IR 05000430/2005003

From kanterella
(Redirected from ML20127M686)
Jump to navigation Jump to search
Notice of Violation from Insp on 850430-0503
ML20127M686
Person / Time
Site: Summer, 05000430 South Carolina Electric & Gas Company icon.png
Issue date: 05/15/1985
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20127M680 List:
References
50-395-85-19, NUDOCS 8507010326
Download: ML20127M686 (1)


Text

.

.

ENCLOSURE 1 NOTICE OF VIOLATION South Carolina Electric and Gas Company Docket No. 50-395 V. C. Summer Nuclear Plant License No. NPF-12 The following violation was identified during an inspection conducted on April 30 - May 3, 1985. The Severity Level was assigned in accordance with the NRC Enforcement Policy (10 CFR Part 2, Appendix C).

Technical Specification Table 4.11-2 requires the analysis of Xe-138 in gaseous waste samples at a Lower Limit of Detection (LLD) of 1E-04 micro-curies per cc.

Contrary to the above, during the period January 1984 through April 1985, there were two examples of failure to achieve the required LLD for Xe-138 due to excessive decay time between sampling and analysis.

This is a Severity Level V violation (Supplement IV).

Pursuant to 10 CFR 2.201, you are required to submit to this office within 30 days of the date of this Notice, a written statement or explanation in reply, including:

(1) admission or dental of the alleged violations; (2) the reasons for the violations if admitted; (3) the corrective steps which have been taken and the results achieved; (4) corrective steps which will be taken to avoid further violations; and (5) the date when full compliance will be achieved.

Security or safeguards information should be submitted as an enclosure to facilitate withholding it from public disclosure as required by 10 CFR 2.790(d)

or 10 CFR 73.21.

fMy 151985 Date:

g 70{0 g $$

.35

0

!

.

-

-

...

.

--,A