ST-HL-AE-3375, Application for Amends to Licenses NPF-71 & NPF-80,revising Tech Specs Re Tendon Surveillance

From kanterella
(Redirected from ML20006F002)
Jump to navigation Jump to search
Application for Amends to Licenses NPF-71 & NPF-80,revising Tech Specs Re Tendon Surveillance
ML20006F002
Person / Time
Site: South Texas  
Issue date: 02/14/1990
From: Rosen S
HOUSTON LIGHTING & POWER CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20006F003 List:
References
ST-HL-AE-3375, NUDOCS 9002270064
Download: ML20006F002 (4)


Text

,y The Light company P.O. Ilox 1700 ifouston. 'lixas 77001 (713) 228 9211 th usion Lighting k Power-February 14, 1990 ST-HL-AE-3375 File No.:

G2.06 10CFR50.90 U. S. Nur. lear Regulatory Commicslon Attention: Document Control Desk Washington, DC 20555 South Texas Project Electric Generating Station Units 1 & 2 Docket Nos. STN 50-498, STN 50-l.99 Proposed Amendment to the Unit 1 and Unit 2 Technical Specif g @ nj n Tendon Surveily m l

Referonca Letter from R. W. Chewning te MBC Docunent Control Desk Jated November *19, 1999 (ST itL-AE-3212)

The f.d:puse of this eubm3tta) is to revise the above referenced letter regarding the Technical Specification on Tandon Survs111ance.

In the i

November 7.9. 1969 submittal HLW regtter.ted a Sheathing fl',ler 6rease voJ'l volume of 10% of the net duct vc'lu>ae.

In a te?.ephor,e cesiver:sation on January 26, 1790 with members ol' ths NnC staf f.!t sas s. greed that a sheathirg ti'.ler grease vo.id volume of 5% vill continue to bo used.

STPEGS currently utili;tss a 5% rheathing fiMer grease void allowance in Technical Specitiention St,rveillance 4.6.1. 6.1.e. l.

STPEGS requests that the current surveillance requirement of 5% net duct volume be applied to sheathing filler grease and has revised the November 29, 1989 request as shown in the attachment.

HL&P has reviewed the attached proposed revision to the November 29, 1989 submittal and determined that a significant hazards evaluation is nct required pursuant to 10CFR50.91 because STPEGS is revising the November 29, 1989 submittal to maintain the current Technical Specification Surveillance requirement for void content of sheathing filler grease.

The detep ' nation of l

significant hazards considerations provided in the November 29, 190. letter and the conclusions that the proposed changes do not involve a sign.sicant hazards consideration remains valid.

In addition, based on the information contained in this submittal and the NRC Final Environmental Assessment for STPEGS Units 1 and 2 HL&P has concluded that pursuant to 10CFR51, there are no significant radiological or nonradiological impacts associated with the proposed action and that the proposed license amendment will not have a significant effect on the quality of the environment.

9002270064 900214 I

PDR ADOCK 05000498 P

PNV l

NL.89.163.01 A Subsidiary of Ilouston Industries incorporated

[()p f

'll

p I

U iloustosi 1.ightilig & 1%cr Coliiltati)

ST-HL-AE-3375 File No.:

G2.06 Page 2 l

1 In accordance with 10CFR50.91(b) HL&P is providing the State of Texas lL with a copy of this proposed amendment.

i If the NRC should have any questions concerning this matter, please contact Mr. M. A. McDurnett at ($12) 972-8530 or myself at ($12) 972-7138.

L i

i M S. L. Rosen Vice President Nuclear Engineering and Construction GEV/GCS/nl Attach: tent Mark-up of Attachment 2 to the Let*,er Dated November 29, 1989 I

a f

)

NL.89.163.01

r I

ST.HL.AE. 3375 Houston Lighting & Power Company File No.: C2.06

(

South Texas Pngect Electric Generating Station Page 3 cc:

Regional Administrator, Region IV Rufus S. Scott Nuclear Regulatory Commission Associate General Counsel 611 Ryan Plaza Drive, Suite 1000 Houston Lighting & Power Company Arlington, TX 76011 P. O. Box 61867 Houston, TX 77208 l

George Dick, Project Manager U.S. Nuclear Regulatory Commission INPO Vashington, DC 20555 Records Center 1100 circle 75 Parkway J. I. Tapia Atlanta, GA 30339 3064 Senior Resident Inspector c/o V. S. Nuclear Regulatory Dr. Joseph M. Hendrie Commission 50 Be11 port Lane P. O. Box 910 Be11 port, NY 11713 Bay City, TX 77414 D. K. Lacker J. R. Newman, Esquire Buromu of Radiation Contvoi Newman & Holtzinger, P.C.

Texas Department of Health y~

1415 L Stceet, N.W.

1100 *.'est 49th Streen Washington, DC 20036 Austin, TX 78704 D, E. Var 6 R. P. Verret f

Central Power & Light Ceopony P. O. Box 2121 Corru9 %risti, TX 78403 J. C. Esnier Director of Generation City of Austin Electric Utility 721 Barton Springs Road Austin, TX 78704 R. J. Coste11c/M. T. Hardt City Public Service Board P. O. Box 1771 San Antonio, TX 78296 Revised 12/15/89 L4/NRC/

7 1

i f

i UNITED STATES OF AMERICA I

i NUCLEAR REGULATORY COMMISSION In the Matter

)

)

Houston Lighting & Power

)

Docket Nos. 50-498 i

Company,-et al.,

)

50-499 i

)

i South Texas Project

)

i Unit I and Unit 2

)

AFFIDAVIT S. L. Rosen being duly sworn, hereby deposes and says that he is Vice 1

President, Nuclear Engineering and Construction, of Houston Lighting & Power i

Company; that he is duly authorized to siCn and file with the Nuclear Regulatory Commissions is familiar with the content of the attached proposed

]

change to the South Texas Project Electric Generating Station Technical Specification autveillance 4.6.1.6.1.6,d.2; and that the matters set forth therein art true and correct to the best of his knowledge and belief.

i S, L. Rosen Vice President, Nuclear Engineering and j

Construction 2

State of Texcs this /fLys orn to before me, a Notary Public in and for The Subscribed and day of FEdt uM4V,1990.

l.

JACGE A(AUL1 d

haf-[

non Put*c.5** d 1**

g wa te t.1393 Notary Public in and for the

[

State of Texas I

l l

l' NL.89.163.01 h