NLS8500277, Responds to NRC Re Violations Noted in Insp Rept 50-298/85-21.Corrective Actions:Grade 8 SAE Bolts & Nuts Replaced W/Sa 193 Bolts & SA 194 Nuts & Engineering Evaluation Performed Re Torus Drain Flanged Connection

From kanterella
(Redirected from ML20137V836)
Jump to navigation Jump to search
Responds to NRC Re Violations Noted in Insp Rept 50-298/85-21.Corrective Actions:Grade 8 SAE Bolts & Nuts Replaced W/Sa 193 Bolts & SA 194 Nuts & Engineering Evaluation Performed Re Torus Drain Flanged Connection
ML20137V836
Person / Time
Site: Cooper 
Issue date: 10/07/1985
From: Pilant J
NEBRASKA PUBLIC POWER DISTRICT
To: Johnson E
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
Shared Package
ML20137V833 List:
References
NLS8500277, NUDOCS 8512100098
Download: ML20137V836 (4)


Text

- _ _ _ - _ _ - _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _.

GENERAL OFFICE Nebraska Public Power District

" * "?EfC??Saff"^!A^"""

NLk8500277 g @ 3 0 E EtQ October 7,1985 t

J Mr. E. H. Johnson, Chief u

Reactor Project Branch I g

U.S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011

Dear Mr. Johnson:

Subject:

Nebraska Public Power District Response to IE Inspection Report No. 50-298/85-21 This letter is written in response to your letter dated September 6,1985, transmitting Inspection Report No. 50-298/85-21.

Therein you indicated that one of our activities was in violation of Nuclear Regulatory Commission requirements. The following is a statement of the violation and our response in accordance with 10CFR2.201:

STATEMENT OF VIOLATION Nebraska Public Power District (NPPD) Procedures for Preparation and Completion Closure of CNS Design Change 10CFR Part 50, Appendix B, Criterion V requires that activities affecting quality be prescribed by documented instructions or procedures which shall include appropriate quantitative or qualitative acceptance l

criteria.

l Contrary to the above, no NPPD procedure existed to assure inclusion of engineered preload torques for ASME boiler and pressure vessel code Section III (Nuclear) CNS design changes, nor did NPPD procedures exist to verify that nonconforming material wes not installed or that as-built design changes met the specified design criteria.

This is a Severity Level IV violation (Supplement ID) (50-298/8521-01).

Corrective Steps Which Have Been Taken and the Results Achieved The corrective actions taken regarding the specific design changes addressed during the inspection are listed below:

a.

Design Change 77-130 " Blind Flanges on Scram Discharge" The existing nonconforming Grade 8 (SAE) bolts and nuts were replaced with SA 193 (bolts) and SA 194 (nuts), respectively.

'Ug$

85121000 9 851202 PDR ADOCK 05000298 h

G PDR

Mo, E. 'H. Johnson Piga 2 October 7,1985 Additionally, engineering analysis was performed and documented to determine the proper bolt preload torques in accordance with ANSI B31.7.

b.

Design Change 78-016 " Torus Drain Connection" The existing nonconforming A-193 (bolts) and A-194 (nuts) were replaced with SA 193 (bolts) and SA 194 (nuts), respectively. The existing nonconforming spiral-wound, metal-asbestos gaskets were left in place pending tentative plans to drain the suppression pool during a refueling outage scheduled for the Fall of 1986, at which time they would be replaced.

Following replacement of the nonconforming bolts and nuts during the 1984-85 refueling outage, the subject flanged joints showed no evidence of leakage during the primary containment Integrated Leak Rate Test (ILRT) and are thus considered adequate for operation until the Fall of 1986.

Additionally, an engineering evaluation was performed to determine the acceptability of the existing 8" elbow to 8" torus drain flanged connection.

This evaluation concluded that the existing surface finish on the torus penetration flange was acceptable as is, for use with a spiral-wound metal asbestos ("flexitallic") gasket.

Engineering analysis was performed to determine the proper bolt preload torques for the torus drain flanges in accordance with ASME Section VIII as was discussed in Design Change 77-130.

c.

Torus Drain Flanges The new blind flange was intended to replace tne criginal supplied by CBI per their Drawing 64 on Contract 68-2211.

The drawing did not require a surface finish on either the flange surface or the O-ring groove surface.

Since the groove shown is a nonstandard O-ring groove and no dimensions were given, we specified the two known 0-rings to be supplied with appropriate grooves leaving the manufacturer with the requirement to develop the correct groove dimensions and finish.

The nitrile O-ring provided, while certainly not as long-lived as a silicone O-ring, will give satisfactory service during its allowable life span.

The bolt design and preload were provided by EDS Nuclear as part of their Mark I work.

This was transmitted to NPPD and DUCI (our installer) under EDS File Memorandum CNS/EDS138.

DUCI performed the work and QC'd it per their process control sheet for NPPD Sketch No.1, Revision 0.

Corrective Steps Which Will Be Taken To Avoid Further Violation The District feels that this violation stems from an inadequate station design change procedure in that the existing procedure did not specifically address the shortcomings noted in the Statement of Violation.

i Me, E.'H. Johnson Pcge 3 October 7,1985 The following steps will be taken to avoid future violations in this area:

a.

A review of all completed safety-related station design changes will be performed to verify inclusion of engineered preload torque calculations, where required:

Engineering Procedure 3.4.

" Station Design Changes", will be b.

revised as follows:

_1)

The. design input checklist, Attachment D, will be revised to a

ensure adequate specificity in the area of code design requirements.

It is anticipated that, as a result of this review -, the design input checklist will be expanded to address additional specific line items such as bolt preload torque and code material verification.

2)

Changes will be made to address procedural adequacy regarding verification of conforming materials used and as-built conditions versus design specifications.

These changes will emphasize the area of QC Implementation.

The District feels that the procedure revisions noted above will completely address the concerns raised in this violation and preclude further violations in this area.

Date When Full Compliance Will Be Achieved Full compliance for the following items will be achieved by the indicated dates:

j' Item Date

,1.

Revise Attachment D to Station Procedure 3.4.

December 31, 1985 2.

_ Revise Procedure 3.4 to address procedural adequacy -as described in b.2 above.

June 30,1986 3.

Review of all completed safety-related design changes to verify preload torque calculation.

June 30,1986 As stated above, the nonconforming spiral-wound, metal-asbestos gaskets in Design Change 'i8-016 will be replaced if plant conditions (i.e, torus drained)' permit during the Fall 1986 outage.

It was requested in the transmittal letter of Violation 50-298/8521-01 that our response address the adequacy and accuracy of completion closure of design changes.

It should be noted that two of the design changes reviewed during this inspection were written in 1977 and 1978.

Since then, the station design change procedure has undergone approximately-ten revisions, including a major procedure rewrite.in May,1985, as a result of PAT Audit 50-298/84-21 findings. With the ' additional procedure changes described in this response, it is felt that the administrative controls governing the design change process are now adequate.

Regarding past design change control practices, an effort to determine the adequacy of station drawings in reflecting the as-built condition of the station was performed prior to start-up from the last outage.

While minor problems were noted and are being corrected, and in

Mr. E.* H. Johnson Pega 4 October 7,1985 consideration of the review of all safety-related design changes noted in the response given above, the District feels that the existing as-built configuration is sufficient such that reactor safety is not affected.

Sincerely, M

Jay M. Pilant Technical Staff Manager Nuclear Power Group JMP/SSF/WilR:emz8/3 e

i

[

.,.