L-2016-132, Revised Technical Specifications for License Amendment Request for Adoption of Technical Specifications Task Force (TSTF) Traveler TSTF-422, Revision 2, Change in Technical Specifications End States, (CE NPSD-1186), Using

From kanterella
(Redirected from ML16201A236)
Jump to navigation Jump to search

Revised Technical Specifications for License Amendment Request for Adoption of Technical Specifications Task Force (TSTF) Traveler TSTF-422, Revision 2, Change in Technical Specifications End States, (CE NPSD-1186), Using
ML16201A236
Person / Time
Site: Saint Lucie  
Issue date: 07/15/2016
From: Costanzo C
Florida Power & Light Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
CE NPSD-1186, L-2016-132
Download: ML16201A236 (6)


Text

JUL 1 5 2016 U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001

Subject:

References:

St. Lucie Units 1 and 2 Docket Nos. 50-335 and 50-389 Revised Technical Specifications for License Amendment Request for Adoption of Technical Specifications Task Force (TSTF)

Traveler TSTF-422, Revision 2, "Change in Technical Specifications End States, (CE NPSD-1186)," Using the Consolidated Line Item Improvement Process L-2016-132 10 CFR 50.90

1.

FPL Letter L-2015-182 dated August 31, 2015, "License Amendment Request for Adoption of Technical Specifications Task Force (TSTF) Traveler TSTF-422, Revision 2, 'Change in Technical Specifications End States, (CE NPSD-1186),' Using the Consolidated Line Item Improvement Process," ADAMS Accession No. ML15084A141 In Reference 1 Florida Power & Light (FPL) submitted a Technical Specification (TS) license amendment request (LAR) that would utilize risk-informed requirements to modify selected Required Action End States.

Based on teleconferences between the Staff and FPL, FPL is submitting some revised TS markups and their corresponding word-processed TSs. The attachment contains the justification for the proposed changes. The revised TSs replace those provided in Reference 1.

The no significant hazards consideration determination within Reference 1 bounds the scope of these changes. If you should have any questions, please contact Mr. Ken Frehafer at (772) 467-7748.

I declare under penalty of perjury that the foregoing is true and correct.

Executed on JUL 1 5 2016 Sincerely, a~-C,.~

Christopher R. Costanzo Site Vice President St. Lucie Plant CRC/KWF Attachment cc:

NRC Region II Administrator St. Lucie Plant NRC Senior Resident Inspector

L-2016-132 Attachment Page 1of5 Some of the original FPL-proposed TS changes were not consistent with the changes authorized by TSTF-422. Specifically:

1.

One of the TSTF-422 assumptions was that the control room emergency ventilation system filter subsystem consists of two independent trains. Although the Unit 1 Control Room Emergency Ventilation System has only one filter train, FPL applied the HOT SHUTDOWN end state in the original TS markups for TS 3.7.7.1.c. Because applying the HOT SHUTDOWN end state for loss of the Unit l's CREVS single filter train could be considered non-conservative, FPL is withdrawing the originally proposed HOT

  • SHUTDOWN end state proposal from TS 3/4.7.7.1 Action c.
2. FPL originally proposed a HOT SHUTDOWN end state for a Unit 2 de-energized AC instrument bus in TS 3/4.8.3 action b(l), even though this proposal had no counterpart in TSTF-422. Therefore, FPL is withdrawing the originally proposed HOT SHUTDOWN end state from TS 3/4.8.3 Action b(l).

FPL is providing replacement proposed markups and word processed TSs that address the above inconsistencies.

PLANT SYSTEMS 3/4.7.7 CONTROL ROOM EMERGENCY VENTILATION SYSTEM LIMITING CONDITION FOR OPERATION 3.7.7.1 The control room emergency ventilation system shall be OPERABLE with:

a.

Two booster fans,

b.

Two isolation valves in each outside air intake duct,

c.

Two isolation valves in the toilet area air exhaust duct,

d.

One filter train,

e.

At least two air conditioning units, and

f.

Two isolation valves in the kitchen area exhaust duct.

NOTE L-2016-132 Attachment Page 2of5 The control room envelope boundary may be opened intermittently under administrative control.

APPLICABILITY: MODES 1, 2, 3, 4, 5 and 6 or during movement of irradiated fuel assemblies.

ACTION:

MODES 1, 2, 3 and 4:

HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. LCO 3.0.4.a is not applicable when entering HOT SHUTDOWN

a.

With one booster fan inoperable, restore the inoperable fan to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in GGLD SHUTDO\\a.IN withiA the fellowin§ 30 hoUFS.

b.

With ne isolation valve per air duct inoperable, operation may continue prov* ed the other isolation valve in the same duct is maintained closed;

c.
d.

oth rwise, be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in GGbQ With the ao requirements not met, be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

With only one air conditionin

  • 1 OPERABLE, restore at least two air conditioning units to OPERABLE s within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SMUTDOlA/l>l withiA the folleWiA§ ¢0 heUFS.

ST. LUCIE - UNIT 1 3/4 7-20 Amendment No. 400, W, 206 227

ELECTRICAL POWER SYSTEMS ACTION:

a.
b.

HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. LCO 3.0.4.a is not applicable when entering HOT SHUTDOWN

c.

With one of the required trains of AC. Emergency busses not fully energized, re-energize the train within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

With one AC. Instrument Bus either not energized from its associated inverter, or with the inverter not connected to its associated D.C. Bus: (1) re-energize the AC. Instrument Bus within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> and (2) re-energize the

,---_,......__,,nstrument Bus from its associated inverter connected to its associated..

  • hin 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and COLD SHUTDO'.!'JN within the following 38 het:JFS.

With one D.C. Bus not energized from its associated Battery Bank, re-energize the D.C. Bus from its associated Battery Bank within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.8.3.1 The specified busses shall be determined energized in the required manner in accordance with the Surveillance Frequency Control Program by verifying correct breaker alignment and indicated voltage on the busses.

ST. LUCIE-UNIT 2 3148-15 Amendment No. +75 L-2016-132 Attachment Page 3of5

L-2016-132 Attachment Page 4of5 PLANT SYSTEMS 3/4.7.7 CONTROL ROOM EMERGENCY VENTILATION SYSTEM LIMITING CONDITION FOR OPERATION 3.7.7.1 The control room emergency ventilation system shall be OPERABLE with:

a.

Two booster fans,

b.

Two isolation valves in each outside air intake duct,

c.

Two isolation valves in the toilet area air exhaust duct,

d.

One filter train,

e.

At least two air conditioning units, and

f.

Two isolation valves in the kitchen area exhaust duct.

NOTE control room envelope boundary may be.opened intermittently under administrative control.

APPLICABILITY: MODES 1, 2, 3, 4, 5 and 6 or during movement of irradiated fuel assemblies.

ACTION:

MODES 1, 2, 3 and 4:

a.

With one booster fan inoperable, restore the inoperable fan to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. LCO 3.0.4.a is not applicable when entering HOT SHUTDOWN.

b.

With one isolation valve per air duct inoperable, operation may continue provided the other isolation valve in the same duct is maintained closed; otherwise, be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. LCO 3.0.4.a is not applicable when entering HOT SHUTDOWN.

c.

With the filter train inoperable for reasons other than an inoperable Control Room Envelope boundary:

1.

Immediately initiate action to implement mitigating actions, and

2.

Within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, verify LCO 3.4.8, "Specific Activity," is met, and

3.

Within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> restore the filter train to OPERABLE status.

With the above requirements not met, be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

d.

With only one air conditioning unit OPERABLE, restore at least two air conditioning units to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. LCO 3.0.4.a is not applicable when entering HOT SHUTDOWN.

ST. LUCIE - UNIT 1 3/4 7-20 Amendment No..wfl, -W+, :lOO, 227-

L-2016-132 Attachment Page 5of5 ELECTRICAL POWER SYSTEMS ACTION:

a.

With one of the required trains of A.C. Emergency busses not fully energized, re-energize the train within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With one A.C. Instrument Bus either not energized from its associated inverter, or with the inverter not connected to its associated D.C. Bus: (1) re-energize the A.C. Instrument Bus within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> and (2) re-energize the A.C. Instrument Bus from its associated inverter connected to its associated D.C. Bus within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

LCO 3.0.4.a is not applicable when entering HOT SHUTDOWN.

c.

With one D.C. Bus not energized from its associated Battery Bank, re-energize the D.C. Bus from its associated Battery Bank within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.8.3.1 The specified busses shall be determined energized in the required manner in accordance with the Surveillance Frequency Control Program by verifying correct breaker alignment and indicated voltage on the busses.

ST. LUCIE - UNIT 2 3/4 8-15 Amendment No.~