LER-1981-039, /03L-0:on 810703,inverter for Alarm Panel XA-55-8E Became Inoperable.Caused by Failure of Inverter Control Card.Card Replaced & Successfully Tested |
| Event date: |
|
|---|
| Report date: |
|
|---|
| 2591981039R03 - NRC Website |
|
text
.,
Nnc rcnM ass [
u. S. NUCLE AR REGUL ATORY COMMISSICN (7-77) -
' ICENSEE EVENT REPORT 8
CONTHOL BLOCK; l l
l l
l l
l (PLE ASE PRINT OR TYPE ALL REQUIRED INFORMATION) 6 jo li j l ^l hl Bl Rl F] 1l@l 0l 0l -l 0l 0l 0l 0l 0 l -l 0l 0 l@l 4 l 1 l 1 l 1l 1l@l l
l@
F 48
'l LIC( N$tt CODt 14 tb LICENSE NUMBEH 26 26 LICENSE TYPE JO
$7 LAT $8 CON' T lo]il Z l Ll@l 01 S l 0l 01 0 l 21 S l 91@l 0 l 71 0 l 3 l 8 l 1 ]@l 0 l 7 l 3 l 0 l 8 ll l@
/
n t,u GI DOCKET NUMBER 68 63 EVENT DATE 74 75 REPORT DATE 80 EVEN T OESCntrTION AND PROBABLE CONSEQUENCES h 101.'] l During refueling outage, while performing SI 4.11.C 3 & 4, the inverter for alarm l
ln ;3l l panel XA-55-8E became inoperable. The inverter control card was tightened in its l
l n [. l l slot arvi began to operate. The next day while perfonning SI 4.11.C 3 & 4, it I
o s l again became inoperable.
(See T.S. 3.ll.C.1).
There waE no danget to the health 1
l o l r, l l or safety of the public. There were no redundant systems. Previous similar event:
l [o lil l BFRO-50-296/79015.
I I
10181l 80 i
n9 C DE CO E SUBC E COMPONENT CODE S BCOD'E SU E
l A lB l@ Wh W@ l A lN lN lU lN lC lh y@ J @
lol9 8 p
H 0
to 11 12 33 18 19 20 SEQUEN TI AL OCCURRENCE REPOftT R E VISION REPORT NO.
COOE TYPE NO.
lVEN T YEAR
[-j l0l3l9l y
l 0l 3l W
[.--J y
t F RcHO E
@ ljeg 8l1l
_ 21 22 23 24 26 27 N
29 30 31 32 KEN A Of ON PL NT 9ET D HOURS SB IT D FOR h B.
SUPPL 1 R MAN FACTU ER [Aj@[Zj@
W@
lZl@
l0l0l0l0l l Yl@
l Y l@
lLl@
l L l 2 l 9 l 5 l@
J3 J4 3S A,
31 40 41 42 43 44 47 CAUSE OESCRIPTION AND CORRECTIVE ACTIONS l i l o l l The inverter control card for alarm panel XA-55-8E failed. The Lundell inverter l
1 i I ij L control card model 1265A was replaced, successfully tested, the anruw.ciator returned I I to service, and S1 4.11.C 3 6 4 complete successi'ully. This is considered a l
l random failure and no further recurrer.e control is required.
I i i l e l41 l I
.t
.0
% PfhNE R oTHER STATUS ISCOV R DISCOVEHY DESCRIPTION 1
l r l',l (_Ijj(@ l 0 l 0 l 0 l@l NA l
lBl@l Surveillance testing l
" a',,vi r, carENT
~
- - OUNT o, ACTiv,1Y @ l n,u rs w or R u f u.E LOCATION OF RELE ASE NA l
NA l
P, nsnN,J",,P,s L or sauP1.oN @
~n nt n rvPr [i l r l l Ol 0l 0l@l Zl@l NA l
P, n. on~,",n. A ne.cnPno @
No,,,, o li l l l 01 01 Ol@l NA l
u
.0 1.0:;'i 0, OH f)AMAGE TO F ACit.t TV t YPt-OL*Kn P flON l l.,l [ZJ@l NA l
't IU 80 g.,.,g g y 9 '
l >E
_f tiP f lON e
Il"ILNj@l NA l
[]lllllllllllj 4
at
's 10 68 69 80 li; Gene Holder (205) 729-6134 o
8103100213 810730 HER PHONE:
PDR ADOCK 05000259 PDR j
j
..b Tenessee Valley Authority Form HF 17
!!F 15.2 browns Ferry Nurlear Plant o
G/t)4/81 1.F.!! StiPPl.F. MENTAL. INFORMATIOis itelt() bO. 259 f,81039 T..chnical Spe~cifi..i on in c< deed 3.11.C.1 d
!!cporte.l liniter Technic.d Specification 6.7.2.b(2)
=j,n te, hie tutC:,8/2/81 flate of Oce iri ence '7/3/81 Time of Utcurrence 0905 Unit 1
identification ant! Deneription of Occurrene" While performing SI 4.ll.C' 3 & 4, the inverter control card for alarm panel XA-55-8E failed. It was tightened in its slot and began to operate. The next day while again performing S14.ll.C 3 & 4, it became inoperabie and power could not be restored.
1 Conditions Prior to Occurrence' Unit 1 in refueling outage.
Un'it 2 at 99%.
Unit 3 at 99%.
Action spec ified in the Technical Specification Surveillance Requirements met l
d:se to inoperable espipment.
Desc ribe.
Met surveillance requirements of T.S. 3.11.C.2.
l t
i App.trellt QtuSe of ()"currence-Loss of power to panel XA-55-8E.
Cause is unknown.
4 Analy:.is, of, Ocep rrence i'-
There was no-danger to the health or safety of the public, no release of activity, no damage'to the plant or equipment, and no'resulting significant
. chain of events.
Corrective Action
When power to panel first failed, the inverter card for panel XA-55-8E was tighted in its slot and the annunciator operated. The next day while again performing SI 4.ll.C 3 & 4, the inverter'again failed and power could not be restored. The inverter control card was replaced, successfully.
tested, and returned to' service. This is considered a random failure and_no further recurrence control is required.
Failure Data:
BFRO-50-296/79015.
!!ctention.:
P (1 - I.ifetime; llesponsibility - Document Control Supervisor -
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000260/LER-1981-001, Forwards LER 81-001/01T-0 | Forwards LER 81-001/01T-0 | | | 05000260/LER-1981-001-01, /01T-0:on 810102,scram Discharge Vol Level Switch 2-LS-85-45A Found Inoperable & -C & -D Found Offscale.Caused by One Robert Shaw Switch Model SL-305-EI-X Sticking & Setpoint Drift.Stuck Switches Float Chamber Back Flushed | /01T-0:on 810102,scram Discharge Vol Level Switch 2-LS-85-45A Found Inoperable & -C & -D Found Offscale.Caused by One Robert Shaw Switch Model SL-305-EI-X Sticking & Setpoint Drift.Stuck Switches Float Chamber Back Flushed | | | 05000259/LER-1981-001, Forwards LER 81-001/03L-0 | Forwards LER 81-001/03L-0 | | | 05000296/LER-1981-001, Forwards LER 81-001/03L-0 | Forwards LER 81-001/03L-0 | | | 05000296/LER-1981-001-03, /03L-0:on 810106,both Smoke Detectors in Reactor Bldg Fixed Spray Zone Were Inoperable.Caused by Loose Screw in Terminal Block.Screw Replaced | /03L-0:on 810106,both Smoke Detectors in Reactor Bldg Fixed Spray Zone Were Inoperable.Caused by Loose Screw in Terminal Block.Screw Replaced | | | 05000259/LER-1981-001-03, /03L-0:on 810105,core Spray Sparger to Reactor Pressure Vessel D/P Switch 1-PDIS-75-28 Found Set Above Tech Spec Limit.Caused by Barton Model 288 Setpoint Drift.Switch Replaced W/New Switch on 810115 | /03L-0:on 810105,core Spray Sparger to Reactor Pressure Vessel D/P Switch 1-PDIS-75-28 Found Set Above Tech Spec Limit.Caused by Barton Model 288 Setpoint Drift.Switch Replaced W/New Switch on 810115 | | | 05000260/LER-1981-002-03, /03L-0:on 810102,scram Discharge Instrument Vol Rod Block Level Switch 2-LS-85-45E Found Set at 27 Gallons. Alarm Switch 2-LS-85-45F Found Inoperable.Caused by Drift of Robertshaw Model SL-305-EI-X.Switch Recalibr | /03L-0:on 810102,scram Discharge Instrument Vol Rod Block Level Switch 2-LS-85-45E Found Set at 27 Gallons. Alarm Switch 2-LS-85-45F Found Inoperable.Caused by Drift of Robertshaw Model SL-305-EI-X.Switch Recalibr | | | 05000296/LER-1981-002-03, /03L-0:on 810104,excess Flow Check Valves in B3 & B7 Instrument Lines to Panel 25-7 Would Not Restrict Flow Properly.Cause Not Stated.Internals Changed & SI 4.7.D.1.d Successfully Completed | /03L-0:on 810104,excess Flow Check Valves in B3 & B7 Instrument Lines to Panel 25-7 Would Not Restrict Flow Properly.Cause Not Stated.Internals Changed & SI 4.7.D.1.d Successfully Completed | | | 05000259/LER-1981-002, Forwards LER 81-002/03L-0 | Forwards LER 81-002/03L-0 | | | 05000259/LER-1981-002-03, /03L-0:on 810114,smoke Detector in Relay Room Alarmed & Would Not Clear.Caused by Detector Sensitivity Increasing Due to Normal,Natural Aging.Detector Replaced & Tested | /03L-0:on 810114,smoke Detector in Relay Room Alarmed & Would Not Clear.Caused by Detector Sensitivity Increasing Due to Normal,Natural Aging.Detector Replaced & Tested | | | 05000296/LER-1981-002, Forwards LER 81-002/03L-0 | Forwards LER 81-002/03L-0 | | | 05000260/LER-1981-002, Forwards LER 81-002/03L-0 | Forwards LER 81-002/03L-0 | | | 05000260/LER-1981-003-03, /03L-0:on 810112,core Spray Pump Discharge Pressure Switch 2-PS-75-16 Found Outside Tech Spec Limits. Caused by Setpoint Drift.Switch Recalibr & Replaced | /03L-0:on 810112,core Spray Pump Discharge Pressure Switch 2-PS-75-16 Found Outside Tech Spec Limits. Caused by Setpoint Drift.Switch Recalibr & Replaced | | | 05000259/LER-1981-003-01, /01T-0:on 810124,Div of Engineering Notified That 1-inch Vent Line on Unit 1 Scram Discharge Vol Not Seismically Qualified.Caused by Piping Configuration Not Conforming to Design Requirements | /01T-0:on 810124,Div of Engineering Notified That 1-inch Vent Line on Unit 1 Scram Discharge Vol Not Seismically Qualified.Caused by Piping Configuration Not Conforming to Design Requirements | | | 05000259/LER-1981-003, Forwards LER 81-003/01T-0 | Forwards LER 81-003/01T-0 | | | 05000260/LER-1981-003, Forwards LER 81-003/03L-0 | Forwards LER 81-003/03L-0 | | | 05000296/LER-1981-003, Forwards LER 81-003/03L-0 | Forwards LER 81-003/03L-0 | | | 05000296/LER-1981-003-03, /03L-0:on 810107,during Refueling Outage,Fuel Pool Cooling Sys Auto Isolated When Power Was Removed.Fuel Pool Sampling Not Performed on 8-h Schedule.Caused by Personnel Error.Personnel Reinstructed | /03L-0:on 810107,during Refueling Outage,Fuel Pool Cooling Sys Auto Isolated When Power Was Removed.Fuel Pool Sampling Not Performed on 8-h Schedule.Caused by Personnel Error.Personnel Reinstructed | | | 05000260/LER-1981-004-01, /01T-0:on 810119,reactor Water Level Switches LIS-3-203A Switch 1 & LIS-3-A,B,C,D Switch 2 Found Outside Tech Specs.Caused by Drift Due to Air Impact Drilling Next to Switch Panel.Switches Recalibr | /01T-0:on 810119,reactor Water Level Switches LIS-3-203A Switch 1 & LIS-3-A,B,C,D Switch 2 Found Outside Tech Specs.Caused by Drift Due to Air Impact Drilling Next to Switch Panel.Switches Recalibr | | | 05000296/LER-1981-004-03, Diesel Generator 3A & Breaker 1836 Tripped from Generator Overspeed During Testing.Caused by Vs Relay on Speed Sensing Panel Energizing at Less than 870 Rpm,Closing Breaker 1836 | Diesel Generator 3A & Breaker 1836 Tripped from Generator Overspeed During Testing.Caused by Vs Relay on Speed Sensing Panel Energizing at Less than 870 Rpm,Closing Breaker 1836 | | | 05000296/LER-1981-004, Forwards Updated LER 81-004/03X-1 | Forwards Updated LER 81-004/03X-1 | | | 05000259/LER-1981-004, Forwards Updated LER 81-004/03L-1 | Forwards Updated LER 81-004/03L-1 | | | 05000259/LER-1981-004-03, Standby Gas Treatment Sys Train C Relative Humidity Heaters Declared Inoperable.Caused by Dwyer Photohelic Pressure Switch/Gage Circuit Hh & Ite Imperial Relay Contact Block Malfunction | Standby Gas Treatment Sys Train C Relative Humidity Heaters Declared Inoperable.Caused by Dwyer Photohelic Pressure Switch/Gage Circuit Hh & Ite Imperial Relay Contact Block Malfunction | | | 05000260/LER-1981-005-03, /03L-0:on 810119,core Max Fraction of Limiting Power Density Exceeded Limit for One Node in Core.Caused by Operation Close to Limit in Conjunction W/Minor (Normal) Perturbation in Monitored Parameters.Power Reduced Slightly | /03L-0:on 810119,core Max Fraction of Limiting Power Density Exceeded Limit for One Node in Core.Caused by Operation Close to Limit in Conjunction W/Minor (Normal) Perturbation in Monitored Parameters.Power Reduced Slightly | | | 05000259/LER-1981-005-04, /04T-0:on 810131,hydrogen Ion Concentration of Reservoir Near Plant Found in Excess of Allowable Discharge Limit.Probably Caused by Upstream Source.Discharge of Spent Regenerants Stopped & Monitoring Program Established | /04T-0:on 810131,hydrogen Ion Concentration of Reservoir Near Plant Found in Excess of Allowable Discharge Limit.Probably Caused by Upstream Source.Discharge of Spent Regenerants Stopped & Monitoring Program Established | | | 05000296/LER-1981-005-03, /03L-0:on 810127,containment Atmosphere Hydrogen analyzer,3-H2M-76-94,removed from Svc.Caused by Maint on Sensing Line at 3-FIC-76-94,Model 1350,due to Water Collection.Water Removed & Lines Returned to Svc | /03L-0:on 810127,containment Atmosphere Hydrogen analyzer,3-H2M-76-94,removed from Svc.Caused by Maint on Sensing Line at 3-FIC-76-94,Model 1350,due to Water Collection.Water Removed & Lines Returned to Svc | | | 05000296/LER-1981-005, Forwards LER 81-005/03L-0 | Forwards LER 81-005/03L-0 | | | 05000260/LER-1981-005, Forwards LER 81-005/03L-0 | Forwards LER 81-005/03L-0 | | | 05000259/LER-1981-005, Forwards LER 81-005/04T-0 | Forwards LER 81-005/04T-0 | | | 05000259/LER-1981-006, Forwards LER 81-006/03L-0 | Forwards LER 81-006/03L-0 | | | 05000259/LER-1981-006-03, /03L-0:on 810211,while Performing SI 4.2.B-57,RHR Area Cooling Fan Temp Switch 1-TS-64-68 Failed to Operate. Caused by Switch T675A1540 Failure.Switch Replaced,Calibr & 4.2.B-57 Completed | /03L-0:on 810211,while Performing SI 4.2.B-57,RHR Area Cooling Fan Temp Switch 1-TS-64-68 Failed to Operate. Caused by Switch T675A1540 Failure.Switch Replaced,Calibr & 4.2.B-57 Completed | | | 05000296/LER-1981-006-03, /03L-0:on 810128,containment Atmosphere Hydrogen Analyzer Removed from Svc.Caused by Maint on Sensing Lines Due to Effect of Water Accumulation on Model 76-01A625 Timer.Water Removed & Monitor Returned to Svc | /03L-0:on 810128,containment Atmosphere Hydrogen Analyzer Removed from Svc.Caused by Maint on Sensing Lines Due to Effect of Water Accumulation on Model 76-01A625 Timer.Water Removed & Monitor Returned to Svc | | | 05000296/LER-1981-006, Forwards LER 81-006/03L-0 | Forwards LER 81-006/03L-0 | | | 05000260/LER-1981-006-03, /03L-0:on 810121,core Max Fraction of Limiting Power Density Exceeded Limit.Caused by Power Increase in Conjunction W/Inoperable Process Computer.Power Reduced & Control Rod Pattern Adjustment Made on 810123 | /03L-0:on 810121,core Max Fraction of Limiting Power Density Exceeded Limit.Caused by Power Increase in Conjunction W/Inoperable Process Computer.Power Reduced & Control Rod Pattern Adjustment Made on 810123 | | | 05000260/LER-1981-006, Forwards LER 81-006/03L-0 | Forwards LER 81-006/03L-0 | | | 05000260/LER-1981-007-03, /03L-0:on 810129,during Power Increases,Tech Spec Limit of 13.33 Kw/Ft for Linear Heat Generation Rate Exceeded in One Node.Node Reached 13.77 Kw/Ft.Caused by Xenon Transient Resulting from Increased Core Power | /03L-0:on 810129,during Power Increases,Tech Spec Limit of 13.33 Kw/Ft for Linear Heat Generation Rate Exceeded in One Node.Node Reached 13.77 Kw/Ft.Caused by Xenon Transient Resulting from Increased Core Power | | | 05000260/LER-1981-007, Forwards LER 81-007/03L-0 | Forwards LER 81-007/03L-0 | | | 05000259/LER-1981-007, Forwards LER 81-007/03L-0 | Forwards LER 81-007/03L-0 | | | 05000259/LER-1981-007-03, /03L-0:on 810210,during Fire Door Insp,Fire Door Damper (Door 472) Not Closed.Caused by Paint Buildup in Operating Mechanism.Damper Closed & Other Dampers Inspected. Procedure for Insp & Preventive Maint Will Be Written | /03L-0:on 810210,during Fire Door Insp,Fire Door Damper (Door 472) Not Closed.Caused by Paint Buildup in Operating Mechanism.Damper Closed & Other Dampers Inspected. Procedure for Insp & Preventive Maint Will Be Written | | | 05000296/LER-1981-007-03, /03L-0:on 810202,setpoint for 3-PS-1-76 Below Tech Specs Limit.Caused by B2TA12SS Setpoint Drift.Switch Recalibr & Verified.Switch to Be Replaced W/Analog Trip Sys by DCR 1398 | /03L-0:on 810202,setpoint for 3-PS-1-76 Below Tech Specs Limit.Caused by B2TA12SS Setpoint Drift.Switch Recalibr & Verified.Switch to Be Replaced W/Analog Trip Sys by DCR 1398 | | | 05000296/LER-1981-007, Forwards LER 81-007/03L-0 | Forwards LER 81-007/03L-0 | | | 05000260/LER-1981-008-03, /03L-0:on 810220,reactor Core Isolation Cooler Turbine Trip & Throttle Valve Closed & Would Not Reopen. Caused by Overload Heater Relay.Relay Replaced | /03L-0:on 810220,reactor Core Isolation Cooler Turbine Trip & Throttle Valve Closed & Would Not Reopen. Caused by Overload Heater Relay.Relay Replaced | | | 05000259/LER-1981-008-01, /01T-0:on 810226,secondary Containment Integrity Lost When Exterior Equipment Access Door 229 & Interior Personnel Door 228 Opened Simultaneously.Caused by Lack of Interlocks Between Doors.Interlocks to Be Installed | /01T-0:on 810226,secondary Containment Integrity Lost When Exterior Equipment Access Door 229 & Interior Personnel Door 228 Opened Simultaneously.Caused by Lack of Interlocks Between Doors.Interlocks to Be Installed | | | 05000296/LER-1981-008-03, /03L-0:on 810202,RHR Pump Found Inoperable.Caused by Loose Pump 3D Breaker Trip Adjustment Nut & Adjustment Change,Causing Breaker to Trip Free on Attempting to Close. Breaker Replaced.Adjustment Locknut Tightness Checks Add | /03L-0:on 810202,RHR Pump Found Inoperable.Caused by Loose Pump 3D Breaker Trip Adjustment Nut & Adjustment Change,Causing Breaker to Trip Free on Attempting to Close. Breaker Replaced.Adjustment Locknut Tightness Checks Added | | | 05000296/LER-1981-008, Forwards LER 81-008/03L-0 | Forwards LER 81-008/03L-0 | | | 05000259/LER-1981-008, Forwards LER 81-008/01T-0 | Forwards LER 81-008/01T-0 | | | 05000260/LER-1981-008, Forwards LER 81-008/03L-0 | Forwards LER 81-008/03L-0 | | | 05000296/LER-1981-009, Forwards LER 81-009/03L-0 | Forwards LER 81-009/03L-0 | | | 05000259/LER-1981-009, Forwards LER 81-009/01T-0 | Forwards LER 81-009/01T-0 | | | 05000260/LER-1981-009, Forwards LER 81-009/03L-0 | Forwards LER 81-009/03L-0 | |
|