ND-20-1041, ITAAC Closure Notification on Completion of ITAAC 3.3.00.02a.i.a (Index Number 760)
| ML20259A425 | |
| Person / Time | |
|---|---|
| Site: | Vogtle |
| Issue date: | 09/15/2020 |
| From: | Yox M Southern Nuclear Operating Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| ND-20-1041 | |
| Download: ML20259A425 (12) | |
Text
^
Southern Nuclear SEP 1 5 2020 Michael J. Yox Regulatory Affairs Director Vogtle 3 & 4 7825 River Road Waynesboro, GA 30830 706-848-6459 tel ND-20-1041 10CFR 52.99(c)(1)
Docket No.;52-025 U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001 Southern Nuclear Operating Company Vogtle Electric Generating Plant Unit 3 ITAAC Closure Notification on Completion of ITAAC 3.3.00.02a.i.a findex Number 7601 Ladies and Gentlemen:
In accordance with 10 CFR 52.99(c)(1), this letter is to notify the Nuclear Regulatory Commission (NRC) of the completion of Vogtle Electric Generating Plant (VEGP) Unit 3 Inspections, Tests, Analyses, and Acceptance Criteria (ITAAC) Item 3.3.00.02a.i.a [Index Number 760]. This ITAAC verified that a report exists and concludes that the as-built containment internal structures, including critical sections, conform to the approved design with deviations reconciled such that it will withstand design basis loads without loss of structural integrity, safety-related functions, and radiation protection. The closure process for this ITAAC is based on the guidance described in NEI 08-01, Industry Guideline for the ITAAC Closure Process under 10 CFR Part 52, which was endorsed by the NRC in Regulatory Guide 1.215.
This letter contains no new NRC regulatory commitments. Southern Nuclear Operating Company (SNC) requests NRC staff confirmation of this determination and publication of the required notice in the Federal Register per 10 CFR 52.99.
If there are any questions, please contact Tom Petrak at 706-848-1575.
Respectfully submitted.
Michael J. Yox Regulatory Affairs Director Vogtle 3 & 4
Enclosure:
Vogtle Electric Generating Plant (VEGP) Unit 3 Completion of ITAAC 3.3.00.02a.i.a [Index Number 760]
MJY/JFV/sfr
U.S. Nuclear Regulatory Commission ND-20-1041 Page 2 of 3 To:
Southern Nuclear Operating Company/ Georgia Power Company Mr. Peter P. Sena III (w/o enclosures)
Mr. D. L. McKinney (w/o enclosures)
Mr. M. D. Meier (w/o enclosures)
Mr. G. Chick Mr. S. Stimac Mr. P. Martino Mr. M. J. Yox Mr. A. S. Parton Ms. K. A. Roberts Mr. T. G. Petrak Mr. C. T. Defnall Mr. C. E. Morrow Mr. R. L. Beiike Mr. S. Leighty Ms. A. C. Chamberlain Mr. J. C. Haswell Document Services RTYPE: VND.LI.L06 File AR.01.02.06 cc:
Nuclear Reoulatorv Commission M
M M
M M
M Ms. N. C. Coovert M
M M
M M
M M
M M
M M
M M
M M
M C. P. Patel G. J. Khouri N. D. Karlovich A. Lerch C. J. Even B. J. Kemker C. Welch J. Gaslevic V. Hall G. Armstrong M. Webb T. Fredette S. Smith C. Santos
- s. M. Bailey S. Rose B. Davis J. Vasquez
. J. Eargle Ms. K. Carrington
. M. King E. Davidson
. T. Fanelli
U.S. Nuclear Regulatory Commission ND-20-1041 Page 3 of 3 Oqlethorpe Power Corporation Mr. R. B. Brinkman Mr. E. Rasmussen Municipal Electric Authority of Georgia Mr. J. E. Fuller Mr. 8. M. Jackson Daiton Utilities Mr. T. Bundros Westinqhouse Electric Company. LLC Dr. L. Oriani (w/o enclosures)
Mr. D. 0. Durham (w/o enclosures)
Mr. M. M. Corletti Mr. Z. 8. Harper Mr. J. L. Coward Other Mr. J. E. Hosier, Bechtel Power Corporation Ms. L. Matis, Tetra Tech NUS, Inc.
Dr. W. R. Jacobs, Jr., Ph.D., CDS Associates, Inc.
Mr. 8. Roetger, Georgia Public Service Commission Mr. R. L.Trokey, Georgia Public Service Commission Mr. K. C. Greene, Troutman Sanders Mr. 8. Blanton, Baich Bingham
U.S. Nuclear Regulatory Commission ND-20-1041 Enclosure Page 1 of 9 Southern Nuclear Operating Company ND-20-1041 Enclosure Vogtle Electric Generating Plant (VEGP) Unit 3 Completion of ITAAC 3.3.00.02a.i.a [Index Number 760]
U.S. Nuclear Regulatory Commission ND-20-1041 Enclosure Page 2 of 9 ITAAC Statement Design Commitment 2.a) The nuclear island structures, Including the critical sections listed in Table 3.3-7, are seismic Category I and are designed and constructed to withstand design basis loads as specified in the Design Description, without loss of structural integrity and the safety-related functions.
3.) Walls and floors of the nuclear island structures as defined on Table 3.3-1 except for designed openings or penetrations, provide shielding during normal operations.
Inspections. Tests. Analvsis i) An inspection of the nuclear island structures will be performed. Deviations from the design due to as-built conditions will be analyzed for the design basis loads, and for radiation shielding.
Acceptance Criteria i.b) A report exists which reconciles deviations during construction, including Table 3.3-1 wall and floor thicknesses, and concludes that the as-built containment internal structures, including the critical sections, conform to the approved design and will withstand the design basis loads specified in the Design Description without loss of structural integrity or the safety-related functions, and without impacting compliance with the radiation protection licensing basis.
ITAAC Determination Basis Multiple ITAAC were performed to demonstrate that the Nuclear Island (Nl) structures, including the critical sections listed in VEGP Unit 3 Combined License (COL) Appendix C (Reference 1)
Table 3.3-7 (Attachment A), are seismic Category I and were designed and constructed to withstand design basis loads as specified in the VEGP Unit 3&4 COL Appendix C Section 3.3 Design Description, without loss of structural integrity and the safety-related functions. In addition, multiple ITAAC are performed on walls and floors of the Nl structures as defined on Table 3.3-1 (Attachment B) except for designed openings or penetrations, that provide radiation shielding during normal operations.
The subject ITAAC performed inspections of the as-built shield building structures, including the critical sections and Table 3.3-1 wall and floor thicknesses, and reconcilied deviations during construction to the approved design such that the as-built structures will withstand design basis loads specified in the Design Description without loss of structural integrity or the safety-related functions, and without impacting compliance with the radiation protection licensing basis.
Design bases loads are defined in VEGP Unit 3 COL Appendix C Section 3.3 as those loads associated with:
Normal plant operation (including dead loads, live loads, lateral earth pressure loads, and equipment loads, including hydrodynamic loads, temperature and equipment vibration):
U.S. Nuclear Regulatory Commission ND-20-1041 Enclosure Page 3 of 9 External events (Including rain, snow, flood, tornado, tornado generated missiles and earthquake); and Internal events (including flood, pipe rupture, equipment failure, and equipment failure generated missiles).
VEGP 3&4 Updated Final Safety Analysis Report (Reference 2), Section 3.7 "Seismic Design",
Section 3.8 "Design of Category I Structures", and Appendix 3H "Auxiliary and Shield Building Critical Sections" describe the analyses for the design basis loads for the Ml Structures. Section 3.8 specifies the applicable codes and standards governing the design, materials, fabrication, construction inspection and testing for the Ml structures. Section 3.8 also describes the as-built design summary reports which document that the seismic Category I structures meet the specified acceptance criteria.
Radiation zone and equipment qualification requirements were met in accordance with VEGP 3&4 UFSAR Tier 2 design criteria including UFSAR Subsections 3.11.4 "Estimated Radiation and Chemical Environment," 3D.5.1.2 "Radiation Dose," and 12.3.2.1 "Shielding, Design Objectives".
The containment internal structures, including the critical sections, listed in Attachment A, and walls and floors of the Nl structures as defined on Table 3.3-1 (Attachment B) except for designed openings or penetrations, provide radiation shielding during normal operations and were constructed as designed and specified in the VEGP Unit 3 COL Appendix C Section 3.3 Design Description to withstand the Design Description design basis loads without loss of structural integrity and the safety-related functions, and without impacting compliance with the radiation protection licensing basis.
The containment internal structures, including the critical sections, listed in Attachment A, and walls and floors of the Nl structures as defined on Table 3.3-1 (Attachment B), except for designed openings or penetrations, which provide radiation shielding during normal operations were inspected during construction to verify the as-built structures conform to the specified design, codes and standards. Construction identified structural deviations were documented, evaluated, and reconciled by engineering to confirm the structures' ability to withstand design basis loads without impacting compliance with the radiation protection licensing basis. The As-Built Summary Reports (References 3 & 4) exist and documents the reconciliation of Nl structural deviations identified during construction and conclude that the as-built containment internal structures, including the critical sections and walls and floors of the Nl structures as defined on Table 3.3-1 except for designed openings or penetrations, will withstand the design basis loads specified in the Design Description without loss of structural integrity or the safety-related functions, and without impacting compliance with the radiation protection licensing basis.
Unit 3 Principle Closure Documents (References 3 & 4) are available for NRG inspection as part of the Unit 3 ITAAC 3.3.00.02a.i.a Completion Packages (Reference 5).
ITAAC Finding Review In accordance with plant procedures for ITAAC completion. Southern Nuclear Operating Company (SNC) performed a review of all ITAAC findings pertaining to the subject ITAAC and associated corrective actions. This review found that there are sixteen (16) relevant ITAAC NRC findings associated with this ITAAC.
U.S. Nuclear Regulatory Commission ND-20-1041 Enclosure Page 4 of 9
- 1.05200025/2015002-01 (Closed)
- 2.05200026/2015002-01 (Closed)
- 3.05200025/2014005-01 (Closed)
- 4.05200025/2012004-01 (Closed)
- 5.05200025/2014004-01 (Closed)
- 6.05200025/2014004-02 (Closed)
- 7.05200025/2016004-01 (Closed)
- 8.05200026/2016004-01 (Closed)
- 9.05200026/2017001-01 (Closed) 10.05200025/2012004-01 (Closed)
- 11. 99901439/2015-201 -01 (Closed)
- 12. 99901439/2015-201-02 (Closed)
- 13. 99901439/2014-201-01 (Closed)
- 14. 99901425/2014-201-01 (Closed)
- 15. 99901419/2012-201-03 (Closed)
- 16. 99901409/2011-201-03 (Closed)
The corrective actions for each finding have been completed and each finding is closed. The ITAAC completion review is documented in the ITAAC Completion Package for IT/WC 3.3.00.02a.i.a (Reference 5) and is available for NRC review.
ITAAC Completion Statement Based on the above information, SNC hereby notifies the NRC that ITAAC 3.3.00.02a.i.a was performed for VEGP Unit 3 and that the prescribed acceptance criteria were met.
Systems, structures, and components verified as part of this ITAAC are being maintained in their as-designed, ITAAC compliant condition in accordance with approved plant programs and procedures.
References (available for NRC Inspection)
- 1.
VEGP Unit 3 COL Appendix C, Amendment 182
- 2.
- 3.
As-Built Building Summary Report for Containment Structures & Modules, SV3-1100-GRC-001, Rev. 0.
- 4.
Vogtle Unit #3 As-Built Summary Report: Nuclear Island Basemat, SV3-1010-GCR-001, Rev. 1.
- 5.
3.3.00.02a.i.a-U3-CP-Rev0, IT/\\AC Completion Package
- 6.
NEI 08-01, "Industry Guideline for the ITAAC Closure Process Under 10 CFR Part 52".
U.S. Nuclear Regulatory Commission ND-20-1041 Enclosure Page 5 of 9 Attachment A: Excerpt of COL Appendix C Table 3.3-7 Table 3.3-7 Nuclear Island Critical Structural Sections Containment Internal Structures South west wall of the refueling cavity South wall of the west steam generator compartment North east wall of the in-containment refueling water storage tank In-containment refueling water storage tank steel wall Column supporting the operating floor
U.S. Nuclear Regulatory Commission ND-20-1041 Enclosure Page 6 of 9 Attachment B: Excerpt of COL Appendix C Table 3.3-1 Table 3.3-1 Definition of Wail Thicknesses for Nuclear Island Buildings, Turbine Building, and Annex Building^^)
Wall or Section Description Column Lines'^)
Floor Elevation or Elevation Range<^)')
Concrete Thickness<2)(3)('>>)(5)(9)(i8)
Applicable Radiation Shielding Wall (Yes/No)
Containment Buiiding internai Structure^^^^
Shield Wall between Reactor Vessel Cavity and RCDT Room E-W wall parallel with column line 7 (Inside face is S'-O" north of column line 7. Width of wall section with stated thickness is defined by inside wall of reactor vessel cavity.)
From 71 "-6" to 83'-0" 3'.0"(io)
Yes West Reactor Vessel Cavity Wall N-S wall parallel with column line N (Width of wall section with stated thickness is defined by inside wall of reactor vessel cavity.)
From 83'-0" to 98'-0" 7'.6" (10)
Yes North Reactor Vessel Cavity Wall E-W wall parallel with column line 7 (Width of wall section with stated thickness is defined by inside wall of reactor vessel cavity.)
From 83'-0" to 98'-0" 9'.0"(io)
Yes
U.S. Nuclear Regulatory Commission ND-20-1041 Enclosure Page 7 of 9 Attachment B: Excerpt of COL Appendix C Table 3.3-1 Table 3.3-1 Definition of Waii Thicknesses for Nuciear isiand Buildings, Turbine Building, and Annex Buiiding^^^
Wall or Section Description Column Lines^^^
Floor Elevation or Elevation Range<^'<'
Concrete Thlckness<2)(3)('>>)(5)(9)(i8)
Applicable Radiation Shielding Wall (Yes/No)
Containment Building Internal Structureh^)
East Reactor Vessel Cavity Wail N-S wall parallel with column line N (Width of wall section with stated thickness is defined by inside wall of reactor vessel cavity.)
From 83'-0" to 98'-0" 7'-6"<0)
Yes West Refueling Cavity Wall N-S wall parallel with column line N From 98'-0" to135'-3" 4'-0" Yes North Refueling Cavity Wall E-W wall parallel with column line 7 From 98'-0"to135'-3" 4'-0" Yes East Refueling Cavity Wall N-S wall parallel with column line N From 98'-0"to135'-3" 4'-0" Yes South Refueling Cavity Wall E-W wall parallel with column line 7 From 98'-0"to135'-3" 4'-0" Yes South wall of west steam generator compartment Not Applicable From 103'-0" to 153'-0" 2'-6" Yes West wall of west steam generator compartment N-S wall parallel with column line N From 103'-0" to 153-0" 2'-6" Yes North wall of west steam generator compartment Not Applicable From 103'-0" to 153'-0" 2'-6" Yes South wall of pressurizer compartment Not Applicable From103'-0" to 153'-6" 2'-6" Yes West wall of pressurizer compartment N-S wall parallel with column line N From107'-2"to160'-0" 2'-6" Yes
U.S. Nuclear Regulatory Commission ND-20-1041 Enclosure Page 8 of 9 Attachment B: Excerpt of COL Appendix C Table 3.3-1 Table 3.3-1 Definition of Wall Thicknesses for Nuclear Island Buildings, Turbine Building, and Annex Building^^^
Wall or Section Description Column Lines^^)
Fioor Eievation or Eievation Range<^><>
Concrete Appiicabie Radiation Shielding Wail (Yes/No)
Containment Building internai Structure^^^'
North wall of pressurizer compartment E-W wall parallel with column line 7 From107'-2"to160'-0" 2'-6" Yes East wall of pressurizer compartment N-S wall parallel with column line N From118'-6"to160'-0" 2'-6" Yes North-east wall of in-containment refueling water storage tank Parallel to column line N From 103'-0"to 135'-3" 2'-6" No West wall of in-containment refueling water storage tank Not Applicable From 103'-0"to 135'-3" 5/8" steel plate with stiffeners No South wall of east steam generator compartment Not Applicable From 87'-6" to 153'-0" 2'-6" Yes East wall of east steam generator compartment N-S wall parallel with column line N From 94'-0"to 153'-0" 2'-6" Yes North wall of east steam generator compartment Not Applicable From 87'-6"to 153'-0" with a 158'-0" portion 2'-6" Yes
U.S. Nuclear Regulatory Commission ND-20-1041 Enclosure Page 9 of 9 Attachment B: Excerpt of COL Appendix C Table 3.3-1
- 1.
The column lines and floor elevations are identified and included on Figures 3.3-1 through 3.3-13.
- 2.
These wall (and floor) thicknesses have a construction tolerance of +/- 1 Inch, except as noted and for exterior walls below grade where the tolerance Is +12 Inches, -1 Inch. These tolerances are not applicable to the nuclear Island basemat.
- 3.
For walls that are part of structural modules, the concrete thickness also Includes the steel face plates. Where faceplates with a nominal thickness of 0.5 Inches are used In the construction of the wall modules, the wall thicknesses In this column apply. Where faceplates thicker than the nominal 0.5 Inches are used In the construction of the structural wall modules, the wall thicknesses In the area of the thicker faceplates are greater than Indicated In this column by the amount of faceplate thickness Increase over the nominal 0.5 Inches. Overlay plates are not considered part of the faceplates, and thus are not considered In the wall thicknesses Identified In this column.
- 4.
For floors with steel surface plates, the concrete thickness also Includes the plate thickness.
- 5.
Where a wall (or a floor) has openings, the concrete thickness does not apply at the opening.
- 6.
N/A to ITAAC 3.3.00.02a.l.a.
- 7.
The Wall or Section Description, Column Line Information, and Floor Elevation or Elevation Ranges are provided as reference points to define the general location. The concrete thickness of an Item Intersecting other walls, roofs or floors at a designated location (e.g., column line) Is not Intended to be measured to the stated column line, but only to the point where the Intersection occurs.
- 8.
Where applicable, the upper wall portions extend to their associated roofs, which may vary In elevation, e.g., sloped roofs.
- 9.
From one wall/floor section to another, the concrete thickness transitions from one thickness to another, consistent with the configurations In Figures 3.3-1 through 3.3-14.
- 10.
N/A to ITAAC 3.3.00.02a.l.a.
- 11.
N/A to ITAAC 3.3.00.02a.l.a.
- 12.
N/A to ITAAC 3.3.00.02a.l.a.
- 13.
N/A to ITAAC 3.3.00.02a.l.a.
- 14.
N/A to ITAAC 3.3.00.02a.l.a.
- 15.
Reconciliation of construction deviations In the nuclear Island structures from the thickness and tolerances specified In this table Is Included In the reconciliation reports, and demonstrate that the as-bullt structures will withstand design basis loads without loss of structural Integrity or safety functions and without Impacting compliance with the radiation protection licensing basis, such as GDC 19, established radiological zoning and equipment qualification In accordance with ITAAC 3.3.00.02a.l.a, 3.3.00.02a.l.b, 3.3.00.02a.l.c, or 3.3.00.02a.l.d.
- 16.
N/A to ITAAC 3.3.00.02a.l.a.
- 17.
N/A to ITAAC 3.3.00.02a.l.a.
- 18. Nonconformances from the thicknesses and tolerances specified In Table 3.3-1 (I.e. out of tolerance conditions) are addressed under the 10 CFR Part 50, Appendix B process and subsequently are screened In accordance with the 10 CFR Part 52, Appendix D,Section VIII process, to ensure that the licensing basis Is adequately maintained. Construction deviations will continue to be assessed against the licensing basis requirements and will be addressed In accordance with licensee procedures and regulatory requirements and. If applicable, a license amendment will be obtained prior to Implementation of the change.