IR 05000316/2005010

From kanterella
(Redirected from ML20127P257)
Jump to navigation Jump to search
Notice of Violation from Insp on 850316-0510
ML20127P257
Person / Time
Site: Peach Bottom, Cook  Constellation icon.png
Issue date: 06/26/1985
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20127P150 List:
References
50-277-85-12, 50-278-85-12, NUDOCS 8507020360
Download: ML20127P257 (2)


Text

r O

e APPENDIX A NOTICE OF VIOLATION Philadelphia Electric Company Docket / License: 50-277/DRP-44 Peach Bottom Unit 2 50-278/DRP-56 As a result of the inspection conducted on March 16, 1985 - May 10, 1985, and in accordance with the revised NRC Enforcement Policy (10 CFR 2, Appendix C)

published in the Federal Register on March 8, 1984 (49 FR 8583), the following violation was identified: Technical Specification 6.8.1 and Appendix A to Regulatory Guide 1.33, November 1972, require implementation of procedures for surveillance testing and for the control of shift operation A. FSAR Section 10.14 indicates that the Emergency Ventilating systems for the Emergency Switchgear and Battery Rooms are seismically qualifie Surveillance Test Procedure ST 7.9.2, Daily Check of Seismic Gas Supply Bottle Pressure, requires visual verification that each bottle, including nitrogen bottle 0B55385, is seismically restraine Contrary to the above from about March 5,1985, to April 8,1985, seismic qualification of the nitrogen bottle 0855385 was invalidated in that the bottle was out of its seismically designed restraint rack, secured only by a piece of rope, and the ST 7.9.2 daily checks did not identify this conditio A.1.2 Administrative Procedure A-7, Shift Operations requires that when the Control Room Supervisor is away from his post for more than one-half hour, the on-coming Control Rcc= Supervisor receive a verbal turnover report, review and sign the turnover check-off list l completed by the Control Room Supervisor leaving the post, read the l logs, and inspect the control panel Contrary to the above, on May 5, 1985 the Control Room Supervisor position was changed four times to relieve the Senior Licensed l Operator on the refuel floor with each change being longer than one-half hour, and the turnover check-off list was not completed for each change.

l This is a Severity Level IV Violation (Supplement I) applicable to l DPR-44 and DPR-5 PDR ADOCK 05000277 l G PDR l

l OFFICIAL RECORD COPY CIR PB 85-12 A - 0003.0.0 l 06/15/85 t

-

,

.

.

Appendix A 2-Pursuant to the provisions of 10 CFR 2.201, Philadelphia Electric Company is hereby required to submit to this office within 30 days of the date of the letter transmitting this Notice, a written statement or explanation of reply, including: (1) the corrective steps which have been taken and the results achieved; (2) the corrective steps which will be taken to avoid further viola-tions, and (3) the date when full compliance will be achieved. Where good cause is shown consideration will be given to extending the response tim Because Violation A.1.2 was corrected during the inspection period and correc-tive actions to avoid further violations were also made, no written response is required for A. OFFICIAL RECORD COPY CIR PB 85-12 A - 0004. /14/85