GO2-89-059, Application for Amend to License NPF-21,reducing Age Factor of Div 1 250-volt Dc Battery Sys to 20%,per 10CFR50.59,in Tech Spec 3/4.8.2, DC Sources

From kanterella
(Redirected from ML17285A394)
Jump to navigation Jump to search

Application for Amend to License NPF-21,reducing Age Factor of Div 1 250-volt Dc Battery Sys to 20%,per 10CFR50.59,in Tech Spec 3/4.8.2, DC Sources
ML17285A394
Person / Time
Site: Columbia 
Issue date: 04/12/1989
From: Sorensen G
WASHINGTON PUBLIC POWER SUPPLY SYSTEM
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML17285A395 List:
References
GO2-89-059, GO2-89-59, TAC-67620, NUDOCS 8904240044
Download: ML17285A394 (5)


Text

gc Cp~RA,TED 3)lSTR1BUT10N DEMONSTRA,TlON SYSTEM REGULATOR'NFORMATION DISTRIBUTION ~EM (RIDE)

~I ACCESSION NBR:8904240044 DOC.DATE: 89/04/12 NOTARIZED: YES DOCKET I FACIL:50-397 WPPSS Nuclear Project, Unit 2, Washington Public Powe 05000397 AUTH.NAME AUTHOR AFFILIATION SORENSEN,G.C.

Washington Public Power Supply System RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)

SUBJECT:

Application for amend to License NPF-2l,reflecting results of rev to dc sys battery calculations.

DISTRIBUTION CODE:

AOOZD COPIES RECEIVED:LTR t

ENCL J SIZE:

~+/

TITLE: OR Submittal: General Distribution NOTES:

RECIPIENT ID CODE/NAME PD5 LA SAMWORTHFR COPIES LTTR ENCL 1

1 5

5 RECIPIENT ID CODE/NAME PD5 PD COPIES LTTR ENCL 1

1 INTERNAL: ACRS NRR/DEST/CEB 8H NRR/DEST/ICSB NRR/DEST/RSB 8E NUDOCS-ABSTRACT OGC/HDS2 RES/DSIR/EIB EXTERNAL: LPDR NSIC 6

6 1

1 1

1 1

1 1

1 1

0 1

1 1

1 1

1 NRR/DEST/ADS 7E NRR/DEST/ESB 8D NRR/DEST/MTB 9H NRR/DOEA/TSB 11 OC/LFMB RE Ol NRC PDR 1

1 1

1 1

1 1

1 1

0 1

1 1

1 NVZE 'lo ALL RIDS" RECIPZERIS'IEASE HELP US TO REDUCE McEBE!

CGNI'ACT 'IHE DOCUMENT CXKHKL DESK RDCN Pl-37 (EXT. 20079)

%0 EIJMZNLTE MOR MME ESCA DZSXVUBUTIGN LISTS H3R DOCtlMEMIS VXJ DGNFT NEED<

TOTAL NUMBER OF COPIES REQUIRED:

LTTR 28 ENCL 26

v't

t. p

~

h WASHINGTON PUBLIC POWER SUPPLY SYSTEM P.O. Box 968

~ 3000 George Washington Way

~ Richland, Washington 99352 April 12, 1989 G02-89-059 Docket No. 50-397 U. S. Nuclear Regulatory Commission Attn:

Document Control Desk Mail Station Pl-137

'jlashington, D.C.

20555 Gentlemen:

Subject:

Refernece:

NUCLEAR PLANT NO. 2 OPERATING LICENSE NPF-21 REQUEST FOR AMENDMENT TO TECHNICAL SPECIFICATION 3/4.8.2, DC SOURCES (ADDITIONAL CHANGES)

Letter,,

G02-88-065, GC Sorensen (SS) to NRC, same subject, dated March 18, 1988 In the reference

letter, changes were requested to the load profiles for, the Division 1, 2

and 3-125 Volt DC Power

Systems, and the Division 1-250 Volt DC Power System.

These changes were requested to reflect the results of the revisions to the DC System battery calculations.

Although already considered in the new load profiles submitted with the referenced request for, amendment, an additional change is necessary to accurately reflect the assumptions used in the referenced calculations for, the Division 1-250 Volt DC System.

In most cases a battery aging factor of 25% was used in sizing the batteries.

This results in a battery being replaced when its actual measured capacity drops to 80K of its rated capacity.

However,,

a 20$ aging factor was utilized for sizing the Division 1-250 Volt DC Battery System.

The aging factor was reduced to 20K to keep the calculation results within the bounds

'of the'nstalled equipment.

This will require the battery system to be replaced when its measured capacity drops to 83.4X of its rated capacity.

This and an asso-ciated change is reflected in the attached marked up Tech.

Spec.

page 3/4 8-13.

The Supply System has reviewed the revision to the aging factor for the Divi-sion 1-250 Volt DC batteries

per, 10CFR50.59 and concluded that it does not involve an unreviewed safety question.

The Supply System has also evaluated this request

per, 10CFR50.92 and provides the following in support of a finding for no significant hazards consideration.

This change does not:

8904240044 890412 Q

'DR ADOCK 05000397i P

swum po I

Page Two REQUEST FOR AMENDMENT TO TECHNICAL SPECIFICATION 3/4.8.2 DC SOURCES (ADDITIONAL CHANGE) 1)

Involve a significant increase in the probability or, consequences of an accident previously evaluated because changing the aging factor does not represent a change in the methodology for sizing the batteries or a change in the'attery design requirements.

It also does not extend the duty life since it is to be replaced on an earlier schedule, consistent with the other batteries.

2)

Create the possibility of a

new or different kind of accident from any previously evaluated because the batteries themselves are not being changed nor are any changes being made to the way they were being utilized or asked to perform.

The only change is in the input assumptions for. the calculation, and that change is being accounted for by an additional conservatism with respect to replacement period.

3)

Involve a significant reduction in a margin of safety because the capacity requirement for the Division 1-250 Volt DC battery has been raised from 80 to 83.4 percent of the manufacturer,'s rating to offset a reduction in the sizing calculations "aging factor," from 25 to 20 percent.

Additionally, the indication of degradation has been changed from 90 to 93.4 percent of manufacturer's rating.

The only effect of this change is to potentially require earlier, replacement of the battery which will be identified by the

'ech.

Spec.

surveillance results.

As discussed

above, the Supply System considers that this change does not involve a significant hazards consideration, nor is there a

potential for significant change in the types or significant increase in the amount of any effluents that may be released

offsite, nor.

does it involve a significant increase in individual or cummulative occupational radiation exposure.

Accor-

dingly, the proposed change meets the eligibility criteria for categorical exclusion set forth in 10CFR 51.22(c)(9) and therefore, per 10CFR 51.22(b),

an environmental assessment of the change is not required.

This Technical Specification change has been reviewed and approved by the llNP-2 Plant Operations Committee (POC) and the Supply System Corporate Nuclear Safety Review Board (CNSRB).

In accordance with 10CFR 50.91, the State of Washington has been provided a copy of this letter.

Very truly yours, G.

C. Sorensen, Manager Regulatory Programs HLA/bk Attachments cc:

C Eschels - EFSEC JB Martin NRC RV NS Reynolds - BCP&R RB Samworth NRC DL llilliams - BPA/399 NRC Site Inspector - 901A

STATE OF WASHINGTON

)

)

" COUNTY OF BENTON

Subject:

DC Sources I, G. C.

SORENSEN, being duly sworn, subscribe to and say that I am the Manager, Regulatory Progr ams, for the WASHINGTON PUBLIC POWER SUPPLY
SYSTEM, the applicant herein; that I have full authority to execute this oath; that I have reviewed the foregoing; and that to the best of my knowledge, information and belief the statements made in it ar e true.

DATE IZ 6, g c 1989 G.

C.

SO NS N, Manager Regulat ry Programs On this day personally appeared before,me G.

C.

SORENSEN to me known to be the individual who executed the foregoing instrument and acknowledged that he signed the same as his free act and deed for the uses and purposes herein mentioned.

GIVEN under my hand and seal this ~/0/

day of I

,1989.

s

  • tijt LgI Notary Pu lac sn and or t State of Washington Residing at uA Pip Cu~~a>z " ey ~'7 lzplyi

~7

'a Y'P,Qi h 'Q, a

p).t(>>,

pq ~ q>> p