Grant's Bayou (Outfalls 002, 003, 004, 104, 005, 007) (070201)to discharge in accordance with effluent limitations, monitoring requirements, and other conditions set forth in Parts I, II, and III attached hereto.This permit shall become effective on 2 &//This permit and the authorization to discharge shall expire five (5) years from the effective date of the permit.onsued on Sam L. Phillips Assistant Secretary GAL VEZ BUILDING

  • 602 N. FIFTH STREET P.O. BOX 4313
  • BA TON ROUGE, LA 70821-4313*

(225) 219-3181 PART I Page 2 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 001, the continuous discharge of cooling tower blowdown, previously monitored effluent from Internal Outfalls 101, 201, 301, 401, 501, and 601, and previously monitored hydrostatic test wastewater from Outfall 007.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)Monitoring Requirements STORET Monthly Code Average Daily Monthly Daily Measurement Maximum Average Maximum Frequency Flow-MGD Temperature (OF) (*1)Free Available Chlorine (*2)Total Chromium Total Zinc pH Minimum/Maximum Values (standard units)WHOLE EFFLUENT (ACUTE)TOXICITY TESTING (*4) (*5)50050 00011 50064 01034 01092 00400 Report 0.63 Report 1.64 105 0.2 0.2 1.0 6.0 (*3)(Min)110 0.5 0.2 1.0 9.0 (*3)(Max)Continuous Continuous 1/week 1/year 1/week 1/week Sample Type Recorder Recorder Grab Grab Grab Grab STORET Code NOEC, Pass/Fail

[0/1], TEM6C Lethality, Static Renewal, 48-Hour Acute, Pimephales promelas NOEC, Value [%], TOM6C Lethality, Static Renewal, 48-Hour Acute, Pimephales promelas NOEC, Value [%], TQM6C Coefficient of Variation, Static Renewal, 48-Hour Acute, Pimeohales oromelas (Percent %, UNLESS STATED)Monthly Avg 48-Hour Minimum Minimum Maximum Report Report ---Report Report ---Report Measurement Frequency

(*4)Sample Type 1/year 1/year 1/year 24-hr. Composite 24-hr. Composite 24-hr. Composite PART I EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (Outfall 001 continued)

Page 3 of 17 Permit No. LA0042731 AI No. 2889 Monitoring Requirements Measurement Sample Frequency

(*4) Type Effluent Characteristic WHOLE EFFLUENT (ACUTE)TOXICITY TESTING Discharge Limitations Other units (Percent %, UNLESS STATED)Monthly Avg 48-Hour Minimum Minimum Maximum STORET Code NOEC, Pass/Fail

[0/1], TEM3D Lethality, Static Renewal, 48-Hour Acute, Daphnia pulex NOEC, Value [%], TOM3D Lethality, Static Renewal, 48-Hour Acute Daohnia pulex NOEC, Value [%], TQM3D Coefficient of Variation, Static Renewal, 48-Hour Acute Daphnia ulex Report Report ---Report Report Report 1/year 1/year 1/year 24-hr. Composite 24-hr. Composite 24-hr. Composite There shall be no discharge of floating solids or visible foam in other than trace amounts, nor of free oil or other oil materials, nor of toxic materials in quantities such as to cause acute toxicity to aquatic organisms.

Furthermore, there shall be no visible sheen or stains attributable to this discharge.

Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):

Outfall 001, at the exposed vacuum-break chamber of the buried 30-inch diameter discharge pipeline prior to discharge to the Mississippi River. As an alternative, the permittee may report temperature measurements based on the balance of plant computer points, and flow may be measured from the auxiliary control room flow recorder.FOOTNOTENS):

(*1) See Part II. N.(*2) Samples shall be representative of any periodic episodes of chlorination, biocide usage, or other potentially toxic substances discharged on an intermittent basis.(*3) The permittee shall report on the Discharge Monitoring Reports both the minimum and maximum instantaneous pH values measured.(*4) Biomonitoring shall be conducted during periods of chlorination, biocide (s) usage or potentially toxic substances being discharged.

However, if no biofouling agent or chlorine is used during the monitoring period, the permittee must still conduct the required annual testing.(*5) See Part II. U.

PART I Page 4 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)

During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 101, the intermittent discharge of low level radioactive low volume wastewater from the liquid radwaste wastewater system (LWS) which includes equipment and building floor drain sumps, equipment washing, personnel decontamination, laboratory drains, filter press effluent, RO unit wastewater, other low volume wastewater sources as defined in 40 CFR 423 and maintenance wastewaters.

During maintenance activities, Internal Outfall 101 may be discharged via the cooling tower flume rather than the common discharge header. (*2)Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency

(*1) Type Flow-MGD TSS Oil & Grease 50050 Report 00530 ---03582 ---Report ------ 30--- 15 100 20 1/month 1/month 1/month Estimate Grab Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):

Internal Outfall 101, at the point of discharge from the Radwaste Building prior to combining with other wastestreams and the waters of Final Outfall 001.FOOTNOTE(S):

(*1) When discharging.

(*2) The permittee shall monitor all low volume wastewater sources that contribute to Outfall 101 from various locations on the property once per month when discharging.

PART I Page 5 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)

During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 201, the intermittent discharge of treated sanitary wastewater; also, during maintenance activities, sanitary wastewater may be combined with previously monitored hydrostatic test wastewater, wastewater from floor drains of the control building and the diesel generator oil/water separator (and other low volume wastewaters as defined in 40 CFR 423), and maintenance wastewaters and may be routed to Outfall 002 (*4).Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency

(*1) Type Flow-MGD BODs TSS Fecal Coliform colonies/100 ml (*2)50050 00310 00530 Report Report 30 30 45 45 400 1/quarter 1/quarter 1/quarter 1/quarter Estimate Grab'Grab Grab 74055 ---200 In addition to the above monitoring requirements, the following limitations and monitoring frequencies are applicable during maintenance activities:

Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency

(*3) Type Flow-MGD TSS Oil & Grease 50050 00530 03582 Report Report ------ 30--- 15 45 20 1/week 1/week 1/week Estimate Grab Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):

Internal Outfall 201, at the point of discharge from the sewage treatment plant prior to combining with the waters of Final Outfall 001 or Final Outfall 002.FOOTNOTE(S):

(*1) When discharging.

PART I Page 6 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (Internal Outfall 201 continued)

(*2) Future water quality studies may indicate potential toxicity from the presence of residual chlorine in the treatment facility's effluent.

Therefore, the permittee is hereby advised that a future Total Residual Chlorine Limit may be required if chlorine is used as a method of disinfection.

In many cases, this becomes a NO MEASURABLE Total Residual Chlorine Limit.(*3) Samples shall be representative of discharges occurring during maintenance activities.

(*4) Discharge Monitoring Reports must be submitted for BOTH Outfall 201 operational scenarios.

If either scenario does not discharge within the monitoring period, mark "no discharge" on the top right hand corner of the DMR for that operational scenario.

PART I Page 7 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)

During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 301, the intermittent discharge of mobile metal cleaning wastewater generated from cleaning processes of internal components of plant equipment.

Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency

(*1) Type Flow-MGD 50050 Report Report 1-- l/week Estimate TSS 00530 --- 30 100 I/week Grab Oil & Grease 03582 15 20 I/week Grab Total Copper 01042 --- 1.0 1.0 1/week Grab Total Iron 01045 ...... 1.0 1.0 I/week Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):

Internal Outfall 301, at the point of discharge of metal cleaning wastewaters prior to combining with other waters and the waters of Final Outfall 001.FOOTNOTE(S):

(*1) When discharging.

PART I Page 8 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)

During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 401, the intermittent discharge of previously monitored hydrostatic test wastewater and low volume wastewater treatment systems to Final Outfall 001 via the common header. The low volume waste management systems receive effluent from the following sources, including but not limited to: ion exchange resin backwash and regeneration, auxiliary boiler blowdown, floor washdown, equipment washing, personnel decontamination, laboratory drains, filter press, and maintenance wastewaters and other low volume wastewater sources as defined in 40 CFR 423. During maintenance activities, Internal Outfall 401 may be discharged via the cooling tower flume rather than the common discharge header. During maintenance activities, reverse osmosis reject water from the makeup water polishing system may be discharged via Outfall 401 rather than Outfall 003.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency

(*1) Type Flow-MGD 50050 Report Report 1-- -/month Estimate TSS 00530 --- 30 100 1/month Grab Oil & Grease 03582 --- 15 20 I/month Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):

Internal Outfall 401, at the makeup water pump house off one of the two discharge pumps, after filtration prior to combining with other wastestreams and the waters of Final Outfall 001.FOOTNOTE(S):

(*1) When discharging.

PART I Page 9 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)

During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 501, the intermittent discharge of low volume wastewaters including but not limited to wastewaters from the mobile standby service water reverse osmosis filtration unit and standby cooling tower reject.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency

(*1) Type Flow-MGD 50050 Report Report 1-- -/month Estimate TSS 00530 --- 30 100 1/month Grab Oil & Grease 03582 --- 15 20 1/month Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):

Internal Outfall 501, at the northwest end of the flume at the point of discharge of low volume wastewater prior to combining with other wastestreams and the waters of Final Outfall 001.FOOTNOTE(S):

(*1) When discharging.

PART I Page 10 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)

During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 601, the intermittent discharge of low volume wastewater including but not limited to wastewaters from the filter backwash from service water polishing and feed-and-bleed from the service water system.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency

(*1) Type Flow-MGD 50050 Report Report --- --- 1/month Estimate TSS 00530 --- --- 30 100 1/month Grab Oil & Grease 03582 --- --- 15 20 I/month Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):

Internal Outfall 601, at the southeast end of the flume at the point of discharge of low volume wastewater prior to combining with other wastestreams and the waters of Final Outfall 001.FOOTNOTE(Sa):

(*1) When discharging.

PART I Page 11 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)

During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 002, the intermittent discharge of stormwater runoff from the industrial materials storage area, low-level storage building and sewage treatment plant area; air conditioning condensate, potable water, and previously monitored hydrostatic test wastewater.

During periods of maintenance activities, previously monitored treated wastewater from Internal Outfall 201 may be discharged through Outfall 002.Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency

(*1) Type Flow-MGD TOC Oil & Grease pH Minimum/Maximum Values (standard units)50050 00680 03582 00400--- Report ---50 1/quarter 1/quarter 1/quarter I/quarter Estimate Grab Grab Grab--- --- 15--- 6.0 (*2) 9.0 (*2)(Min) (Max)There shall be no discharge of floating solids or visible foam in other than trace amounts, nor of free oil or other oil materials, nor of toxic materials in quantities such as to cause acute toxicity to aquatic organisms.

Furthermore, there shall be no visible sheen or stains attributable to this discharge.

Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):

Outfall 002, at the point of discharge from the plant drainage ditch system where the stormwater runoff from the sewage treatment plant area converges with that from the industrial materials storage area and Low Level Waste Storage Building prior to combining with other waters.FOOTNOTE(S):

(*1) When discharging.

(*2) The permittee shall report on the Discharge Monitoring Reports both the minimum and maximum instantaneous pH values measured.

PART I Page 12 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)

During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 003, the intermittent discharge of stormwater runoff from the reactor building, turbine building, services building, clarifiers, main transformer yard and auxiliary transformer yard; maintenance wastewaters including but not limited to flushing of piping systems and vessels (including Fire Protection Water Supply System and Automatic Sprinkler System); low volume wastewaters including but not limited to reverse osmosis reject water from the standby service water polishing system, effluent from floor drains within power plant buildings (domestic potable water, well water, reject mobile reverse osmosis and fire suppression water treated in the fire pump house oil/water separator), air compressor condensate, and reverse osmosis reject water from makeup water polishing system; air conditioning condensate, previously monitored hydrostatic test wastewater, and de minimis quantities of cooling tower drift/mist

(*5).Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Flow-MGD TOC Oil & Grease TSS pH Minimum/Maximum Values (standard units)Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency

(*1) Type I/quarter

(*2) Estimate I/quarter Grab 1/quarter

(*2) Grab 1/month (*3) Grab 1/quarter

(*2) Grab 50050 00680 03582 00530 00400 Report ---50 15... .100--- 6.0 (*2) 9.0 (*4)(Min) (Max)There shall be no discharge of floating solids or visible foam in other than trace amounts, nor of free oil or other oil materials, nor of toxic materials in quantities such as to cause acute toxicity to aquatic organisms.

Furthermore, there shall be no visible sheen or stains attributable to this discharge.

Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):

Outfall 003, at the point of discharge from the plant drainage ditch system along the East Creek prior to combining with other waters.FOOTNOTE(S):

(*1) When discharging.

(*2) Sampling shall be monthly when discharging low volume wastewaters.

(*3) When discharging low volume wastewater, total suspended solids shall be monitored and reported as required above.(*4) The permittee shall report on the Discharge Monitoring Reports both the minimum and maximum instantaneous pH values measured.(*5) Discharge Monitoring Reports must be submitted for BOTH operational scenarios:

(1) discharges which do not include low volume wastewaters; and (2) discharges which include low volume wastewaters.

If either scenario does not discharge within the monitoring period, mark "no discharge" on the top right hand corner of the DMR for that operational scenario.

PART I Page 13 of 17 Permit No. LA0042731 Al No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)

During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 004, the intermittent discharge of stormwater runoff from the office areas, warehouse areas, materials storage areas, and equipment/vehicle maintenance areas; maintenance wastewaters including but not limited to flushing of piping systems and vessels (fire protection water supply system and automatic sprinkler system, etc.); air conditioning condensate, potable water, previously monitored hydrostatic test wastewater, and previously monitored effluent from Internal Outfall 104 Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Code Average Maximum Average Maximum Monitoring Requirements Measurement Sample Frequency

(*1) Type Flow-MGD TOC Oil & Grease pH Minimum/Maximum Values (standard units)50050 00680 03582 00400--- Report ......---.-.-.-.-

50---.-.-.-.-

15--- ---6.0 (*2) 9.0 (*2)(Min) (Max)1/quarter I/quarter I/quarter 1/quarter Estimate Grab Grab Grab There shall be no discharge of floating solids or visible foam in other than trace amounts, nor of free oil or other oil materials, nor of toxic materials in quantities such as to cause acute toxicity to aquatic organisms.

Furthermore, there shall be no visible sheen or stains attributable to this discharge.

Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):

Outfall 004, at the point of discharge from the plant drainage ditch system along the West Creek prior to combining with other waters.FOOTNOTE(S):

(*1) When discharging.

(*2) The permittee shall report on the Discharge Monitoring Reports both the minimum and maximum instantaneous pH values measured.

PART I Page 14 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)

During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Internal Outfall 104, the intermittent discharge of exterior vehicle washwater.

Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency

(*1) Type Flow-MGD 50050 Report Report ---.-- 1/quarter Estimate COD 00340 ...... ...-300 1/quarter Grab TSS 00530 ---...---

45 1/quarter Grab Oil & Grease 03582 ...... ... 15 1/quarter Grab pH Minimum/Maximum Values 00400 --- 6.0 (*2) 9.0 (*2) 1/quarter Grab (standard units) (Min) (Max)Soaps and/or Detergents

(*3) --- ...--- Report --- 1/quarter Inventory Calculation Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):

Internal Outfall 104, at the point of discharge from the area where vehicles will be washed prior to combining with the waters of Final Outfall 004.FOOTNOTE(S):

(*1) When discharging.

(*2) The permittee shall report on the Discharge Monitoring Reports both the minimum and maximum instantaneous pH values measured.(*3) Soaps/Detergents:

Monitor by inventory records and calculations quarterly.

Retain inventory records (quantity and type), and a Material Safety Data Sheet (MSDS) for each material used for three years. No DMR reporting shall be required.

PART I Page 15 of 17 Permit No. LA0042731 AI No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)

During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 005, the intermittent discharge of stormwater runoff from the cooling tower yard, air conditioning condensate, previously monitored hydrostatic test wastewater, and de minimis quantities of cooling tower drift/mist.

Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency

(*1) Type Flow-MGD 50050 --- Report 1..... I/quarter Estimate TOC 00680 ...... ...-50 1/quarter Grab Oil & Grease 03582 ...... ...-15 1/quarter Grab pH Minimum/Maximum Values 00400 --- 6.0 (*2) 9.0 (*2) 1/quarter Grab (standard units) (Min) (Max)There shall be no discharge of floating solids or visible foam in other than trace amounts, nor of free oil or other oil materials, nor of toxic materials in quantities such as to cause acute toxicity to aquatic organisms.

Furthermore, there shall be no visible sheen or stains attributable to this discharge.

Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):

Outfall 005, at the point of discharge from the stormwater drainage ditch east of the cooling towers prior to combining with other waters.FOOTNOTE(S):

(*1) When discharging.

(*2) The permittee shall report on the Discharge Monitoring Reports both the minimum and maximum instantaneous pH values measured.

PART I Page 16 of 17 Permit No. LA0042731 Al No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)

During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 006, the intermittent discharge of clarifier underflow.

Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic Discharge Limitations Monitorinq Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average Maximum Average Maximum Frequency

(*1) Type Flow-MGD 50050 --- Report 1-- l/day Estimate COAGULANTS The quantity and types of all coagulants (clarifying agents) used in the intake raw river water treatment clarification system during the sampling month shall be recorded.

Records of the quantity and type of coagulants used shall be retained for three (3) years. No DMR reporting shall be required.Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):

Outfall 006, at the point of discharge of the underflow from the raw river water intake clarifier.

FOOTNOTE(S):

(*1) When discharging.

PART I Page 17 of 17 Permit No. LA0042731 Al No. 2889 EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS (continued)

During the period beginning the effective date and lasting through the expiration date the permittee is authorized to discharge from: Outfall 007, the discharge of hydrostatic test wastewater Such discharges shall be limited and monitored by the permittee as specified below: Effluent Characteristic

(*1) Discharge Limitations Monitoring Requirements Other Units (lbs/day, UNLESS STATED) (mg/L, UNLESS STATED)STORET Monthly Daily Monthly Daily Measurement Sample Code Average(*2)

Maximum(*3)Average Maximum(*3)

Frequency(*4)

Type Flow-MGD 50050 Report Report 1-- -/discharge Estimate TSS (*5) 00530 ...... ...-90 1/discharge Grab Oil & Grease 03582 ---.. ...15 1/discharge Grab TOC 00680 ...... ...-50 1/discharge Grab Benzene 34030 ...... ...-50 pg/L 1/discharge Grab Total BTEX (*6) 49491 ...... ...-250 /g/L 1/discharge Grab Total Lead 01051 ...... ...-50 1/discharge Grab Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s):

Internal Outfall 007, at the point of discharge from the hydrostatic testing activity, prior to combining with other wastewaters (may be discharged through Outfalls 001, 002, 003, 004, 005, 201, and 401).FOOTNOTE(S):

(*1) Flow, TSS, and Oil and Grease shall be measured on discharges from all new and existing pipelines, flowlines, vessels, or tanks.In addition, Total Organic Carbon (TOC) shall be measured on discharges from existing pipelines, flowlines, vessels, or tanks which have previously been in service; (i.e., those which are not new). Benzene, Total BTEX, and Total Lead shall be measured on discharges from existing pipelines, flowlines, vessels, or tanks which have been used for the storage or transportation of liquid or gaseous petroleum hydrocarbons.

(*2) The flow for the month with the highest monthly average flow shall be reported.(*3) The highest result from any individual hydrostatic test must be reported.(*4) Monitoring is required once prior to discharge.

(*5) Report the TSS concentration of the intake on the DMR along with the concentration of TSS in the effluent, if the effluent is being returned to the same water source from which the intake water was obtained.

In these cases, concurrent sampling of the influent and the effluent is required, and the net value shall not exceed 90 mg/L.(*6) BTEX shall be measured as the sum of benzene, toluene, ethylbenzene, ortho-xylene, and para-xylene as quantified using methods prescribed by the latest approved 40 CFR 136, Tables, A-G.

Page 1 of 20 Permit No. LA0042731 Al No. 2889 PART II OTHER REQUIREMENTS In addition to the standard conditions required in all permits and listed in Part III, the Office has established the following additional requirements in accordance with the Louisiana Water Quality Regulations.

A. This permit does not in any way authorize the permittee to discharge a pollutant not listed or quantified in the application or limited or monitored for in the permit.B. Authorization to discharge pursuant to the conditions of this permit does not relieve the permittee of any liability for damages to state waters or private property.

For discharges to private land, this permit does not relieve the permittee from obtaining proper approval from the landowner for appropriate easements and rights of way.C. For definitions of monitoring and sampling terminology see STANDARD CONDITIONS FOR LPDES PERMITS, Section F.D. 24-HOUR ORAL REPORTING:

DAILY MAXIMUM LIMITATION VIOLATIONS Under the provisions of Part III.D.6.e.(3) of this permit, violations of daily maximum limitations for the following pollutants shall be reported orally to the Office of Environmental Compliance within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> from the time the permittee became aware of the violation followed by a written report in five days.Pollutant(s):

Benzene Lead Total BTEX Total Chromium Total Copper Total Zinc E. COMPOSITE SAMPLING Unless otherwise specified in this permit, the term "24-hour composite sample" means a sample consisting of a minimum of four (4) aliquots of effluent collected at regular intervals over a normal 24-hour operating day and combined in proportion to flow or a sample continuously collected in proportion to flow over a normal 24-hour operating period.F. 40 CFR PART 136 (See LAC 33:IX.4901)

ANALYTICAL REQUIREMENTS Unless otherwise specified in this permit, monitoring shall be conducted according to analytical, apparatus and materials, sample collection, preservation, handling, etc., procedures listed at 40 CFR Part 136, and in particular, Appendices A, B, and C (See LAC 33:IX.4901).

Part II Page 2 of 20 Permit No. LA0042731 Al No. 2889 OTHER REQUIREMENTS (continued)

G. FLOW MEASUREMENT "ESTIMATE" SAMPLE TYPE If the flow measurement sample type in Part I is specified as "estimate", flow measurements shall not be subject to the accuracy provisions established at Part III.C.6 of this permit. The daily flow value may be estimated using best engineering judgement.

H. MINIMUM QUANTIFICATION LEVEL (MQL)If any individual analytical test result is less than the minimum quantification level listed below, a value of zero (0) may be used for that individual result for the Discharge Monitoring Report (DMR) calculations and reporting requirements.

NONCONVENTIONAL Phenolics, Total Recoverable (4AAP)Chlorine (Total Residual)3 -Chlorophenol 4-Chlorophenol 2,3-Dichlorophenol 2,5-Dichlorophenol 2,6-Dichlorophenol 3,4-Dichlorophenol 2,4-D 2,4,5-TP (Silvex)METALS AND CYANIDE Aluminum (Total)Antimony (Total)Arsenic (Total)Beryllium (Total)Cadmium (Total)Chromium (Total)Chromium (3+)Chromium (6+)Copper (Total)Lead (Total)Mercury (Total)Molybdenum (Total)Nickel (Total) Freshwater Nickel (Total) Marine Selenium (Total)Silver (Total)Thallium (Total)Zinc (Total)Cyanide (Total)MQL (gg/L)5 33 10 10 10 10 10 10 10 4 MOL (gg/L)2.5 60 5 0.5 1 10 10 10 3 2 0.005 30 5 5 5 0.5 0.5 20 10 MOL (gg/L)0.00001 DIOXIN 2,3,7,8-TCDD Part II Page 3 of 20 Permit No. LA0042731 AI No. 2889 OTHER REQUIREMENTS (continued)

VOLATILE COMPOUNDS Acrolein Acrylonitrile Benzene Bromoform Carbon Tetrachloride Chlorobenzene Chlorodibromomethane Chloroethane 2-Chloroethylvinylether Chloroform 1,2-Dichlorobenzene 1,3-Dichlorobenzene 1,4-Dichlorobenzene Dichlorobromomethane 1,1 -Dichloroethane 1,2-Dichloroethane 1,1 -Dichloroethylene 1,2-Dichloropropane 1,3-Dichloropropylene Ethylbenzene Methyl Bromide [Bromomethane]

Methyl Chloride [Chloromethane]

Methylene Chloride 1,1,2,2-Tetrachloroethane Tetrachloroethylene Toluene 1,2-trans-Dichloroethylene 1,1,1 -Trichloroethane 1,1,2-Trichloroethane Trichloroethylene Vinyl Chloride MOL (iggL)50 20 10 10 2 10 10 50 10 10 10 10 10 10 10 10 10 10 10 10 50 50 20 10 10 10 10 10 10 10 10 MOL (WWg/L)10 10 10 50 50 20 50 10 5 10 10 MOL (gg/L)10 10 10 ACID COMPOUNDS 2-Chlorophenol 2,4-Dichlorophenol 2,4-Dimethylphenol 4,6-Dinitro-o-Cresol

[2-Methyl-4,6-Dinitrophenol]

2,4-Dinitrophenol 2-Nitrophenol 4-Nitrophenol p-Chloro-m-Cresol

[4-Chloro-3-Methylphenol]

Pentachlorophenol Phenol 2,4,6-Trichlorophenol BASE/NEUTRAL COMPOUNDS Acenaphthene Acenaphthylene Anthracene Part II Page 4 of 20 Permit No. LA0042731 AI No. 2889 OTHER REQUIREMENTS (continued)

Benzidine 50 Benzo(a)anthracene 5 Benzo(a)pyrene 5 3,4-Benzofluoranthene 10 Benzo(ghi)perylene 20 Benzo(k)fluoranthene 5 Bis(2-chloroethoxy)

Methane 10 Bis(2-chloroethyl)

Ether 10 Bis(2-chloroisopropyl)

Ether 10 Bis(2-ethylhexyl)

Phthalate 10 4-Bromophenyl Phenyl Ether 10 Butylbenzyl Phthalate 10 2-Chloronapthalene 10 4-Chlorophenyl Phenyl Ether 10 Chrysene 5 Dibenzo(a,h)anthracene 5 3,3'-Dichlorobenzidine 5 Diethyl Phthalate 10 Dimethyl Phthalate 10 Di-n-Butyl Phthalate 10 2,4-Dinitrotoluene 10 2,6-Dinitrotoluene 10 Di-n-octyl Phthalate 10 1,2-Diphenylhydrazine 20 Fluoranthene 10 Fluorene 10 Hexachlorobenzene 5 Hexachlorobutadiene 10 Hexachlorocyclopentadiene 10 Hexachloroethane 20 Indeno(1,2,3-cd)pyrene

[2,3-o-Phenylene Pyrene] 5 Isophorone 10 Naphthalene 10 Nitrobenzene 10 n-Nitrosodimethylamine 50 n-Nitrosodi-n-Propylamine 20 n-Nitrosodiphenylamine 20 Phenanthrene 10 Pyrene 10 1,2,4-Trichlorobenzene 10 PESTICIDES MOL (1ýg/L)Aldrin 0.01 Alpha-BHC 0.05 Beta-BHC 0.05 Gamma-BHC

[Lindane]

0.05 Delta-BHC 0.05 Chlordane 0.2 4,4'-DDT 0.02 4,4'-DDE [p,p-DDX]

0.1 Part II Page 5 of 20 Permit No. LA0042731 Al No. 2889 OTHER REQUIREMENTS (continued) 4,4'-DDD [p,p-TDE]

0.1 Dieldrin 0.02 Alpha-Endosulfan 0.01 Beta-Endosulfan 0.02 Endosulfan Sulfate 0.1 Endrin 0.02 Endrin Aldehyde 0.1 Heptachlor 0.01 Heptachlor Epoxide [BHC-Hexachlorocyclohexane]

0.01 PCB-1242 0.2'PCB-1254 0.2 PCB-1221 0.2 PCB-1232 0.2 PCB-1248 0.2 PCB-1260 0.2 PCB-1016 0.2 Toxaphene 0.3 The permittee may develop an effluent specific method detection limit (MDL) in accordance with Appendix B to 40 CFR Part 136 (See LAC 33:IX.4901).

For any pollutant for which the permittee determines an effluent specific MDL, the permittee shall send to this Office a report containing QA/QC documentation, analytical results, and calculations necessary to demonstrate that the effluent specific MDL was correctly calculated.

An effluent specific minimum quantification level (MQL) shall be determined in accordance with the following calculation:

MQL = 3.3 x MDL Upon written approval by this Office, the effluent specific MQL may be utilized by the permittee for all future Discharge Monitoring Report (DMR) calculations and reporting requirements.

1. The permittee shall achieve compliance with the effluent limitations and monitoring requirements specified for discharges in accordance with the following schedule: Effective date of the permit J. PERMIT REOPENER CLAUSE This permit may be modified, or alternatively, revoked and reissued, to comply with any applicable effluent standard or limitations issued or approved under sections 301(b)(2)(C) and (D); 304(b)(2);

and 307(a)(2) of the Clean Water Act or more stringent discharge limitations and/or additional restrictions in the future to maintain the water quality integrity and the designated uses of the receiving water bodies based upon additional water quality studies and/or TMDL's, if the effluent standard, limitations, water quality studies or TMDL's so issued or approved: 1. Contains different conditions or is otherwise more stringent than any effluent limitation in the permit; or Part II Page 6 of 20 Permit No. LA0042731 Al No. 2889 OTHER REQUIREMENTS (continued)

2. Controls any pollutant not limited in the permit; or 3. Require reassessment due to change in 303(d) status of waterbody; or 4. Incorporates the results of any total maximum daily load allocation, which may be approved for the receiving water body.The Louisiana Department of Environmental Quality (LDEQ) reserves the right to modify or revoke and reissue this permit based upon any changes to established TMDLs for this discharge, or to accommodate for pollutant trading provisions in approved TMDL watersheds as necessary to achieve compliance with water quality standards.

Therefore, prior to upgrading or expanding this facility, the permittee should contact the Department to determine the status of the work being done to establish future effluent limitations and additional permit conditions.

K. PROHIBITION OF PCB DISCHARGES There shall be no discharge of polychlorinated biphenyls (PCBs). The minimum quantification level for PCBs is 0.2 ig/l. If any individual analytical test result for PCBs is less than the minimum quantification level, then a value of zero (0) shall be used for the Discharge Monitoring Report (DMR) calculations and reporting requirements.

L. PROHIBITION OF 126 PRIORITY POLLUTANTS There shall be no discharge of any 126 priority pollutants (40 CFR 423 Appendix A)associated with the chemicals added for cooling tower maintenance, except for Total Chromium and Total Zinc. The minimum quantification levels for the 126 priority pollutants are found in Part II, Paragraph H.M. FREE AVAILABLE CHLORINE The term "free available chlorine" shall mean the value obtained using the amperometric titration method for free available chlorine described in the latest edition of Standard Methods for the Examination of Water and Wastewater.

Free available chlorine may not be discharged from any unit for more than two hours in any one day and not more than one unit in any plant may discharge free available chlorine at any one time.N. TEMPERATURE Daily temperature discharge is defined as the flow-weighted average temperature (FWAT)and, on a daily basis, shall be monitored and recorded in accordance with Part I of this permit. FWAT shall be calculated at equal time intervals not greater than two hours. The method of calculating FWAT is as follows: FWAT = SUMMATION (INSTANTANEOUS FLOW X INSTANTANEOUS TEMPERATURE)

SUMMATION (INSTANTANEOUS FLOW)

Part II Page 7 of 20 Permit No. LA0042731 Al No. 2889 OTHER REQUIREMENTS (continued)"Daily Average Temperature" (also known as monthly average) shall be the arithmetic average of all FWATs calculated during the calendar month."Daily Maximum Temperature" (also known as daily maximum) shall be the highest FWAT calculated during the calendar month.0. CHEMICAL METAL CLEANING WASTE The term "chemical metal cleaning waste" means any wastewater resulting from the cleaning of any metal process equipment with chemical compounds, including but not limited to, boiler tube cleaning.P. METAL CLEANING WASTE The term "metal cleaning waste" means any wastewater resulting from cleaning (with or without chemical cleaning compounds) any metal process equipment including, but not limited to, boiler tube cleaning, boiler fireside cleaning, and air preheater cleaning.Q. LOW VOLUME WASTE SOURCES The term "low volume waste sources" mean, taken collectively as if from one source, wastewater from all sources except those for which specific limitations are otherwise established in this part. Low volume wastes sources include, but are not limited to: wastewaters from wet scrubber air pollution control systems, ion exchange water treatment system, water treatment evaporator blowdown, laboratory and sampling streams, boiler blowdown, floor drains, cooling tower basin cleaning wastes, and recirculating house service water systems. Sanitary and air conditioning wastes are not included.R. ZEBRA MUSSEL TREATMENT The terms and conditions of the most recently approved zebra mussel treatment program submitted by Entergy Operations, Inc., River Bend Station shall be enforceable as if part of this permit.According to Paragraph U. 3.d., "Samples and Composites", of the biomonitoring requirements paragraph of this permit, the permittee must collect composite samples that are"representative of any periodic episodes of chlorination, biocide usage, or other potentially toxic substances discharged on an intermittent basis." Any time the treatment method involves an increase in the concentration of a treatment chemical, a change in the type of treatment chemical used, or if any event occurs that creates the potential for an effluent with a higher toxic nature, additional biomonitoring according to the terms and conditions of the biomonitoring section of Part II of this permit shall be required.The permittee must notifly this Office if changes occur in the zebra mussel control plan and obtain approval prior to initiating the new treatment.

If chlorine is applied to control zebra mussels, the discharge shall not exceed a daily maximum Total Residual Chlorine (TRC)concentration of 0.2 mg/L. Monitoring shall be performed at a frequency of 1/day by grab sample, during periods of chlorine application.

Part II Page 8 of 20 Permit No. LA0042731 Al No. 2889 OTHER REQUIREMENTS (continued)

S. STORMWATER DISCHARGES

1. This section applies to all stormwater discharges from the facility, either through permitted outfalls or through outfalls which are not listed in the permit or as sheet flow.The purpose of the pollution prevention plan is to identify potential sources of pollution that would reasonably be expected to affect the quality of stormwater and identify the practices that will be used to prevent or reduce the pollutants in stormwater discharges.
2. Any runoff leaving the developed areas of the facility, other than the permitted outfall(s), exceeding 50 mg/L TOC, 15 mg/L Oil and Grease, or having a pH less than 6.0 or greater than 9.0 standard units shall be a violation of this permit. Any discharge in excess of these limitations, which is attributable to offsite contamination shall not be considered a violation of this permit. A visual inspection of the facility shall be conducted and a report made annually as described in Paragraph 4 below.3. For first time permit issuance, the permittee shall prepare, implement, and maintain a Storm Water Pollution Prevention Plan (SWP3) within six (6) months of the effective date of the final permit. For renewal permit issuance, the permittee shall review and update, if necessary, a Storm Water Pollution Prevention Plan (SWP3) within six (6)months of the effective date of the final permit. The terms and conditions of the SWP3 shall be an enforceable Part of the permit. If the permittee maintains other plans that contain duplicative information, those plans could be incorporated by reference into the SWP3. Examples of these type plans include, but are not limited to: Spill Prevention Control and Countermeasure Plan (SPCC), Best Management Plan (BMP), Response Plans, etc. EPA document 832-R-92-006 (Storm Water Management for Industrial Activities) may be used as a guidance and may be obtained by writing to the Water Resource Center (RC-4100T), U.S. Environmental Protection Agency, 1200 Pennsylvania Avenue NW, Washington D.C. 20460 or by calling (202) 566-1729 or via the Wetlands Helpline (800) 832-7828.4. The following conditions are applicable to all facilities and shall be included in the SWP3 for the facility.a. The permittee shall conduct an annual inspection of the facility site to identify areas contributing to the storm water discharge from developed areas of the facility and evaluate whether measures to reduce pollutant loadings identified in the SWP3 are adequate and have been properly implemented in accordance with the terms of the permit or whether additional control measures are needed.b. The permittee shall develop a site map which includes all areas where stormwater may contact potential pollutants or substances which can cause pollution.

Any location where reportable quantities leaks or spills have previously occurred are to be documented in the SWP3. The SWP3 shall contain a description of the potential pollutant sources, including, the type and quantity of material present and what action has been taken to assure stormwater precipitation will not directly contact the substances and result in contaminated runoff.c. Where experience indicates a reasonable potential for equipment failure (e.g. a tank overflow or leakage), natural condition of (e.g. precipitation), or other Part II Page 9 of 20 Permit No. LA0042731 AI No. 2889 OTHER REQUIREMENTS (continued) circumstances which result in significant amounts of pollutants reaching surface waters, the SWP3 should include a prediction of the direction, rate of flow and total quantity of pollutants which could be discharged from the facility as a result of each condition or circumstance.

d. The permittee shall maintain for a period of three years a record summarizing the results of the inspection and a certification that the facility is in compliance with the SWP3, and identifying any incidents of noncompliance.

The summary report should contain, at a minimum, the date and time of inspection, name of inspector(s), conditions found, and changes to be made to the SWP3.e. The summary report and the following certification shall be signed in accordance with LAC 33:IX.2503.

The summary report is to be attached to the SWP3 and provided to the Department upon request."I certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted.

Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete.

I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations." Signatory requirements for the certification may be found in Part III, Section D. 10 of this permit.f. The permittee shall make available to the Department, upon request, a copy of the SWP3 and any supporting documentation.

5. The following shall be included in the SWP3, if applicable.
a. The permittee shall utilize all reasonable methods to minimize any adverse impact on the drainage system including but not limited to: i. maintaining adequate roads and driveway surfaces;ii. removing debris and accumulated solids from the drainage system; and iii. cleaning up immediately any spill by sweeping, absorbent pads, or other appropriate methods.b. All spilled product and other spilled wastes shall be immediately cleaned up and disposed of according to all applicable regulations, Spill Prevention and Control (SPC) plans or Spill Prevention Control and Countermeasures (SPCC) plans. Use of detergents, emulsifiers, or dispersants to clean up spilled product is prohibited except where necessary to comply with State or Federal safety regulations (i.e., requirement for non-slippery work surface) except where the cleanup practice does not result in a discharge and does not leave residues exposed to future storm events. In all such cases, initial cleanup shall be done by physical removal and chemical usage shall be minimized.

Part II Page 10 of 20 Permit No. LA0042731 Al No. 2889 OTHER REQUIREMENTS (continued)

c. All equipment, parts, dumpsters, trash bins, petroleum products, chemical solvents, detergents, or other materials exposed to stormwater shall be maintained in a manner which prevents contamination of stormwater by pollutants.
d. All waste fuel, lubricants, coolants, solvents, or other fluids used in the repair or maintenance of vehicles or equipment shall be recycled or contained for proper disposal.

Spills of these materials are to be cleaned up by dry means whenever possible.e. If applicable, all storage tank installations (with a capacity greater than 660 gallons for an individual container, or 1,320 gallons for two or more containers in aggregate within a common storage area) shall be constructed so that a secondary means of containment is provided for the entire contents of the largest tank plus sufficient freeboard to allow for precipitation.

Diked areas should be sufficiently impervious to contain spills.f. All diked areas surrounding storage tanks or stormwater collection basins shall be free of residual oil or other contaminants so as to prevent the accidental discharge of these materials in the event of flooding, dike failure, or improper draining of the diked area. All drains from diked areas shall be equipped with valves which shall be kept in the closed condition except during periods of supervised discharge.

g. All check valves, tanks, drains, or other potential sources of pollutant releases shall be inspected and maintained on a regular basis to assure their proper operation and to prevent the discharge of pollutants.
h. The permittee shall assure compliance with all applicable regulations promulgated under the Louisiana Solid Waste and Resource Recovery Law and the Hazardous Waste Management Law (L.R.S. 30:2151, etc.). Management practices required under above regulations shall be referenced in the SWP3.i. The permittee shall amend the SWP3 whenever there is a change in the facility or change in the operation of the facility which materially increases the potential for the ancillary activities to result in a discharge of significant amounts of pollutants.
j. If the SWP3 proves to be ineffective in achieving the general objectives of preventing the release of significant amounts of pollutants to water of the state, then the specific objectives and requirements of the SWP3 shall be subject to modification to incorporate revised SWP3 requirements.
6. Facility Specific SWP3 Conditions:

None T. DISCHARGE MONITORING REPORTS Monitoring results must be reported on a Discharge Monitoring Report (DMR) form (EPA No. 3320-1 or an approved substitute).

All monitoring reports must be retained for a period of at least three (3) years from the date of the sample measurement.

The permittee shall Part II Page 11 of 20 Permit No. LA0042731 AI No. 2889 OTHER REQUIREMENTS (continued) make available to this Department, upon request, copies of all monitoring data required by this permit.If there is no discharge during the reporting period, place an "X" in the NO DISCHARGE box located in the upper right comer of the Discharge Monitoring Report for that outfall.Monitoring results for each reporting period shall be summarized on a Discharge Monitoring Report (DMR) Form (one DMR form per monitoring period per outfall) and submitted to the Office of Environmental Compliance either hand delivered, postmarked, or electronically submitted in accordance with LAC 33:1.2101.A and B no later than the 15th day of the month following each reporting period.1. For parameter(s) with monitoring frequencies of 1/month or more frequent (i.e.continuous, 1/batch, l/discharge event, 1/day, 3/week, 2/week, 1/week, 2/month, etc.), DMRs shall be submitted in accordance with the following schedule: Submit DMR postmarked by the 15th day of the following month.2. For parameter(s) that require a monitoring frequency of 1/ 2 months, DMRs shall be submitted in accordance with the following schedule: Monitoring Period January -June July -December DMR Postmark Date July 15th January 15th 3. For parameter(s) that require a monitoring frequency of quarterly, DMRs shall be submitted in accordance with the following schedule: Monitoring Period January, February, March April, May, June July, August, September October, November, December DMR Postmark Date April 15th July 15th October 15th January 15th 4. For parameter(s) that require a semiannual monitoring frequency, DMRs shall be submitted in accordance with the following schedule: Monitoring Period January -June July -December DMR Postmark Date July 15th January 15th 5. For parameter(s) that require an annual monitoring frequency, DMRs shall be submitted in accordance with the following schedule: Monitoring Period January-December DMR Postmark Date January 15th Part II Page 12 of 20 Permit No. LA0042731 Al No. 2889 OTHER REQUIREMENTS (continued)

For facilities with individually permitted hydrostatic test water discharges, the monitoring results for each hydrostatic test shall be summarized and reported on a Discharge Monitoring Report (DMR) form EPA 3320-1 or an approved substitute, and submitted to the Office of Environmental Compliance on a quarterly basis (in accordance with the quarterly submittal schedule above). If there is no discharge during an entire quarter, the DMR shall be submitted with "No Discharge" written in the upper right comer of the DMR.If not submitting electronically, duplicate sets of DMR's (one set of originals and one set of copies) signed and certified as required by LAC 33:IX.2503, and all other reports (one set of originals) required by this permit shall be submitted to the Permit Compliance Unit at the following address: Department of Environmental Quality Office of Environmental Compliance Permit Compliance Unit Post Office Box 4312 Baton Rouge, Louisiana 70821-4312 U. 48 HR ACUTE BIOMONITORING REQUIREMENTS:

FRESHWATER It is unlawful and a violation of this permit for a permittee or the designated agent to manipulate test samples in any manner, to delay shipment, or to terminate a toxicity test.Once initiated, all toxicity tests must be completed unless specific authority has been granted by the Louisiana Department of Environmental Quality.1. SCOPE AND METHODOLOGY

a. The permittee shall test the effluent for toxicity in accordance with the provisions in this section.APPLICABLE TO OUTFALL(S):

001 CRITICAL DILUTION:

0.14%EFFLUENT DILUTION SERIES: 0.06%, 0.08%, 0.11%, 0.14%, and 0.19%COMPOSITE SAMPLE TYPE: Defined at PART I TEST SPECIES/METHODS:

40 CFR Part 136 (See LAC 33:IX.4901)

Daphnia pulex acute static renewal 48-hour definitive toxicity test using EPA 821-R-02-012, or the latest update thereof. A minimum of five (5)replicates with ten (10) organisms per replicate must be used in the control and in each effluent dilution of this test.Pimephales promelas (Fathead minnow) acute static renewal 48-hour definitive toxicity test using EPA 821-R-02-012, or the latest update Part II Page 13 of 20 Permit No. LA0042731 AI No. 2889 OTHER REQUIREMENTS (continued) thereof. A minimum of five (5) replicates with ten (10) organisms per replicate must be used in the control and in each effluent dilution of this test.b. The NOEC (No Observed Effect Concentration) is defined as the greatest effluent dilution at and below which lethality that is statistically different from the control (0% effluent) at the 95% confidence level does not occur.c. This permit may be reopened to require whole effluent toxicity limits, chemical specific effluent limits, additional testing, and/or other appropriate actions to address toxicity.d. Test failure is defined as a demonstration of statistically significant sub-lethal or lethal effects to a test species at or below the effluent critical dilution.2. PERSISTENT LETHALITY The requirements of this subsection apply only when a toxicity test demonstrates significant lethal effects at or below the critical dilution.

Significant lethal effects are herein defined as a statistically significant difference at the 95% confidence level between the survival of the appropriate test organism in a specified effluent dilution and the control (0% effluent).

If any valid test demonstrates significant lethal effects to a test species at or below the critical dilution, the frequency of testing for that species is automatically increased to once per quarter for the term of the permit.a. The permittee shall conduct a total of three (3) additional tests for any species that demonstrates statistically significant lethal toxic effects at the critical dilution or lower effluent dilutions.

The additional tests shall be conducted monthly during the next three consecutive months in which a discharge occurs to determine if toxicity is persistent or occurs on a periodic basis. The purpose of this testing is to determine whether toxicity is present at a level and frequency that will provide toxic sample results to use in performing a Toxicity Reduction Evaluation (TRE). If no additional test failures occur during the retest monitoring period, the testing frequency will be once per quarter for the term of the permit or until another test failure occurs. The permittee may substitute one of the additional tests in lieu of one routine toxicity test. A full report shall be prepared for each test required by this section in accordance with procedures outlined in Item 4 of this section and submitted with the period discharge monitoring report (DMR) to the permitting authority for review.b. If any of the valid additional tests demonstrates significant lethal effects at or below the critical dilution, the permittee shall initiate Toxicity Reduction Evaluation (TRE) requirements as specified in Item 6 of this section. The permittee shall notify the Department of Environmental Quality, Office of Environmental Compliance

-Permit Compliance Unit in writing within 5 days of the failure in any retest, and the TRE initiation date will be the test Part II Page 14 of 20 Permit No. LA0042731 AI No. 2889 OTHER REQUIREMENTS (continued) completion date of the first failed retest. A TRE may also be required due to a demonstration of intermittent lethal effects at or below the critical dilution, or for failure to perform the required retests.c. The provisions of Item 2.a are suspended upon submittal of the TRE Action Plan.3. REQUIRED TOXICITY TESTING CONDITIONS

a. Test Acceptance The permittee shall repeat a test, including the control and all effluent dilutions, if the procedures and quality assurance requirements defined in the test methods or in this permit are not satisfied, including the following additional criteria: i. Each toxicity test control (0% effluent) must have a survival equal to or greater than 90%.ii. The percent coefficient of variation between replicates shall be 40% or less in the control (0% effluent) for: Daphnia pulex survival test; and Fathead minnow survival test.iii. The percent coefficient of variation between replicates shall be 40% or less in the critical dilution, unless significant lethal effects are exhibited for: Daphnia pulex survival test; and Fathead minnow survival test.Test failure may not be construed or reported as invalid due to a coefficient of variation value of greater than 40%. A repeat test shall be conducted within the required reporting period of any test determined to be invalid.b. Statistical Interpretation For the Daphnia pulex survival test and the Fathead minnow survival test, the statistical analyses used to determine if there is a statistically significant difference between the control and the critical dilution shall be in accordance with the methods for determining the No Observed Effect Concentration (NOEC) as described in EPA 821-R-02-012, or the most recent update thereof.If the conditions of Test Acceptability are met in Item 3.a above and the percent survival of the test organism is equal to or greater than 90% in the critical dilution concentration and all lower dilution concentrations, the test shall be considered to be a passing test regardless of the NOEC, and the permittee shall report a NOEC of not less than the critical dilution for the DMR reporting requirements found in Item 4 below.

Part II Page 15 of 20 Permit No. LA0042731 Al No. 2889 OTHER REQUIREMENTS (continued)

c. Dilution Water Dilution water used in the toxicity tests will be receiving water collected as close to the point of discharge as possible but unaffected by the discharge.

The permittee shall substitute synthetic dilution water of similar pH, hardness and alkalinity to the closest downstream perennial water for;(A) toxicity tests conducted on effluent discharges to receiving water classified as intermittent streams; and (B) toxicity tests conducted on effluent discharges where no receiving water is available due to zero flow conditions.

ii. If the receiving water is unsatisfactory as a result of instream toxicity (fails to fulfill the test acceptance criteria of Item 3.a), the permittee may substitute synthetic dilution water for the receiving water in all subsequent tests provided the unacceptable receiving water test met the following stipulations: (A) a synthetic dilution water control which fulfills the test acceptance requirements of Item 3.a was run concurrently with the receiving water control;(B) the test indicating receiving water toxicity has been carried out to completion (i.e., 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />);(C) the permittee includes all test results indicating receiving water toxicity with the full report and information required by Item 4 below; and (D) The synthetic dilution water shall have a pH, hardness and alkalinity similar to that of the receiving water or closest downstream perennial water not adversely affected by the discharge, provided the magnitude of these parameters will not cause toxicity in the synthetic dilution water.d. Samples and Composites

i. The permittee shall collect two 24-hour flow-weighted composite samples from the outfall(s) listed at Item L.a above. A 24-hour composite sample consists of a minimum of 4 effluent portions collected at equal time intervals representative of a 24-hour operating day and combined proportional to flow or a sample continuously collected proportional to flow over a 24-hour operating day.ii. The permittee shall collect a second 24-hour composite sample for use during the 24-hour renewal of each dilution concentration for both tests. The permittee must collect the 24-hour composite samples so that the maximum holding time for any effluent sample shall not Part II Page 16 of 20 Permit No. LA0042731 AI No. 2889 OTHER REQUIREMENTS (continued) exceed 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. The permittee must have initiated the toxicity test within 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> after the collection of the last portion of the first 24-hour composite sample. Samples shall be chilled to 0-6 degrees Centigrade during collection, shipping and/or storage.iii. The permittee must collect the 24-hour composite samples such that the effluent samples are representative of any periodic episode of chlorination, biocide usage or other potentially toxic substance discharged on an intermittent basis.iv. If the flow from the outfall(s) being tested ceases during the collection of effluent samples, the requirements for the minimum number of effluent samples, the minimum number of effluent portions and the sample holding time are waived during that sampling period.However, the permittee must collect an effluent composite sample volume during the period of discharge that is sufficient to complete the required toxicity tests with daily renewal of effluent.

When possible, the effluent samples used for the toxicity tests shall be collected on separate days. The effluent composite sample collection duration and the static renewal protocol associated with the abbreviated sample collection must be documented in the full report required in Item 4. of this section.4. REPORTING a. A valid test must be completed and test results must be submitted for each species during each Monitoring Period. The permittee shall prepare a full report of the results of all tests conducted pursuant to this Part in accordance with the Report Preparation Section of EPA 821-R-02-012, for every valid or invalid toxicity test initiated, whether carried to completion or not. The permittee shall retain each full report pursuant to the provisions of Part III.C.3 of this permit. For any test which fails, is considered invalid or which is terminated early for any reason, the full report must be submitted for agency review. The permittee shall submit the first full report to the following address: Department of Environmental Quality Office of Environmental Compliance Enforcement Division P.O. Box 4312 Baton Rouge, Louisiana 70821-4312 Attn: Permit Compliance Unit In addition, if enforcement authority has been retained by EPA, a copy of the report must also be submitted to the following address: U.S. Environmental Protection Agency, Region 6 Water Enforcement Branch, 6 EN-WC 1445 Ross Ave.Dallas, Texas 75202 Part II Page 17 of 20 Permit No. LA0042731 Al No. 2889 OTHER REQUIREMENTS (continued)

b. The permittee shall submit the results of each valid toxicity test on the DMR for that Monitoring Period in accordance with Part III.D.4 of this permit. Submit retest information clearly marked as such on the DMR for the Monitoring Period in which the retest occurred.

Only results of valid tests are to be reported on the DMR. The permittee shall submit the Table 1 Summary Sheet with each valid test.i. Pimephales promelas (Fathead minnow)(A) If the No Observed Effect Concentration (NOEC) for survival is less than the critical dilution, enter a "1"; otherwise, enter a "0" for Parameter No. TEM6C.(B) Report the NOEC value for survival, Parameter No. TOM6C.(C) Report the highest (critical dilution or control) Coefficient of Variation, Parameter No. TQM6C.ii. Daphnia pulex (A) If the NOEC for survival is less than the critical dilution, enter a "1";otherwise, enter a "0" for Parameter No. TEM3D.(B) Report the NOEC value for survival, Parameter No. TOM3D.(C) Report the highest (critical dilution or control) Coefficient of Variation, Parameter No. TQM3D.iii. The permittee shall report the following results for all VALID toxicity retests on the DMR for that Monitoring Period.(A) Retest #1 (STORET 22415): If the first monthly retest following failure of a routine test for either test species results in an NOEC for survival less than the critical dilution, report a "1 "; otherwise, report a t'o".(B) Retest #2 (STORET 22416): If the second monthly retest following failure of a routine test for either test species results in an NOEC for survival less than the critical dilution, report a "1"; otherwise, report a"1011.(C) Retest #3 (STORET 51443): If the third monthly retest following failure of a routine test for either test species results in an NOEC for survival less than the critical dilution, report a "1 "; otherwise, report a 11011.If, for any reason, a retest cannot be performed during the Monitoring Period in which the triggering routine test failure is experienced, the permittee shall report it on the following Monitoring Period's DMR, and the comments section of the DMRs shall be annotated to that effect. If Part II Page 18 of 20 Permit No. LA0042731 Al No. 2889 OTHER REQUIREMENTS (continued) retesting is not required during a given Monitoring Period, the permittee shall leave these DMR fields blank.The permittee shall submit the toxicity testing information contained in Table 1 of this permit with the DMR subsequent to each and every toxicity test Monitoring Period. The DMR and the summary tables should be sent to the address indicated in 4.a.5. MONITORING FREQUENCY REDUCTION a. Upon successfully passing the first four quarters of WET testing after permit issuance/reissuance and in the absence of subsequent lethal toxicity for one or both test species at or below the critical dilution, the permittee may apply for a testing frequency reduction.

If granted, the monitoring frequency for that test species may be reduced to not less than once per year for the less sensitive species (usually the Fathead minnow) and not less than once per six months for the more sensitive test species (usually the Daphnia pulex). Monitoring frequency reduction shall not apply to monitoring frequencies of once per year.b. CERTIFICATION

-The permittee must certify in writing that no test failures have occurred and that all tests meet all test acceptability criteria in Item 3.a.above. In addition, the permittee must provide a list with each test performed including test initiation date, species, NOEC's for lethal and sub-lethal effects and the maximum coefficient of variation for the controls.

Upon review and acceptance of this information the agency will issue a letter of confirmation of the monitoring frequency reduction.

A copy of the letter will be forwarded to the agency's Permit Compliance Unit to update the permit reporting requirements.

c. This monitoring frequency reduction applies only until the expiration date of this permit, at which time the Monitoring Frequency/Monitoring Period for both test species reverts to once per quarter until the permit is re-issued.
d. SURVIVAL FAILURES -If any test fails the survival endpoint at any time during the term of this permit, three monthly retests are required and the monitoring frequency for the affected test species shall be increased to once per quarter until the permit is reissued.

Monthly retesting is not required if the permittee is performing a TRE.6. TOXICITY REDUCTION EVALUATION (TRE)a. Within ninety (90) days of confirming lethality in the retests, the permittee shall submit a Toxicity Reduction Evaluation (TRE) Action Plan and Schedule for conducting a TRE. The TRE Action Plan shall specify the approach and methodology to be used in performing the TRE. A Toxicity Reduction Evaluation is an investigation intended to determine those actions necessary to achieve compliance with water quality-based effluent requirements/and or chemical-specific limits by reducing an effluent's toxicity to an acceptable level. A TRE is defined as a step-wise process which combines toxicity testing and analyses of the physical and chemical characteristics of a toxic effluent to identify the constituents causing effluent toxicity and/or treatment methods which will reduce Part II Page 19 of 20 Permit No. LA0042731 AI No. 2889 OTHER REQUIREMENTS (continued) the effluent toxicity.

The TRE Action Plan shall lead to the successful elimination of effluent toxicity at the critical dilution and include the following:

1. Specific Activities.

The plan shall detail the specific approach the permittee intends to utilize in conducting the TRE. The approach may include toxicity characterizations, identifications and confirmation activities, source evaluation, treatability studies, or alternative approaches.

When the permittee conducts Toxicity Characterization Procedures the permnittee shall perform multiple characterizations and follow the procedures specified in the document "Methods for Aquatic Toxicity Identification Evaluations:

Phase I Toxicity Characterization Procedures" (EPA-600/6-91/003) or alternate procedures.

When the permittee conducts Toxicity Identification Evaluations and Confirmations, the permittee shall perform multiple identifications and follow the methods specified in the documents "Methods for Aquatic Toxicity Identification Evaluations, Phase II Toxicity Identification Procedures for Samples Exhibiting Acute and Chronic Toxicity" (EPA/600/R-92/080) and "Methods for Aquatic Toxicity Identification Evaluations, Phase III Toxicity Confirmation Procedures for Samples Exhibiting Acute and Chronic Toxicity" (EPA/600/R-92/081), as appropriate.

The documents referenced above may be obtained through the National Technical Information Service (NTIS) by phone at (703) 487-4650, or by writing: U.S. Department of Commerce National Technical Information Service 5285 Port Royal Road Springfield, Va. 22161 ii. Sampling Plan (e.g., locations, methods, holding times, chain of custody, preservation, etc.). The effluent sample volume collected for all tests shall be adequate to perform the toxicity test, toxicity characterization, identification and confirmation procedures, and conduct chemical specific analyses when a probable toxicant has been identified; Where the permittee has identified or suspects specific pollutant(s) and/or source(s) of effluent toxicity, the permittee shall conduct, concurrent with toxicity testing, chemical specific analyses for the identified and/or suspected pollutant(s) and/or source(s) of effluent toxicity.

Where lethality was demonstrated within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of test initiation, each composite sample shall be analyzed independently.

Otherwise the permittee may substitute a composite sample, comprised of equal portions of the individual composite samples, for the chemical specific analysis;iii. Quality Assurance Plan (e.g., QA/QC implementation, corrective actions, etc.); and iv. Project Organization (e.g., project staff, project manager, consulting services, etc.).

Part II Page 20 of 20 Permit No. LA0042731 AI No. 2889 OTHER REQUIREMENTS (continued)

b. The permittee shall initiate the TRE Action Plan within thirty (30) days of plan and schedule submittal.

The permittee shall assume all risks for failure to achieve the required toxicity reduction.

c. The permittee shall submit a quarterly TRE Activities Report, with the Discharge Monitoring Report in the months of January, April, July and October, containing information on toxicity reduction evaluation activities including:
i. any data and/or substantiating documentation which identify the pollutant(s) and/or source(s) of effluent toxicity;ii. any studies/evaluations and results on the treatability of the facility's effluent toxicity; and iii. any data which identify effluent toxicity control mechanisms that will reduce effluent toxicity to the level necessary to achieve compliance with permit biomonitoring requirements and/or chemical-specific limits.The TRE Activities Report shall be submitted to the following addresses:

Department of Environmental Quality Office of Environmental Compliance Enforcement Division P.O. Box 4312 Baton Rouge, Louisiana 70821-4312 Attn: Permit Compliance Unit U.S. Environmental Protection Agency, Region 6 Water Enforcement Branch, 6 EN-WC 1445 Ross Avenue Dallas, Texas 75202 d. The permittee shall submit a Final Report on Toxicity Reduction Evaluation Activities no later than twenty-eight (28) months from confirming lethality in the retests, which provides information pertaining to the specific control mechanism selected that will, when implemented, result in the permittee achieving compliance with permit biomonitoring requirements and/or chemical-specific limits. The report will also provide a specific corrective action schedule for implementing the selected control mechanism.

A copy of the Final Report on Toxicity Reduction Evaluation Activities shall also be submitted to the above addresses.

e. Quarterly testing during the TRE is a minimum monitoring requirement.

LDEQ recommends that permittees required to perform a TRE not rely on quarterly testing alone to ensure success in the TRE, and that additional screening tests be performed to capture toxic samples for identification of toxicants.

At the end of the TRE, LDEQ will consider all information submitted and establish appropriate controls to prevent future toxic discharges, including WET and/or chemical-specific limits per state regulations at LAC 33:IX.2707.D.1 .e.

TABLE 1

SUMMARY

SHEET Daphnia pulex ACUTE SURVIVAL TEST RESULTS PERMITTEE:

Entergy Operations, Inc.FACILITY SITE: River Bend Station LPDES PERMIT NUMBER: LA0042731/

AI 2889 OUTFALL IDENTIFICATION:

001 OUTFALL SAMPLE IS FROM SINGLE MULTIPLE DISC BIOMONITORING LABORATORY:

DILUTION WATER USED: RECEIVING WATER LAB W CRITICAL DILUTION 0.14% DATE TEST INITIATED HARGES ATER 1. LOW-FLOW LETHALITY:

Is the mean survival at 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> significantly less (p=0.05) than the control survival for the low flow or critical dilution?__ yes no DILUTION SERIES RESULTS-DAPHNIA TIME OF REP 0% 0.06% 0.08% 0.11% 0.14% 0.19%READING A 24-HOUR B C D E A 48-HOUR B C D E I MEAN 2. Are the test results to be considered valid? _yes _no If X no (test invalid), what are the reasons for invalidity?

3. Is this a retest of a previous invalid test? __yes no Is this a retest of a previous test failure? yes no 4. Enter percent effluent corresponding to each NOEC (No Observed Effect Concentration) for Daphnia pulex: NOEC _% effluent LC504 8 % effluent TABLE 1

SUMMARY

SHEET Pimephales promelas ACUTE SURVIVAL TEST RESULTS PERMITTEE:

Entergy Operations, Inc.FACILITY SITE: River Bend Station LPDES PERMIT NUMBER: LA0042731/

AI 2889 OUTFALL IDENTIFICATION:

001 OUTFALL SAMPLE IS FROM SINGLE MULTIPLE DISCHARGES BIOMONITORING LABORATORY:

DILUTION WATER USED: RECEIVING WATER LAB WATER CRITICAL DILUTION 0.14% DATE TEST INITIATED 1. LOW-FLOW LETHALITY:

Is the mean survival at 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> significantly less (p=0.05) than the control survival for the low flow or critical dilution?_ _ yes -no DILUTION SERIES RESULTS-PIMEPHALES TIME OF REP 0% 0.06% 0.08% 0.11% 0.14% 0.19%READING A 24-HOUR B C D E A 48 -HOUR B C D 2. Are the test results to be considered valid? _ yes _ no if X no (test invalid), what are the reasons for invalidity?

3. Is this a retest of a previous invalid test? __yes no Is this a retest of a previous test failure? __yes no 4. Enter percent effluent corresponding to each NOEC (No Observed Effect Concentration) for Pimephales:

NOEC =% effluent LC4-4 8 =W effluent REVISED- 013-23-11 Paae 1 of 18 PART III STANDARD CONDITIONS FOR LPDES PERMITS SECTION A. GENERAL CONDITIONS

1. Introduction In accordance with the provisions of LAC 33:X.2701, et seq., this permit incorporates either expressly or by reference ALL conditions and requirements applicable to the Louisiana Pollutant Discharge Elimination System Permits (LPDES) set forth in the Louisiana Environmental Quality Act (LEQA), as amended, as well as ALL applicable regulations.
2. Duty to Comply The permittee must comply with all conditions of this permit. Any permit noncompliance constitutes a violation of the Clean Water Act (CWA) and the Louisiana Environmental Quality Act and is grounds for enforcement action; for permit termination, revocation and reissuance, or modification:

or for denial of a permit renewal application.

3. Penalties for Violation of Permit Conditions
a. La. R. S. 30:2025 provides for civil penalties for violations of these regulations and the Louisiana Environmental Quality Act. La. R. S. 30:2076.2 provides for criminal penalties for violation of any provisions of the LPDES or any order or any permit condition or limitation issued under or implementing any provisions of the LPDES program. (See Section E. Penalties for Violation of Permit Conditions for additional details).b. Any person may be assessed an administrative penalty by the State Administrative Authority under La.R. S. 30:2025 for violating a permit condition or limitation implementing any of the requirements of the LPDES program in a permit issued under the regulations or the Louisiana Environmental Quality Act.4. Toxic Pollutants
a. Other effluent limitations and standards under Sections 301, 302, 303, 307, 318, and 405 of the Clean Water Act. If any applicable toxic effluent standard or prohibition (including any schedule of compliance specified in such effluent standard or prohibition) is promulgated under Section 307(a) of the Clean Water Act for a toxic pollutant and that standard or prohibition is more stringent than any limitation on the pollutant in this permit, the state administrative authority shall institute proceedings under these regulations to modify or revoke and reissue the permit to conform to the toxic effluent standard or prohibition.
b. The permittee shall comply with effluent standards or prohibitions established under Section 307(a) of the Clean Water Act for toxic pollutants and with standards for sewage sludge use or disposal established under Section 405(d) of the Clean Water Act within the time provided in the regulations that establish these standards or prohibitions, or standards for sewage sludge use or disposal, even if the permit has not yet been modified to incorporate the requirement.
5. Duty to Reapply a. Individual Permits. If the permittee wishes to continue an activity regulated by this permit after the expiration date of this permit, the permittee must apply for and obtain a new permit. The new application shall be submitted at least 180 days before the expiration date of the existing permit, unless permission for a later date has been granted by the state administrative authority. (The state administrative authority shall not grant permission for applications to be submitted later than the expiration date of the existing permit.) Continuation of expiring permits shall be governed by regulations promulgated at LAC 33:IX.2321 and any subsequent amendments.

form 7027 r08 3-23-11 REVISED 03-23-11 Paqe 2 of 18 b. General Permits. General permits expire five years after the effective date. The 180-day reapplication period as defined above is not applicable to general permit authorizations.

Reissued general permits may provide automatic coverage for permittees authorized under the previous version of the permit, and no new application is required.

Requirements for obtaining authorization under the reissued general permit will be outlined in Part I of the new permit. Permittees authorized to discharge under an expiring general permit should follow the requirements for obtaining coverage under the new general permit to maintain discharge authorization.

6. Permit Action This permit may be modified, revoked and reissued, or terminated for cause in accordance with LAC 33:1IX.2903, 2905, 2907, 3105 and 6509. The causes may include, but are not limited to, the following:
a. Noncompliance by the permittee with any condition of the permit;b. The permittee's failure in the application or during the permit issuance process to disclose fully all relevant facts, or the permittee's misrepresentation of any relevant facts at any time; or c. A determination that the permitted activity endangers human health or the environment and can only be regulated to acceptable levels by permit modification or termination;
d. A change in any condition that requires either a temporary or a permanent reduction or elimination of any discharge;
e. Failure to pay applicable fees under the provisions of LAC 33: IX. Chapter 13;f. Change of ownership or operational control.The filing of a request by the permittee for a permit modification, revocation and reissuance, or termination, or a notification of planned changes or anticipated noncompliance does not stay any permit condition.
7. Property Rights and State and Local Laws Issuance of this permit does not authorize any injury to persons or property or invasion of other private rights, or any infringement of state or local law or regulations.
8. Duty to Provide Information The permittee shall furnish to the state administrative authority, within a reasonable time, any information which the state administrative authority may request to determine whether cause exists for modifying, revoking and reissuing, or terminating this permit, or to determine compliance with this permit. The permittee shall also furnish to the state administrative authority, upon request, copies of records required to be kept by this permit.9. Criminal and Civil Liability Except as provided in permit conditions on "Bypassing" and "Upsets", nothing in this permit shall be construed to relieve the permittee from civil or criminal penalties for noncompliance.

Any false or materially misleading representation or concealment of information required to be reported by the provisions of the permit, the Act, or applicable regulations, which avoids or effectively defeats the regulatory purpose of the Permit may subject the Permittee to criminal enforcement pursuant to La. R.S. 30:2025.10. Oil and Hazardous Substance Liability Nothing in this permit shall be construed to preclude the institution of any legal action or relieve the permittee from any responsibilities, liabilities, or penalties to which the permittee is or may be subject under Section 311 of the Clean Water Act.form 7027 r08 3-23-11 IRI=:VI£FD A3-73-11 Pnae 3 of 18 11. State Laws Nothing in this permit shall be construed to preclude the institution of any legal action or relieve the permittee from any responsibilities, liabilities, or penalties established pursuant to any applicable State law or regulation under authority preserved by Section 510 of the Clean Water Act.12. Severability If any provision of these rules and regulations, or the application thereof, is held to be invalid, the remaining provisions of these rules and regulations shall not be affected, so long as they can be given effect without the invalid provision.

To this end, the provisions of these rules and regulations are declared to be severable.

13. Dilution A permittee shall not achieve any effluent concentration by dilution unless specifically authorized in the permit. A permittee shall not increase the use of process water or cooling water or otherwise attempt to dilute a discharge as a partial or complete substitute for adequate treatment to achieve permit limitations or water quality.14. Facilities Requiring Approval from Other State Agencies In accordance with La. R.S.40.4(A)(6) the plans and specifications of all sanitary sewerage treatment systems, both public and private, must be approved by the Department of Health and Hospitals state health officer or his designee.

It is unlawful for any person, firm, or corporation, both municipal and private to operate a sanitary sewage treatment facility without proper authorization from the state health officer.In accordance with La. R.S.40.1149, it is unlawful for any person, firm or corporation, both municipal and private, operating a sewerage system to operate that system unless the competency of the operator is duly certified by the Department of Health and Hospitals state health officer. Furthermore, it is unlawful for any person to perform the duties of an operator without being duly certified.

In accordance with La. R.S.48.385, it is unlawful for any industrial wastes, sewage, septic tanks effluent, or any noxious or harmful matter, solid, liquid or gaseous to be discharged into the side or cross ditches or placed upon the rights-of-ways of state highways without the prior written consent of the Department of Transportation and Development chief engineer or his duly authorized representative and of the secretary of the Department of Health and Hospitals.

15. The standards provided in Chapter 11 -Surface Water Quality Standards are official regulations of the state, and any person who discharges pollutants to the waters of the state in such quantities as to cause these standards to be violated shall be subject to the enforcement procedures of the state as specified in R.S. 30:2025.SECTION B. PROPER OPERATION AND MAINTENANCE
1. Need to Halt or Reduce not a Defense It shall not be a defense for a permittee in an enforcement action that it would have been necessary to halt or reduce the permitted activity in order to maintain compliance with the conditions of this permit.2. Duty to Mitigate The permittee shall take all reasonable steps to minimize or prevent any discharge in violation of this permit which has a reasonable likelihood of adversely affecting human health or the environment.

The permittee shall also take all reasonable steps to minimize or correct any adverse impact on the environment resulting from noncompliance with the permit, including such accelerated or additional monitoring as necessary to determine the nature and impact of the noncomplying discharge.

3. Proper Operation and Maintenance
a. The permittee shall at all times properly operate and maintain all facilities and systems of treatment and control (and related appurtenances) which are installed or used by the permittee to achieve compliance with the conditions of this permit. Proper operation and maintenance also includes adequate laboratory controls and appropriate quality assurance procedures.

This provision requires the operation of back-up form_7027_r08 3-23-11 REVISED 03-23-11 Paqle 4 of 18 or auxiliary facilities or similar systems which are installed by a permittee only when the operation is necessary to achieve compliance with the conditions of the permit.b. The permittee shall provide an adequate operating staff which is duly qualified to carry out operation, maintenance and other functions necessary to ensure compliance with the conditions of this permit.4. Bypass of Treatment Facilities

a. Bypass. The intentional diversion of waste streams from any portion of a treatment facility.b. Bypass not exceeding limitations.

The permittee may allow any. bypass to occur which does not cause effluent limitations to be exceeded, but only if it also is for essential maintenance to assure efficient operation.

These bypasses are not subject to the provisions of Section B.4.c. and 4.d of these standard conditions.

c. Notice (1) Anticipated bypass. If the permittee knows in advance of the need for a bypass, it shall submit prior notice to the Office of Environmental Services, Water Permits Division, if possible at least ten days before the date of the bypass.(2) Unanticipated bypass. The permittee shall submit notice of an unanticipated bypass as required in LAC 33:IX.2701 .L.6 (24-hour notice) and Section D.6.e. of these standard conditions.
d. Prohibition of bypass (1) Bypass is prohibited, and the state administrative authority may take enforcement action against a permittee for bypass, unless: (a) Bypass was unavoidable to prevent loss of life, personal injury, or severe property damage;(b) There were no feasible alternatives to the bypass, such as the use of auxiliary treatment facilities, retention of untreated wastes, or maintenance during normal periods of equipment downtime.

This condition is not satisfied if adequate back-up equipment should have been installed in the exercise of reasonable engineering judgment to prevent a bypass which occurred during normal periods of equipment downtime or preventive maintenance; and, (c) The permittee submitted notices as required by Section B.4.c of these standard conditions.

(2) The state administrative authority may approve an anticipated bypass after considering its adverse effects, if the state administrative authority determines that it will meet the three conditions listed in Section B.4.d(1) of these standard conditions.

5. Upset Conditions
a. Upset. An exceptional incident in which there is unintentional and temporary noncompliance with technology-based permit effluent limitations because of factors beyond the reasonable control of the permittee.

An upset does not include noncompliance to the extent caused by operational error, improperly designed treatment facilities, inadequate treatment facilities, lack of preventive maintenance, or careless or improper operation.

-b. Effect of an upset. An upset constitutes an affirmative defense to an action brought for noncompliance with such technology-based permit effluent limitations if the requirements of Section B.5.c. are met. No determination made during administrative review of claims that noncompliance was caused by an upset, and before an action for noncompliance, is final administrative action subject to judicial review.I c. Conditions necessary for a demonstration of upset. A permittee who wishes to establish the affirmative defense of upset shall demonstrate, through properly signed, contemporaneous operating logs, or other relevant evidence that: (1) An upset occurred and that the permittee can identify the cause(s) of the upset;form_7027_r08 3-23-11 REVISED 03-23-11 Paae 5 nf 18 REVISED 3-P3a1e 5 of 18 (2) The permitted facility was at the time being properly operated; and (3) The permittee submitted notice of the upset as required by LAC 33:IX.2701.L.6.b.ii.

and Section D.6.e.(2) of these standard conditions; and (4) The permittee complied with any remedial measures required by Section B.2 of these standard conditions.

d. Burden of proof. In any enforcement proceeding, the permittee seeking to establish the occurrence of an upset has the burden of proof.6. Removed Substances Solids, sewage sludges, filter backwash, or other pollutants removed in the course of treatment or wastewater control shall be properly disposed of in a manner such as to prevent any pollutant from such materials from entering waters of the state and in accordance with environmental regulations.
7. Percent Removal For publicly owned treatment works, the 30-day average percent removal for Biochemical Oxygen Demand and Total Suspended Solids shall not be less than 85 percent in accordance with LAC 33:IX.5905.A.3.

and B.3. Publicly owned treatment works utilizing waste stabilization ponds/oxidation ponds are not subject to the 85 percent removal rate for Total Suspended Solids.SECTION C. MONITORING AND RECORDS 1. Inspection and Entry The permittee shall allow the state administrative authority or an authorized representative (including an authorized contractor acting as a representative of the Administrator), upon the presentation of credentials and other documents as may be required by the law to: a. Enter upon the permittee's premises where a regulated facility or activity is located or conducted, or where records must be kept under the conditions of this permit.Enter upon the permittee's premises where a discharge source is or might be located or in which monitoring equipment or records required by a permit are kept for inspection or sampling purposes.Most inspections will be unannounced and should be allowed to begin immediately, but in no case shall begin more than thirty (30) minutes after the time the inspector presents his/her credentials and announces the purpose(s) of the inspection.

Delay in excess of thirty (30) minutes shall constitute a violation of this permit. However, additional time can be granted if the inspector or the Administrative Authority determines that the circumstances warrant such action; and b. Have access to and copy, at reasonable times, any records that the department or its authorized representative determines are necessary for the enforcement of this permit. For records maintained in either a central or private office that is open only during normal office hours and is closed at the time of inspection, the records shall be made available as soon as the office is open, but in no case later than the close of business the next working day;c. Inspect at reasonable times any facilities, equipment (including monitoring and control equipment), practices, or operations regulated or required under this permit; and d. Sample or monitor at reasonable times, for the purposes of assuring permit compliance or as otherwise authorized by the Clean Water Act or the Louisiana Environmental Quality Act, any substances or parameters at any location.e. Sample Collection (1) When the inspector announces that samples will be collected, the permittee will be given an additional thirty (30) minutes to prepare containers in order to collect duplicates.

If the permittee form_7027 r08 3-23-11 REVISFD 03-23-11 Paae 6 of 18 REVISED .0.3-23-1 1 6f1 cannot obtain and prepare sample containers within this time, he is considered to have waived his right to collect duplicate samples and the sampling will proceed immediately.

Further delay on the part of the permittee in allowing initiation of the sampling will constitute a violation of this permit.(2) At the discretion of the administrative authority, sample collection shall proceed immediately (without the additional 30 minutes described in Section C.i.a. above) and the inspector shall supply the permittee with a duplicate sample.f. It shall be the responsibility of the permittee to ensure that a facility representative familiar with provisions of its wastewater discharge permit, including any other conditions or limitations, be available either by phone or in person at the facility during all hours of operation.

The absence of such personnel on-site who are familiar with the permit shall not be grounds for delaying the initiation of an inspection except in situations as described in Section C.l.b. of these standard conditions.

The permittee shall be responsible for providing witnesses/escorts during inspections.

Inspectors shall abide by all company safety rules and shall be equipped with standard safety equipment (hard hat, safety shoes, safety glasses) normally required by industrial facilities.

g. Upon written request copies of field notes, drawings, etc., taken by department personnel during an inspection shall be provided to the permittee after the final inspection report has been completed.
2. Representative Sampling Samples and measurements taken for the purpose of monitoring shall be representative of the monitored activity.

All samples shall be taken at the outfall location(s) indicated in the permit. The state administrative authority shall be notified prior to any changes in the outfall location(s).

Any changes in the outfall location(s) may be subject to modification, revocation and reissuance in accordance with LAC 33:1IX.2903.

3. Retention of Records Except for records of monitoring information required by this permit related to the permittee's sewage sludge use and disposal activities, which shall be retained for a period of at least five years (or longer as required by 40 CFR 503), the permittee shall retain records of all monitoring information, including all calibration and maintenance records and all original strip chart recordings for continuous monitoring instrumentation, copies of all reports required by this permit, and records of all data used to complete the application for this permit, for a period of at least 3 years from the date of the sample, measurement, report, or application.

This period may be extended by request of the state administrative authority at any time.4. Record Contents Records of monitoring information shall include: a. The date, exact place, and time of sampling or measurements;

b. The individual(s) who performed the sampling or measurements;
c. The date(s) analyses were performed;
d. The time(s) analyses were begun;e. The individual(s) who performed the analyses;f. The analytical techniques or methods used;g. The results of such analyses; and h. The results of all quality control procedures.
5. Monitoring Procedures
a. Monitoring results must be conducted according to test procedures approved under 40 CFR Part 136 or, in the case of sludge use or disposal, approved under 40 CFR Part 136 unless otherwise specified in 40 CFR Part 503, unless other test procedures have been specified in this permit.b. The permittee shall calibrate and perform maintenance procedures on all monitoring and analytical instruments at intervals frequent enough to insure accuracy of measurements and shall maintain appropriate records of such activities.

form 7027 r08 3-23-11 REVISED 03-23-11 Paqe 7 of 18 c. The permittee or designated laboratory shall have an adequate analytical quality assurance/quality control program to produce defensible data of known precision and accuracy.

All quality control measures shall be assessed and evaluated on an on-going basis and quality control acceptance criteria shall be used to determine the validity of the data. All method specific quality control as prescribed in the method shall be followed.

If quality control requirements are not included in the method, the permittee or designated laboratory shall follow the quality control requirements as prescribed in the Approved Edition (40 CFR Part 136) Standard Methods for the Examination of Water and Wastes, Sections 1020A and 1020B. General sampling protocol shall follow guidelines established in the"Handbook for Sampling and Sample Preservation of Water and Wastewater, 1982 "U.S. Environmental Protection Agency. This publication is available from the National Technical Information Service (NTIS), Springfield, VA 22161, Phone number (800) 553-6847.

Order by NTIS publication number PB-83-124503.6. Flow Measurements Appropriate flow measurement devices and methods consistent with accepted scientific practices shall be selected and used to ensure the accuracy and reliability of measurements of the volume of monitored discharges.

The devices shall be installed, calibrated, and maintained to insure that the accuracy of the measurements is consistent with the accepted capability of that type of device. Devices selected shall be capable of measuring flows with a maximum deviation of less than 10% from true discharge rates throughout the range of expected discharge volumes. Guidance in selection, installation, calibration and operation of acceptable flow measurement devices can be obtained from the following references:

a. "A Guide to Methods and Standards for the Measurement of Water Flow, 1975," U.S. Department of Commerce, National Bureau of Standards.

This publication is available from the National Technical Information Service (NTIS), Springfield, VA 22161, Phone number (800) 553-6847.

Order by NTIS publication number COM-75-10683.

b. "Flow Measurement in Open Channels and Closed Conduits, Volumes 1 and 2," U.S. Department of Commerce, National Bureau of Standards.

This publication is available from the National Technical Service (NTIS), Springfield, VA, 22161, Phone number (800) 553-6847.

Order by NTIS publication number PB-273 535.c. "NPDES Compliance Flow Measurement Manual," U.S. Environmental Protection Agency, Office of Water Enforcement.

This publication is available from the National Technical Information Service (NTIS), Springfield, VA 22161, Phone number (800) 553-6847.

Order by NTIS publication number PB-82-131178.

7. Prohibition for Tampering:

Penalties a. La. R.S. 30:2025 provides for punishment of any person who falsifies, tampers with, or knowingly renders inaccurate any monitoring device or method required to be maintained under this permit.b. La. R.S. 30:2076.2 provides for penalties for any person who knowingly makes any false statement, representation, or certification in any record or other document submitted or required to be maintained under this permit, including monitoring reports or reports of compliance or non-compliance.

8. Additional Monitorinq by the Permittee If the Permittee monitors any pollutant more frequently than required by the permit using test procedures approved under 40 CFR Part 136 (See LAC 33:IX.4901) or, in the case of sludge use and disposal, approved under 40 CFR Part 136 (See LAC 33:IX.4901) unless otherwise specified in 40 CFR Part 503, or as specified in the permit, the results of this monitoring shall be included in the calculation and reporting of the data submitted in the DMR or sludge reporting form specified by the state administrative authority.
9. Averaging of Measurements Calculations for all limitations which require averaging of measurements shall utilize an arithmetic mean unless otherwise specified by the state administrative authority in the permit.form_7027_r08 3-23-11 REVISEDF 03-23-11 PaQe 8 of 18 10. Laboratory Accreditation.a. LAC 33:l.Subpart 3, Chapters 45-59 provide requirements for an accreditation program specifically applicable to commercial laboratories, wherever located, that provide chemical analyses, analytical results, or other test data to the department, by contract or by agreement, and the data is: (1) Submitted on behalf of any facility, as defined in La. R.S.30:2004; (2) Required as part of any permit application; (3) Required by order of the department; (4) Required to be included on any monitoring reports submitted to the department; (5) Required to be submitted by contractor (6) Otherwise required by department regulations.
b. The department laboratory accreditation program, Louisiana Environmental Laboratory Accreditation Program (LELAP) is designed to ensure the accuracy, precision, and reliability of the data generated, as well as the use of department-approved methodologies in generation of that data. Laboratory data generated by commercial environmental laboratories that are not (LELAP) accredited will not be accepted by the department.

Retesting of analysis will be required by an accredited commercial laboratory.

Where retesting of effluent is not possible (i.e. data reported on DMRs for prior month's sampling), the data generated will be considered invalid and in violation of the LPDES permit.c. Regulations on the Louisiana Environmental Laboratory Accreditation Program and a list of labs that have applied for accreditation are available on the department website located under DIVISIONS

-*PERMIT SUPPORT SERVICES --) LABORATORY ACCREDITATION at the following link: http://www.deg.louisiana.gov Questions concerning the program may be directed to (225) 219-9800.SECTION D. REPORTING REQUIREMENTS

1. Facility Changes The permittee shall give notice to the state administrative authority as soon as possible of any planned physical alterations or additions to the permitted facility.

Notice is required only when: a. The alteration or addition to a permitted facility may meet one of the criteria for determining whether a facility is a new source in 40 CFR 122.29(b);

or b. The alteration or addition could significantly change the nature or increase the quantity of pollutants discharged.

This notification applies to pollutants which are subject neither to effluent limitations in the permit, nor to notification requirements under LAC 33:IX.2703.A.1.

c. For Municipal Permits. Any new introduction of pollutants into the POTW from an indirect discharger which would be subject to Section 301, or 306 of the CWA if it were directly discharging those pollutants; and any substantial change in the volume or character of pollutants being introduced into that POTW by a source introducing pollutants into the POTW at the time of issuance of the permit. In no case are any new connections, increased flows, or significant changes in influent quality permitted that will cause violation of the effluent limitations specified herein.2. Anticipated Noncompliance The permittee shall give advance notice to the state administrative authority of any planned changes in the permitted facility or activity which may result in noncompliance with permit requirements.
3. Transfers This permit is not transferable to any person except after notice to the state administrative authority.

The state administrative authority may require modification or revocation and reissuance of the permit to change form_7027 rO8 3-23-11 POAn 9 of 18 rCII P' r) 1 1 rI.-VIQ I U -L-J I0_the name of the permittee and incorporate such other requirements as may be necessary under the Clean Water Act or the Louisiana Environmental Quality Act. (See LAC 33:1IX.2901; in some cases, modification or revocation and reissuance is mandatory.)

A permit may be transferred by the permittee to a new owner or operator only if: (1)the permit has been modified or revoked and reissued (under LAC 33:IX.2903.A.2.b) by the permittee and new owner submitting a Name/Ownership/Operator Change Form (NOC-1 Form) and approved by LDEQ (LAC 33:l.Chapter 19).or (2) a minor modification made (under LAC 33:iX.2905) to identify the new permittee and incorporate such other requirements as may be necessary under the Clean Water Act and the Louisiana Environmental Quality Act.The NOC-1 form can be found at the following link: http://www.deg louisiana.gov/portal/Portals/O/assistance/NOC-1`%20FORM%2OJan/`2025,/%202006.

pdf 4. Monitoring Reports Monitoring results shall be reported at the intervals and in the form specified in Part I or Part II of this permit.The permittee shall submit properly completed Discharge Monitoring Reports (DMRs) on the form specified in the permit. Preprinted DMRs are provided to majors/92-500s and other designated facilities.

Please contact the Permit Compliance Unit concerning preprints.

Self-generated DMRs must be pre-approved by the Permit Compliance Unit prior to submittal.

Self-generated DMRs are approved on an individual basis. Requests for approval of self-generated DMRs should be submitted to: Supervisor, Permit Compliance Unit Office of Environmental Compliance Post Office Box 4312 Baton Rouge, LA 70821-4312 Copies of blank DMR templates, plus instructions for completing them, and EPA's LPDES Reporting Handbook are available at the department website located at: http://www.deq.louisiana.gov/portal/Default.aspx?tabid=2276

5. Compliance Schedules Reports of compliance or noncompliance with, or any progress reports on, interim and final requirements contained in any compliance schedule of this permit shall be submitted no later than 14 days following each schedule date.6. Requirements for Notification
a. Emergency Notification As required by LAC 33.1.3915, in the event of an unauthorized discharge that does cause an emergency condition, the discharger shall notify the hotline (DPS 24-hour Louisiana Emergency Hazardous Materials Hotline) by telephone at (225) 925-6595 (collect calls accepted 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> a day) immediately (a reasonable period of time after taking prompt measures to determine the nature, quantity, and potential off-site impact of a release, considering the exigency of the circumstances), but in no case later than one hour after learning of the discharge. (An emergency condition is any condition which could reasonably be expected to endanger the health and safety of the public, cause significant adverse impact to the land, water, or air environment, or cause severe damage to property.)

Notification required by this section will be made regardless of the amount of discharge.

Prompt Notification Procedures are listed in Section D.6.c. of these standard conditions.

A written report shall be provided within seven calendar days after the notification.

The report shall contain the information listed in Section D.6.d. of these standard conditions and any additional information in LAC 33:1.3925.B.

form_7027_r08 3-23-11 REVISEDr 03-23-11 Paae 10 of 18 b. Prompt Notification As required by LAC 33:1.3917, in the event of an unauthorized discharge that exceeds a reportable quantity specified in LAC 33:l.Subchapter E, but does not cause an emergency condition, the discharger shall promptly notify the department within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after learning of the discharge.

Notification should be made to the Office of Environmental Compliance, Surveillance Division Single Point of Contact (SPOC) in accordance with LAC 33:1.3923.

In accordance with LAC 33:1.3923, prompt notification shall be provided within a time frame not to exceed 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and shall be given to the Office of Environmental Compliance, Surveillance Division (SPOC) as follows: (1) by the Online Incident Reporting screens found at http://www.deq.louisiana.gov/portal/tabid/66/Default.aspx

or (2) by e-mail utilizing the Incident Report Form and instructions found at http://www.deq.louisiana.gov/portal/tabid/66/Default.aspx;or (3) by telephone at (225) 219-3640 during office hours, or (225) 342-1234 after hours and on weekends and holidays.c. Content of Prompt Notifications.

The following guidelines will be utilized as appropriate, based on the conditions and circumstances surrounding any unauthorized discharge, to provide relevant information regarding the nature of the discharge:

(1) the name of the person making the notification and the telephone number where any return calls from response agencies can be placed;(2) the name and location of the facility or site where the unauthorized discharge is imminent or has occurred, using common landmarks.

In the event of an incident involving transport, include the name and address of the transporter and generator; (3) the date and time the incident began and ended, or the estimated time of continuation if the discharge is continuing; (4) the extent of any injuries and identification of any known personnel hazards that response agencies may face;(5) the common or scientific chemical name, the U.S. Department of Transportation hazard classification, and the best estimate of amounts of any and all discharged pollutants; (6) a brief description of the incident sufficient to allow response agencies to formulate their level and extent of response activity.d. Written Notification Procedures.

Written reports for any unauthorized discharge that requires notification under Section D.6.a. or 6.b., or shall be submitted by the discharger to the Office of Environmental Compliance, Surveillance Division SPOC in accordance with LAC 33:1.3925 within seven calendar days after the notification required by D.6.a. or 6.b., unless otherwise provided for in a valid permit or other department regulation.

Written notification reports shall include, but not be limited to, the following information:

(1) the name, address, telephone number, Agency Interest (Al) number (number assigned by the department) if applicable, and any other applicable identification numbers of the person, company, or other party who is filing the written report, and specific identification that the report is the written follow-up report required by this section;(2) the time and date of prompt notification, the state official contacted when reporting, the name of person making that notification, and identification of the site or facility, vessel, transport vehicle, or storage area from which the unauthorized discharge occurred;(3) date(s), time(s), and duration of the unauthorized discharge and, if not corrected, the anticipated time it is expected to continue;(4) details of the circumstances (unauthorized discharge description and root cause) and events leading to any unauthorized discharge, including incidents of loss of sources of radiation, and if the release point is subject to a permit: (a) the current permitted limit for the pollutant(s) released;and (b) the permitted release point/outfall ID.form_7027 r08 3-23-11 Paae 11 of 18I Pa e1 f1 (5) the common or scientific chemical name of each specific pollutant that was released as the result of an unauthorized discharge, including the CAS number and U.S. Department of Transportation hazard classification, and the best estimate of amounts of any and all released pollutants (total amount of each compound expressed in pounds, including calculations), (6) a statement of the actual or probable fate or disposition of the pollutant or source of radiation and what off-site impact resulted: (7) remedial actions taken, or to be taken, to stop unauthorized discharges or to recover pollutants or sources of radiation.

(8) Written notification reports shall be submitted to the Office of Environmental Compliance, Surveillance Division SPOC by mail or fax. The transmittal envelope and report or fax cover page and report should be clearly marked "UNAUTHORIZED DISCHARGE NOTIFICATION REPORT." Written reports (LAC 33:1.3925) should be mailed to: Louisiana Department of Environmental Quality Post Office Box 4312 Baton Rouge, LA 70821-4312 ATTENTION; EMERGENCY AND RADIOLOGICAL SERVICES DIVISION -SPOC"UNAUTHORIZED DISCHARGE NOTIFICATION REPORT" The Written Notification Report may also be faxed to the Louisiana Department of Environmental Quality, Office of Environmental Compliance, Emergency and Radiological Services Division at: (225)-219-4044.

Please see LAC 33:1.3925.B for additional written notification procedures.

e. Twenty-four Hour Reporting.

The permittee shall report any noncompliance which may endanger human health or the environment.

Any information shall be provided orally within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> from the time the permittee becomes aware of the circumstances.

A written submission shall also be provided within five days of the time the permittee becomes aware of the circumstances.

The written submission shall contain a description of the noncompliance and its cause; the period of noncompliance, including exact dates and times, and if the noncompliance has not been corrected, the anticipated time it is expected to continue.

and steps taken or planned to reduce, eliminate, and prevent recurrence of the noncompliance.

The following shall be included as information which must be reported within 24hours: (1) Any unanticipated bypass which exceeds any effluent limitation in the permit (see LAC 33:1IX.2701.M.3.b.);

(2) Any upset which exceeds any effluent limitation in the permit;(3) Violation of a maximum daily discharge limitation for any of the pollutants listed by the state administrative authority in Part Il'of the permit to be reported within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> (LAC 33:IX.2707.G.).

7. Other Noncompliance The permittee shall report all instances of noncompliance not reported under Section D.4., 5., and 6., at the time monitoring reports are submitted.

The reports shall contain the information listed in Section D.6.e.8. Other Information Where the permittee becomes aware that it failed to submit any relevant facts in a permit application, or submitted incorrect information in a permit application or in any report to the state administrative authority, it shall promptly submit such facts or information.

9. Discharges of Toxic Substances In addition to the reporting requirements under Section D.1-8, all existing manufacturing, commercial, mining, and silvicultural dischargers must notify the Office of Environmental Services, Water Permits Division as soon as they know or have reason to believe: a. That any activity has occurred or will occur which would result in the discharge, on a routine or frequent basis, of any toxic pollutant:

form_7027_r08 3-23-11 REVISED 03-23-11 Pacte 12 of 18 i. listed at LAC 33:IX.7107, Tables II and III (excluding Total Phenols) which is not limited in the permit, if that discharge will exceed the highest of the following notification levels: (1) One hundred micrograms per liter (100 pg/L);(2) Two hundred micrograms per liter (200 pg/L) for acrolein and acrylonitrile, five hundred micro-grams per liter (500 pg/L) for 2,4 -dinitro-phenol and for 2-methyl-4,6-dinitrophenol; and one milligram per liter (1 mg/L) for antimony;(3) Five (5) times the maximum concentration value reported for that pollutant in the permit application in accordance with LAC33:IX.2501.G.7; or (4) The level established by the state administrative authority in accordance with LAC 33:IX.2707.F; or ii. which exceeds the reportable quantity levels for pollutants at LAC 33:1. Subchapter E.b. That any activity has occurred or will occur which would result in any discharge, on a non-routine or infrequent basis, of a toxic pollutant:

i. listed at LAC 33:IX.7107, Tables II and III (excluding Total Phenols) which is not limited in the permit, if that discharge will exceed the highest of the following "notification levels": (1) Five hundred micrograms per liter (500 pg/L);(2) One milligram per liter (1 mg/L) for antimony;(3) Ten (10) times the maximum concentration value reported for that pollutant in the permit application in accordance with LAC 33:IX.2501.G.7; or (4) The level established by the state administrative authority in accordance with LAC 33:IX.2707.F; or ii. which exceeds the reportable quantity levels for pollutants at LAC 33:1. Subchapter E.10. Signatory Requirements All applications, reports, or information submitted to the state administrative authority shall be signed and certified.
a. All permit applications shall be signed as follows: (1) For a corporation

-by a responsible corporate officer. For the purpose of this section, a responsible corporate officer means: (a) A president, secretary, treasurer, or vice-president of the corporation in charge of a principal business function, or any other person who performs similar, policy or decision making functions for the corporation; or, (b) The manager of one or more manufacturing, production, or operating facilities, provided:

the manager is authorized to make management decisions that govern the operation of the regulated facility, including having the explicit or implicit duty of making major capital investment recommendations and initiating and directing other comprehensive measures to ensure long term environmental compliance with environmental laws and regulations; the manager can ensure that the necessary systems are established or actions taken to gather complete and accurate information for permit application requirements; and the authority to sign documents has been assigned or delegated to the manager in accordance with corporate procedures.

NOTE: DEQ does not require specific assignments or delegations of authority to responsible corporate officers identified in Section D.10.a(1)(a).

The agency will presume that these responsible corporate officers have the requisite authority to sign permit applications unless the corporation has notified the state administrative authority to the contrary.

Corporate procedures governing authority to sign permit applications may provide for assignment or delegation to applicable corporate positions under Section D. 10. a(1)(b) rather than to specific individuals.

(2) For a partnership or sole proprietorship

-by a general partner or the proprietor, respectively:

or (3) For a municipality, state, federal, or other public agency -by either a principal executive officer or ranking elected official.

For purposes of this section, a principal executive officer of a federal agency includes: form 7027 r08 3-23-11 REVISED 03-23-11 Paae 13 of 18 (a) The chief executive officer of the agency, or (b) A senior executive officer having responsibility for the overall operations of a principal geographic unit of the agency (e.g., Regional Administrators of EPA).b. All reports required by permits and other information requested by the state administrative authority shall be signed by a person described in Section D.10.a., or by a duly authorized representative of that person. A person is a duly authorized representative only if: (1) The authorization is made in writing by a person described in Section D.10.a. of these standard conditions; (2) The authorization specifies either an individual or a position having responsibility for the overall operation of the regulated facility or activity such as the position of plant manager, operator of a well or a well field, superintendent, position of equivalent responsibility, or an individual or position having overall responsibility for environmental matters for the company, (a duly authorized representative may thus be either a named individual or an individual occupying a named position, and, (3) The written authorization is submitted to the state administrative authority.

c. Changes to authorization.

If an authorization under Section D.10.b. is no longer accurate because a different individual or position has responsibility for the overall operation of the facility, a new authorization satisfying the requirements of Section D.10.b. must be submitted to the state administrative authority prior to or together with any reports, information, or applications to be signed by an authorized representative.

d. Certification.

Any person signing a document under Section D.10. a. or b. above, shall make the following certification:

'I certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure'that qualified personnel properly gather and evaluate the information submitted.

Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete.

I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations." 11. Availability of Reports All recorded information (completed permit application forms, fact sheets, draft permits, or any public document) not classified as confidential information under La. R.S. 30:2030(A) and 30:2074(D) and designated as such in accordance with these regulations (LAC 33:IX.2323 and LAC 33:1IX.6503) shall be made available to the public for inspection and copying during normal working hours in accordance with the Public Records Act, La. R.S. 44:1 et seq.Claims of confidentiality for the following will be denied: a. The name and address of any permit applicant or permittee;

b. Permit applications, permits, and effluent data.c. Information required by LPDES application forms provided by the state administrative authority under LAC 33:IX.2501 may not be claimed confidential.

This includes information submitted on the forms themselves and any attachments used to supply information required by the forms.SECTION E. PENALTIES FOR VIOLATIONS OF PERMIT CONDITION 1. Criminal a. Neg licent Violations The Louisiana Revised Statutes La. R. S. 30:2076.2 provides that any person who negligently violates any provision of the LPDES, or any order issued by the secretary under the LPDES, or any permit condition or limitation implementing any such provision in a permit issued under the LPDES by the secretary, or any requirement imposed in a pretreatment program approved under the LPDES is subject form 7027 r08 3-23-11 REVISED 03-23-11 Paqe 14 of 18 to a fine of not less than $2,500 nor more than $25,000 per day of violation, or by imprisonment for not more than 1 year, or both. If a conviction of a person is for a violation committed after a first conviction of such person, he shall be subject to a fine of not more than $50,000 per day of violation, or imprisonment of not more than two years, or both.b. Knowing Violations The Louisiana Revised Statutes La. R. S. 30:2076.2 provides that any person who knowingly violates any provision of the LPDES, or any permit condition or limitation implementing any such provisions in a permit issued under the LPDES, or any requirement imposed in a pretreatment program approved under the LPDES is subject to a fine of not less than $5,000 nor more than $50,000 per day of violation, or imprisonment for not more than 3 years, or both. If a conviction of a person is for a violation committed after a first conviction of such person, he shall be subject to a fine of not more than $100,000 per day of violation, or imprisonment of not more than six years, or both.c. Knowing Endangerment The Louisiana Revised Statutes La. R. S. 30:2076.2 provides that any person who knowingly violates any provision of the LPDES, or any order issued by the secretary under the LPDES, or any permit condition or limitation implementing any of such provisions in a permit issued under the LPDES by the secretary, and who knows at that time that he thereby places another person in imminent danger of death or serious bodily injury, shall, upon conviction, be subject to a fine of not more than $250,000, or by imprisonment for not more than 15 years, or both. A person which is an organization shall, upon conviction of violating this Paragraph, be subject to a fine of not more than one million dollars. If a conviction of a person is for a violation committed after a first conviction of such person under this Paragraph, the maximum punishment shall be doubled with respect to both fine and imprisonment.

d. False Statements The Louisiana Revised Statutes La. R. S. 30:2076.2 provides that any person who knowingly makes any false material statement, representation, or certification in any application, record, report, plan, or other document filed or required to be maintained under the LPDES or who knowingly falsifies, tampers with, or renders inaccurate, any monitoring device or method required to be maintained under the LPDES, shall, upon conviction, be subject to a fine of not more than $10,000, or imprisonment for not more than 2 years, or both. If a conviction of a person is for a violation committed after a first conviction of such person under this Subsection, he shall be subject to a fine of not more than $20,000 per day of violation, or imprisonment of not more than 4 years, or both.2. Civil Penalties The Louisiana Revised Statutes La. R. S. 30:2025 provides that any person found to be in violation of any requirement of this Subtitle may be liable for a civil penalty, to be assessed by the secretary, an assistant secretary, or the court, of not more than the cost to the state of any response action made necessary by such violation which is not voluntarily paid by the violator, and a penalty of not more than $32,500 for each day of violation.

However, when any such violation is done intentionally, willfully, or knowingly, or results in a discharge or disposal which causes irreparable or severe damage to the environment or if the substance discharged is one which endangers human life or health, such person may be liable for an additional penalty of not more than one million dollars.(PLEASE NOTE: These penalties are listed in their entirety in Subtitle II of Title 30 of the Louisiana Revised Statutes.)

SECTION F. DEFINITIONS All definitions contained in Section 502 of the Clean Water Act shall apply to this permit and are incorporated herein by reference.

Additional definitions of words or phrases used in this permit are as follows: 1. Clean Water Act (CWA) means the Clean Water Act (formerly referred to as the Federal Water Pollution Control Act or the Federal Water Pollution Control Act Amendments of 1972) Pub.L.92-500, as amended by Pub.L.95-217, Pub.L.95-576, Pub.L.96-483 and Pub.L.97-117, 33 U.S.C. 1251 et. seq.).form_7027_r08 3-23-11 REVISED 03-23-11 Pacie 15 of 18 2. Accreditation means the formal recognition by the department of a laboratory's competence wherein specific tests or types of tests can be accurately and successfully performed in compliance with all minimum requirements set forth in the regulations regarding laboratory accreditation.

3. Administrator means the Administrator of the U.S. Environmental Protection Agency, or an authorized representative.
4. Applicable Standards and Limitations means all state, interstate and federal standards and limitations to which a discharge is subject under the Clean Water Act, including, effluent limitations, water quality standards of performance, toxic effluent standards or prohibitions, best management practices, and pretreatment standards under Sections 301, 302, 303, 304, 306, 307, 308 and 403.5. Applicable water quality standards means all water quality standards to which a discharge is subject under the Clean Water Act.6. Commercial Laboratory means any laboratory, wherever located, that performs analyses or tests for third parties for a fee or other compensation and provides chemical analyses, analytical results, or other test data to the department.

The term commercial laboratory does not include laboratories accredited by the Louisiana Department of Health and Hospitals in accordance with La. R.S.49:1001 et seq.7. Daily Discharge means the discharge of a pollutant measured during a calendar day or any 24..hour period that reasonably represents the calendar day for purposes of sampling.

For pollutants with limitations expressed in terms of mass, the daily discharge is calculated as the total mass of the pollutant discharged over the sampling day. For pollutants with limitations expressed in other units of measurement, the daily discharge is calculated as the average measurement of the pollutant over the sampling day. Daily discharge determination of concentration made using a composite sample shall be the concentration of the composite sample.8. Daily Maximum discharge limitation means the highest allowable "daily discharge".

9. Director means the U.S. Environmental Protection Agency Regional Administrator, or the state administrative authority, or an authorized representative.
10. Domestic septage means either liquid or solid material removed from a septic tank, cesspool, portable toilet, Type III marine sanitation device, or similar treatment works that receives only domestic sewage. Domestic septage does not include liquid or solid material removed from a septic tank, cesspool, or similar treatment works that receives either commercial wastewater or industrial wastewater and does not include grease removed from grease trap at a restaurant.
11. Domestic sewage means waste and wastewater from humans, or household operations that is discharged to or otherwise enters a treatment works.12. Environmental Protection Agency or (EPA) means the U.S. Environmental Protection Agency.13. Grab sample means an individual sample collected over a period of time not exceeding 15 minutes, unless more time is needed to collect an adequate sample, and is representative of the discharge.
14. Industrial user means a nondomestic discharger, as identified in 40 CFR 403, introducing pollutants to a publicly owned treatment works.15. LEQA means the Louisiana Environmental Quality Act.16. Louisiana Pollutant Discharge Elimination System (LPDES) means those portions of the Louisiana Environmental Quality Act and the Louisiana Water Control Law and all regulations promulgated under their authority which are deemed equivalent to the National Pollutant Discharge Elimination System (NPDES)form 7027 r08 3-23-11 REVISE:;D 03-21-11 Paae 16 of 18 under the Clean Water Act in accordance with Section 402 of the Clean Water Act and all applicable federal regulations.

17 Monthly Average, other than for fecal coliform bacteria, discharge limitations are calculated as the sum of all"daily discharge(s)" measured during a calendar month divided by the number of "daily discharge(s)" measured during that month. When the permit establishes monthly average concentration effluent limitations or conditions, and flow is measured as continuous record or with a totalizer, the monthly average concentration means the arithmetic average (weighted by flow) of all "daily discharge(s)" of concentration determined during the calendar month where C = daily discharge concentration, F = daily flow and n =number of daily samples; monthly average discharge

=C1F1 + C2F2 + .. + CnF F, +F2 +... +Fn When the permit establishes monthly average concentration effluent limitations or conditions, and the flow is not measured as a continuous record, then the monthly average concentration means the arithmetic average of all "daily discharge(s)" of concentration determined during the calendar month.The monthly average for fecal coliform bacteria is the geometric mean of the values for all effluent samples collected during a calendar month.18. National Pollutant Discharge Elimination System (NPDES) means the national program for issuing, modifying, revoking and reissuing, terminating, monitoring and enforcing permits, and imposing and enforcing pretreatment requirements, under Sections 307, 318, 402, and 405 of the Clean Water Act.19. Severe property damage means substantial physical damage to property, damage to the treatment facilities that causes them to become inoperable, or substantial and permanent loss of natural resources that can reasonably be expected to occur in the absence of a bypass. Severe property damage does not mean economic loss caused by delays in production.

20. Sewage sludge means any solid, semi-solid, or liquid residue removed during the treatment of municipal wastewater or domestic sewage. Sewage sludge includes, but is not limited to, solids removed during primary, secondary, or advanced wastewater treatment, scum, domestic septage, portable toilet pumpings, Type III marine sanitation device pumpings (33 CFR Part 159), and sewage sludge products.

Sewage sludge does not include grit or screenings, or ash generated during the incineration of sewage sludge.21. Stormwater Runoff-aqueous surface runoff including any soluble or suspended material mobilized by naturally occurring precipitation events.22. Surface Water: all lakes, bays, rivers, streams, springs, ponds, impounding reservoirs, wetlands, swamps, marshes, water sources, drainage systems and other surface water, natural or artificial, public or private within the state or under its jurisdiction that are not part of a treatment system allowed by state law, regulation, or permit.23. Treatment works means any devices and systems used in the storage, treatment, recycling and reclamation of municipal sewage and industrial wastes of a liquid nature to implement Section 201 of the Clean Water Act, or necessary to recycle or reuse water at the most economical cost over the estimated life of the works, including intercepting sewers, sewage collection systems, pumping, power and other equipment, and their appurtenances, extension, improvement, remodeling, additions, and alterations thereof. (See Part 212 of the Clean Water Act)24. For fecal coliform bacteria, a sample consists of one effluent grab portion collected during a 24-hour period at peak loads.25. The term MGD shall mean million gallons per day.26. The term GPD shall mean gallons per day.form 7027 r08 3-23-11 REVISED 03-23-2311 Paqe 17 of 18 27. The term mq/L shall mean milligrams per liter or parts per million (ppm).28. The term SPC shall mean Spill Prevention and Control. Plan covering the release of pollutants as defined by the Louisiana Administrative Code (LAC 33:IX.Chapter 9).29. The term SPCC shall mean Spill Prevention Control and Countermeasures Plan. Plan covering the release of pollutants as defined in 40 CFR Part 112.30. The term ic/L shall mean micrograms per liter or parts per billion (ppb).31. The term ng/L shall mean nanograms per liter or parts per trillion (ppt).32. Visible Sheen: a silvery or metallic sheen, gloss, or increased reflectivity; visual color; or iridescence on the water surface.33. Wastewater-liquid waste resulting from commercial, municipal, private, or industrial processes.

Wastewater includes, but is not limited to, cooling and condensing waters, sanitary sewage, industrial waste, and contaminated rainwater runoff.34. Waters of the State: for the purposes of the Louisiana Pollutant Discharge Elimination system, all surface waters within the state of Louisiana and, on the coastline of Louisiana and the Gulf of Mexico, all surface waters extending there from three miles into the Gulf of Mexico. For purposes of the Louisiana Pollutant Discharge Elimination System, this includes all surface waters which are subject to the ebb and flow of the tide, lakes, rivers, streams, (including intermittent streams), mudflats, sandflats, wetlands, sloughs, prairie potholes, wet meadows, playa lakes, natural ponds, impoundments of waters within the state of Louisiana otherwise defined as "waters of the United States" in 40 CFR 122.2, and tributaries of all such waters."Waters of the state" does not include waste treatment systems, including treatment ponds or lagoons designed to meet the requirements of the Clean Water Act, 33 U.S.C. 1251 et seq.35. Weekly averaqe, other than for fecal coliform bacteria, is the highest allowable arithmetic mean of the daily discharges over a calendar week, calculated as the sum of all "daily discharge(s)" measured during a calendar week divided by the number of "daily discharge(s)" measured during that week. When the permit establishes weekly average concentration effluent limitations or conditions, and flow is measured as continuous record or with a totalizer, the weekly average concentration means the arithmetic average (weighted by flow) of all "daily discharge(s)" of concentration determined during the calendar week where C= daily discharge concentration, F = daily flow and n = number of daily samples; weekly average discharge C 1 F 1 + C 2 F 2 + ... + CFn F,+F 2+... +F, When the permit establishes weekly average concentration effluent limitations or conditions, and the flow is not measured as a continuous record, then the weekly average concentration means the arithmetic average of all "daily discharge(s)" of concentration determined during the calendar week.The weekly average for fecal coliform bacteria is the geometric mean of the values for all effluent samples collected during a calendar week.36. Sanitary Wastewater Term(s): a. 3-hour composite sample consists of three effluent portions collected no closer together than one hour (with the first portion collected no earlier than 10:00 a.m.) over the 3-hour period and composited according to flow, or a sample continuously collected in proportion to flow over the 3-hour period.form_7027_r08 3-23-11 REVISEDFr n3-23-11 Paoe 18 of 18 REV.E.. 3-2-11Pane 18 of 18 b. 6-hour composite sample consists of six effluent portions collected no closer together than one hour (with the first portion collected no earlier than 10:00 a.m.) over the 6-hour period and composited according to flow, or a sample continuously collected in proportion to flow over the 6-hour period.c.12-hour composite sample consists of 12 effluent portions collected no closer together than one hour over the 12-hour period and composited according to flow, or a sample continuously collected in proportion to flow over the 12-hour period. The daily sampling intervals shall include the highest flow periods.d. 24-hour composite sample consists of a minimum of 12 effluent portions collected at equal time intervals over the 24-hour period and combined proportional to flow or a sample continuously collected in proportion to flow over the 24-hour period.form_7027_r08 3-23-11