/01T-0:on 800602,while Reviewing Instrument Buses Per IE Bulletin 79-27,failure of 250 Volt Dc Battery Board Determined to Cause Feedwater Flow to Increase to Full Flow & Disable Feed Pump Trips.Caused by Power Nonseparation
ML19323J229
Person / Time
Site: Browns Ferry 
Issue date: 06/13/1980
From:
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19323J228 List:
References
IEB-79-27, LER-80-044-01T-01, LER-80-44-1T-1, NUDOCS 8006190470
Download: ML19323J229 (2)


LER-1980-044, /01T-0:on 800602,while Reviewing Instrument Buses Per IE Bulletin 79-27,failure of 250 Volt Dc Battery Board Determined to Cause Feedwater Flow to Increase to Full Flow & Disable Feed Pump Trips.Caused by Power Nonseparation
Event date:
Report date:
2591980044R01 - NRC Website

text

_.,

(G)m 5

LICEN3E EVEN r ncPOHT CONTROt. BLOcrh l l

l l

l l lh

.PLEASE PRINT OR TYPl; 44t REQUIRED INFORMATIONI e

a foTIl l Al Ll Bl Rl Fl 1l@! 0 l 0 l - l 0 l 0 l 0 l 0 l 0 l - l 0 l 0 l@l 4 l 1 l 1 l 1 l 1 l@l l-* ! 54 @

l s 9 L LEP4SEE CODE le 15 LICENSE Nuv6E n 2$

26 LICE NSE T* *E J0 S7 CON'T lol'4l

$[?"c, lX }@l 0l 5 l 0 l 0 l 0 l 2 l 5 l 9 @! 0161012 l 810 @l 016 l1l_318lOl@

7 60 6s CoCr ET NuYB E q 41 61 EVENT oATE 14 75 AEPonT DATE SO EVFN T CESCHIPTtON AND PROll A8LE CONSEQUENCtS O'o 10121 l During normal operation while reviewing instrument buses per IE Bulletin 79'27, i

g ; it was detemined that failure of 250V DC battery board would cause feedwater flow g ; to increase to full flow and feed pump trips to be disabled.

Reference FSAR section j

g,14.5.7.

It was initially reported that this postulated event could only occur in j

"A" m de.

Further investigation revealed it could occur in "B" mode also.

No o 6 l

redundant systems. No previous occurrences. No danger to the health or safety of g o g,; g y,the public.

a-a3 SYSitu C AUSE CAU0E r oA

VALvt CCCE COCE SLuCODE CovPONENT CODE SuR 70E SU9CCOE lo191 i Cl ul@ LzJG I z l@ l zl zl zl zl zl zl@ Lz_J@ LZ_]@

7 8

9 10 It 12 13 1 41 t) 20 SE oOE N TI AL oCCU N 4('diJ RE' ORT R E V'SION L E n no EVENT YEAR RE*0RT No.

CoCE tveE

  • . 0 h,aE,*j;r, l8 l0 l l-l l 0l 4l 4l

], -l l0l1l lTl l-l l0l

,,,, J i 2/

73 24 26 21 29 29

0 J'

L' "s*cs*0I71IS' rNESb

'Ee' EON u m'su"[AlNE n l 0l 0l 0@l 0l I

^[1'.N 'AN84 oWtN1

'"N?OF wouas [X Jgl34X[g W@

[ Z l@

y@

l N l@

l Z]@

l Z l 9 l 9 l 9 l(

JJ,

35 36 31 40 46 42 43 44 4;

CAUSE DESCAIPTION AND COHRECTIVE ACTIONS h g l Caused by non-separation of power to feedwater flow control and trip solenoids.

,,, j ; Temporary alteration made to provide unit preferred power to two flow control i

gmodules so "B" mode would be independent of 250V DC.

Established administrative controls

,,,,,g for operation in "A" mode.

Investigating ways to permanently separate flow controls and trip solenoid power.

I i

s 3 m

's^r'A Els' oveE n si ATVs bEd$.N'

. r.i u n i " cc. Es cesCn'rTicN l1 15 I LEJ@ l') 18Iil@l NA I

lo l@l Division of Engineering Designnotified]

' 2treirv UN ttNT a..ouNr or AcrivirY h l tec a rioN or acte Asc h A

W [ z] @o es no rwl Z lgl an E.c t l

NA l

NA 7

8 3 _

10 tt 44 45 d

'E RSONNf t f

  • POSLnES l t l 7 l l 0 l 0 l 0 l@l Z l@l J

NA

" ',Enmst!',NJhs n E sCn,,,,0N @

....n f7TlI010101@l NA l

7 8 9 11 12 BC TOSS OF C58 D AMAGE TO F ACILITV vitt DEsenie TION NA J

l Z j@l i,

,o

  • lCn,,T,oN@ 800619o #f 74 E

,,u0tLt 61 lllll11IlIliI N

2 a a g to 69 69 M -

.:Avr rig pr ronor et __

7383NE

~

t, i

Tennessee Valley Authority Ferm DFv17 i

~ Browns Ferry Nuclear Plant B F 15. 2 i

1/10/79 LER SUPPLEMENTAL INFORMATION BFRO-50-2L/ 8044 Technical Specification Involved FSAR section 14.5.7,

Reported Under Technical Specification 6.7.2.A.8 Data e Occurrence 6/2/80 Time of Occurrence 1545 Unit

1. 2, and 3 Identification and Description'of Occurrence:

While reviewing instrument buses per IE Bulletin 79-27, it was determined that f ailure of the 250 V DC battery board would cause feedwatet flow to increase to full flow and It was initially reported this postulated event could feed pump trips to be disabled.~

only occur in "A" mode. Further investigation revealed it could also occur in "B" mode.

Conditions ' Prior to Occurrence:

Unit 1 @ 81%

Unit 2 @ 96%

Unie 3 @ 100%

Action specified in the Technical Specification Surveillance Requirements met due to inoperable equipment. Describe.

NA Apparent Cause of Occurrence:

No separation of power to feedwater flow control and feed pump trip solenoids.

Analysis of Occurrence:

There was no damage to plant equipment. There was no activity release, no personnel exposure or injury and no danger to the health or safety of the public. This postulated event constitutes an unanalyzed transient resulting from full, uncontrolled feedwater flow and no feed pump trip capability.

l

Corrective Action

Upon the review and verbal concurrence of Engineering Design a temporary alteration was made to provide unit preferred power to two flow control modules so that "B" mode operation would be independent of 250 V DC.

Established temporary administrative controls to minimize and control operation in "A" mode. An investigation is underway to determine a way to permanently separate the flow control and trip solenoid power supplies.