Application for Amend to License DPR-20,providing Clarifications & Editorial Corrections to Radiological Effluent Tech Specs Approved in Amend 85.Submittal Fulfills Commitment Made in LER 86-037.Fee Paid
ML18052A896
Person / Time
Site: Palisades Entergy icon.png
Issue date: 03/10/1987
From: Berry K
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML18052A897 List:
References
NUDOCS 8703160275
Download: ML18052A896 (5)


Text

consumers Power Kenneth W Ber_ry

  • pawERINli Director ll/llCHlliAN'S PllOlillESS Nuclear Licensing General Offices: 1945 West Parnall Road, Jackson, Ml 49201 * (517) 788-1636 March 10, 1987 Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT -

TECHNICAL SPECIFICATIONS CHANGE REQUEST - RETS*CORRECTIONS Attached are proposed changes to the Palisades Technical Specifications. The changes provide clarifications and editorial corrections to the Radiological Effluent Technical Specifications (RETS) approved in Amendment No 85. In*

Licensee Event Report 86-037, Consumers Power identified two discrepancies in RETS concerning the Hi Range Noble Gas Monitor annunciation and continuous sampling of the service water effluent. In the LER, Consumers Power committed to submit clarifications and.corrections to the Technical Specifica-tions. This submittal fulfills that commitment.

Pursuant t.o 10 CFR 170.12(e), an application fee of $150.00 is attached.

Kenneth W Berry Director, Nuclear Licensing CC Administrator, Region III, NRG NRG Resident Inspector - Palisades Attachment 8703160275 870310 .'

PDR . . ADOCK 05000255 *"

1

.. c _P -~* . -- -~-~ ' .. :.. '"' '-'- ~- f'P~. - . 1-f-----'

OC0287-0062A-NL02

CONSUMERS POWER COMPANY Docket 50-255 Request for Change to the Technical Specifications License DPR-20 For the reasons hereinafter set forth, it is requested that the Technical Specifications contained in the Provisional Operating License DPR-20, Docket 50-255, issued to Consumers Power Company on October 16, 1972, for the Palisades Plant be changed as described in Section I below:

I. CHANGES A. In Table 3.24-1, change Item 4 to read as follows:

  • "4. CONTINUOUS COMPOSITE SAMPLERS (Alarm/Trip Setpoint are not

.applicable)

a. Turbine Building Sumps Effluent Line (1) 30
b. Service Water System Effluent (1) 30" B. In Table 4.2.1, delete the sampling test for gas radioactivity by the air ejector gas monitor as listed in Item 7. Also, delete the corresponding footnote 5 from this table.

C. In Table 4.2.1, delete Items 8, 9 and 10. Also, delete the asso-ciated footnote 4 from this table.

D. In Table 4.24-1, add Item 5 to read:

CHANNEL CHANNEL SOURCE CHANNEL FUNCTIONAL "Instrument CHECK CHECK CALIBRATION TEST

5. SERVICE WATER SYSTEM D(4) NA NA .NA" EFFLUENT COMPOSITE SAMPLER E. In Table 4.24-2, change Table Notation (2)a. to read:

"a. Instrument indicates measured levels above the alarm set point (not applicable foi; Item 3.d, Hi Range Noble Gas)."

II. DISCUSSION A. This change adds a continuous composite sampler for the service water system effluent to the list of effluent monitoring instruments provided in Table 3.24-1. This addition is necessary for consis-tency with Table 4.24-3 which implies that a composite sampler is available. Also, the addition of the sampler to Table 3.24-1 TSP0287-0003-NL02

2 provides an appropriate action to be taken in the event of an inoperable service water system effluent composite sampler. The action statement provides for a grab sample to be taken on a daily basis. As discussed in LER 86-037, a continuous composite service water sampler does not now exist. Consumers Power Company has committed to install a sampler and the modification is expected to be completed by July 31, 1987. Until that time, the alternate grab sample in the action statement will provide a method to meet the specification.

B. This change eliminates a redundant requirement from Table 4.2.1 and removes corresponding footnote 5. The equivalent sample requirement is provided by Item 2 of Table 3.24-2. This change is editorial and was overlooked during the implementation of the RETS.

c. The sample requirements provided by Items 8, 9 and 10 on Table 4.2.1 are equivalent to those provided in Table 4.24-3 for liquid waste batch releases, Table 4.24-5 for a radioactive gas release and Table 4.24-5 for stack gas particulate samples. Therefore, Items 8, 9 and 10 and the corresponding footnote 4 should be deleted. This change is editorial and was overlooked during the implementation of the RETS.

D. The service water system effluent composite sampler has been added to Table 4.24-1 to require periodic checks of the-equipment's operating status.

E. An exception has been added for the Hi Range Noble Gas Monitor for control room annunciation if the instrument indicates measured levels above the alarm setpoint. This instrument does not have this capability, nor was _the instrument expected to perform this function.

The alarms provided by the normal range monitor are used to signal the need for emergency actions. Effluents are closely monitored once an alarm is received, so any further.alarms from higher rates of release are unnecessary. Therefore, the alarm function is not; provided for the Hi Range Noble Gas Monitor and an exception should be provided for this item.

Analysis of No Significant Hazards Consideration These changes are administrative. Sampling of the service *water discharge is being clarified, editorial corrections from Technical Specification Amendment 85 are being made and the requirement for quarterly testing of the Hi Range Noble Gas Monitor high alarm annunciator is being removed as no high alarm annunciator exists.

A continuous service water system composite sampler does not presently exist at Palisades. Plans are for installation by July 31, 1987.

Historically, daily grab samples of the service water effluent have TSP0287-0003-NL02

3 pro.vided a method for determining if radioactive material is entering the *service water system. This grab sample will continue to be the sampling method until the continuous sampler is installed. In processing the RETS, an apparent omission was made in not clarifying the method of service water effluent sampling.

The Hi Range Noble Gas Monitor (RIA 2327) was incorrectly noted on Technical Specification Table 4. 24-2 as. requiring the high alarm control room annunciator to be tested. There is no high alarm* annunciator from the monitor. This will not affect the consequences of an accident as the Hi Range Noble Gas Monito*r is part of an integrated system with the Normal Range Noble Gas Monitor (RIA 2326). The alert or high alarms on the Normal Range Monitor (RIA 2326) will initiate Emergency Plan classi-fications and actions to continuously monitor effluents. Therefore, another alarm has no value.

The service water sampling via a grab sample, corrections to the func-tional test, alarm surveillance of the Hi Range Noble Ga.s Monitor, and other changes are essentially adminstrative and are requested to clear up discrepancies in the specifications that resulted from implementation of the Radiological Effluent Technical Specifications Amendment. The changes do not increase the probability or consequences* of an accident

_nor create the possibility of an accident or malfunction of a different type than previously evaluated.* Furthermore, no margin of safety as defined ~n the basis for any technical specification is affected by these administrative changes.

  • III. Conclusion The Palisades Plant Review Committee has reviewed this Technical Specification Change Request and has. determined that this change does not involve an unreviewed safety question and* therefore involves no
  • significant hazards consideration. This change has also b~en reviewed under the cognizance of the Nuclear Safety Board. A copy of this Technical Specification Change Request has been sent to the State of Michigan official designated to receive*such 'Amendments to the Operating License.

CONSUMERS POWER COMPANY By olds, Executive Vice Energy Supply

.*' ~L.x...4...a:o:::J~::....;.,..=..i\;.....:..~~=..L..J:;_.:;i:µL-=:..:......:=

H~leh ~:t Demp.~k *, No tar

.. <.

  • J.~S'.~~otj(,County,

' . . ,.,,, . Michigan My. commf"s'sion expires October 12, 1987 TSP0287-0003-NL02

. ~ .: _:

. ATTACHMENT Consumers Power Company Palisades Plant Docket 50-255 PROPOSED TECHNICAL SPECIFICATIONS PAGE CHANGES March 10, 1987 5 Page.s TSP0287-0003-NL02