Southern Nuclear OCT 3 0 2020 Docket No.:

52-025 Michael J. Yox Regulatory Affairs Director Vogtle 3 & 4 7825 River Road Waynesboro, GA 30830 706-848-6459 tel ND-20-0730 10CFR 52.99(c)(1)

U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001 Southern Nuclear Operating Company Vogtle Electric Generating Plant Unit 3 ITAAC Closure Notification on Completion of ITAAC 3.3.00.02b [Index Number 7701 Ladies and Gentlemen:

In accordance with 10 CFR 52.99(c)(1), the purpose of this letter is to notify the Nuclear Regulatory Commission (NRC) of the completion of Vogtle Electric Generating Plant (VEGP)

Unit 3 Inspections, Tests, Analyses, and Acceptance Criteria (ITAAC) Item 3.3.00.02b [Index Number 770]. This ITAAC verified that as-built site grade is consistent with design plant grade within the dimension defined on VEGP Combined License (COL) Appendix C Table 3.3-5 (+/- 3ft-6in). The closure process for this ITAAC is based on the guidance described in NEI 08-01, "Industry Guideline for the ITAAC Closure Process under 10 CFR Part 52", which is endorsed by the NRC in Regulatory Guide 1.215.

This letter contains no new NRC regulatory commitments. Southern Nuclear Operating Company (SNC) requests NRC staff confirmation of this determination and publication of the required notice in the Federal Register per 10 CFR 52.99.

If there are any questions, please contact Tom Petrak at 706-848-1575.

Respectfully submitted.

Michael J. Yo>

Regulatory Affairs Director Vogtle 3 & 4

Enclosure:

Vogtle Electric Generating Plant (VEGP) Unit 3 Closure Notification on Completion of ITAAC 3.3.00.02b [Index Number 770]

MJY/TST/sfr

U.S. Nuclear Regulatory Commission ND-20-0730 Page 2 of 3 To:

Southern Nuclear Operating Company/ Georgia Power Company Mr. Peter P. Sena III (w/o enclosures)

Mr. D. L. McKinney (w/o enclosures)

Mr. M. D. Meier (w/o enclosures)

Mr. G. Chick Mr. S. Stimac Mr. P. Martino Mr. M. J. Yox Mr. A. S. Parton Ms. K. A. Roberts Mr. T. G. Petrak Mr. C. T. Defnall Mr. C. E. Morrow Mr. R. L. Belike Mr. S. Leighty Ms. A. C. Chamberlain Mr. J. C. Haswell Document Services RTYPE: VND.LI.L06 File AR.01.02.06 cc:

Nuclear Reoulatorv Commission M

M M

M M

M Ms. N. C. Coovert M

M M

M M

M M

M M

M M

M M

M M

M C. P. Patel G. J. Khouri N. D. Karlovich A. Lerch C. J. Even B. J. Kemker C. Welch J. Gaslevic V. Hall G. Armstrong M. Webb T. Fredette S. Smith C. Santos

s. M. Bailey S. Rose B. Davis J. Vasquez J. Eargle M. King E. Davidson T. Fanelli

U.S. Nuclear Regulatory Commission ND-20-0730 Page 3 of 3 Qqlethorpe Power Corporation Mr. R. B. Brinkman Mr. E. Rasmussen Municipal Electric Authority of Georgia Mr. J. E. Fuller Mr. 8. M. Jackson Dalton Utilities Mr. T. Bundros Westinqhouse Electric Company. LLC Dr. L. Oriani (w/o enclosures)

Mr. D. C. Durham (w/o enclosures)

Mr. M. M. Corletti Mr. Z. 8. Harper Mr. J. L. Coward Other Mr. 8. W. Kline, Bechtel Power Corporation Ms. L. Matis, Tetra Tech NUS, Inc.

Dr. W. R. Jacobs, Jr., Ph.D., CDS Associates, inc.

Mr. 8. Roetger, Georgia Public Service Commission Mr. R. L. Trokey, Georgia Public Service Commission Mr. K. C. Greene, Troutman Sanders Mr. 8. Blanton, Baich Bingham

U.S. Nuclear Regulatory Commission ND-20-0730 Enclosure Page 1 of 5 Southern Nuclear Operating Company ND-20-0730 Enclosure Vogtle Electric Generating Riant (VEGP) Unit 3 Completion of ITAAC 3.3.00.02b [Index Number 770]

U.S. Nuclear Regulatory Commission ND-20-0730 Enclosure Page 2 of 5 ITAAC Statement Design Commitment:

2.b) Site grade level is located relative to floor elevation 100'-0" per Table 3.3-5.

Inspections. Tests. Analvses:

Inspection of the as-built site grade will be conducted.

Acceptance Criteria:

Site grade is consistent with design plant grade within the dimension defined on Table 3.3-5.

ITAAC Determination Basis Inspection of the as-built site grade was conducted to confirm that the site grade is consistent with design plant grade within the dimension defined on VEGP Combined License (COL) Appendix C Table 3.3-5, row 10 (Attachment A) (Reference 1). VEGP COL Appendix C Section 1.1, Definitions, defines site grade as the as-built elevation of the soil to the west side of the nuclear island (Reference 1). The design plant grade for VEGP is defined as 220'-0" above mean sea level (MSL), which is equivalent to the lOO'-O" elevation for the standard plant design (Reference 2).

An as-built site grade inspection was performed to demonstrate that the as-built elevation of the area to the west side of the nuclear island is at elevation 220' MSL within a tolerance of +/-3'-6". The tolerance of +/-3'-6" defined in the COL Appendix C is based on seismic and soil structure interaction considerations for the Auxiliary Building, Shield Building, and Containment (Reference 3). The zone of influence of soil characteristics on the structural response of an embedded structure is generally considered to extend horizontally away from the structure the same distance as the depth of the embedment. For VEGP, this distance is approximately 40 feet from the auxiliary and shield buildings (Reference 3). The Power Block Grading Plan (Reference 5) has details of the site grading in the vicinity of the nuclear island, including local slope to encourage runoff away from the doorways of the buildings.

The site grade was determined with a walkdown and field survey of locations of as-built structures that are at elevations of lOO'-O" or lower (see Attachment B and Figure 1). The inspection involved a survey of storm drain covers using the Power Block Grading Plan (Reference 5). Measurements were taken using survey equipment in accordance with site survey procedures (Reference 6). The measured elevations of the four storm drain covers were compared to floor elevation 10O'-O" and within a tolerance of +/-

3'-6".

The as-built site grade inspection results are documented in Attachment B and Principal Closure Document "ITAAC Technical Report, Unit 3 Inspection of the As-Built Site Grade: ITAAC 3.3.00.02b" (Reference 4). The inspection determined that the as-built site grade is consistent with design plant grade within the dimension defined on Table 3.3-5 (+/- 3'-6").

The inspection Principal Closure Document (Reference 4) is available for NRC inspection as part of the ITAAC Completion Package (Reference 7).

U.S. Nuclear Regulatory Commission ND-20-0730 Enclosure Page 3 of 5 ITAAC Finding Review In accordance with plant procedures for ITAAC completion, Southern Nuclear Operating Company (SNC) performed a review of all findings pertaining to the subject ITAAC and associated corrective actions. This review found there are no relevant ITAAC findings associated with this ITAAC. The ITAAC completion review is documented in the ITAAC Completion Package for ITAAC 3.3.00.02b (Reference 7) and is available for NRC review.

ITAAC Completion Statement Based on the above information, SNC hereby notifies the NRC that ITAAC 3.3.00.02b was performed for VEGP Unit 3 and that the prescribed acceptance criteria are met.

Systems, structures, and components verified as part of this ITAAC are being maintained in their as-designed, ITAAC compliant condition in accordance with approved plant programs and procedures.

References ^available for NRC inspection)

1. Combined License Vogtle Electric Generating Plant Unit 3 Appendix C, Amendment 184
2. VEGP 3&4 Updated Final Safety Analysis Report, Revision 9.1
3. NUREG-1793 Supplement 2, Final Safety Evaluation Report Related to Certification of the API000 Standard Riant Design Docket No.52-006
4. SV3-0000-ITR-800770, Rev. 0, "Unit 3 Inspection of the As-Built Site Grade: ITAAC 3.3.00.02b, NRC Index Number: 770"
5. SVO-OOO-XG-800009, Rev. 2, Power Block Grading Plan
6. 26139-000-4MP-T81C-N3201, "Construction Survey", Rev. 5
7. 3.3.00.02b-U3-CP-Rev0, ITAAC Completion Package
8. NEI 08-01 Rev. 5 corrected 6-30-2014, Industry Guideline for the ITAAC Closure Process under 10 CFR Part 52

U.S. Nuclear Regulatory Commission ND-20-0730 Enclosure Page 4 of 5 Attachment A Excerpt from VEGP Unit 3 COL Appendix C - Table 3.3-5*

Key Dimensions o1 Table 3.3-5*

Nuclear Island Building Features Key Dimension*

Nominal Dimension*

Tolerance*

Distance of Design Plant Grade (Floor elevation 10O'-O") relative to Site Grade Oft

+/- 3 ft-6 in Attachment B Unit 3 Grading Plan Elevations for As-Built Structures Location west of Nuclear Island Distance from Nuclear Island (approximate)

Site Grading Plan Elevation (in feet MSL)

Surveyed Elevation (in feet MSL)

Within +/-

3'-6" tolerance of Plant Grade?

Y/N Site Drainage cover plate DI-NI-24 100' 218.35' 218.27' Y

Site Drainage cover plate DI-NI-25 100' 218.00' 218.06' Y

Site Drainage cover plate DI-NI-26 80' 218.00' 218.02' Y

Site Drainage cover plate DI-NI-27 90' 218.00' 217.97' Y

Note: Design Plant Grade is defined as 220'-0" MSL.