ND-22-0586, ITAAC Closure Notification on Completion of ITAAC 2.6.01 .02.i (Index Number 579)

From kanterella
(Redirected from ML22306A268)
Jump to navigation Jump to search
ITAAC Closure Notification on Completion of ITAAC 2.6.01 .02.i (Index Number 579)
ML22306A268
Person / Time
Site: Vogtle 
Issue date: 11/02/2022
From: Coleman J
Southern Nuclear Operating Co
To:
Office of Nuclear Reactor Regulation, Document Control Desk
References
ND-22-0586, ITAAC 2.6.01.02.i
Download: ML22306A268 (1)


Text

._ Southern Nuclear Jamie M. Coleman Regulatory Affairs Director Vogtle 3 & 4 NOV O 2 2022 Docket No.:

52-026 U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001 Southern Nuclear Operating Company Vogtle Electric Generating Plant Unit 4 7825 River Road Waynesboro, GA 30830 706-848-6926 tel ND-22-0586 1 O CFR 52.99(c)(1)

ITAAC Closure Notification on Completion of ITAAC 2.6.01.02.i [Index Number 5791 Ladies and Gentlemen:

In accordance with 1 O CFR 52.99(c)(1 ), the purpose of this letter is to notify the Nuclear Regulatory Commission (NRC) of the completion of Vogtle Electric Generating Plant (VEGP)

Unit 4 Inspections, Tests, Analyses, and Acceptance Criteria (ITAAC) Item 2.6.01.02.i [Index Number 5791. This ITAAC confirms that the seismic Category I Main ac Power System equipment identified in the VEGP Unit 4 Combined License (COL) Appendix C, Table 2.6.1-1 can withstand seismic design basis loads without loss of safety function. The closure process for this ITAAC is based on the guidance described in Nuclear Energy Institute (NEI) 08-01,

"Industry Guideline for the ITAAC Closure Process Under 10 CFR Part 52," which was endorsed by the NRC in Regulatory Guide 1.215.

This letter contains no new NRC regulatory commitments. Southern Nuclear Operating Company (SNC) requests NRC staff confirmation of this determination and publication of the required notice in the Federal Register per 1 O CFR 52.99.

If there are any questions, please contact Kelli Roberts at 706-848-6991.

Respectfully submitted,

~~~

Jamie M. Coleman Regulatory Affairs Director Vogtle 3 & 4

Enclosure:

Vogtle Electric Generating Plant (VEGP) Unit 4 Completion for ITAAC 2.6.01.02.i [Index Number 5791 JMC/AD/sfr

U.S. Nuclear Regulatory Commission ND-22-0586 Page 2 of 2 cc:

Regional Administrator, Region II Director, Office of Nuclear Reactor Regulation (NRR)

Director, Vogtle Project Office NRR Senior Resident Inspector - Vogtle 3 & 4

U.S. Nuclear Regulatory Commission ND-22-0586 Enclosure Page 1 of 5 Southern Nuclear Operating Company ND-22-0586 Enclosure Vogtle Electric Generating Plant (VEGP) Unit 4 Completion of ITAAC 2.6.01.02.i [Index Number 579]

U.S. Nuclear Regulatory Commission ND-22-0586 Enclosure Page 2 of 5 ITAAC Statement Design Commitment

2. The seismic Category I equipment identified in Table 2.6.1-1 can withstand seismic design basis loads without loss of safety function.

Inspections, Tests, Analyses i) Inspection will be performed to verify that the seismic Category I equipment identified in Table 2.6.1-1 is located on the Nuclear Island.

ii) Type tests, analyses, or a combination of type tests and analyses of seismic Category I equipment will be performed.

iii) Inspection will be performed for the existence of a report verifying that the as-built equipment including anchorage is seismically bounded by the tested or analyzed conditions.

Acceptance Criteria i) The seismic Category I equipment identified in Table 2.6.1-1 is located on the Nuclear Island.

ii) A report exists and concludes that the seismic Category I equipment can withstand seismic design basis loads without loss of safety function.

iii) A report exists and concludes that the as-built equipment including anchorage is seismically bounded by the tested or analyzed conditions.

IT AAC Determination Basis This ITAAC requires that inspections, tests, and analyses be performed and documented to ensure the Main ac Power System (ECS) equipment identified as seismic Category I or Class 1 E in the Combined License (COL) Appendix C, Table 2.6.1-1 (the Table) are designed and constructed in accordance with applicable requirements.

i) The seismic Category I equipment identified in Table 2.6.1-1 is located on the Nuclear Island.

To assure that seismic Category I equipment can withstand seismic design basis loads without loss of safety function, all the equipment in the Table is designed to be located on the seismic Category I Nuclear Island. In accordance with Equipment Qualification (EQ) Walkdown ITAAC Guideline and the EQ ITAAC As-Built Installation Documentation Guideline (References 1 and 2), an inspection was conducted of the ECS to confirm the satisfactory installation of the seismically qualified equipment. The inspection includes verification of equipment make/model/serial number and verification of equipment location (Building, Elevation, Room).

The EQ As-Built Reconciliation Reports (EQRR) (Reference 3) identified in Attachment A document the results of the inspection and conclude that the seismic Category I equipment is located on the Nuclear Island.

U.S. Nuclear Regulatory Commission ND-22-0586 Enclosure Page 3 of 5 ii) A report exists and concludes that the seismic Category I equipment can withstand seismic design basis loads without loss of safety function.

Seismic Category I equipment in the Table requires type tests and/or analyses to demonstrate structural integrity and operability. Safety-related (Class 1 E) electrical equipment in the Table was seismically qualified by type testing combined with analysis in accordance with Institute of Electrical and Electronics Engineers (IEEE) Standard 344-1987 (Reference 4). The specific qualification method (i.e., type testing, analysis, or combination) used for each piece of equipment in the Table is identified in Attachment A. Additional information about the methods used to qualify AP1000 safety-related equipment is provided in the Updated Final Safety Analysis Report (UFSAR) Appendix 3D (Reference 5). The EQ Reports (Reference 6) identified in Attachment A contain applicable test reports and associated documentation and conclude that the seismic Category I equipment can withstand seismic design basis loads without loss of safety function.

iii) A report exists and concludes that the as-built equipment including anchorage is seismically bounded by the tested or analyzed conditions.

An inspection (References 1 and 2) was conducted to confirm the satisfactory installation of the seismically qualified equipment in the Table. The inspection verifies the equipment make/model/serial number, as-designed equipment mounting orientation, anchorage and clearances, and electrical and other interfaces. The documentation of installed configuration of seismically qualified equipment includes photographs and/or sketches/drawings of equipment/mounting/interfaces.

As part of the seismic qualification program, consideration is given to the definition of the clearances needed around the equipment mounted in the plant to permit the equipment to move during a postulated seismic event without causing impact between adjacent pieces of safety-related equipment. When required, seismic testing by measuring the maximum dynamic relative displacement of the top and bottom of the equipment was performed. EQ Reports (Reference 6) identified the equipment mounting employed for qualification and establish interface requirements for assuring that subsequent in-plant installation does not degrade the established qualification. Interface requirements are defined based on the test configuration and other design requirements.

Attachment A identifies the EQRR (Reference 3) completed to verify that the as-built seismic Category I equipment listed in the Table, including anchorage, are seismically bounded by the tested or analyzed conditions, IEEE Standard 344-1987 (Reference 4) and NRC Regulatory Guide (RG) 1.100 (Reference 7).

Together, these reports (References 3 and 6) provide evidence that the ITAAC Acceptance Criteria requirements are met:

The seismic Category I equipment identified in Table 2.6.1-1 is located on the Nuclear Island; A report exists and concludes that the seismic Category I equipment can withstand seismic design basis loads without loss of safety function; and

U.S. Nuclear Regulatory Commission ND-22-0586 Enclosure Page 4 of 5 A report exists and concludes that the as-built equipment including anchorage is seismically bounded by the tested or analyzed conditions.

References 3 and 6 are available for NRC inspection as part of the Unit 4 ITAAC 2.6.01.02.i Completion Package (Reference 8).

ITAAC Finding Review In accordance with plant procedures for ITAAC completion, Southern Nuclear Operating Company (SNC) performed a review of all lTAAC findings pertaining to the subject ITAAC and associated corrective actions. This finding review, which included now-consolidated ITAAC Indexes 580 and 581, found there are no relevant ITAAC findings associated with this ITAAC.

The ITAAC completion review is documented in the ITAAC Completion Package for ITAAC 2.6.01.02.i (Reference 8) and is available for NRG review.

ITAAC Completion Statement Based on the above information, SNC hereby notifies the NRC that ITAAC 2.6.01.02.i was performed for VEGP Unit 4 and that the prescribed acceptance criteria are met.

Systems, structures, and components verified as part of this ITAAC are being maintained in their as-designed, ITAAC compliant condition in accordance with approved plant programs and procedures.

References (available for NRC inspection)

1. ND-RA-001-014, EQ ITAAC As-built Walkdown Guideline, Version 3.1
2. ND-RA-001 -016, "EQ ITAAC As-built Installation Documentation Guideline", Version 1.0
3. EQ As-Built Equipment Qualification Reconciliation Report (EQRR) as identified in Attachment A
4. IEEE Standard 344-1987, IEEE Recommended Practices for Seismic Qualification of Class 1 E Equipment for Nuclear Power Generating Stations
5. Vogtle 3&4 Updated Final Safety Analysis Report Appendix 30, Methodology for Qualifying AP1000 Safety-Related Electrical and Mechanical Equipment, Revision 11.1
6. Equipment Qualification (EQ) Reports as identified in Attachment A
7. Regulatory Guide 1.100, Seismic Qualification of Electric and Mechanical Equipment for Nuclear Power Plants, Revision 2
8. 2.6.01.02.i-U4-CP-Rev0, Completion Package for Unit 4 ITAAC 2.6.01.02.i [Index Number 579]

U.S. Nuclear Regulatory Commission ND-22-0586 Enclosure Page 5 of 5 Attachment A System: Main ac Power System (ECS)

Equipment Name +

Tag No.+

Seismic Type of EQ Reports (Reference 5)

Cat. I+

Qual.

Reactor Coolant Type SV4-ES02-VBR-003 / SV4-Pump (RCP) Circuit ECS-ES-31 Yes Test &

ES02-VBR-001 Breaker Analysis Type SV4-ES02-VBR-003 / SV4-RCP Circuit Breaker ECS-ES-32 Yes Test &

ES02-VBR-001 Analysis Type SV4-ES02-VBR-003 / SV4-RCP Circuit Breaker ECS-ES-41 Yes Test &

ES02-VBR-001 Analysis Type SV4-ES02-VBR-003 / SV4-RCP Circuit Breaker ECS-ES-42 Yes Test &

ES02-VBR-001 Analysis Type SV4-ES02-VBR-003 / SV4-RCP Circuit Breaker ECS-ES-51 Yes Test &

ES02-VBR-001 Analysis Type SV4-ES02-VBR-003 / SV4-RCP Circuit Breaker ECS-ES-52 Yes Test &

ES02-VBR-00 1 Analysis Type SV4-ES02-VBR-003 / SV4-RCP Circuit Breaker ECS-ES-61 Yes Test &

ES02-VBR-001 Analysis Type SV4-ES02-VBR-003 / SV4-RCP Circuit Breaker ECS-ES-62 Yes Test &

ES02-VBR-001 Analysis Notes:

+ Excerpt from COL Appendix C Table 2.6.1-1 As-Built EORR (Reference 2)

  • 2.6.01.02.i-U4-EQRR-PCD001-Rev0 2.6.01.02.i-U4-EQRR-PCD001-Rev0 2.6.01.02.i-U4-EQRR-PCD001-Rev0 2.6.01.02.i-U4-EQRR-PCD001-Revo 2.6.01.02.i-U4-EQRR-PCD001-Rev0 2.6.01.02.i-U4-EQRR-PCD001-Rev0 2.6.01.02.i-U4-EQRR-PCD001-Rev0 2.6.01.02.i-U4-EQRR-PCD001-Rev0