CNRO-2015-00017, Entergy Submits Relief Request RR EN-15-1 - Proposed Alternative to Use ASME Code Case N-789-1, Alternative Requirements for Pad Reinforcement of Class 2 and 3 Moderate Energy Carbon Steel Piping for Raw Waster Service, Section XI, D
| ML15159A200 | |
| Person / Time | |
|---|---|
| Site: | Palisades, Indian Point, Grand Gulf, Pilgrim, Arkansas Nuclear, River Bend, Waterford, FitzPatrick |
| Issue date: | 06/05/2015 |
| From: | Ford B Entergy Nuclear Operations, Entergy Operations |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| CNRO-2015-00017 | |
| Download: ML15159A200 (17) | |
Text
-~~* Entergy CNR0-2015-00017 June 5, 2015 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Entergy Operations, Inc.
Entergy Nuclear Operations, Inc.
1340 Echelon Parkway Jackson MS 39213 Bryan 5. Ford Senior Manager, Fleet Regulatory Assurance
SUBJECT:
Relief Request Number RR EN-15-1 -Proposed Alternative to Use ASME Code Case N-789-1, "Alternative Requirements for Pad Reinforcement of Class 2 and 3 Moderate Energy Carbon Steel Piping for Raw Water Service,Section XI, Division 1" Arkansas Nuclear One, Units 1 & 2 Docket Nos. 50-313 & 50-368 License Nos. DPR-51 & NPF-6 Grand Gulf Nuclear Station, Unit 1 Docket No. 50-416 License No. NPF-29 James A Fitzpatrick Nuclear Power Plant Docket No. 50-333 License No. DPR-59 Indian Point Energy Center, Units 2 & 3 Docket Nos. 50-247 & 50-286 License Nos. DPR-26 & DPR-64
Dear Sir or Madam:
Palisades Nuclear Plant Docket 50-255 License No. DPR-20 Pilgrim Nuclear Power Station Docket No. 50-293 License No. DPR-35 River Bend Station, Unit 1 Docket No. 50-458 License No. NPF-47 Waterford 3 Steam Electric Station Docket No. 50-382 License No. NPF-38 Pursuant to 10 CFR 50.55a(z)(2), Entergy Operations, Inc. and Entergy Nuclear Operations, Inc. (hereafter referred to collectively as "Entergy") hereby request NRC approval of a relief request to the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code,Section XI, "Rules for lnservice Inspection of Nuclear Power Plant Components," on the basis that the current code requirements result in hardship and/or unusual difficulty. The proposed relief request is provided in the attachment to this letter.
Specifically, this request is for application of American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code, Code Case N-789-1, for Class 2 and Class 3 moderate energy raw water piping system repairs resulting from degradation mechanisms such as erosion, corrosion, cavitation and pitting at the Entergy nuclear plants listed above.
The information provided in the attachment demonstrates that the proposed request provides an acceptable level of quality and safety and that compliance with the specified requirements
CNR0-2015-00017 Page 2 of 3 of ASME Section XI would result in a hardship and/or unusual difficulty without a compensating increase in the level of quality and safety.
This relief request is proposed for the 10-year lnservice Inspection (lSI) intervals for the facilities as identified in Section 2 of the attached relief request.
Since this relief request could be needed at any time to address an emergent condition, Entergy requests NRC approval as soon as possible or by June 5, 2016.
This letter contains no new commitments.
If you have any questions, please contact Mr. Bryan Ford, Senior Manager, Fleet Regulatory Assurance at (601) 368-5516.
Sincerely, BSF/ghd/aye
Attachment:
Relief Request Number RR EN-15-1 cc: J. Forbes (ECH)
T. Mitchell (ECH)
J. Ventosa (WPO)
D. Jacobs (ECH)
M. Perito (ECH)
J. Kowalewski (ECH)
M. Woodby (ECH)
J. Browning (ANO)
K. Mulligan (GGNS)
E. Olson (RBS)
M. Chisum (WF3)
B. Sullivan (JAF)
L. Coyle (IPEC)
J. Dent (PIL)
T. Vitale (PAL)
D. Mannai (WPO)
G. H. Davant (ECH)
All above w/o attachments NRC Region I Administrator NRC Region Ill Administrator NRC Region IV Administrator NRC Project Manager (ANO)
NRC Project Manager (GGNS)
NRC Project Manager (RBS)
NRC Project Manager (WF3)
NRC Project Manager (IPEC)
CNR0-2015-00017 Page 3 of 3 NRC Project Manager (JAF)
NRC Project Manager (PIL)
NRC Project Manager (PAL)
NRC Senior Resident Inspector (ANO)
NRC Senior Resident Inspector (GGNS)
NRC Senior Resident Inspector (RBS)
NRC Senior Resident Inspector (WF3)
NRC Senior Resident Inspector (IPEC)
NRC Senior Resident Inspector (JAF)
NRC Senior Resident Inspector (PIL)
NRC Senior Resident Inspector (PAL)
ATTACHMENT CNR0-2015-00017 RELIEF REQUEST RR EN-15-1
Attachment to CNR0-2015-00017 Page 1 of 6 RELIEF REQUEST RR EN-15-1
- 1. ASME Code Component(s) Affected This relief request applies to all ASME Class 2 and 3 moderate energy carbon steel raw water piping systems. Raw water is defined as water such as a river, lake, or well or brackish/salt water used in plant equipment, area coolers, and heat exchangers. In many plants, it is referred to as "Service Water." Moderate energy is defined as less than or equal to 200°F (93°C) and less than or equal to 275 psig (1.9 MPa) maximum operating conditions.
2. Applicable Code Edition and Addenda
The following table identifies the ASME Section XI Code of Record for performing lnservice Inspection (lSI) activities at each Entergy site.
Plant lSI ASME Section XI Interval Interval Interval Edition/Addenda Start End Arkansas Nuclear One 4
2001 Edition I 2003 Addenda 5131108 5130117 Unit 1 (AN0-1)
Arkansas Nuclear One 4
2001 Edition I 2003 Addenda 3126110 3125120 Unit 2 (AN0-2)
Grand Gulf Nuclear Station 3
2001 Edition I 2003 Addenda 5131108 611117 (GGNS)
Indian Point Energy Center 4
2001 Edition I 2003 Addenda 311107 5131116 Unit 2 (IPEC-2) (Note 1) 5 2007 Edition I 2008 Addenda 611116 5131126 Indian Point Energy Center 4
2001 Edition I 2003 Addenda 7121109 7120119 Unit 3 (IPEC-3)
James A. FitzPatrick 4
2001 Edition I 2003 Addenda 311107 12/31116 (JAF) (Note 1) 5 2007 Edition I 2008 Addenda 111117 12131126 Palisades (PLP) (Note 21 5
2007 Edition I 2008 Addenda 12113115 12112125 Pilgrim Nuclear Power Station (PNPS) (Note z) 5 2007 Edition I 2008 Addenda 711115 6130/25 River Bend Station (RBS) 3 2001 Edition I 2003 Addenda 5131108 11130117 Waterford Unit 3 (WF3) 3 2001 Edition I 2003 Addenda 5131108 6130117 Notes:
- 1) The 4th lSI intervals for IPEC-2 and JAF end soon after the requested relief request approval date.
Therefore, Entergy requests the NRC to approve this alternative for the 4th and 51h IPEC-2 and JAF intervals.
- 2) The 41h lSI intervals for PLP and PNPS end prior to the requested relief request approval date.
Therefore, Entergy requests the NRC to approve this alternative for the 51h PLP and PNPS lSI intervals.
Attachment to CNR0-2015-00017 Page 2 of6 The table above identifies the ASME Section XI Code of Record for performing lSI activities at each Entergy nuclear plant. However, it should be noted that ASME Section XI repair/replacement activities at all Entergy nuclear plants are performed in accordance with a standardized Repair/Replacement Program that is based on a common Edition/Addenda of ASME Section XI which, at present, is the 2001 Edition/ 2003 Addenda. As Entergy nuclear sites update their lSI Programs in accordance with 10 CFR 50.55a(g)(4)(ii), Entergy will also update the Code bases of the Repair/ Replacement Program to a later Edition/Addenda of ASME Section XI. The planned update to the Repair/Replacement Program is scheduled for 2017 and no later than December 31, 2017. The Repair/Replacement Program update must comply with 10 CFR 50.55a and, where appropriate, in accordance with 10 CFR 50.55a(g)(4)(iv) and 10 CFR 50.55a(z). (Ref: PNPS PRR-26, dated November 26, 2014; ML1434280001)
3. Applicable Code Requirements
The Editions/Addenda of ASME Section XI for which the alternative is requested are specified in Section 2, above. Subsection IWA-4000 of these Editions and Addenda provide requirements for welding, brazing, metal removal, and installation of repair/replacement activities.
4. Reason for Request
IWA-4000 requires replacement or internal weld repair of wall-thinning conditions resulting from degradation to be in accordance with the Owner's Requirements and the original or later Construction Code. However, the repair and replacement provisions of IWA-4000 cannot always be utilized when degradation or leakage is identified during plant operations. Other approved alternative repair or evaluation methods are not always practicable because of wall thinness and/or moisture issues. The proposed alternative will permit installation of a technically sound temporary repair to provide adequate time for evaluation, design, material procurement, planning, and scheduling of an appropriate permanent repair or replacement of the defective piping, considering the impact on system availability, maintenance rule applicability, and availability of replacement materials. Without this repair option, compliance with the specified requirements of IWA-4000 would result in hardship and/or unusual difficulty
- including higher risks associated with plant shut-downs and extended technical specification actions -without a compensating increase in the level of quality and safety.
5. Proposed Alternative and Basis for Use
Pursuant to 1 OCFR50.55a(z)(2), Entergy proposes to implement the requirements of Code Case N-789-1 as a temporary repair of degradation in Class 2 and 3 moderate energy raw water piping systems resulting from mechanisms such as erosion, corrosion, cavitation, or pitting, but excluding conditions involving flow accelerated corrosion (FAG), corrosion-assisted cracking, or any other form of cracking. These types of defects are typically identified by small leaks in the piping system or by pre-emptive, non-code required examinations performed to monitor the degradation mechanisms. This repair technique involves welding a metal reinforcing pad - pressure pad or structural pad - to the exterior of the piping system to reinforce the degraded area and restore pressure integrity. This repair technique will be used when it is determined that the temporary repair method is suitable for the particular defect and type of degradation present. Code Case N-789-1 is included in the enclosure of this request.
Attachment to CNR0-2015-00017 Page 3 of6 The Code Case requires that the cause of the degradation be determined, and that the extent and rate of degradation in the piping be evaluated to ensure there are no other unacceptable locations within the surrounding area that could affect the integrity of the repaired piping. The area of evaluation is dependent on the degradation mechanism present.
Entergy implementation of Code Case N-789-1 will include the following restrictions and clarifications:
- 1) Regarding paragraph 3.1 (a)( 1) of the Code Case, Entergy designs of pressure pads will be based on a corrosion rate of 2 times the actual measured corrosion rate in that location. If a repair must be performed without sufficient time to determine the actual rate of corrosion at the repair location, then the pressure pad design will be based on a corrosion rate that is 4 times the estimated maximum (worst-case) corrosion rate for the same degradation mechanism in that system or a similar system at the same plant site.
- 2) Paragraph 3.2(i) of the Code Case includes an incorrect reference to NC-2650 for the flexibility analysis associated with Class 2 designs. The correct reference should be NC-3650. Entergy will comply with NC-3650.
- 3) When gasket material is used in accordance with paragraph 3.2(1) of the Code Case (water-backed applications), Entergy will also require removal of any residual moisture by heating prior to welding.
- 4) Regarding paragraph 8(b) of the Code Case, Entergy will perform monitoring on a monthly basis during the first quarter as required by Code Case N-789-1. The subsequent monitoring frequency shall be based on corrosion rates calculated using reductions in thicknesses since the previous monitoring inspection, but at least quarterly.
- 5) Sections 1, 3, 5, and 6 of the Code Case specify that materials, design, installation, and examination of reinforcement pads shall be performed in accordance with the Construction Code or ASME Section Ill applicable to each Entergy site. As allowed by IWA-4200 and IWA-4411, later Editions and Addenda of the Construction Code or ASME Section Ill may be used provided any required reconciliations are performed. However, only Editions/Addenda of ASME Section Ill that have been approved by the NRC in 10 CFR 50.55a will be used.
- 6) Entergy performs repair/replacement activities in accordance with a fleet-wide, standardized Repair/Replacement Program based on the 2001 Edition/2003 Addenda of ASME Section XI. Therefore, this Edition/Addenda of AS ME Section XI will be used by all plants whenever the Code Case refers to IWA-4000 until the code bases of the Repair/Replacement Program is updated as noted in Section 2 of this request.
Code Case N-789-1 includes requirements for incorporating actual or estimated corrosion rates in the design of all reinforcing pads. For pressure pads that cannot be directly measured for the on-going effects of corrosion, rates of twice the measured actual or four times the worst-case corrosion for the system must be incorporated in the design. Structural pads are required to be directly measured for the on-going effects of corrosion, so these conservative multipliers do not apply to the design of reinforcing pads. In addition, compensatory measures are included to account for any uncertainties in the corrosion rates used, thus providing reasonable assurance that structural integrity and leakage integrity will
Attachment to CNR0-2015-00017 Page 4 of 6 be maintained. These measures include limiting the design life of reinforcing pads to a maximum of one refueling cycle, and requiring on-going monitoring as follows:
For structural pads, including their attachment welds and the surrounding area, a baseline thickness examination will be performed followed by monthly thickness monitoring for the first three months. The subsequent examination frequency will be based on the results of corrosion rates calculated as a result of this monitoring, but at a minimum of quarterly.
Areas containing pressure pads will be visually observed at least once per month to monitor for evidence of leakage. If the areas containing pressure pads are not accessible for direct observation, then monitoring will be accomplished by visual assessment of surrounding areas, or ground surface areas above pressure pads on buried piping, or by monitoring of leakage collection systems, if available.
Regardless of when during a fuel cycle a repair is performed, each repair will be considered to have a maximum service life until no later than the end of the next refueling outage, when a permanent repair or replacement must be performed. The Code Case specifies additional requirements for design of reinforcing pads, installation, examination, pressure testing, and inservice monitoring.
Code Case N-789-1 was approved by ASME Codes and Standards on November 13, 2013; however, it has not been incorporated into Regulatory Guide 1.147, "lnservice Inspection Code Case Acceptability, ASME Section XI, Division 1,"and, thus, is not available for application at nuclear power plants without specific NRC approval.
6. Duration of Proposed Alternative
Use of the proposed alternative is requested for the duration of the lSI intervals identified in Section 2. In the case of IPEC-2 and JAF, approval of this relief request is anticipated within 1 year prior to the end of the 41h lSI intervals; therefore, this request also includes the 51h lSI intervals for those units.
Code Case N-789-1, paragraph 1 (e) requires that reinforcing pads, including those installed during refueling outages, shall not remain in service beyond the end of the next refueling outage. Therefore, regardless of when the pressure or structural pad is installed, Entergy will comply with this requirement with the following clarifications:
Reinforcing pads installed before the end of the 1 0-year lSI interval will be removed during the next refueling outage after installation, even if that refueling outage occurs after the end of the 1 0-year lSI interval. In this case, absent detrimental defects or degradation, duration of the proposed alternative would be until the first refueling outage after the end date of the lSI interval for the applicable Entergy plant.
Some piping systems are required to be functional and cannot be repaired during refueling outages. The repair of this piping can only be performed when the plant is operating. For this unique case, the reinforcing pad will have to be removed prior to, but no later than, the refueling outage unless specific regulatory relief is obtained.
Attachment to CNR0-2015-00017 Page 5 of 6
7. Precedents
A similar alternative was approved for application of Code Case N-789 for ten (10) Exelon Nuclear Power Plants (a total of 17 Units) on May 10, 2012 (Reference 2). Differences between that Code Case and Code Case N-789-1 referenced in this relief request are as follows:
Design: Paragraph 3.1(a) was revised to clarify the difference between pressure pads and structural pads.
Design Requirements: Figure 2 was clarified to agree with 3.1(a)(1) to require the design corrosion rate for pressure pads to be twice the actual measured corrosion rate at the location, or if not known then four times the maximum corrosion rate for the system. (See clarification 1 Section 5, above.)
Water-Backed Applications: A new paragraph 4(b) was inserted: "When welding a reinforcing pad to a leaking area, precautions shall be taken to prevent welding on wet surfaces, such as installation of a gasket or sealant beneath the pad."
Pressure Testing: A new sentence was added to 7: "Reinforcing pads attached to piping that has not been breached shall be equipped with pressure taps for performance of pressure testing."
lnservice Monitoring:
A new sentence was added to paragraph 8(b ): "Provisions shall be made for access to structural pads on buried piping during operation in order to accomplish these examinations."
A new paragraph 8(c) was added requiring pressure pads to be monitored once per month for leakage.
Paragraph 8(e) of the revised Code Case now specifically requires that all reinforcing pads, regardless of when they are installed, shall have a maximum service life until the end of the next refueling outage.
The NRC also approved an alternative for application of Code Case N-789-1 for two (2) Excel Energy Nuclear Power Plants on May 4, 2015 (Reference 3). A similar repair relief request (RR-3-43) was approved for Indian Point Nuclear Generating Unit No. 3 on February 22, 2008 (Reference 1 ).
- 8. References
- 1) Entergy Indian Point Nuclear Generating Unit No. 3, Safety Evaluation for Temporary Non-Code Repair (Relief Request RR-3-43), February 22, 2008-See Adams Accession No. ML080280073
- 2) Exelon Generation Company, LLC, Safety Evaluation for Use of Code Case N-789, May 10, 2012-See Adams Accession No. ML12121A637
- 3) Excel Energy Safety Evaluation for Use of Code Case N-789-1, May 4, 2015-See Adams Accession No. ML15079A003
Attachment to CNR0-2015-00017 Page 6 of 6
- 9. Enclosure
- 1. ASME Code Case N-789-1, "Alternative Requirements for Pad Reinforcement of Class 2 and 3 Moderate-Energy Carbon Steel Piping for Raw Water Service,Section XI, Div. 1"
RELIEF REQUEST RR EN-15-1 ENCLOSURE ASME Code Case N-789-1, Alternative Requirements for Pad Reinforcement of Class 2 and 3 Moderate-Energy Carbon Steel Piping for Raw Water Service,Section XI. Division 1
CASE CASES OF ASME BOILER AND PRESSURE VESSEL CODE N-789-1 Approval Date: November 13, 2013 Code Cases will remain available for use until annulled by the applicable Standards Committee.
Case N-789-1 Alternative Requirements for Pad Reinforcement of Class 2 and 3 Moderate-Energy Carbon Steel Piping for Raw Water Service Section XI, Division 1 Inquiry: As an alternative to replacement or internal weld repair in accordance with IWA-4400, what require-ments may be applied for wall reinforcement of Class 2 and 3 moderate-energy carbon steel raw water 1 piping systems that have experienced internal wall thinning from localized erosion, corrosion, and cavitation or pitting?
Reply: It is the opinion of the Committee that, in lieu of meeting IWA-4400, areas of Class 2 and 3 moderate-energy [i.e., less than or equal to 200°F (93°C) and less than or equal to 275 psig (1.9 MPa) maximum op-erating conditions] carbon steel raw water piping experi-encing internal wall thinning from localized erosion, corrosion, and cavitation or pitting may have the wall re-inforced by applying reinforcing pads to the outside sur-face of the piping in accordance with the following requirements. Excluded from these provisions are condi-tions involving flow-accelerated corrosion (FAC),
corrosion-assisted cracking, or any other form of cracking.
1 GENERAL REQUIREMENTS (a) Application of the reinforcing pad shall be per-formed in accordance with a Repair/Replacement Plan sa-tisfying the requirements of IWA-4150.
(b) The design, materials, and installation shall meet the requirements of the Construction Code and IWA-4000, ex-cept as stated in this Case.
(c) If the minimum required thickness of reinforcing pad necessary to satisfy the requirements of 3 is greater than the nominal thickness for the size and schedule of the piping, this Case shall not be used.
(d) Additional reinforcement or repair is not permitted on top of an existing reinforcing pad.
(e) Reinforcing pads, including those installed during a refueling outage, shall not remain in service beyond the end of the next refueling outage.
(/] This Case may only be applied to piping not required to be ultrasonically examined for inservice inspection.
2 INITIAL EVALUATION (a) The material beneath the surface to which the rein-forcing pad is to be applied and the adjacent area shall be ultrasonically measured to establish the existing wall thickness and the extent and configuration of degradation to be corrected by the reinforcing pad.
(b) The cause and rate of degradation shall be deter-mined. If the cause is determined to be flow-accelerated corrosion (FAC), corrosion-assisted cracking, or any other form of cracking, this Case shall not apply. The extent and rate of degradation in the piping shall be evaluated to en-sure that there are no other unacceptable locations within the surrounding area that could affect the integrity of the repaired piping. The dimensions of the surrounding area to be evaluated shall be determined by the Owner, consid-ering the type of degradation present.
(c) The effects of the repair on the piping and any re-maining degradation shall be evaluated in accordance with IWA-4311.
3 DESIGN 3.1 TYPES OF REINFORCING PADS (a) Reinforcing pads may be used for leak prevention only (pressure pad), or for leak prevention plus structural reinforcement of thinned areas including areas that do, or are expected to, penetrate the piping wall (structural pad).
(1) Pressure pads are designed to retain pressure, and may be used only where the piping is predicted to re-tain full structural integrity until the next refueling outage assuming a corrosion rate of either 2 times the actual mea-sured corrosion rate in that location, or 4 times the esti-mated maximum corrosion rate for the system.
1 Raw water is defined as water such as from a river, lake, or well or brackish/salt water; used in plant equipment, area coolers, and heat exchangers. In many plants it is referred to as "Service Water:*
The Committee's function is to establish rules of safety, relating only to pressure integrity, governing the construction of boilers, pressure vessels, transport tanks and nuclear components, and lnservice inspection for pressure integrity of nuclear components and transport tanks, and to interpret these rules when questions arise regarding their intent This Code does not address other safety issues relating to the construction of boilers, pressure vessels. transport tanks and nuclear components, and the inservice inspection of nuclear components and transport tanks. The user of the Code should refer to other pertinent codes, standards, laws, regulations or other relevant documents.
Copyright ASME lntemalional (BPVC)
Prcvi:ted by IHS under Hcense with ASME X No reproduction or networil.ing permitted without license from IHS 1 (N-789-1) llc:ansee=Amaren Energy Services/9970656101, User:O'Sullivan. J m Not for Resale, 06/0512014 11.45 22 MOT NC-SUPP. 4
CASE (continued)
N-789-1 CASES OF ASME BOILER AND PRESSURE VESSEL CODE (2) Structural pads are designed for pressure plus structural reinforcement and may be used where the pip-ing is predicted not to retain full structural integrity until the next refueling outage.
3.2 GENERAL DESIGN REQUIREMENTS -
PRESSURE AND STRUCTURAL PADS (a) The design of reinforcing pads shall be in accor-dance with the applicable requirements of the Construc-tion Code or Section lli (NC-3100, ND-3100 and NC-3600, ND-3600 including Appendix II).
(b) The reinforcing pad shall be sized to encompass the unacceptable area with the attachment welds located on adjacent base material of sufficient thickness to accommo-date the design stresses.
(c) The plate for the reinforcing pad shall be rolled or otherwise formed to fit the contour of the piping to achieve proper weld fit-up.
(d) The thickness of the reinforcing pad shall be suffi-cient to maintain required thickness until the next refuel-ing outage.
(e) The tensile strengths of the plate and weld filler me-tal for the reinforcing pad shall be at least that specified for the base metal to which it is applied.
(f) The predicted maximum degradation of the rein-fo~ced piping until the next refueling outage shall be in-chided in the design. The predicted degradation of the piping shall be based on in-situ inspection of, and estab-lished data for, similar base metals in similar environ-ments. If the reinforcing pad is predicted to become exposed to the raw water, the predicted degradation of the reinforcing pad shall be based upon established data for base metals or weld metals with similar chemical com-position to that used for the reinforcing pad.
(g) Material for reinforcing pads shall be ferritic, with welds of compatible weld filler metal.
(h) The following factors shall be included, as applic-able, in the design and application of the pad:
(1) shrinkage effects, if any, on the piping (2) stress concentrations caused by installation of the reinforcing pad or resulting from existing and predicted piping internal surface configuration (3) effects of welding on any interior coating (4) added weight of the pad with respect to any de-sign analyses that could be affected (i) If flexibility analysis was required by the original Construction Code, the effect of the reinforcing pad shall be reconciled with the original analysis. For rectangular-shaped reinforcing pads on piping designed to NC-2650, ND-3650 and aligned parallel or perpendicular to the axis of the piping, unless a lower stress intensification factor
[SIF or (i)] is established, an SIF (i) of 2.1 shall be applied for reinforcing pads on straight pipe and adjacent welds.
Also, a stress multiplier of 1.7 shall be applied to the SIF (i) for standard elbows, and an SIF (i) of 2.1 shall be 2 Design thickness as prescribed by the Construction Code.
applied for tees and branch connections when the toe of the attachment weld is not less than 2.5~Rtnom from any branch reinforcement in Figure 1.
(j) Corners of reinforcing pad plates shall be rounded with radii not less than the reinforcing pad thickness, and the toes of attachment welds at the corners shall have 1 in. (25 mm) minimum radius.
(k) The distance between toes of attachment welds and other attachments or branch reinforcement (Figure 1 and
- 2) shall not be less than the following equation:
d = Z.S~Rtnom where d = minimum distance between toes of fillet welds of adjacent fillet welded attachments R = the outer radius of the piping tnam = nominal thickness of the piping (I) When permitted by the design, suitable gasket mate-rial may be applied inside the pad to prevent moisture during welding (see Figures 1 and 2).
3.3 SPECIFIC DESIGN REQUIREMENTS-PRESSURE PADS Pressure pads shall meet the requirements of 3.2, Figure 2, and the following:
(a) Fillet-welded pressure pads shall be designed to withstand the membrane strain of the piping in accor-dance with the requirements of the Code specified in 3.2(a) such that the following criteria are satisfied:
(1) The allowable membrane stress is not exceeded in the piping or the pad.
(2) The strain in the pad does not result in fillet weld stresses exceeding allowable stresses for such welds.
(b) Design as a reinforced opening in accordance with the Construction Code shall satisfy (a).
(c) As an alternative to (a), pressure pads may be de-signed as structural pads in accordance with 3.4 or as pre-qualified designs in accordance with 3.5.
3.4 SPECIFIC DESIGN REQUIREMENTS -
STRUCTURAL PADS Structural pads shall meet the requirements of 3.2, Figure 1, and the following:
(a) Unless otherwise established by analysis in accor-dance with the requirements of 3.2(a), structural pads shall be attached by partial penetration attachment welds (see Figure 1) that extend for a distance of at least s in each direction beyond the area predicted, by the next re-fueling outage, to infringe upon the required thickness. 2 s ~ 0.75~Rtnom NC-SUPP. 4 2 (N-789-1)
Copyright ASME International (BPVC)
Provited by IHS under license with ASME X No reproduction or networking permitted without license from IHS Licensee=Ameren Energy Services/9970656101, User=O'SuHivan, Jim Not ror Resale, 06/0512014 11:45 22 MDT
CASE (continued)
CASES OF ASME BOILER AND PRESSURE VESSEL CODE N-789-1 Figure 1 Structural Pad d
D l
Appropriate gasket material C =predicted circumferential growth of degradation L = predicted axial growth where t
Minimum dimensions of plate _}
bevel optional
=predicted maximum dimensions of degradation below minimum required thickness R = outer radius of the component s = 1 in. (25 mm) minimum tnom = nominal wall thickness of the component (b) The thickness of the partial penetration attachment welds shall equal the thickness of the pad and the edges of the welds shall be tapered to the piping surface at a max*
imum angle ("a" in Figure 1) of 45 deg.
(c) Final configuration of the structural pad including attachment welds shall permit the examinations and eva-luations required herein, including any required preser-vice or inservice examinations of encompassed or adjacent welds.
Required thickness treq
~-- d -----+-1 Limit of branch reinforcement d 2: 2.5 ~ Rtnom (d) Except for the tapered edges, the structural pad plate and attachment welds shall have a uniform thickness.
3.5 PREQUALIFIED DESIGN Application of structural pads on straight pipe, standard elbows, and associated welds shall be exempt from the re-quirements of 3.2(a), provided all of the following condi-tions are satisfied.
(a) All other requirements of 3.1, 3.2, and 3.4 are satisfied.
(b) The axial length of structural pad plus width of par-tial penetration attachment welds shall not exceed the greater of 6 in. (150 mm) or the outside diameter of the piping.
3 (N-789-1)
NC-SUPP. 4 Copyright ASME lntematlonal (BPVC)
Prcvi1ed by lHS undtl' license with ASME X No reproduclion or networ1dng penniltad without license from IHS L lcensee~Amaran Energy Services/9970656101, User-O'Sullivan. Jim Not for Resale, 06JC512014 11 45 22 MDT
CASE (continued)
N-789-1 CASES OF ASME BOILER AND PRESSURE VESSEL CODE Figure 2 Pressure Pad D
1 Predicted growth of degradation below minimum wall thickness based on 2 x or 4 x estimated corrosion rate.
Appropriate gasket material if required
._.--- L--~~1 tnom treq Required t
/1 t
thickness
?
~ ~
+
~L, C Minimum dimensions of plate __I
= predicted extent of degradation below minimum wall thickness based on 2 x the measured corrosion rate at the location or 4 x the maximum estimated corrosion rate for the system.
(c) The finished structural pad shall be circular, oval, or rectangular in shape.
(1) The maximum dimension compensated by a circu-lar structural pad shall not exceed two-thirds of the nom-inal outside diameter of the piping.
(2) Rectangular structural pads shall be aligned par-allel with or perpendicular to the axis of the piping.
(3) For oval structural pads, the end radii shall not be less than 0.7S~Rtnom* and the axis of the structural pad shall be aligned parallel with or perpendicular to the axis of the piping.
4 WATER-BACKED APPLICATIONS (a) Attachment welds on water backed piping shall be applied using the SMAW process with low-hydrogen electrodes.
(b) When welding a reinforcing pad to a leaking area, precautions shall be taken to prevent welding on wet sur-faces, such as installation of a gasket or sealant beneath the pad.
(c) For piping materials other than P-No. 1, Group 1, the surface examination required in 6 shall be performed no sooner than 48 hr after completion of welding.
5 INSTALLATION (a) The base material in the area to be welded shall be cleaned to bare metal.
(b) Weld metal shall be deposited using a groove -
welding procedure qualified in accordance with Section IX and the Construction Code.
(c) Provisions for venting during the final closure weld, or for pressurizing for leak-testing, shall be included, if necessary.
NC-SUPP. 4 4 (N-789-1)
Copyright ASME lntamational (BPVC)
Provited by IHS under license with ASME X No reproduction or networ1(ing permitted without license from IHS Licensee=Ameren Energy Services/9970656101, Usar=O'Sullivan, Jim Not for Resale, 06/0512014 11 45 22 MOT
CASE (continued)
CASES OF ASME BOILER AND PRESSURE VESSEL CODE N-789-1 (d) The surface of the attachment weld shall be pre-pared, if necessary, by machining or grinding to permit performance of surface and volumetric examinations re-quired by 6. For ultrasonic examination, a surface finish of 250 RMS or better is required.
6 EXAMINATION (a) The completed attachment weld shall be examined using the liquid penetrant or magnetic particle method and shall satisfy the surface examination acceptance cri-teria for welds of the Construction Code or Section Ill (NC-5300, ND-5300).
(b) Except for the tapered edges, partial penetration at-tachment welds, including the piping base metal upon which they are applied, shall be ultrasonically measured to verify acceptable wall thickness.
(c) Partial penetration attachment welds shall be volu-metrically examined when full penetration girth welds in the piping are required by the Construction Code to be vo-lumetrically examined. Where configuration does not per-mit meaningful volumetric examination, the first layer, each Yz in. (13 mm) thickness of weld deposit, and the fi-nal surface shall be examined in accordance with (a) in lieu of volumetric examination.
(d) If volumetric examination is required, the full vo-lume of the attachment weld, excluding the tapered edges, but including the volume of base metal required for the in-tended life of the reinforcing pad, shall be examined in ac-cordance with the Construction Code or Section III, using either the ultrasonic or radiographic method, and shall, to the depth at the surface of the piping. satisfy the accep-tance criteria for weldments of the Construction Code or Section Ill (NC-5320, ND-5320 or NC-5330, ND-5330).
Any volume of the piping beneath the reinforcing pad that is credited in the design shall satisfy the volumetric accep-tance criteria of Section III (NC-5320, ND-5320 or NC-5330, ND-5330), as applicable.
7 PRESSURE TESTING In lieu of IWA-4540, a system leakage test of the repair I replacement activity shall be performed in accordance with IWA-5000 prior to, or as part of, returning to service.
Reinforcing pads attached to piping that has not been breached shall be equipped with pressure taps for perfor-mance of pressure testing.
8 INSERVICE MONITORING (a) Upon completion of the repair, inspections shall be performed for structural pads, using ultrasonic or direct thickness measurement, to record the thickness of the plate, the thickness at the attachment welds, including the underlying base metal, and to the extent examinable in a 3 in. (75 mm) wide band, surrounding the repair, as a baseline for subsequent monitoring of the repair.
(b) The Owner shall prepare a plan for additional thick-ness monitoring for structural pads using ultrasonic or di-rect thickness measurement to verify that minimum design thicknesses, as required by the Construction Code or Section III, are maintained until the next refueling out-age. The monitoring shall be monthly for the first quarter and the subsequent frequency shall be based on the re-sults of the monitoring activities, but at least quarterly.
Provisions shall be made for access to structural pads on buried piping during operation to accomplish these examinations.
(c) Areas containing pressure pads shall be monitored monthly for evidence of leakage. If the areas containing pressure pads are not accessible for direct observation, monitoring shall be accomplished by observation of sur-rounding areas or ground surface areas above pressure pads on buried piping; or leakage collection systems, if available, shall be monitored.
(d) If the results of the monitoring program identify leakage or indicate that the structural margins required by 3 will not be maintained until the next refueling outage, additional repair/replacement activities not prohibited by l(d) shall be performed prior to encroaching upon the de-sign limits.
(e) All reinforcing pads, regardless of when installed, shall be removed no later than the end of the next refuel-ing outage.
5 (N-789-1)
NC-SUPP. 4 Copyright ASME lntematlonal (BPVC)
Provi:ted by IHS under license with ASME X No reproduction or networ1dng pennitted without license from IHS licensee=Ameren Energy Services/9970656101, Usar=O'Sullivan, Jim Not for Resale, 06/0512014 11:45 22 MDT
Cog~ht ASME IM&malional {BPVC.
Prov'dodbyiHSundowlicetwowilnASME X No reproduction or NIWOI'fcing penni't&d wi1Mut kensa from IHS INTENTIONALLY LEFT BLANK Llcensee-Amtren EfWlrgy Servioa5J9970658101, U&er=O'Sulllvan. Jim Not for Ret81t, 11&1051201 4 11 45 22 MOT