RAIO-0518-60139, LLC - Response to NRC Request for Additional Information No. 110 (Erai No. 8932) on the NuScale Design Certification Application

From kanterella
(Redirected from ML18142C204)
Jump to navigation Jump to search
LLC - Response to NRC Request for Additional Information No. 110 (Erai No. 8932) on the NuScale Design Certification Application
ML18142C204
Person / Time
Site: NuScale
Issue date: 05/22/2018
From: Rad Z
NuScale
To:
Document Control Desk, Office of New Reactors
References
RAIO-0518-60139
Download: ML18142C204 (183)


Text

RAIO-0518-60139 NuScale Power, LLC 1100 NE Circle Blvd., Suite 200 Corvalis, Oregon 97330, Office: 541.360.0500, Fax: 541.207.3928 www.nuscalepower.com May 22, 2018 Docket No.52-048 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk One White Flint North 11555 Rockville Pike Rockville, MD 20852-2738

SUBJECT:

NuScale Power, LLC Response to NRC Request for Additional Information No.

110 (eRAI No. 8932) on the NuScale Design Certification Application

REFERENCES:

1. U.S. Nuclear Regulatory Commission, "Request for Additional Information No. 110 (eRAI No. 8932)," dated July 30, 2017 2.

NuScale Power, LLC Response to NRC "Request for Additional Information No. 110 (eRAI No.8932)," dated September 27, 2017 3.

NuScale Power, LLC Response to NRC "Request for Additional Information No. 110 (eRAI No.8932)," dated December 21, 2017 4.

NuScale Power, LLC Response to NRC "Request for Additional Information No. 110 (eRAI No.8932)," dated April 30, 2018 The purpose of this letter is to provide the NuScale Power, LLC (NuScale) response to the referenced NRC Request for Additional Information (RAI).

The Enclosure to this letter contains NuScale's response to the following RAI Question from NRC eRAI No. 8932:

03.07.02-6 The majority of the responses to RAI No. 110, eRAI No. 8932, questions were previously provided in Reference 2, Reference 3 and Reference 4. The response to question 03.07.02-5 will be provided by November 29, 2018.

This letter and the enclosed response make no new regulatory commitments and no revisions to any existing regulatory commitments.

If you have any questions on this response, please contact Marty Bryan at 541-452-7172 or at mbryan@nuscalepower.com.

Sincerely, Zackary W. Rad Director, Regulatory Affairs NuScale Power, LLC Za Z ckary W. Rad Director Regulatory Affairs

RAIO-0518-60139 NuScale Power, LLC 1100 NE Circle Blvd., Suite 200 Corvalis, Oregon 97330, Office: 541.360.0500, Fax: 541.207.3928 www.nuscalepower.com Distribution:

Samuel Lee, NRC, OWFN-8G9A

  • UHJRU\\&UDQVWRQ NRC, OWFN-8G9A

Marieliz Vera, NRC, OWFN-8G9A : NuScale Response to NRC Request for Additional Information eRAI No. 8932

RAIO-0518-60139 NuScale Power, LLC 1100 NE Circle Blvd., Suite 200 Corvalis, Oregon 97330, Office: 541.360.0500, Fax: 541.207.3928 www.nuscalepower.com :

NuScale Response to NRC Request for Additional Information eRAI No. 8932

NuScale Nonproprietary Response to Request for Additional Information Docket No.52-048 eRAI No.: 8932 Date of RAI Issue: 07/31/2017 NRC Question No.: 03.07.02-6 10 CFR 50 Appendix S requires that the safety functions of structures, systems, and components (SSCs) must be assured during and after the vibratory ground motion associated with the Safe Shutdown Earthquake (SSE) through design, testing, or qualification methods.

DSRS 3.7.2 provides guidance that effects of potential separation or loss of contact a.

between the structure and the soil during the earthquake should be considered in SSI analysis. On Page 3.7-23 of the FSAR, in the second paragraph from the bottom, the applicant states, To model the soil separation, the Young's modulus of the backfill elements down to a depth of 25 (the top four layers of backfill elements) was decreased by a factor of 100. The applicant is requested to provide a basis for 25 ft of separation depth.

Also, please clarify if the modulus reduction by a factor of 100 applies only to the backfill elements interfacing with the exterior walls or to all the backfill elements outside the exterior walls.

On Page 3.7-23 of the FSAR, in the bottom paragraph, the applicant states, Soil b.

separation has negligible effect on the response of the structure. The primary point of comparison is at the NPM. The study showed that the maximum reaction force at the base of the NPMs decreased by approximately 5 percent, and the maximum reaction force at the NPM lug restraints decreased by more than 15 percent. The applicant is requested to provide information on soil separation effect on computed transfer functions and seismic demands (forces, ISRS) at critical section locations and external walls. Please provide comparison plots for results between the intact and soil-separated cases. When soil-separation results in increased seismic demands, such increased demands should be taken into account in establishing the design basis seismic demands.

The staff notes that a soil-separation study was conducted for the RXB but not for the c.

CRB. The applicant is requested to provide a technical justification for not conducting a similar study for the CRB.

NuScale Response:

a. The soil separation depth of 1/3 the embedment depth was chosen based on the fact that

NuScale Nonproprietary the Reactor Building (RXB) and Control Building (CRB) are deeply embedded structures and are surrounded by engineered, compacted backfill.

In addition, ASCE 4-98, Section 3.3.1.9, indicates that a method to address soil separation is to assume no connectivity between the structure and lateral soil over the upper half of the embedment, or 20 feet, whichever is less. Given the model element sizes, 25 feet was a more convenient depth rather than the ASCE 4-98 stipulation of 20 feet.

Also note that the soil separation zone only applies to cohesive soils, where the lateral soil pressure at the top of the wall, down to a certain depth, is negative, creating a tension zone (separation zone) between the wall and the soil. For the NuScale reactor and control buildings, all FSAR soil cases are cohesionless, i.e., the lateral soil pressure at the top of the wall is zero, and increases with depth, meaning, physically, there will be no soil separation.

The soil modulus is reduced for the full width of the backfill soil, 25.

b. Spectral acceleration transfer functions and ISRS at critical locations are provided below.

Overall, there is very little difference between the transfer functions and ISRS of the two models.

Additionally, forces at the NuScale Power Module (NPM) lug supports, soil pressures on the external walls, maximum shears and moments in exterior walls and two pilasters, and total vertical base reaction results are presented. There are some instances where the design loads increase due to soil separation effects. However, the design margins of the RXB structural members are such that these increases do not affect the building design.

c. A soil-separation study has been conducted for the CRB. Conclusions similar to those of the RXB were reached, i.e., the spectral acceleration transfer functions and ISRS at critical locations between the two models are similar, increases in forces due to soil separation are within design margins of the building components, leaving the building design unaltered.

NuScale Nonproprietary Figure 1: RXB Node 3996, NW Corner on Top of Basemat, X-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 2: RXB Node 3996, NW Corner on Top of Basemat, Y-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 3: RXB Node 3996, NW Corner on Top of Basemat, Z-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 4: RXB Node 4741, Mid-Span of North Exterior Wall on Top of Basemat, X-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 5: RXB Node 4741, Mid-Span of North Exterior Wall on Top of Basemat, Y-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 6: RXB Node 4741, Mid-Span of North Exterior Wall on Top of Basemat, Z-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 7: RXB Node 5642, NE Corner on Top of Basemat, X-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 8: RXB Node 5642, NE Corner on Top of Basemat, Y-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 9: RXB Node 5642, NE Corner on Top of Basemat, Z-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 10: RXB Node 6013, RXM 1 West Pool Wall at Floor - SW Corner, X-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 11: RXB Node 6013, RXM 1 West Pool Wall at Floor - SW Corner, Y-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 12: RXB Node 6013, RXM 1 West Pool Wall at Floor - SW Corner, Z-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 13: RXB Node 6017, RXM 1 West Pool Wall at Floor - NW Corner, X-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 14: RXB Node 6017, RXM 1 West Pool Wall at Floor - NW Corner, Y-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 15: RXB Node 6017, RXM 1 West Pool Wall at Floor - NW Corner, Z-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 16: RXB Node 6065, RXM 1 East Pool Wall at Floor - SE Corner, X-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 17: RXB Node 6065, RXM 1 East Pool Wall at Floor - SE Corner, Y-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 18: RXB Node 6065, RXM 1 East Pool Wall at Floor - SE Corner, Z-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 19: RXB Node 6069, RXM 1 East Pool Wall at Floor - NE Corner, X-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 20: RXB Node 6069, RXM 1 East Pool Wall at Floor - NE Corner, Y-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 21: RXB Node 6069, RXM 1 East Pool Wall at Floor - NE Corner, Z-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 22: RXB Node 6273, RXM 6 West Pool Wall at Floor - SW Corner, X-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 23: RXB Node 6273, RXM 6 West Pool Wall at Floor - SW Corner, Y-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 24: RXB Node 6273, RXM 6 West Pool Wall at Floor - SW Corner, Z-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 25: RXB Node 6277, RXM 6 West Pool Wall at Floor - NW Corner, X-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 26: RXB Node 6277, RXM 6 West Pool Wall at Floor - NW Corner, Y-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 27: RXB Node 6277, RXM 6 West Pool Wall at Floor - NW Corner, Z-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 28: RXB Node 6325, RXM 6 East Pool Wall at Floor - SE Corner, X-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 29: RXB Node 6325, RXM 6 East Pool Wall at Floor - SE Corner, Y-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 30: RXB Node 6325, RXM 6 East Pool Wall at Floor - SE Corner, Z-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 31: RXB Node 6329, RXM 6 East Pool Wall at Floor - NE Corner, X-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 32: RXB Node 6329, RXM 6 East Pool Wall at Floor - NE Corner, Y-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 33: RXB Node 6329, RXM 6 East Pool Wall at Floor - NE Corner, Z-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 34: RXB Node 30357, Mid-Span of Roof Slab, X-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 35: RXB Node 30357, Mid-Span of Roof Slab, Y-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 36: RXB Node 30357, Mid-Span of Roof Slab, Z-ISRS Comparison, Cracked Model

NuScale Nonproprietary Figure 37: RXB Node 3996, NW Corner on Top of Basemat, X-TF Comparison, Cracked Model

NuScale Nonproprietary Figure 38: RXB Node 3996, NW Corner on Top of Basemat, Y-TF Comparison, Cracked Model

NuScale Nonproprietary Figure 39: RXB Node 3996, NW Corner on Top of Basemat, Z-TF Comparison, Cracked Model

NuScale Nonproprietary Figure 40: RXB Node 4741, Mid-Span of North Exterior Wall on Top of Basemat, X-TF Comparison, Cracked Model

NuScale Nonproprietary Figure 41: RXB Node 4741, Mid-Span of North Exterior Wall on Top of Basemat, Y-TF Comparison, Cracked Model

NuScale Nonproprietary Figure 42: RXB Node 4741, Mid-Span of North Exterior Wall on Top of Basemat, Z-TF Comparison, Cracked Model

NuScale Nonproprietary Figure 43: RXB Node 5642, NE Corner on Top of Basemat, X-TF Comparison, Cracked Model

NuScale Nonproprietary Figure 44: RXB Node 5642, NE Corner on Top of Basemat, Y-TF Comparison,Cracked Model.

NuScale Nonproprietary Figure 45: RXB Node 5642, NE Corner on Top of Basemat, Z-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 46: RXB Node 6013, RXM 1 West Pool Wall at Floor - SW Corner, X-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 47: RXB Node 6013, RXM 1 West Pool Wall at Floor - SW Corner, Y-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 48: RXB Node 6013, RXM 1 West Pool Wall at Floor - SW Corner, Z-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 49 RXB Node 6017, RXM 1 West Pool Wall at Floor - NW Corner, X-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 50 RXB Node 6017, RXM 1 West Pool Wall at Floor - NW Corner, Y-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 51: RXB Node 6017, RXM 1 West Pool Wall at Floor - NW Corner, Z-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 52: RXB Node 6065, RXM 1 East Pool Wall at Floor - SE Corner, X-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 53: RXB Node 6065, RXM 1 East Pool Wall at Floor - SE Corner, Y-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 54: RXB Node 6065, RXM 1 East Pool Wall at Floor - SE Corner, Z-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 55: RXB Node 6069, RXM 1 East Pool Wall at Floor - NE Corner, X-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 56: RXB Node 6069, RXM 1 East Pool Wall at Floor - NE Corner, Y-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 57: RXB Node 6069, RXM 1 East Pool Wall at Floor - NE Corner, Z-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 58: RXB Node 6273, RXM 6 West Pool Wall at Floor - SW Corner, X-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 59: RXB Node 6273, RXM 6 West Pool Wall at Floor - SW Corner, Y-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 60: RXB Node 6273, RXM 6 West Pool Wall at Floor - SW Corner, Z-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 61: RXB Node 6277, RXM 6 West Pool Wall at Floor - NW Corner, X-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 62: RXB Node 6277, RXM 6 West Pool Wall at Floor - NW Corner, Y-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 63: RXB Node 6277, RXM 6 West Pool Wall at Floor - NW Corner, Z-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 64: RXB Node 6325, RXM 6 East Pool Wall at Floor - SE Corner, X-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 65: RXB Node 6325, RXM 6 East Pool Wall at Floor - SE Corner, Y-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 66: RXB Node 6325, RXM 6 East Pool Wall at Floor - SE Corner, Z-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 67: RXB Node 6329, RXM 6 East Pool Wall at Floor - NE Corner, X-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 68: RXB Node 6329, RXM 6 East Pool Wall at Floor - NE Corner, Y-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 69: RXB Node 6329, RXM 6 East Pool Wall at Floor - NE Corner, Z-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 74: RXB Node 30357, Mid-Span of Roof Slab, X-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 71: RXB Node 30357, Mid-Span of Roof Slab, Y-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 72: RXB Node 30357, Mid-Span of Roof Slab, Z-TF Comparison, Cracked Model.

NuScale Nonproprietary Figure 73: CRB - East-West (X) ISRS, Node 32345, Northwest Corner at El 50'-0", Capitola Input.

NuScale Nonproprietary Figure 74: CRB - North-South (Y) ISRS, Node 32345, Northwest Corner at El 50'-0", Capitola Input.

NuScale Nonproprietary Figure 75: CRB - Vertical (Z) ISRS, Node 32345, Northwest Corner at El 50'-0", Capitola Input.

NuScale Nonproprietary Figure 76: CRB - East-West (X) ISRS, Node 32526, Midpoint of Basemat Slab at El. 50'-0",

Capitola Input.

Table 1. Comparison of Lug Reactions due to Capitola Input for Model A and Model B.

NuScale Nonproprietary Table 2. Comparison of Soil Pressures due to Capitola Input on RXB West Wall.

Table 3. Comparison of Soil Pressures due to Capitola Input on RXB East Wall.

NuScale Nonproprietary Table 4. Comparison of Soil Pressures due to Capitola Input on RXB South Wall.

Table 5. Comparison of Soil Pressures due to Capitola Input on RXB North Wall.

NuScale Nonproprietary Table 6. Comparison of Maximum Out-of-Plane Shears and Moments due to Capitola Input in RXB Exterior Walls.

Note: Two layers are above grade, eight layers are below grade, Rows 3 through 6 are within the separation zone.

  • See Figure 76a for row locations.

NuScale Nonproprietary Figure 76a. Shell Elements in RXB Exterior Walls for Force and Moment Comparison.

NuScale Nonproprietary Table 7. Forces in Pilaster A1 (X=0") by Model A and Model B.

NuScale Nonproprietary Table 8. Moments in Pilaster A1 (X=0") by Model A and Model B.

NuScale Nonproprietary Table 9. Comparison of Maximum Forces and Moments in Pilaster A1 (X=0") between Model A and Model B.

NuScale Nonproprietary Table 10. Forces in Pilaster A4 (X=1872") by Model A and Model B.

NuScale Nonproprietary Table 11. Moments in Pilaster A4 (X=1872") by Model A and Model B.

NuScale Nonproprietary Table 12. Comparison of Maximum Forces and Moments in Pilaster A4 (X=1872") between Model A and Model B.

NuScale Nonproprietary Table 13. D/C Ratios and Capacities of Pilaster A4 (X=1872").

NuScale Nonproprietary Table 14. RXB Locations for Relative Displacement Calculation.

NuScale Nonproprietary Table 15. Comparison of Relative Displacements of RXB Model without and with Soil Separation due to Capitola Input.

NuScale Nonproprietary Table 16. Total Vertical Seismic RXB Base Reactions due to Capitola Input.

Figure 77: CRB - North-South (Y) ISRS, Node 32526, Midpoint of Basemat Slab at El. 50'-0",

Capitola Input.

NuScale Nonproprietary Figure 78: CRB - Vertical (Z) ISRS, Node 32526, Midpoint of Basemat Slab at El. 50'-0",

Capitola Input.

NuScale Nonproprietary Figure 79: CRB - East-West (X) ISRS, Node 34320, Northwest Corner at El. 63'-3", Capitola Input.

NuScale Nonproprietary Figure 80: CRB - North-South (Y) ISRS, Node 34320, Northwest Corner at El. 63'-3", Capitola Input.

NuScale Nonproprietary Figure 81: CRB - Vertical (Z) ISRS, Node 34320, Northwest Corner at El. 63'-3", Capitola Input.

NuScale Nonproprietary Figure 82: CRB - East-West (X) ISRS, Node 34380, Slab between Grid Line CB-D and CB-E at El. 63', Capitola Input.

NuScale Nonproprietary Figure 83: CRB - North-South (Y) ISRS, Node 34380, Slab between Grid Line CB-D and CB-E at El. 63', Capitola Input.

NuScale Nonproprietary Figure 84: CRB - Vertical (Z) ISRS, Node 34380, Slab between Grid Line CB-D and CB-E at El.

63', Capitola Input.

NuScale Nonproprietary Figure 85: CRB - East-West (X) ISRS, Node 35637, Northwest Corner at El. 76-6", Capitola Input.

NuScale Nonproprietary Figure 86: CRB - North-South (Y) ISRS, Node 35637, Northwest Corner at El. 76'-6", Capitola Input.

NuScale Nonproprietary Figure 87: CRB - Vertical (Z) ISRS, Node 35637, Northwest Corner at El. 76'-6", Capitola Input.

NuScale Nonproprietary Figure 88: CRB - East-West (X) ISRS, Node 35713, Emergency Equipment Room between Grid Lines CB-D and CB-E at El. 76'-6", Capitola Input.

NuScale Nonproprietary Figure 89 CRB - North-South (Y) ISRS, Node 35713, Emergency Equipment Room between Grid Lines CB-D and CB-E at El. 76'-6, Capitola Input.

NuScale Nonproprietary Figure 90: CRB - Vertical (Z) ISRS, Node 35713, Emergency Equipment Room between Grid Lines CB-D and CB-E at El. 76'-6, Capitola Input.

NuScale Nonproprietary Figure 91: CRB - East-West (X) ISRS, Node 38144, Northwest Corner at El. 100'-0", Capitola Input.

NuScale Nonproprietary Figure 92 CRB - North-South (Y) ISRS, Node 38144, Northwest Corner at El. 100'-0", Capitola Input.

NuScale Nonproprietary Figure 93: CRB - Vertical (Z) ISRS, Node 38144, Northwest Corner at El. 100'-0", Capitola Input.

NuScale Nonproprietary Figure 94: CRB - East-West (X) ISRS, Node 38298, Slab between Grid Line CB-A and CB-B (Technical Support Center) at El. 100'-0", Capitola Input.

NuScale Nonproprietary Figure 95: CRB - North-South (Y) ISRS, Node 38298, Slab between Grid Line CB-A and CB-B (Technical Support Center) at El. 100'-0", Capitola Input.

NuScale Nonproprietary Figure 96: CRB - Vertical (Z) ISRS, Node 38298, Slab between Grid Line CB-A and CB-B (Technical Support Center) at El. 100'-0", Capitola Input.

NuScale Nonproprietary Figure 97: CRB - East-West (X) ISRS, Node 39105, Northwest Corner at El. 120'-0", Capitola Input.

NuScale Nonproprietary Figure 98: CRB - North-South (Y) ISRS, Node 39105, Northwest Corner at El. 120'-0", Capitola Input.

NuScale Nonproprietary Figure 99: CRB - Vertical (Z) ISRS, Node 39105, Northwest Corner at El. 120'-0", Capitola Input.

NuScale Nonproprietary Figure 100: CRB - East-West (X) ISRS, Node 39214, Mid-span of Slab between Grid Lines CB-B and CB-C at El. 120'-0", Capitola Input.

NuScale Nonproprietary Figure 101: CRB - North-South (Y) ISRS, Node 39214, Mid-span of Slab between Grid Lines CB-B and CB-C at El. 120'-0", Capitola Input.

NuScale Nonproprietary Figure 102 CRB - Vertical (Z) ISRS, Node 39214, Mid-span of Slab between Grid Lines CB-B and CB-C at El. 120'-0", Capitola Input.

NuScale Nonproprietary Figure 103 CRB - East-West (X) ISRS, Node 39715, Northwest Corner of Roof at El. 140'-0",

Capitola Input.

NuScale Nonproprietary Figure 104: CRB - North-South (Y) ISRS, Node 39715, Northwest Corner of Roof at El. 140'-0",

Capitola Input.

NuScale Nonproprietary Figure 105: CRB - Vertical (Z) ISRS, Node 39715, Northwest Corner of Roof at El. 140'-0",

Capitola Input.

NuScale Nonproprietary Figure 106: Cracked CRB Transfer Function Amplitudes, X Response at Node 32345, Northwest Corner at El 50'-0" for Soil Type 7.

NuScale Nonproprietary Figure 107 Cracked CRB Transfer Function Amplitudes, Y Response at Node 32345, Northwest Corner at El 50'-0" for Soil Type 7.

NuScale Nonproprietary Figure 108: Cracked CRB Transfer Function Amplitudes, Z Response at Node 32345, Northwest Corner at El 50'-0" for Soil Type 7.

NuScale Nonproprietary Figure 109: Cracked CRB Transfer Function Amplitudes, X Response at Node 32526, Midpoint of Basemat Slab at El. 50'-0" for Soil Type 7.

NuScale Nonproprietary Figure 110: Cracked CRB Transfer Function Amplitudes, Y Response at Node 32526, Midpoint of Basemat Slab at El. 50'-0" for Soil Type 7.

NuScale Nonproprietary Figure 111 Cracked CRB Transfer Function Amplitudes, Z Response at Node 32526, Midpoint of Basemat Slab at El. 50'-0" for Soil Type 7.

NuScale Nonproprietary Figure 112: Cracked CRB Transfer Function Amplitudes, X Response at Node 34320, Northwest Corner at El. 63'-3" for Soil Type 7.

NuScale Nonproprietary Figure 113: Cracked CRB Transfer Function Amplitudes, Y Response at Node 34320, Northwest Corner at El. 63'-3" for Soil Type 7.

NuScale Nonproprietary Figure 114: Cracked CRB Transfer Function Amplitudes, Z Response at Node 34320, Northwest Corner at El. 63'-3" for Soil Type 7.

NuScale Nonproprietary Figure 115: Cracked CRB Transfer Function Amplitudes, X Response at Node 34380, Slab Between Grid Line CB-D and CB-E at El. 63' for Soil Type 7.

NuScale Nonproprietary Figure 116: Cracked CRB Transfer Function Amplitudes, Y Response at Node 34380, Slab Between Grid Line CB-D and CB-E at El. 63 for Soil Type 7.

NuScale Nonproprietary Figure 117: Cracked CRB Transfer Function Amplitudes, Z Response at Node 34380, Slab Between Grid Line CB-D and CB-E at El. 63 for Soil Type 7.

NuScale Nonproprietary Figure 118: Cracked CRB Transfer Function Amplitudes, X Response at Node 35637, Northwest Corner at El. 76'-6" for Soil Type 7.

NuScale Nonproprietary Figure 119 Cracked CRB Transfer Function Amplitudes, Y Response at Node 35637, Northwest Corner at El. 76'-6" for Soil Type 7.

NuScale Nonproprietary Figure 120: Cracked CRB Transfer Function Amplitudes, Z Response at Node 35637, Northwest Corner at El. 76'-6" for Soil Type 7.

NuScale Nonproprietary Figure 121: Cracked CRB Transfer Function Amplitudes, X Response at Node 35713, Emergency Equipment Room Between Grid Lines CB-D and CB-E at El. 76'-6" for Soil Type 7.

NuScale Nonproprietary Figure 122: Cracked CRB Transfer Function Amplitudes, Y Response at Node 35713, Emergency Equipment Room Between Grid Lines CB-D and CB-E at El. 76'-6" for Soil Type 7.

NuScale Nonproprietary Figure 123: Cracked CRB Transfer Function Amplitudes, Z Response at Node 35713, Emergency Equipment Room Between Grid Lines CB-D and CB-E at El. 76'-6" for Soil Type 7.

NuScale Nonproprietary Figure 124 Cracked CRB Transfer Function Amplitudes, X Response at Node 38144, Northwest Corner at El. 100'-0" for Soil Type 7.

NuScale Nonproprietary Figure 125: Cracked CRB Transfer Function Amplitudes, Y Response at Node 38144, Northwest Corner at El. 100'-0" for Soil Type 7.

NuScale Nonproprietary Figure 126: Cracked CRB Transfer Function Amplitudes, Z Response at Node 38144, Northwest Corner at El. 100'-0" for Soil Type 7.

NuScale Nonproprietary Figure 127: Cracked CRB Transfer Function Amplitudes, X Response at Node 38298, Slab between Grid Line CB-A and CB-B (Technical Support Center) at El. 100'-0" for Soil Type 7.

NuScale Nonproprietary Figure 128: Cracked CRB Transfer Function Amplitudes, Y Response at Node 38298, Slab between Grid Line CB-A and CB-B (Technical Support Center) at El. 100'-0" for Soil Type 7.

NuScale Nonproprietary Figure 129: Cracked CRB Transfer Function Amplitudes, Z Response at Node 38298, Slab between Grid Line CB-A and CB-B (Technical Support Center) at El. 100'-0" for Soil Type 7.

NuScale Nonproprietary Figure 130: Cracked CRB Transfer Function Amplitudes, X Response at Node 39105, Northwest Corner at El. 120'-0" for Soil Type 7.

NuScale Nonproprietary Figure 131: Cracked CRB Transfer Function Amplitudes, Y Response at Node 39105, Northwest Corner at El. 120'-0" for Soil Type 7.

NuScale Nonproprietary Figure 132: Cracked CRB Transfer Function Amplitudes, Z Response at Node 39105, Northwest Corner at El. 120'-0" for Soil Type 7.

NuScale Nonproprietary Figure 133: Cracked CRB Transfer Function Amplitudes, X Response at Node 39214, Mid-span of Slab between Grid Lines CB-B and CB-C at El. 120'-0" for Soil Type 7.

NuScale Nonproprietary Figure 134: Cracked CRB Transfer Function Amplitudes, Y Response at Node 39214, Mid-span of Slab between Grid Lines CB-B and CB-C at El. 120'-0" for Soil Type 7.

NuScale Nonproprietary Figure 135: Cracked CRB Transfer Function Amplitudes, Z Response at Node 39214, Mid-span of Slab between Grid Lines CB-B and CB-C at El. 120'-0" for Soil Type 7.

NuScale Nonproprietary Figure 136: Cracked CRB Transfer Function Amplitudes, X Response at Node 39715, Northwest Corner of Roof at El. 140'-0" for Soil Type 7.

NuScale Nonproprietary Figure 137: Cracked CRB Transfer Function Amplitudes, Y Response at Node 39715, Northwest Corner of Roof at El. 140'-0" for Soil Type 7.

NuScale Nonproprietary Figure 138: Cracked CRB Transfer Function Amplitudes, Z Response at Node 39715, Northwest Corner of Roof at El. 140'-0" for Soil Type 7.

NuScale Nonproprietary Table 17. Comparison of Maximum Out-of-Plane Shear Forces and Moments in CRB Exterior Walls due to Capitola Input.

NuScale Nonproprietary Table 18. Comparison of Forces in 4B Pilaster at Y=23' in CRB East Wall due to Capitola Input.

NuScale Nonproprietary Table 19. Comparison of Moments in 4B Pilaster at Y=23' in CRB East Wall due to Capitola Input.

NuScale Nonproprietary Table 20. Comparison of Forces in 4E Pilaster at SE Corner of CRB Exterior Walls due to Capitola Input.

NuScale Nonproprietary Table 21. Comparison of Moments in 4E Pilaster at SE Corner of CRB Exterior Walls due to Capitola Input.

NuScale Nonproprietary Table 22. Selected CRB Locations for Relative Displacement Comparison.

NuScale Nonproprietary Table 23. CRB Relative Displacement due to Capitola Input at Critical Locations.

NuScale Nonproprietary Table 24. Total Vertical Seismic CRB Base Reactions.

Impact on DCA:

FSAR Tier 2, Section 3.7.2 has been revised as described in the response above and as shown in the markup provided in this response.

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-113 Draft Revision 2 the bending stiffness in half for the cracked concrete condition. In this approach, the uncracked axial stiffness is reduced by a factor of 0.7937.

Soil Separation A study was performed to investigate the effects of a gap forming between the RXB and the backfill soil during an earthquake.

The RXB was analyzed for Soil Type 7 with cracked concrete properties and 7 percent concrete material damping. Soil Type 7 was chosen because that is the case that produced the highest ISRS and forces and moments at the majority of the locations. Cracked concrete properties were chosen to be consistent with the use of 7 percent damping for the concrete material.

To model the soil separation, the Young's modulus of the backfill elements down to a depth of 25 (the top four layers of backfill elements) was decreased by a factor of 100.

RAI 03.07.02-6 Soil separation has negligible effect on the response of the structure. The primary point of comparison is at the NPM. The study showed that the maximum reaction force at the base of the NPMs decreased by approximately 5 percent, and the maximum reaction force at the NPM lug restraints decreased by more than 15 percent. In addition to examining the forces on the NPM, the in-structure response spectra were compared at the top of the basemat and the roof of the building. The ISRS virtually overlay each other, comparable in shape, and peak of response. Therefore, based upon the results of this study, modeling the structures as fully embedded is an acceptable design approach.The following responses and transfer functions calculated without soil separation are compared with those calculated with soil separation:

RAI 03.07.02-6 Forces at RXM Lug Supports The comparison indicates that the lug support reactions with soil separation are lower than those without soil separation. See Table 3.7.2-39.

RAI 03.07.02-6 ISRS and TFs at Selected Locations The comparison of the spectral acceleration transfer functions (TF) at selected locations indicates a few spurious spikes in the high frequency ranges that have no effect on the corresponding ISRS. See Figure 3.7.2-130 through Figure 3.7.2-135.

RAI 03.07.02-6 Soil Pressures on Walls The comparisons show that there are increases in the average pressures.

However, there is no increase in the maximum forces and moments in the walls.

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-114 Draft Revision 2 RAI 03.07.02-6 Maximum Shears and Moments in Exterior Walls and Two Pilasters The maximum out of plane (OOP) shear remains about the same. The maximum OOP moment decreases about 10% due to soil separation. See Table 3.7.2-40.

The total vertical base reaction remains essentially unchanged. See Table 3.7.2-42.

RAI 03.07.02-6 The ISRS, displacements, and demand forces and moments due to soil separation effects investigated above are within the design capacities.

Therefore, the effect of backfill soil separation is covered by the available design margin and has no effect on the overall RXB design.

RAI 03.07.02-6 A soil-separation study was also done for the CRB. To account for the effect of partial soil separation in the analysis model for the study, the Youngs moduli of the backfill soil solid elements down to 1/3 of the embedment, which is approximately equal to the total thickness of the top three layers of backfill soil (18.75), were factored by 1/100. Conclusions similar to those of the RXB were reached, i.e., the spectral acceleration transfer functions and ISRS at critical locations between the two models virtually overlay one another, increases in forces due to soil separation are within design margins of the building components, leaving the building design unaltered. See Figure 3.7.2-136 through Figure 3.7.2-141 and Table 3.7.2-41 and Table 3.7.2-43.

RAI 03.07.02-6 Based on the results of these studies, it is concluded that modeling the structures as fully embedded is an acceptable design approach.

3.7.2.1.2 Finite Element Models RAI 03.07.02-1 Meshing of the area elements was done automatically using SAP2000 by defining a maximum element size in each direction. The aspect ratios were also kept as low as possible (closer to square shape), and internal sharp angles were avoided.

RAI 03.07.02-1 Meshing for both the RXB and CRB models were refined further, and it is shown that further refinement does not affect the structural response. The mesh refinement was done by dividing each side of the area elements into two, breaking each element to four elements. The structural responses compared include both local and global responses of the structure. The comparison shows that effects of further mesh refinement on the structural response is negligible. In addition to the modal analysis, to compare the natural frequencies and mass participation ratios, static analysis cases due to 1g loading in the x, y or z directions were used to make

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-234 Draft Revision 2 RAI 03.07.02-6 Table 3.7.2-39: Comparison of Lug Reactions due to Capitola Input for Model A and Model B Input Model East Wing Wall N-S Lug Reaction (lbf)

Pool Wall E-W Lug Reaction (lbf)

West Wing Wall N-S Lug Reaction (lbf)

CNV Skirt E-W Reaction (lbf)

CNV Skirt N-S Reaction (lbf)

Model A (No Soil Separation) 1,681,105 2,193,854 1,872,121 723,757 809,450 Model B (with Soil Separation) 1,306,025 1,871,725 1,325,447 683,689 739,499

% Difference

-22.3%

-14.7%

-29.2%

-5.5%

-8.6%

% Difference = (Model B - Model A) / (Model A) x 100

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-235 Draft Revision 2 RAI 03.07.02-6 Table 3.7.2-40: Comparison of Maximum Out-of-Plane Shears and Moments due to Capitola Input in RXB Exterior Walls Row No.

Z-Coordinate (in)

Model A (No Soil Separation)

Model B (With Soil Separation)

Vxz Vyz Mxx+Mxy Myy+Mxy Vxz Vyz Mxx+Mxy Myy+Mxy (kip/ft)

(kip/ft)

(kip-ft/ft)

(kip-ft/ft)

(kip/ft)

(kip/ft)

(kip-ft/ft)

(kip-ft/ft) 1 1132.5 91 91 229 220 85 84 207 203 2

1057.5 95 95 413 411 89 87 373 370 3

982.6 67 68 215 225 67 68 165 169 4

907.5 54 53 332 332 65 66 373 373 5

832.5 75 75 221 221 96 97 231 240 6

760.1 96 97 202 166 86 88 170 190 7

682.5 69 66 226 209 88 89 284 286 8

607.5 53 53 168 148 63 64 184 179 9

532.5 49 49 168 158 60 61 217 234 10 457.5 45 45 131 135 56 56 155 171 Maximum 96 97 413 411 96 97 373 373 Capacities 212 1298 212 1298 Minimum OOP shear capacity: 56 kip/ft from concrete and 146 kips/ft from stirrups.

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-236 Draft Revision 2 RAI 03.07.02-6 Table 3.7.2-41: Comparison of Maximum Out-of-Plane Shear Forces and Moments in CRB Exterior Walls due to Capitola Input Row No.

Elevation (ft)

Maximum Seismic Demands in Each Row (No Soil Separation)

Maximum Seismic Demands in Each Row (With Soil Separation)

Vxz Vyz Mxx+Mxy Myy+Mxy Vxz Vyz Mxx+Mxy Myy+Mxy (kip/ft)

(kip/ft)

(kip-ft/ft)

(kip-ft/ft)

(kip/ft)

(kip/ft)

(kip-ft/ft)

(kip-ft/ft)

For the Three Rows of Wall Shell Elements above Grade 1

101.7 12 7

61 21 12 7

59 22 2

95.0 12 4

25 17 12 6

33 25 3

88.3 14 14 45 21 14 18 47 30 Maximum Seismic Demands (above Grade) 14 14 61 21 14 18 59 30 Capacities 37

(=37+0) 37

(=37+0) 378 378 37 37 378 378 For the 8 Rows of Wall Shell Elements below Grade 4

81.9 20 14 35 38 27 18 46 37 5

75.6 12 5

37 26 15 6

50 30 6

69.4 11 6

36 27 13 9

34 28 7

63.1 11 15 35 24 10 16 29 29 8

56.9 12 11 33 20 10 10 28 18 9

50.6 12 4

31 28 10 4

26 26 10 43.8 11 5

25 29 10 5

22 27 11 36.9 6

13 17 28 6

13 15 26 Maximum Seismic Demands (below Grade) 20 15 37 38 27 18 50 37 Capacities 84

(=37+47) 84

(=37+47) 378 378 84 84 378 378 Total OOP Shear Capacity = Concrete Shear Capacity + Stirrup Shear Capacity.

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-237 Draft Revision 2 RAI 03.07.02-6 Table 3.7.2-42: Total Vertical Seismic RXB Base Reactions due to Capitola Input Concrete Case Soil Type Seismic Input Maximum Total Vertical Reaction (kips)

% Diff Model A (No Separation)

Model B (Soil Separation)

Cracked 7% Damping 7

Capitola 222,932 222,537

-0.2%

% = (Model B - Model A) / (Model A) x100

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-238 Draft Revision 2 RAI 03.07.02-6 Table 3.7.2-43: Total Vertical Seismic CRB Base Reactions Concrete Case Soil Type Seismic Input Maximum Total Vertical Reaction (kips)

% Diff Model A (No Separation)

Model B (Soil Separation)

Cracked 7% Damping 7

Capitola 22,228 22,787

+3%

% = (Model B-Model A)/ (Model A)*100%

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-368 Draft Revision 2 RAI 03.07.02-6 Figure 3.7.2-130: RXB Node 3996, NW Corner on Top of Basemat, X-ISRS Comparison, Cracked Model

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-369 Draft Revision 2 RAI 03.07.02-6 Figure 3.7.2-131: RXB Node 3996, NW Corner on Top of Basemat, Y-ISRS Comparison, Cracked Model

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-370 Draft Revision 2 RAI 03.07.02-6 Figure 3.7.2-132: RXB Node 3996, NW Corner on Top of Basemat, Z-ISRS Comparison, Cracked Model

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-371 Draft Revision 2 RAI 03.07.02-6 Figure 3.7.2-133: RXB Node 3996, NW Corner on Top of Basemat, X-TF Comparison, Cracked Model 0

5 10 15 20 25 30 35 40 45 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

X-Direction TF for Node 03996 due to X-Input No Separation Soil Separation 0

2 4

6 8

10 12 14 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

X-Direction TF for Node 03996 due to Y-Input No Separation Soil Separation 0

2 4

6 8

10 12 14 16 18 20 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

X-Direction TF for Node 03996 due to Z-Input No Separation Soil Separation

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-372 Draft Revision 2 RAI 03.07.02-6 Figure 3.7.2-134: RXB Node 3996, NW Corner on Top of Basemat, Y-TF Comparison, Cracked Model 0

1 2

3 4

5 6

7 8

0 10 20 30 40 50 60 TF Amplitude Frequency (Hz)

Y-Direction TF for Node 03996 due to X-Input No Separation Soil Separation 0

5 10 15 20 25 30 35 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

Y-Direction TF for Node 03996 due to Y-Input No Separation Soil Separation 0

2 4

6 8

10 12 14 16 18 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

Y-Direction TF for Node 03996 due to Z-Input No Separation Soil Separation

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-373 Draft Revision 2 RAI 03.07.02-6 Figure 3.7.2-135: RXB Node 3996, NW Corner on Top of Basemat, Z-TF Comparison, Cracked Model 0

2 4

6 8

10 12 14 16 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

Z-Direction TF for Node 03996 due to X-Input No Separation Soil Separation 0

1 2

3 4

5 6

7 8

9 10 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

Z-Direction TF for Node 03996 due to Y-Input No Separation Soil Separation 0

10 20 30 40 50 60 70 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

Z-Direction TF for Node 03996 due to Z-Input No Separation Soil Separation

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-374 Draft Revision 2 RAI 03.07.02-6 Figure 3.7.2-136: CRB - East-West (X) ISRS, Node 34380, Slab between Grid Line CB-D and CB-E at El. 63', Capitola Input 0

0.2 0.4 0.6 0.8 1

1.2 1.4 1.6 0.1 1

10 100 Spectral Acceleration (g)

Frequency (Hz)

Node 34380 X-Direction ISRS No Soil Separation With Soil Separation 5% Damping

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-375 Draft Revision 2 RAI 03.07.02-6 Figure 3.7.2-137: CRB - North-South (Y) ISRS, Node 34380, Slab between Grid Line CB-D and CB-E at El. 63', Capitola Input 0

0.2 0.4 0.6 0.8 1

1.2 1.4 1.6 0.1 1

10 100 Spectral Acceleration (g)

Frequency (Hz)

Node 34380 Y-Direction ISRS No Soil Separation With Soil Separation 5% Damping

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-376 Draft Revision 2 RAI 03.07.02-6 Figure 3.7.2-138: CRB - Vertical (Z) ISRS, Node 34380, Slab between Grid Line CB-D and CB-E at El. 63', Capitola Input 0

1 2

3 4

5 6

7 8

0.1 1

10 100 Spectral Acceleration (g)

Frequency (Hz)

Node 34380 Z-Direction ISRS No Soil Separation With Soil Separation 5% Damping

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-377 Draft Revision 2 RAI 03.07.02-6 Figure 3.7.2-139: Cracked CRB Transfer Function Amplitudes, X Response at Node 34380, Slab Between Grid Line CB-D and CB-E at El. 63' for Soil Type 7 0

5 10 15 20 25 30 35 40 45 50 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

X-Direction TF for Node 34380 due to X-Input No Soil Separation With Soil Separation 0

0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

0 10 20 30 40 50 60 TF Amplitude Frequency (Hz)

X-Direction TF for Node 34380 due to Y-Input No Soil Separation With Soil Separation 0

10 20 30 40 50 60 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

X-Direction TF for Node 34380 due to Z-Input No Soil Separation With Soil Separation

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-378 Draft Revision 2 RAI 03.07.02-6 Figure 3.7.2-140: Cracked CRB Transfer Function Amplitudes, Y Response at Node 34380, Slab Between Grid Line CB-D and CB-E at El. 63 for Soil Type 7 0

1 2

3 4

5 6

7 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

Y-Direction TF for Node 34380 due to X-Input No Soil Separation With Soil Separation 0

10 20 30 40 50 60 70 80 90 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

Y-Direction TF for Node 34380 due to Y-Input No Soil Separation With Soil Separation 0

10 20 30 40 50 60 70 80 90 100 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

Y-Direction TF for Node 34380 due to Z-Input No Soil Separation With Soil Separation

NuScale Final Safety Analysis Report Seismic Design Tier 2 3.7-379 Draft Revision 2 RAI 03.07.02-6 Figure 3.7.2-141: Cracked CRB Transfer Function Amplitudes, Z Response at Node 34380, Slab Between Grid Line CB-D and CB-E at El. 63 for Soil Type 7 0

5 10 15 20 25 30 35 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

Z-Direction TF for Node 34380 due to X-Input No Soil Separation With Soil Separation 0

2 4

6 8

10 12 14 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

Z-Direction TF for Node 34380 due to Y-Input No Soil Separation With Soil Separation 0

10 20 30 40 50 60 70 0

10 20 30 40 50 60 TF Amplitude Frequency (Hz)

Z-Direction TF for Node 34380 due to Z-Input No Soil Separation With Soil Separation