LER 80-050/03L-0:on 800725,at 100% Power,Circuit 25 Panel 9 Had Low Amp Reading.Caused by Heat Tracing Strip Heater Failure Due to Boric Acid Buildup.Tape Repaired & Operability Verified
ML18139A674
Person / Time
Site: Surry Dominion icon.png
Issue date: 08/20/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML18139A672 List:
References
LER-80-050-03L-01, LER-80-50-3L-1, NUDOCS 8008260599
Download: ML18139A674 (2)


Text

,, CONTROL BLOCK: G) (PLEASE PRlfn DR TYPE ALL REQUIRED INFORMATION)

,J~ l VIR S AI s I pI LICENSEE CODE.

s 11 10 0 0_.__...._____

1 < : 1._!:>_.....,.___

0 I OI O OI O O O L_IC-E--"N-'S_E_N'-u-1.*-.e-"E-R_.____..__....___,;>5 01 426

,., 1 I 1 ,

  • 1 101 I I G)

LICENSE TYPE JO 57 CAT 56 iN'l B B

~:~~~ W©I o I s I o I o Io I 2 1s I oGlo I 2 I 2 I s I s I O l@I ol sI 2 ! oI s I a 10 60 61 DOCKET NUMBER 66 69 EVENT DATE 14 75 REPORT DATE BO I

EVENT DESCRIPTION AND F'ROBABLE CONSEQUENCES@)

IT! J With Unit :/Fl at 100% power, control room indicatio.n revealed Heat Tracing trouble.Further II] [ investigation *revealed that circuit 25 Panel *9 ("A" E-0ric Acid Transfer Pump Strip-Heat) m l had a low amp reading. The redundant Heat Tracing Circuit was verified I operable. This event is a degraded mode of operation as specified in T.S. 3.2.D (3), and I is reportable in accordance with T.S. 6.6.2.b(2) Because the redundant heat tracing circuit was operable, the health and safety of the public were not affected.

illa s 80 SYSTEM CAUSE CAUSE COMP. VALVE CODE CODE SUBCODE COMPONENT CODE SUBCODE SUBCODE 9

8 I Pl cl@

9 10

~@-~@IH!EIAITIE!RI@

11 12 13 16 w

19

~@

20 SEQUENTIAL OCCURRENCE REPORT REVISION r.=:-i LE R/RO LVENT YEAR . REPORT NO. CODE TYPE NO.

~ REPORT NUMBER I 8 I oJ I o Is Io I IO I3 I ~ L=J* LU 21 :n 23 :14 :16 27 28 29 30 31 32 ACTION FUTURE EFFECT SHLJTDOWN NPRD-4 PRIME COMP. COMPONENT TAKEN ACTION ON PLANT METHOD . HOURS FORM~UB. SUPPLIER MANUFACTURER

~.J@UJ@

33 34

~@

3~

~ 101010 36 37 410 W@

412 LlJ@

413 IT 44 I 1j 8 j s J@

417 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS GJ

  • W .J The Heat Tracing Strip.:.heater faileYbecause of Boric Acid Buildup: Repairs

[I] ,*were initiated on the failed tape ' and operability verified .. The pump was inspected 12 .f for existing leakage.

3JB 9 80 FACILITY ~ METHOD OF A STATUS  % POWER OTHER STATUS ~ DISCOVERY DISCOVERY DESCRIPTION \:;/

5 l_gj@ If JO !OJ@).__!_N_A_ _ _~ ~@I.____E_l_e_c_t_r_i_c_i_a_n_ _ _ _ _ _ _ _ _ _ _ _ _.....

B 9 10 12 13 44 415 ,46 80 ACTIVITY CONTENT RELEASED OF RELEASE AMOUNT OF ACTIVITY @ LOCATION OF RELEASE@

TI w@ ~'

8 9 . 10 11 NA Na 80 PERSONNEL EXPOSURES NUMBER TYPE DESCRIPTION@

7 I O I O I O l@[J@ NA B 9 11 1:1 1~3----------------------------------------8.....JO PERSONNEL INJURIES NUMBER DESCRIPTION@

H B

Io,0 9

, o r@

  • 11 NA

~1::1:;-------------------------------=--------------B-lO LOSS OF OR DAMAGE TO FACILITY~

TYPE DESCRIPTION ~

9 L:J@ . NA 8 9 10 PUBLICITY C\ so ISSUEDeDESCRIPTION ~ NRC USE ONLY e I .. f 44 *. ..

O 8

9 LIU ~10:-----------------.:.:.:.:..._ NA ________________ ~ f I I I I I I I I I I I I; ll00B260 S"q't sa 69 tio ;

NAME OF PREPARFR J. L. Wilson .. - - PHON.F* (804) 357-3184 ~ j

A~.:\Cf!.}fENT SL"?2,Y POh'ER DOC::.z:ET NO:

1 STATION ,UNIT 1 50-280 e e REPORT NO: 80-050-03L-0 Ev t.NT DATE: 7-25-80 TITLE OF EVENT: HEAT TRACING SYSTEM =.;._=.DRE

1. Description of Event:

With Unit 4fal at 100% power, control room indicat::.o= revealed Re.at Tracing Trouble.. Further investigation re.ve.ale.d that ci:ccc:.:.t 25 Panel 9 ("A Boric Acid Transfer Pump Strip Heat) had a low amp reao1.:r.;. The redundant H.e.at Tracing Circuit was verified operable. This eve~t :.s a degraded mode of operation as specified in T.S.3.2.D(3), and is repc::-table. in accord~n~e with T.S.6.6.2.b(2) .

2. Probable Consequences & Status of Redundant Systeas:

The redundant Heat Tracing Circuit was verified ope::-ab le, which meant he.at was being supplied to the Boric Acid Piping. There::ore, the health and safety of the public were not affected.

3. Cause:

The Heat Tracing Tape failed due to Boric Acid Boil::up on the St.rip Heater.

4. Immediate Corrective Action:

The immediate corrective action was to replace ltbc defective .Heat Tracing Strip Heater, and verify the operability .. o{ the af:f~cted Heat Tracing Circuit.

5. Subsequent Corrective Action: .

The pump was inspected for seal leakage and no eiis~ing evidence of leakage was found, therefore additional actions were not d~ed necessary.

6. Action Taken to Prevent Recurrence:

No additional actions were deemed necessary

7. Generic Implications:

A* task force has been established to study the tot~l spectrum of the heat tracing system in an attempt to discern present pro:lems and reconnnend solutions which will eliminate sporadic failures e:nerienced.