L-PI-12-107, 2012 180-Day Steam Generator Tube Inspection Report

From kanterella
(Redirected from ML12326A857)
Jump to navigation Jump to search
2012 180-Day Steam Generator Tube Inspection Report
ML12326A857
Person / Time
Site: Prairie Island Xcel Energy icon.png
Issue date: 11/16/2012
From: Jeffery Lynch
Xcel Energy, Northern States Power Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-PI-12-107
Download: ML12326A857 (170)


Text

XcelEnergy-NOV 16 2012 L-PI-12-107 TS 5.6.7 U S Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Prairie Island Nuclear Generating Plant Unit 2 Docket 50-306 Renewed License No. DPR-60 2012 Unit 2 180-Day Steam Generator Tube Inspection Report In accordance with Prairie Island Nuclear Generating Plant, Unit 2 Technical Specification 5.6.7 "Steam Generator Tube Inspection Report", Northern States Power Company, a Minnesota corporation, doing business as Xcel Energy (hereafter "NSPM"),

submits the enclosed report of steam generator tube inspections performed during the 2012 refueling and maintenance outage on Unit 2.

Summary of Commitments This letter contains no new commitments and no revisions to existing commitments.

James E. Lynch Site Vice President, Prairie Island Nuclear Generating Plant Northern States Power Company - Minnesota Enclosure cc:

Administrator, Region III, USNRC Project Manager, Prairie Island, USNRC Resident Inspector, Prairie Island, USNRC A6 0 1717 Wakonade Drive East

  • Welch, Minnesota 55089-9642 Telephone: 651.388.1121

ENCLOSURE I Prairie Island Nuclear Generating Plant - Unit 2 2012 Steam Generator Tube Inspection Report In accordance with Prairie Island Nuclear Generating Plant (PINGP), Unit 2 Technical Specification 5.6.7, Northern States Power Company, a Minnesota corporation, doing business as Xcel Energy (hereafter "NSPM"), submits this report of steam generator tube inspections performed during the 2012 refueling and maintenance outage on Unit 2 (2R27).

PINGP Unit 2 has two Westinghouse Model 51 Steam Generators (SGs) with approximately 51,500 square feet of heat transfer. Each SG has 3,388 mill annealed Alloy 600 u-tubes manufactured by Blairsville and Huntington which have an outside diameter of 0.875 inch and a nominal wall thickness of 0.050 inch. The tubes are configured in a square pitch of 1.281 inches with 46 rows and 94 columns. The tube u-bends vary in radius from 2.1875 inches for a row 1 tube to 59.844 inches for a row 46 tube. The tube straight length is 378.230 inches for all tubes in the bundle. Rows 1 and 2 were subject to in situ stress relieving using Westinghouse thermal treatment process during the May 2000 refueling outage. The tubes were roll expanded at each tube end for approximately 2.75 inches leaving an open tubesheet crevice.

The tubesheet is A-508 Class 2 material 21.0 inches thick with Weld Deposit Inconnel cladding 0.2 inches thick and a tube extension beyond the clad of 0.2 inches for an overall thickness of 21.4 inches. The tubes are supported by seven A-285 Grade C drilled tube support plates (TSPs) 0.750 inches thick and two anti-vibration bars (AVBs).

The original AVB design consisted of two square (0.387" x 0.387") Inconnel 600 bars with an alphatized chrome-plated surface, with a 440 bar nested in a 1360 bar that intersected the tubes between one and four times. The replacement AVB design consisted of two hinged rectangular (0.750" x variable) stainless steel bars set at 250 and 600 from the centerline axis of the tube bundle that intersected the tubes between two and four times.

PINGP Unit 2 has a Technical Specification (T.S.5.5.8.f.2.b) approved repair method of hardroll expanding non-sleeved portions of tubes in the (hot leg) tubesheet in order to apply the F* and EF* criteria. Figure 1 provides an illustration of the original equipment manufacturers (OEM) tube-to-tubesheet configuration and each of the three possible reroll elevations (AR1, AR2 and ARE) utilized at PINGP.

Page 1 of 169

Figure 1 Reroll Configuration Page 2 of 169

Italicized text represents technical specification excerpts. Each excerpt is followed by the appropriate information intended to address each specific requirement and also includes additional details based on benchmarking recent submittals and Staff requests for additional information of peer Licensees. A legend of codes and field names is included at the end of the report.

5.6.7 Steam Generator Tube Inspection Report

a. A report shall be submitted within 180 days after initial entry into MODE 4 following completion of an inspection performed in accordance with the Specification 5.5.8, Steam Generator (SG) Program.

Initial entry into MODE 4 occurred on May 21, 2012, dictating submittal of this report on or before November 18, 2012.

The report shall include:

1. The scope of inspections performed on each SG, Table 1 and the text that follows, provides the scope of inspections performed during 2R27.

Page 3 of 169

TABLE I SCOPE TECHNIQUE S/G 21 S/G 22 Full Length0 Bobbin 100% (3067) 100% (3098)

Rows 1 through 4 U-Bends MRPC 100% (342) 100% (349)

Rows 5 through 8 U-Bends MRPC 33% (113) 33% (124)

Hot Leg Tubesheets MRPC 100% (3067) 100% (3098)

Hot Leg Roll Plugs MRPC 25% (78) 25% (68)

SupplementalO and PID MRPC 100% (550) 100% (454)

Baseline new Re-Rolls Bobbin/MRPC 100% (347) 100% (221)

Post In Situ Pressure Test MRPC N/A N/A Plug Visual 100% (321) 100% (290)

Upper InternalsO Visual 100%

N/A Top of Tubesheet Visual 100%

N/A PLPO Visual 0

1 General Notes:

The scope of inspections is provided as a percentage followed by the total number of tests parenthetically where practical.

For clarity, only three digit codes that require supplemental MRPC testing and utilized during 2R27 are included in 0 below.

DNT is called at > 2.0 Volt, and all the other codes in Q below (DSI, INR, MBM, NQI, PLP and PSI) do not have a voltage calling criteria.

Specific Notes:

0 Except the bend portion of rows 1 through 4 u-bends.

0 Supplemental MRPCO testing (including the +Point coil) was based on bobbin results to inspect all, DNI, DTI, TSP DNT > 2.OV, Freespan DNT >_ 5.OV, DSI, TSP INR >_ 1.5V, MBM, NQI, PLP (Bound MRPC PLP's), PSI, Cold Leg Thinning Ž 40%

or < 40% and _> 1.5V signals/indications to detect latent tube degradation, to refute/confirm, to characterize (axial, circumferential or volumetric) and/or obtain additional length and depth measurements.

0 Inspection of upper internals included the Swirl Vane Moisture Separators, Feed Ring Hangers, Holes, and Plugs, Upper Transition Girth Weld, Thermal Sleeve, Magnetic Particle Examine of the Feedwater Nozzle, Ultrasonic inspections of Feed Ring Tee, and Feedwater to Reducer Welds Downcomer, and other upper bundle components per NRC Generic Letter 97-06.

  • Tube lane and periphery of the tube bundle inspected using Camera Transporter System.
  • Locating new possible loose part (PLP) indications for investigation and possible removal based on eddy current results.

Page 4 of 169

2. Active degradation found, Primary Side Inspections -Thinning, wear, outside diameter stress corrosion cracking (ODSCC) and primary water stress corrosion cracking (PWSCC) were found in both SGs during 2R27 and are captured within the corrective action process. These Mechanisms have been previously reported.

Secondary Side Inspections - None found

3. Nondestructive examination techniques utilized for each degradation mechanism, Table 2 and the text that follows, provides the Electric Power Research Institute (EPRI) Examination Technique Specification Sheet (ETSS) (techniques) utilized during 2R27 for existing and potential degradation and proactive sampling.

Page 5 of 169

TABLE 2 MECHANISM ORIENTATION LOCATION TECHNIQUE Wear Volumetric AVB, TLBD and TSP 96004.3 Rev. 13 Wear Volumetric FO/PLPO 27091.2 Rev. 0 Pitting Volumetric Sludge Pile 96005.2 Rev. 9 Thinning Volumetric Non-dented TSP and Sludge Pile 96001.1 Rev. 11 Hot and Cold Leg Tubesheet IGA/SCC Axial Crevice, Freespan Dent L>5V) and 21409.1 Rev. 7 TSP Dent (>2V)

IGA/SCC Axial Sludge Pile 128413 Rev. 3 IGA/SCC Axial Non-dented (<2V) Freespan 128412 Rev. 3 IGA/SCC Axial Freespan Dent L>2V & <5V) 24013.1 Rev. 2 128411 Rev. 3 and IGA/SCC Axial Non-dented (<2V) TSP GL 95-05 IGA/SCC Circ.

Roll Transition and TSP Dent (>2V) 21410.1 Rev. 6 PWSCC Axial Hot and Cold Leg Tube End and 20511.1 Rev. 8 Hot@ and Cold Leg Roll Transition PWSCC Axial TSP Dent (>2V) 20511.1 Rev. 8 PWSCC Axial U-bend 96511.2 Rev. 16 PWSCC Axial Hot Leg Roll Plug Transition 99-TR-FSW-010 PWSCC Circ.

Hot and Cold Leg Tube End and 20510.1 Rev. 7 Hot and Cold Leg Roll Transition PWSCC Circ.

TSP Dent L>2V) 20510.1 Rev. 7 PWSCC Circ.

U-bend 96511.2 Rev. 16 PWSCC Circ.

Hot Leg Roll Plug Transition 99-TR-FSW-010 D Active is synonymous with the term "existing" degradation that is found in the EPRI Steam Generator Integrity Assessment Guidelines. Therefore the classical definition applies (i.e.,

one historical or current indication equates to active).

Potential degradation based on internal and external operating experience on steam generators with similar designs, operating conditions and materials.

Proactive Sampling is used to challenge engineering assumptions such as material susceptibility or when the Arrhenius equation predicts susceptibility in a future sequential period. These samples are considered informational sample plans that are not subject to the periodicity requirements of T.S.5.5.8.d.3.

© 99-TR-FSW-010 Rev. 00 "Appendix H Qualification for Eddy Current Testing Steam Generator Mechanical Tube Plugs" ABBCE, November 2, 1998.

Page 6 of 169

4. Location, orientation (if linear), and measured sizes (if available) of service induced indications, Tables 3 and 4 provide the location and measured size of each reported indication in each steam generator respectively for degradation found during 2R27 that was sized with the bobbin coil. All the tubes in these two tables were returned to service using the depth based criteria for tube repair.

Tables 5 and 6 provide the location, orientation and length (if available) of each reported indication in each steam generator respectively for degradation found during 2R27 that is located below the F* distance of a tube that has never been repaired by the rerolling process. These tubes are considered F*0 tubes and all the tubes in the two tables were returned to service using the F* Alternate Repair Criteria (ARC) without any additional rerolling during 2R27.

Tables 7 and 8 provide the location, orientation and length (if available) of each reported indication in each steam generator respectively for degradation found during 2R27 (or known to exist from previous inspections) that is located below the F* distance of a tube that was repaired by rerolling in a previous outage at the first reroll repair location (approximately 3.75" to 5.00" above the tube end). These tubes are considered F*1 tubes and all the tubes in the two tables were returned to service using the F* ARC without any additional rerolling during 2R27.

Tables 9 and 10 provide the location, orientation and length (if available) of each reported indication in each steam generator respectively for degradation found during 2R27 (or known to exist from previous inspections) that is located below the F* distance of a tube that was repaired by rerolling in a previous outage at the second reroll repair location (approximately 5.75" to 7.00" above the tube end).

These tubes are considered F*2 tubes and all the tubes in the two tables were returned to service using the F* ARC without any additional rerolling during 2R27.

Tables 11 and 12 provide the location, orientation and length (if available) of each reported indication in each steam generator respectively for degradation found during 2R27 (or known to exist from previous inspections) that is located below the EF* distance of a tube that was repaired by rerolling in a previous outage at the elevated reroll repair location (approximately 16.38" to 18.38" above the tube end).

These tubes are considered EF* tubes and all the tubes in the two tables were returned to service using the EF* ARC without any additional rerolling during 2R27.

Tables 13 and 14 provide the location, orientation and length of each reported indication in each steam generator respectively for degradation found during 2R27 that is located within (and in some cases also below) the F* distance of a tube that has never been repaired by rerolling in a previous outage. These tubes were successfully repaired during 2R27 at the first reroll repair location (approximately 3.75" to 5.00" above the tube end). These tubes are considered new F*1 tubes and all the tubes in the two tables were returned to service using the F* ARC with a new reroll installed during 2R27.

Page 7 of 169

Tables 15 and 16 provide the location, orientation and length (if available) of each reported indication in each steam generator respectively for degradation found during 2R27 (or known to exist from previous inspections) that is located within (and in some cases also below) the F* distance of a tube that was either successfully repaired by rerolling in a previous outage or failed the acceptance criteria during the current outage at the first reroll repair location. These tubes were successfully repaired during 2R27 at the second reroll repair location (approximately 5.75" to 7.00" above the tube end). These tubes are considered F*2 tubes and all the tubes in the two tables were returned to service using the F* ARC with a new reroll installed during 2R27.

Tables 17 and 18 provide the location, orientation and length (if available) of each reported indication in each steam generator respectively for degradation found during 2R27 (or known to exist from previous inspections) that is located within (and in some cases also below) the F* distance of a tube that was successfully repaired by rerolling in a previous outage at the second reroll repair location. These tubes were successfully repaired during 2R27 at the elevated reroll repair location (approximately 16.38" to 18.38" above the tube end). These tubes are considered EF* tubes and all the tubes in the two tables were returned to service using the EF*

ARC with a new reroll installed during 2R27.

Tables 19 and 20 provide the location, orientation (if linear) and measured sizes (if available) of indications in each steam generator respectively for tubes exceeding the plugging or repair criteria during 2R27. These tubes were all removed from service by plugging during 2R27.

A legend of fields and codes with brief explanations is provided at the end of this enclosure for clarification purposes.

Page 8 of 169

TABLE 3 Steam Generator 21 - Less than the Technical Specification Repair Limit TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM 1

1 16 4

0.95 27 01C 0.00 2

2 16 5

1.24 11 02C 0.05 3

3 14 6

1.27 25 01C

-0.06 4

4 19 6

1.11 24 NV1 0.00 5

5 20 6

0.16 11 01C 0.00 6

6 21 7

0.76 1

01C 0.03 7

7 23 7

0.37 5

01C

-0.25 8

8 21 9

1.06 23 NV1 1.30 9

9 27 10 1.57 30 07H 25.56 10 10 25 11 1.06 29 02C 0.25 11 11 29 13 1.08 1

01C

-0.19 12 12 31 17 0.27 19 01C

-0.25 13 13 33 17 0.82 16 02C 0.00 14 14 31 18 0.45 31 01C

-0.30 15 15 36 21 1.43 16 02C 0.22 16 16 41 26 1.08 31 01C 0.27 16 17 41 26 0.65 32 01C

-0.19 17 18 23 27 1.40 26 NV4 4.44 18 19 39 27 0.69 15 NV3

-0.31 19 20 18 28 0.76 21 NV2 12.53 19 21 18 28 0.94 24 07H 23.52 19 22 18 28 1.19 26 NV2 0.38 20 23 34 28 0.38 12 NV1

-0.22 20 24 34 28 1.10 25 NV3 0.00 21 25 25 30 0.95 20 NV4 2.55 21 26 25 30 1.09 22 NV2 0.86 21 27 25 30 1.98 32 NV2 19.83 22 28 39 30 1.00 23 NV4 2.65 23 29 41 32 0.53 14 NV1

-0.03 23 30 41 32 0.79 20 NV2 0.00 23 31 41 32 0.86 21 NV3 0.03 24 32 24 33 0.97 22 NV3 2.66 25 33 25 33 0.87 20 NV4 0.86 25 34 25 33 1.68 31 NV2 20.52 25 35 25 33 1.84 33 NV2 1.36 26 36 39 34 1.18 26 NV4 2.60 27 37 44 34 0.49 13 01C

-0.14 27 38 44 34 0.52 32 05C 0.00 28 39 23 37 1.46 29 NV2 17.47 29 40 17 38 0.61 16 NV2 0.21 30 41 45 42 0.75 15 01C

-0.17 30 42 45 42 2.00 36 02C

-0.06 31 43 11 43 0.41 10 NV1 0.00 32 44 36 43 0.98 22 NV2 2.55 32 45 36 43 1.03 22 NV2 32.82 32 46 36 43 1.03 23 07H 33.96 33 47 46 43 0.42 26 01C

-0.22 34 48 43 44 1.09 29 01C

-0.14 Page 9 of 169

TABLE 3 Steam Generator 21 - Less than the Technical Specification Re air Limit TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM 35 49 44 44 1.33 26 01C

-0.14 36 50 28 45 0.91 21 NV2 24.91 36 51 28 45 1.30 27 NV4 2.41 36 52 28 45 1.58 31 NV2 22.70 36 53 28 45 1.77 32 NV2 0.03 36 54 28 45 1.93 34 07H 29.19 37 55 36 45 1.14 23 NV2 1.19 38 56 44 45 0.50 17 01C

-0.08 39 57 45 45 0.33 14 01C 0.08 40 58 46 45 0.30 19 01C

-0.03 41 59 42 46 0.49 14 01C 0.30 42 60 44 46 2.57 34 01C

-0.14 43 61 46 46 1.27 15 01C 0.25 44 62 36 47 1.13 25 NV2 32.54 44 63 36 47 1.48 30 NV2 2.11 44 64 36 47 1.82 33 07H 33.81 45 65 39 47 1.31 25 NV2 35.15 45 66 39 47 1.77 30 NV4 3.09 46 67 35 48 1.18 24 NV2 1.96 46 68 35 48 2.35 37 07H 33.32 47 69 45 48 0.56 28 01C 0.11 48 70 29 50 2.19 37 NV2 1.11 48 71 29 50 2.63 40 NV2 24.39 49 72 45 50 0.33 34 01C

-0.03 50 73 11 51 0.41 10 NV4 0.00 51 74 29 52 1.09 24 NV2 1.00 52 75 41 53 1.73 13 01C

-0.25 53 76 42 53 0.70 16 NV1 0.00 53 77 42 53 0.80 17 NV2 0.00 54 78 43 54 0.33 22 01C 0.00 55 79 46 54 0.91 21 01C

-0.11 56 80 22 55 1.18 25 NV2 17.70 57 81 34 56 0.60 15 NV4

-0.17 57 82 34 56 1.48 29 NV3 0.00 58 83 40 57 0.67 15 01C 0.25 59 84 43 57 0.94 26 01C 0.17 60 85 19 58 0.95 20 NV2 13.88 61 86 41 58 1.54 14 01C

-0.16 62 87 45 58 1.81 17 01C 0.03 63 88 8

59 0.73 33 04H 1.48 64 89 9

59 0.81 34 04H 1.53 65 90 43 59 1.98 27 01C 0.08 66 91 36 60 1.34 28 NV2 2.52 67 92 42 60 0.47 9

01C 0.03 68 93 21 61 0.67 16 NV4 0.08 68 94 21 61 0.92 21 NV2 16.81 68 95 21 61 1.12 24 NV2 1.19 69 96 23 61 0.94 21 NV2 18.98 Page 10 of 169

TABLE 3 Steam Generator 21 - Less than the Technical Specification Re air Limit TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM 69 97 23 61 1.12 24 NV4 0.28 69 98 23 61 1.45 29 NV2 1.49 70 99 39 61 0.54 2

01C

-0.22 71 100 42 62 2.25 23 01C

-0.11 72 101 36 63 2.54 40 NV2 2.88 73 102 39 63 0.92 8

01C 0.25 74 103 21 64 0.92 20 NV2 17.14 75 104 43 64 1.37 18 01C

-0.11 76 105 40 66 1.58 29 02C

-0.08 77 106 21 67 0.45 12 NV2 0.38 78 107 26 69 0.78 20 NV2 2.67 78 108 26 69 1.07 24 NV2 23.08 78 109 26 69 1.31 28 07H 28.72 79 110 40 70 0.63 24 02C 0.00 80 111 18 71 0.91 21 07H 22.98 80 112 18 71 0.96 21 NV2 13.37 80 113 18 71 1.25 25 NV3

-0.03 81 114 39 71 1.66 24 01C

-0.19 82 115 40 71 0.55 20 01C

-0.22 83 116 26 72 1.37 26 NV2 1.24 83 117 26 72 1.85 32 NV2 21.99 84 118 36 72 1.38 7

01C

-0.06 85 119 39 72 1.89 2

01C 0.00 86 120 38 73 0.62 19 01C

-0.08 87 121 37 74 0.48 37 01C 0.28 88 122 37 75 1.61 5

01C 0.00 89 123 34 76 1.54 22 02C 0.22 90 124 35 77 0.70 9

02C

-0.14 91 125 23 86 3.94 29 01C 0.03 92 126 25 86 2.16 11 01C 0.00 93 127 23 88 0.83 15 01C 0.03 94 128 12 90 1.57 16 01C

-0.11 95 129 15 90 1.48 24 01C 0.05 96 130 16 90 0.75 29 01C 0.03 97 131 17 90 1.06 29 01C

-0.06 98 132 4

91 2.42 36 01C

-0.11 99 133 7

91 2.72 34 01C

-0.14 100 134 14 91 1.36 1

01C 0.00 101 135 3

92 1.77 38 01C 0.19 102 136 8

92 1.12 17 02C

-0.19 102 137 8

92 1.99 39 01C

-0.08 103 138 9

92 1.34 28 01C

-0.03 104 139 10 92 1.88 24 01C

-0.06 105 140 11 92 0.59 20 01C

-0.19 106 141 14 92 0.61 20 01C 0.08 106 142 14 92 1.48 30 NV1 2.70 107 143 2

93 0.39 12 02C 0.00 107 144 2

93 1.66 23 01C

-0.11 Page 11 of 169

TABLE 3 Steam Generator 21 - Less than the Technical Specification Re air Limit TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM 108 145 3

93 0.54 10 01C 0.03 109 14 6 5

94 1.26 21 01C

-0.03 110 147 7

94 0.86 14 01C 0.08 Page 12 of 169

TABLE 4 Steam Generator 22 - Less than the Technical Specification Re air Limit TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM 1

1 16 4

1.32 15 01C 0.14 2

2 17 5

1.39 15 01C 0.14 3

3 16 6

0.50 10 01C

-0.03 4

4 17 6

0.92 34 01C 0.03 5

5 19 6

0.73 14 02C 0.14 6

6 20 6

0.89 35 01C 0.00 7

7 21 7

1.08 11 01C 0.11 7

8 21 7

0.80 3

02C 0.08 8

9 25 9

1.83 37 01C 0.00 9

10 20 10 0.75 18 01C

-0.03 10 11 24 10 1.13 24 01C

-0.06 11 12 26 10 0.57 15 02C 0.22 12 13 28 11 0.85 9

02C 0.17 13 14 31 13 1.79 32 01C

-0.17 14 15 29 15 0.41 7

01C

-0.17 15 16 30 15 2.01 20 01C

-0.08 16 17 34 16 0.48 33 01C 0.17 16 18 34 16 2.61 38 02C 0.00 17 19 34 17 1.97 20 01C

-0.06 17 20 34 17 0.76 15 02C

-0.08 18 21 30 19 0.56 13 01C

-0.06 19 22 31 19 0.96 14 01C

-0.25 20 23 32 20 0.45 17 01C

-0.17 21 24 30 21 0.69 24 01C 0.19 22 25 36 22 0.79 25 02C 0.06 23 26 37 23 0.50 3

01C 0.11 24 27 37 24 1.55 24 01C

-0.08 25 28 38 25 0.70 20 01C 0.19 25 29 38 25 0.76 19 02C

-0.16 26 30 33 27 0.46 30 TSC 0.22 27 31 39 29 0.58 11 02C

-0.08 28 32 41 29 1.33 26 NV1 0.00 28 33 41 29 1.14 23 NV2 0.00 28 34 41 29 0.92 20 NV3 0.00 29 35 19 31 0.44 15 NV1 0.00 29 36 19 31 0.68 20 NV2 2.70 29 37 19 31 0.45 15 NV3 0.00 30 38 19 34 0.71 21 NV1

-0.03 31 39 43 34 0.53 38 03C 0.00 32 40 43 35 2.71 34 02C

-0.14 33 41 38 36 0.80 21 NV2 2.51 34 42 44 36 1.16 24 02C

-0.08 35 43 42 38 1.43 21 02C

-0.22 35 44 42 38 0.38 12 NV1 0.03 35 45 42 38 0.65 18 NV2

-0.17 36 46 38 39 0.20 5

NV1 0.00 36 47 38 39 0.23 6

NV2

-0.19 37 48 43 39 0.57 30 02C

-0.22 Page 13 of 169

TABLE 4 Steam Generator 22 - Less than the Technical Specification Re air Limit TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM 38 49 44 40 3.17 12 02C 0.06 39 50 33 41 0.43 15 NV1 0.00 40 51 40 41 0.96 23 NV1 0.00 40 52 40 41 1.30 28 NV2 0.00 40 53 40 41 0.92 22 NV3 0.00 41 54 44 42 1.45 13 02C

-0.08 42 55 46 42 1.58 22 02C

-0.14 43 56 37 43 1.77 32 NV2 33.35 43 57 37 43 1.23 25 NV4 3.50 44 58 45 44 1.21 19 02C 0.11 45 59 46 44 0.27 14 02C

-0.03 46 60 38 46 1.04 25 07H 35.98 46 61 38 46 0.46 14 NV1

-0.11 46 62 38 46 0.51 15 NV2

-0.06 46 63 38 46 0.83 22 NV4 3.05 47 64 38 47 0.96 21 NV2 2.26 48 65 45 47 0.31 2

01C 0.00 49 66 38 48 1.04 25 NV2 2.34 50 67 41 48 0.40 12 NV1

-0.08 50 68 41 48 0.67 18 NV2 0.00 51 69 44 48 0.87 21 01C 0.00 52 70 45 48 0.80 15 01C 0.25 52 71 45 48 1.39 13 02C

-0.11 53 72 25 49 0.56 16 NV4 0.00 54 73 26 49 0.50 15 NV4 0.30 55 74 32 49 0.47 14 NV3

-0.11 55 75 32 49 0.62 17 NV4

-0.03 56 76 11 50 0.36 11 NV1

-0.11 57 77 33 50 1.11 27 NV2 28.85 58 78 38 50 0.67 19 NV1 0.00 58 79 38 50 0.72 19 NV2

-0.14 58 80 38 50 0.65 18 NV3

-0.06 58 81 38 50 2.18 38 NV4

-0.19 59 82 45 50 2.40 25 01C 0.11 60 83 37 51 0.96 21 NV2 2.17 60 84 37 51 0.95 21 NV2 33.35 61 85 46 51 0.26 23 01C 0.22 62 86 33 52 0.91 20 07H 35.06 63 87 39 52 0.83 22 NV2 2.81 64 88 45 52 0.95 24 01C 0.19 65 89 40 53 0.98 18 01C 0.19 66 90 44 53 1.39 24 01C 0.17 67 91 46 53 1.30 25 02C

-0.14 68 92 36 54 1.13 27 NV4 3.44 69 93 39 54 0.94 24 07H 35.58 70 94 45 54 0.68 25 01C

-0.25 71 95 39 55 0.50 16 01C

-0.19 71 96 39 55 1.02 22 NV2 3.77 Page 14 of 169

TABLE 4 Steam Generator 22 - Less than the Technical Specification Repair Limit TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM 72 97 11 56 0.32 8

NV1

-0.34 73 98 36 56 1.09 26 NV2 33.04 74 99 38 56 0.70 19 NV1 0.06 74 100 38 56 0.78 21 NV2 35.72 75 101 38 57 1.00 21 07H 34.89 76 102 35 58 1.02 25 07H 32.96 77 103 40 59 1.11 23 07H 35.07 77 104 40 59 1.04 22 NV2 3.98 78 105 41 60 1.41 17 02C

-0.11 79 106 41 61 1.19 30 02C

-0.14 80 107 41 63 0.71 5

01C

-0.03 81 108 43 63 1.41 1

02C

-0.22 82 109 32 64 1.39 30 NV2 3.03 82 110 32 64 1.51 31 NV2 28.30 83 111 38 64 1.44 30 NV2 34.57 84 112 39 64 1.38 20 02C

-0.16 85 113 42 64 2.69 24 02C

-0.17 86 114 19 65 1.04 23 NV2 1.27 87 115 42 65 0.95 25 02C

-0.11 88 116 43 65 2.80 16 02C

-0.14 89 117 32 66 0.42 13 NV4

-0.11 90 118 40 66 1.18 6

02C 0.11 91 119 32 68 0.71 20 NV2 28.69 92 120 19 69 0.86 20 NV4 3.56 93 121 32 69 0.99 20 NV2 28.65 93 122 32 69 0.88 20 NV4 3.34 94 123 40 69 3.01 33 02C

-0.11 95 124 41 69 0.75 4

02C

-0.03 96 125 36 70 2.12 37 NV2 4.96 96 126 36 70 2.45 40 NV2 32.59 97 127 38 71 2.01 31 01C 0.00 98 128 40 71 3.73 19 02C

-0.16 99 129 36 73 1.23 23 NV2 32.26 100 130 35 74 0.53 1

02C 0.08 101 131 33 75 1.48 23 01C 0.03 102 132 35 75 1.26 35 01C 0.03 103 133 36 75 2.36 27 02C

-0.14 104 134 33 76 1.24 26 01C 0.05 104 135 33 76 1.43 33 02C

-0.16 105 136 30 79 0.99 9

01C 0.14 105 137 30 79 1.42 27 02C 0.14 106 138 29 81 0.85 18 NV2 0.00 107 139 30 81 2.23 33 0iC 0.00 108 140 29 82 0.44 34 0iC

-0.03 108 141 29 82 2.87 25 02C

-0.16 109 142 30 82 2.68 29 02C

-0.14 110 143 30 83 1.05 1

02C

-0.19 111 144 22 85 0.74 5

01C

-0.11 Page 15 of 169

TABLE 4 Steam Generator 22 - Less than the Technical Specification Re air Limit TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM 112 145 24 85 0.20 5

01C

-0.14 113 146 28 85 0.71 16 01C

-0.14 113 147 28 85 0.77 21 01C 0.11 114 148 26 86 1.48 16 02C

-0.11 115 149 20 87 0.83 3

01C

-0.08 116 150 14 88 0.89 3

02C

-0.11 117 151 22 88 2.01 36 02C

-0.17 118 152 16 89 0.77 9

01C

-0.28 118 153 16 89 1.24 11 02C 0.00 119 154 17 89 1.62 23 01C 0.06 120 155 18 89 0.36 8

02C 0.00 121 156 19 89 1.44 24 01C 0.00 122 157 21 89 1.26 27 02C

-0.11 123 158 6

90 0.35 1

01C 0.00 124 159 12 90 1.36 14 01C

-0.06 125 160 7

91 1.95 14 01C 0.11 126 161 11 91 1.63 12 02C 0.00 127 162 12 91 0.96 2

01C 0.08 127 163 12 91 0.43 8

02C 0.00 128 164 13 91 0.30 10 02C

-0.06 129 165 6

92 1.08 1

02C

-0.03 130 166 7

92 2.08 32 01C 0.03 131 167 9

92 0.79 13 01C 0.06 132 168 4

93 2.08 20 01C 0.11 132 169 4

93 0.56 14 02C 0.00 133 170 5

93 1.34 20 01C 0.08 134 171 6

93 0.84 20 02C

-0.11 135 172 4

94 1.02 8

02C

-0.06 Page 16 of 169

TABLE 5 STEAM GENERATOR 21 - HISTORICAL F*0 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 2

1 5.17 SAN TRH

-2.49

-2.30 0.19 2

2 2

2 3.87 MAN TRH

-2.53

-2.42 0.11 3

3 1

3 0.67 SAN TRH

-2.47

-2.43 0.04 4

4 1

5 4.33 SAN TRH

-2.61

-2.34 0.27 5

5 4

5 2.06 SAN TRH

-2.46

-2.35 0.11 6

6 13 6

1.94 SAN TRH

-2.66

-2.53 0.13 7

7 18 6

4.48 SAN TRH

-2.52

-2.40 0.12 8

8 19 6

1.35 SAN TRH

-2.40

-2.33 0.07 9

9 21 6

1.58 MAN TRH

-2.73

-2.71 0.02 10 10 1

7 4.40 SAN TRH

-2.62

-2.51 0.11 11 11 4

7 1.24 SAN TRH

-2.51

-2.45 0.06 12 12 7

8 1.39 SAN TRH

-2.49

-2.30 0.19 13 13 16 8

2.01 SAN TRH

-2.49

-2.45 0.04 14 14 17 8

0.43 SAI TRH

-2.46

-2.43 0.03 15 15 25 8

2.43 SAN TRH

-2.39

-2.29 0.10

.16 16 16 9

0.64 SAN TRH

-2.51

-2.44 0.07 17 17 3

10 0.81 SAN TRH

-2.57

-2.50 0.07 18 18 6

10 0.45 SAN TRH

-2.59

-2.53 0.06 19 19 13 10 1.90 SAN TRH

-2.65

-2.56 0.09 20 20 22 10 2.80 MAN TRH

-2.73

-2.68 0.05 21 21 25 10 2.46 MAN TRH

-2.66

-2.58 0.08 22 22 26 10 2.23 SAN TRH

-2.64

-2.57 0.07 23 23 28 10 5.69 MAN TRH

-2.48

-2.40 0.08 24 24 7

11 3.55 MAN TRH

-1.61

-1.46 0.15 25 25 19 11 2.64 SAN TRH

-2.46

-2.37 0.09 26 26 22 11 0.55 SAN TRH

-2.41

-2.35 0.06 27 27 25 12 2.13 MAN TRH

-2.70

-2.65 0.05 28 28 17 13 1.65 SAN TRH

-2.44

-2.37 0.07 29 29 19 13 1.52 MAN TRH

-2.61

-2.53 0.08 30 30 23 13 1.85 MAN TRH

-2.50

-2.38 0.12 31 31 24 13 1.28 MAN TRH

-2.48

-2.41 0.07 32 32 28 15 2.49 MAN TRH

-2.57

-2.47 0.10 33 33 23 18 1.80 MAN TRH

-2.62

-2.54 0.08 34 34 33 20 5.88 MAN TRH

-2.55

-2.44 0.11 35 35 32 21 4.68 MAN TRH

-2.37

-2.23 0.14 36 36 7

23 3.99 SAN TRH

-2.44

-2.31 0.13 37 37 28 23 1.26 SAN TRH

-2.75

-2.66 0.09 38 38 33 23 2.47 MAN TRH

-2.60

-2.50 0.10 39 39 1

25 2.98 MAN TRH

-2.53

-2.43 0.10 40 40 26 26 2.06 SAN TRH

-2.48

-2.41 0.07 41 41 1

29 0.83 SAI TRH

-2.69

-2.64 0.05 42 42 32 30 2.07 MAN TRH

-2.71

-2.63 0.08 43 43 29 31 0.37 SAN TRH

-1.99

-1.92 0.07 44 44 1

35 4.51 SAN TRH

-2.60

-2.46 0.14 45 45 15 35 0.51 SAI TRH

-2.44

-2.41 0.03 46 46 28 35 1.71 MAI TRH

-2.64

-2.55 0.09 47 47 26 36 1.83 SAN TRH

-2.40

-2.34 0.06 48 48 1

37 3.39 SAN TRH

-2.56

-2.43 0.13 Page 17 of 169

TABLE 5 STEAM GENERATOR 21 - HISTORICAL F*0 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 49 49 27 39 0.62 SAI TRH

-2.43

-2.40 0.03 50 50 1

40 2.22 SAN TRH

-2.44

-2.37 0.07 51 51 27 45 1.83 SAI TRH

-2.46

-2.34 0.12 52 52 25 46 0.94 MAI TRH

-2.56

-2.45 0.11 53 53 21 47 2.45 MAN TRH

-2.54

-2.51 0.03 54 54 45 55 2.89 SCN TRH

-2.72

-2.55 0.17 55 55 20 57 1.63 SAN TRH

-2.43

-2.33 0.10 56 56 24 58 1.22 SAN TRH

-2.60

-2.53 0.07 57 57 27 60 4.04 MAN TRH

-2.66

-2.43 0.23 58 58 28 60 4.30 MAN TRH

-2.71

-2.54 0.17 59 59 35 60 1.72 MAI TRH

-2.53

-2.46 0.07 60 60 1

61 1.30 SAI TRH

-2.42

-2.36 0.06 61 61 21 61 1.73 MAN TRH

-2.61

-2.49 0.12 62 62 26 61 3.33 MAN TRH

-2.59

-2.48 0.11 63 63 28 61 2.03 MAN TRH

-2.63

-2.50 0.13 64 64 16 62 2.03 SAN TRH

-2.46

-2.36 0.10 65 65 20 62 2.15 SAN TRH

-2.49

-2.38 0.11 66 66 22 62 1.63 SAN TRH

-2.50

-2.39 0.11 67 67 26 62 2.47 MAN TRH

-2.60

-2.51 0.09 68 68 29 62 0.91 SAN TRH

-2.53

-2.49 0.04 69 69 32 62 3.76 MAN TRH

-2.62

-2.49 0.13 70 70 20 63 1.99 SAN TRH

-2.43

-2.35 0.08 71 71 22 63 0.82 SAI TRH

-2.46

-2.40 0.06 72 72 32 63 0.78 SAI TRH

-2.47

-2.41 0.06 73 73 16 64 2.10 MAI TRH

-2.44

-2.36 0.08 74 74 25 64 1.84 SAN TRH

-2.64

-2.50 0.14 75 75 28 64 1.75 SAI TRH

-2.57

-2.50 0.07 76 76 31 64 2.05 SAN TRH

-2.58

-2.51 0.07 77 77 32 64 5.85 MAN TRH

-2.63

-2.46 0.17 78 78 33 64 5.30 MAN TRH

-2.64

-2.42 0.22 79 79 21 65 1.44 SAI TRH

-2.60

-2.52 0.08 80 80 24 65 3.10 SAN TRH

-2.55

-2.44 0.11 81 81 31 65 1.34 SAI TRH

-2.52

-2.37 0.15 82 82 13 66 2.66 SAN TRH

-2.58

-2.50 0.08 83 83 20 66 3.56 SAN TRH

-2.44

-2.30 0.14 84 84 23 66 3.22 SAN TRH

-2.66

-2.31 0.35 85 85 26 66 1.60 SAN TRH

-2.60

-2.52 0.08 86 86 27 66 4.50 SAN TRH

-2.63

-2.35 0.28 87 87 31 66 1.39 SAI TRH

-2.60

-2.48 0.12 88 88 32 66 4.21 SAN TRH

-2.66

-2.53 0.13 89 89 17 67 3.52 SAN TRH

-1.42

-1.35 0.07 90 90 32 67 3.06 MAN TRH

-2.60

-2.52 0.08 91 91 33 67 4.08 MAN TRH

-2.61

-2.38 0.23 92 92 16 68 2.85 SAN TRH

-1.59

-1.52 0.07 93 93 31 68 1.78 SAI TRH

-2.43

-2.39 0.04 94 94 29 69 1.10 SAI TRH

-2.51

-2.37 0.14 95 95 1

70 1.43 SAN TRH

-2.57

-2.49 0.08 96 96 12 70 0.94 SAI TRH

-2.54

-2.44 0.10 Page 18 of 169

TABLE 5 STEAM GENERATOR 21 - HISTORICAL F*0 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 97 97 26 70 0.65 SAI TRH

-2.51

-2.48 0.03 98 98 27 70 5.03 MAN TRH

-2.71

-2.36 0.35 99 99 28 70 1.06 SAI TRH

-2.58

-2.54 0.04 100 100 29 70 1.75 SAI TRH

-2.62

-2.58 0.04 101 101 33 70 2.74 SAN TRH

-2.61

-2.55 0.06 102 102 19 71 1.46 SAN TRH

-2.52

-2.45 0.07 103 103 23 71 4.90 SAN TRH

-2.48

-2.31 0.17 104 104 27 71 4.20 SAN TRH

-2.64

-2.46 0.18 105 105 28 71 1.93 SAN TRH

-2.56

-2.52 0.04 106 106 32 71 2.66 SAN TRH

-2.51

-2.41 0.10 107 107 13 72 1.32 SAI TRH

-2.46

-2.34 0.12 108 108 14 72 2.44 SAN TRH

-2.50

-2.41 0.09 109 109 28 72 1.89 SAN TRH

-2.57

-2.53 0.04 110 110 30 72 2.72 MAN TRH

-2.60

-2.52 0.08 111 111 31 72 5.15 MAN TRH

-2.56

-2.23 0.33 112 112 20 73 2.40 SAN TRH

-2.45

-2.32 0.13 113 113 26 73 1.58 SAN TRH

-2.61

-2.57 0.04 114 114 27 73 3.31 SAN TRH

-2.52

-2.35 0.17 115 115 28 73 2.48 SAN TRH

-2.57

-2.50 0.07 116 116 30 73 2.98 SAN TRH

-2.56

-2.49 0.07 117 117 33 73 2.69 SAN TRH

-2.59

-2.48 0.11 118 118 30 74 3.60 SAN TRH

-2.49

-2.35 0.14 119 119 12 75 1.26 SAN TRH

-2.41

-2.36 0.05 120 120 26 75 1.55 MAI TRH

-2.51

-2.40 0.11 121 121 27 75 3.29 MAN TRH

-2.50

-2.43 0.07 122 122 30 75 2.40 SAN TRH

-2.48

-2.36 0.12 123 123 31 75 3.10 MAN TRH

-2.57

-2.45 0.12 124 124 32 75 3.55 MAN TRH

-2.53

-2.40 0.13 125 125 33 75 3.46 MAN TRH

-2.53

-2.44 0.09 126 126 20 76 3.15 MAN TRH

-2.45

-2.35 0.10 127 127 22 76 0.73 SAI TRH

-2.56

-2.50 0.06 128 128 23 76 1.26 SAI TRH

-2.42

-2.36 0.06 129 129 25 76 0.92 MAN TRH

-2.51

-2.47 0.04 130 130 26 76 5.95 MAN TRH

-2.60

-2.43 0.17 131 131 31 76 2.60 SAN TRH

-2.52

-2.44 0.08 132 132 25 77 1.79 SAN TRH

-2.50

-2.47 0.03 133 133 27 77 4.15 MAN TRH

-2.54

-2.43 0.11 134 134 28 77 1.10 MAI TRH

-2.59

-2.52 0.07 135 135 33 77 1.66 SAN TRH

-2.55

-2.52 0.03 136 136 1

78 3.19 MAN TRH

-2.67

-2.52 0.15 137 137 16 78 4.25 SAN TRH

-2.60

-2.44 0.16 138 138 21 78 0.97 MAN TRH

-2.49

-2.37 0.12 139 139 24 78 3.62 MAN TRH

-2.55

.- 2.44 0.11 140 140 27 78 3.80 MAN TRH

-2.52

-2.42 0.10 141 141 28 78 0.77 SAI TRH

-2.50

-2.42 0.08 142 142 31 78 5.12 SAN TRH

-2.53

-2.42 0.11 143 143 16 79 1.57 MAN TRH

-2.61

-2.56 0.05 144 144 20 79 5.62 MAN TRH

-2.59

-2.34 0.25 Page 19 of 169

TABLE 5 STEAM GENERATOR 21 - HISTORICAL F*0 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 145 145 25 79 2.94 MAN TRH

-2.55

-2.45 0.10 146 146 26 79 5.87 MAN TRH

-2.64

-2.42 0.22 147 147 28 79 2.99 SAN TRH

-2.52

-2.43 0.09 148 148 30 79 2.88 SAN TRH

-2.45

-2.35 0.10 149 149 33 79 2.68 MAN TRH

-2.53

-2.42 0.11 150 150 13 80 1.42 MAI TRH

-2.40

-2.31 0.09 151 151 15 80 0.61 SAI TRH

-2.59

-2.52 0.07 152 152 16 80 1.01 SAN TRH

-2.61

-2.57 0.04 153 153 24 80 3.43 MAN TRH

-2.54

-2.39 0.15 154 154 25 80 5.27 MAN TRH

-2.56

-2.43 0.13 155 155 29 80 1.48 SAN TRH

-2.52

-2.45 0.07 156 156 31 80 1.98 SAN TRH

-2.52

-2.44 0.08 157 157 14 81 4.00 SAN TRH

-2.56

-2.46 0.10 158 158 15 81 1.05 MAN TRH

-2.54

-2.47 0.07 159 159 23 81 5.32 SAN TRH

-2.63

-2.49 0.14 160 160 25 81 5.61 MAN TRH

-2.55

-2.43 0.12 161 161 26 81 2.59 MAN TRH

-2.50

-2.43 0.07 162 162 28 81 1.30 SAI TRH

-2.46

-2.40 0.06 163 163 29 81 1.36 SAN TRH

-2.57

-2.50 0.07 164 164 13 82 1.53 SAI TRH

-2.42

-2.35 0.07 165 165 22 82 6.30 SAN TRH

-2.53

-2.27 0.26 166 166 29 82 1.38 SAN TRH

-2.54

-2.51 0.03 167 167 30 82 1.07 SAN TRH

-2.52

-2.46 0.06 168 168 16 83 0.85 SAI TRH

-2.44

-2.38 0.06 169 169 20 83 4.30 SAN TRH

-2.50

-2.33 0.17 170 170 16 84 1.99 MAN TRH

-2.62

-2.58 0.04 171 171 25 84 2.33 SAN TRH

-2.57

-2.46 0.11 172 172 17 86 0.81 SAI TRH

-2.59

-2.51 0.08 173 173 25 86 2.99 MAN TRH

-2.50

-2.42 0.08 174 174 18 88 0.83 SCN TRH

-2.70

-2.60 0.10 0

Page 20 of 169

TABLE 6 STEAM GENERATOR 22 - HISTORICAL F*0 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 4

1 1.48 SAN TRH

-2.33

-2.22 0.11 2

2 1

2 1.67 SAN TRH

-2.41

-2.34 0.07 2

3 1

2 0.86 SAN TRH

-2.04

-1.93 0.11 2

4 1

2 1.19 SAN TRH

-1.88

-1.77 0.11 3

5 12 4

0.25 SAI TRH

-2.13

-2.03 0.10 4

6 11 6

2.08 SCN TRH

-2.66

-2.58 0.08 5

7 3

10 2.83 MAN TRH

-2.32

-2.21 0.11 6

8.

37 19 1.55 SAI TRH

-2.65

-2.47 0.18 7

9 6

24 0.63 SAN TRH

-2.53

-2.40 0.13 8

10 8

27 SAD TRH

-2.57 9

11 1

28 3.64 SAN TRH

-2.57

-2.47 0.10 10 12 35 28 1.68 MAN TRH

-2.60

-2.49 0.11 11 13 37 28 1.14 MAI TRH

-2.60

-2.52 0.08 12 14 40 28 1.60 MAN TRH

-2.41

-2.31 0.10 13 15 2

29 2.53 SAN TRH

-2.55

-2.30 0.25 14 16 35 29 1.13 MAN TRH

-2.56

-2.45 0.11 15 17 40 29 0.82 SAI TRH

-2.35

-2.29 0.06 16 18 42 35 3.29 SAN TRH

-2.60

-2.44 0.16 17 19 2

39 0.87 SCN TRH

-2.59

-2.49 0.10 18 20 7

48 2.19 SAN TRH

-2.61

-2.53 0.08 19 21 8

48 2.47 SAN TRH

-2.65

-2.57 0.08 20 22 7

49 3.64 SAN TRH

-2.65

-2.49 0.16 21 23 35 49 0.72 SAN TRH

-2.56

-2.47 0.09 22 24 36 49 1.35 SAN TRH

-2.27

-2.22 0.05 23 25 4

50 3.20 SAN TRH

-2.75

-2.64 0.11 24 26 7

50 4.96 SAN TRH

-2.64

-2.47 0.17 25 27 39 50 0.51 SAN TRH

-2.33

-2.25 0.08 26 28 4

51 3.46 MAN TRH

-2.73

-2.62 0.11 27 29 7

51 3.96 SAN TRH

-2.64

-2.49 0.15 28 30 39 51 1.22 SAN TRH

-2.60

-2.46 0.14 29 31 35 52 0.73 SAN TRH

-2.66

-2.49 0.17 30 32 39 52 0.72 SAI TRH

-2.28

-2.14 0.14 31 33 42 52 0.75 SAN TRH

-2.58

-2.52 0.06 32 34 3

53 1.05 SAI TRH

-2.57

-2.50 0.07 33 35 4

53 1.56 SAN TRH

-2.82

-2.74 0.08 34 36 5

53 2.08 MAN TRH

-2.61

-2.53 0.08 35 37 42 53 1.12 SAN TRH

-2.66

-2.56 0.10 36 38 3

55 1.61 SAN TRH

-2.60

-2.52 0.08 37 39 39 55 0.59 SAI TRH

-2.54

-2.47 0.07 38 40 3

56 1.31 MAN TRH

-2.61

-2.53 0.08 39 41 8

56 0.77 SAI TRH

-2.57

-2.50 0.07 40 42 8

57 1.28 MAI TRH

-2.64

-2.52 0.12 41 43 24 57 0.19 SVN TRH

-2.46

-2.24 0.22 42 44 38 57 1.03 MAI TRH

-2.35

-2.26 0.09 43 45 35 58 0.92 SAN TRH

-2.42

-2.35 0.07 44 46 10 59 1.10 SAN TRH

-2.57

-2.47 0.10 45 47 26 59 2.10 MAN TRH

-2.44

-2.29 0.15 46 48 38 59 0.65 MAI TRH

-2.28

-2.19 0.09 Page 21 of 169

TABLE 6 STEAM GENERATOR 22 - HISTORICAL F*0 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 47 49 34 60 2.53 MAN TRH

-2.36

-2.19 0.17 48 50 3

61 0.86 MAI TRH

-2.58

-2.50 0.08 49 51 8

61 1.58 SAN TRH

-2.55

-2.44 0.11 50 52 38 61 0.70 SAN TRH

-2.53

-2.46 0.07 51 53 35 62 1.37 MAN TRH

-2.32

-2.20 0.12 52 54 39 62 1.83 MAI TRH

-2.44

-2.32 0.12 53 55 6

63 3.43 SAN TRH

-2.63

-2.54 0.09 54 56 8

63 3.36 SAN TRH

-2.64

-2.42 0.22 55 57 17 63 2.82 MAN TRH

-2.62

-2.45 0.17 56 58 34 63 3.77 MAN TRH

-2.60

-2.30 0.30 57 59 35 63 2.24 SAN TRH

-2.43

-2.33 0.10 58 60 38 63 1.05 SAI TRH

-2.27

-2.21 0.06 59 61 5

64 2.90 SAN TRH

-2.55

-2.37 0.18 60 62 8

64 3.09 SAN TRH

-2.63

-2.48 0.15 61 63 1

65 0.36 MAN TRH

-2.60

-2.53 0.07 62 64 2

65 1.01 SAI TRH

-2.36

-2.31 0.05 63 65 4

65 0.56 MAN TRH

-2.59

-2.50 0.09 64 66 29 65 1.31 SCI TRH

-2.32

-2.28 0.04 65 67 35 65 2.07 MAN TRH

-2.29

-2.20 0.09 66 68 38 65 0.46 SAI TRH

-2.26

-2.20 0.06 67 69 43 65 1.08 SAI TRH

-2.57

-2.50 0.07 68 70 4

66 0.57 SAN TRH

-2.50

-2.42 0.08 69 71 6

66 1.50 SAN TRH

-2.62

-2.56 0.06 70 72 7

66 1.47 SAN TRH

-2.44

-2.35 0.09 71 73 8

66 3.64 MAN TRH

-2.56

-2.24 0.32 72 74 42 66 0.55 SAI TRH

-2.53

-2.50 0.03 73 75 8

67 2.69 SAN TRH

-2.56

-2.28 0.28 74 76 36 67 2.37 MAN TRH

-2.36

-2.26 0.10 75 77 4

68 1.22 MAI TRH

-2.41

-2.32 0.09 76 78 7

68 2.44 SAN TRH

-2.49

-2.36 0.13 77 79 1

69 7.39 MAN TRH

-2.72

-2.30 0.42 78 80 2

69 0.47 SAI TRH

-2.41

-2.33 0.08 79 81 8

69 1.65 SAN TRH

-2.51

-2.43 0.08 80 82 10 69 2.57 SAN TRH

-2.58

-2.50 0.08 81 83 35 69 2.62 SAN TRH

-2.44

-2.30 0.14 82 84 40 69 0.58 SAI TRH

-2.60

-2.52 0.08 83 85 1

70 4.62 MAN TRH

-2.63

-2.29 0.34 84 86 7

70 1.00 SAN TRH

-2.58

-2.50 0.08 85 87 8

70 2.79 SAN TRH

-2.56

-2.40 0.16 86 88 35 70 1.40 SAN TRH

-2.55

-2.47 0.08 87 89 36 70 1.96 SAN TRH

-2.58

-2.51 0.07 88 90 37 70 2.71 MAN TRH

-2.59

-2.40 0.19 89 91 6

71 4.27 SAN TRH

-2.65

-2.47 0.18 90 92 7

71 2.39 MAN TRH

-2.43

-2.35 0.08 91 93 8

71 2.25 MAN TRH

-2.52

-2.36 0.16 92 94 11 71 3.06 SAN TRH

-2.58

-2.43 0.15 93 95 34 71 1.87 SAN TRH

-2.30

-2.21 0.09 94 96 36 71 1.11 SAN TRH

-2.36

-2.24 0.12 Page 22 of 169

TABLE 6 STEAM GENERATOR 22 - HISTORICAL F*0 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 95 97 1

72 7.06 MAN TRH

-2.70

-2.26 0.44 96 98 2

72 1.79 SAN TRH

-2.60

-2.52 0.08 97 99 6

72 2.96 SAN TRH

-2.64

-2.53 0.11 98 100 7

72 1.93 SAN TRH

-2.45

-2.32 0.13 99 101 10 72 1.36 SAN TRH

-2.58

-2.51 0.07 100 102 36 72 3.15 SAN TRH

-2.60

-2.51 0.09 101 103 37 72 4.94 SAN TRH

-2.68

-2.28 0.40 102 104 5

73 2.96 SAN TRH

-2.54

-2.27 0.27 103 105 8

73 1.56 SAN TRH

-2.60

-2.46 0.14 104 106 35 73 0.57 SAI TRH

-2.58

-2.51 0.07 105 107 1

74 10.79 MAN TRH

-2.60

-2.19 0.41 106 108 2

74 1.15 SAN TRH

-2.47

-2.37 0.10 107 109 5

74 2.13 SAN TRH

-2.49

-2.43 0.06 108 110 6

74 2.40 MAN TRH

-2.45

-2.38 0.07 109 111 36 74 1.67 MAI TRH

-2.60

-2.53 0.07 110 112 5

75 1.79 SAN TRH

-2.53

-2.48 0.05 111 113 1

76 3.40 MAN TRH

-2.70

-2.29 0.41 112 114 5

76 1.24 SAN TRH

-2.46

-2.39 0.07 113 115 6

76 2.50 SAN TRH

-2.49

-2.39 0.10 114 116 1

77 7.76 MAN TRH

-2.69

-2.41 0.28 115 117 2

77 0.93 SAN TRH

-2.44

-2.39 0.05 116 118 4

77 2.77 MAN TRH

-2.61

-2.49 0.12 117 119 5

77 1.98 SAN TRH

-2.57

-2.51 0.06 118 120 6

77 2.92 MAN TRH

-2.58

-2.45 0.13 119 121 2

78 0.58 SAN TRH

-2.46

-2.39 0.07 120 122 3

78 1.28 SAI TRH

-2.68

-2.60 0.08 121 123 5

78 2.70 SAN TRH

-2.54

-2.48 0.06 122 124 7

78 1.79 SAN TRH

-2.58

-2.49 0.09 123 125 1

79 6.93 MAN TRH

-2.64

-2.48 0.16 124 126 5

79 0.80 SAI TRH

-2.60

-2.55 0.05 125 127 7

79 1.33 SAN TRH

-2.66

-2.57 0.09 126 128 8

79 1.81 SAN TRH

-2.48

-2.40 0.08 127 129 11 79 0.40 SAI TRH

-2.65

-2.53 0.12 128 130 1

80 9.38 MAN TRH

-2.68

-2.25 0.43 129 131 5

80 4.51 SAN TRH

-2.67

-2.50 0.17 130 132 7

80 1.63 SAN TRH

-2.53

-2.44 0.09 131 133 8

80 1.54 SAN TRH

-2.60

-2.52 0.08 132 134 11 80 2.19 SAN TRH

-2.63

-2.50 0.13 133 135 2

81 2.07 SAN TRH

-2.45

-2.43 0.02 134 136 3

81 0.93 SAI TRH

-2.61

-2.57 0.04 135 137 6

81 2.56 MAN TRH

-2.56

-2.43 0.13 136 138 7

81 2.17 SAN TRH

-2.50

-2.41 0.09 137 139 8

81 1.05 SAN TRH

-2.60

-2.52 0.08 138 140 1

82 6.79 MAN TRH

-2.57

-2.32 0.25 139 141 2

82 1.09 SAI TRH

-2.64

-2.60 0.04 140 142 3

82 2.04 SAN TRH

-2.68

-2.64 0.04 141 143 4

82 2.05 MAN TRH

-2.58

-2.45 0.13 142 144 5

82 3.41 SAN TRH

-2.61

-2.43 0.18 Page 23 of 169

TABLE 6 STEAM GENERATOR 22 - HISTORICAL F*0 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 143 145 6

82 0.77 SAI TRH

-2.47

-2.41 0.06 144 146 7

82 1.76 SAN TRH

-2.48

-2.38 0.10 145 147 8

82 2.48 MAN TRH

-2.64

-2.50 0.14 146 148 1

83 8.51 MAN TRH

-2.70

-2.27 0.43 147 149 6

83 2.00 SAN TRH

-2.58

-2.46 0.12 148 150 7

83 2.15 SAN TRH

-2.59

-2.43 0.16 149 151 8

83 1.70 SAN TRH

-2.62

-2.51 0.11 150 152 4

84 1.09 SAI TRH

-2.61

-2.54 0.07 151 153 5

84 5.64 MAN TRH

-2.71

-2.49 0.22 152 154 6

84 2.08 SAN TRH

-2.56

-2.42 0.14 153 155 8

84 2.13 SAN TRH

-2.70

-2.62 0.08 154 156 6

85 4.35 SAN TRH

-2.56

-2.33 0.23 155 157 7

85 2.85 SAN TRH

-2.53

-2.44 0.09 156 158 8

85 3.31 SAN TRH

-2.66

-2.46 0.20 157 159 6

86 3.15 SAN TRH

-2.55

-2.42 0.13 158 160 1

87 7.43 MAN TRH

-2.61

-2.35 0.26 159 161 3

87 0.51 SAN TRH

-2.54

-2.47 0.07 160 162 5

87 3.88 SAN TRH

-2.62

-2.48 0.14 161 163 1

88 1.38 SAI TRH

-2.48

-2.44 0.04 162 164 4

88 0.35 SAN TRH

-2.70

-2.67 0.03 163 165 9

88 2.90 SAN TRH

-2.65

-2.54 0.11 164 166 13 88 2.30 SAN TRH

-1.83

-1.75 0.08 165 167 1

89 1.79 SAI TRH

-2.60

-2.53 0.07 166 168 9

90 1.67 SAN TRH

-2.62

-2.54 0.08 167 169 6

91 0.90 SAN TRH

-2.58

-2.50 0.08 168 170 7

91 1.19 SAN TRH

-2.62

-2.54 0.08 169 171 3

92 0.78 SCI TRH

-2.37

-2.31 0.06 170 172 6

94 0.95 MAN TRH

-2.66

-2.58 0.08 171 173 7

94 1.42 SAN TRH

-2.54

-2.43 0.11 Page 24 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 7

1 1.02 MAN 1BH

-0.60

-0.41 0.19 1

2 7

1 SAD 1BH

-0.94 2

3 3

2 SAD 1BH

-1.08 3

4 11 2

SAD 1BH

-0.82 4

5 4

3 MAD 1BH

-1.22 4

6 4

3 5.07 MAN 1BH

-3.70

-3.56 0.14 5

7 5

3 SAD 1BH

-1.04 6

8 9

3 SAD 1BH

-0.95 7

9 14 3

MAD 1BH

-1.63 7

10 14 3

6.42 SAN 1BH

-3.73

-3.60 0.13 8

11 1

4 MAD 1BH

-0.95 8

12 1

4 6.08 SAN 1BH

-3.69

-3.40 0.29 9

13 2

4 SAD 1BH

-0.83 9

14 2

4 1.80 SAN 1BH

-3.56

-3.46 0.10 10 15 3

4 SAD 1BH

-1.01 10 16 3

4 1.49 SAN 1BH

-3.68

-3.57 0.11 11 17 4

4 SAD 1BH

-0.85 11 18 4

4 0.65 SAN 1BH

-3.55

-3.45 0.10 12 19 6

4 SAD 1BH

-1.16 12 20 6

4 3.77 SAN 1BH

-3.64

-3.54 0.10 13 21 7

4 SAD 1BH

-1.00 14 22 9

4 MAD 1BH

-0.88 15 23 13 4

SAD 1BH

-0.79 16 24 2

5 MAD 1BH

-0.86 16 25 2

5 3.42 MAN 1BH

-3.71

-3.50 0.21 17 26 3

5 1.71 MAN 1BH

-3.77

-3.65 0.12 17 27 3

5 SAD 1BH

-1.58 18 28 5

5 MAD 1BH

-0.75 18 29 5

5 1.27 MAN 1BH

-3.79

-3.70 0.09 19 30 7

5 MAD 1BH

-1.16 19 31 7

5 5.39 MAN 1BH

-3.80

-3.65 0.15 19 32 7

5 0.69 SAI 1BH

-0.26

-0.20 0.06 20 33 8

5 SAD 1BH

-0.98 20 34 8

5 2.44 SAN "11BH

-3.77

-3.65 0.12 21 35 10 5

MAD 1BH

-0.75 22 36 13 5

SAD 1BH

-0.77 23 37 1

6 5.63 MAN 1BH

-3.77

-3.45 0.32 23 38 1

6 SAD 1BH

-1.00 24 39 2

6 SAD 1BH

-0.84 24 40 2

6 4.56 SAN 1BH

-3.70

-3.45 0.25 25 41 3

6 6.08 MAN 1BH

-3.68

-3.43 0.25 25 42 3

6 SAD 1BH

-1.61 26 43 4

6 SAD 1BH

-0.84 26 44 4

6 0.88 SAN 131BH

-3.64

-3.54 0.10 27 45 8

6 SAD 1BH

-0.83 28 46 9

6 SAD 1BH

-0.91 29 47 15 6

SAD 1BH

-0.88 30 48 16 6

MAD 1BH

-0.79 Page 25 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 30 49 16 6

2.87 SAN 1BH

-3.46

-3.36 0.10 31 50 2

7 MAD 1BH

-0.71 31 51 2

7 9.26 MAN 1BH

-3.69

-3.29 0.40 32 52 3

7 SAD 11BH

-0.60 32 53 3

7 2.53 SAN 1BH

-3.61

-3.51 0.10 33 54 7

7 7.84 MAN 1BH

-3.60

-3.45 0.15 33 55 7

7 SAD 1BH

-1.74 34 56 10 7

SAD 1BH

-0.78 35 57 13 7

MAD 1BH

-1.00 35 58 13 7

4.41 SAN 1BH

-3.79

-3.64 0.15 36 59 14 7

MAD 1BH

-0.76 37 60 19 7

MAD 1BH

-0.87 38 61 21 7

SAD 1BH

-0.81 39 62 2

8 SAD 1BH

-1.60 39 63 2

8 3.55 SAN 11BH

-3.66

-3.42 0.24 40 64 4

8 SAD 11BH

-0.88 40 65 4

8 0.69 SAN 1BH

-3.45

-3.41 0.04 41 66 5

8 3.55 MAN 1BH

-3.75

-3.64 0.11 41 67 5

8 SAD 1BH

-1.05 42 68 8

8 1.09 MAN 1BH

-3.58

-3.49 0.09 42 69 8

8 SAD 1BH

-0.89 43 70 9

8 SAD 1BH

-0.86 44 71 10 8

MAD 1BH

-0.90 45 72 11 8

SAD 1BH

-0.91 46 73 13 8

MAD 1BH

-1.35 46 74 13 8

4.69 MAN 1BH

-3.75

-3.60 0.15 47 75 14 8

SAD 1BH

-0.85 47 76 14 8

0.81 SAN 1BH

-3.81

-3.77 0.04 48 77 18 8

SAD 1BH

-0.94 48 78 18 8

1.23 SAN 1BH

-3.69

-3.66 0.03 49 79 19 8

MAD 1BH

-0.73 50 80 20 8

SAD 1BH

-0.80 51 81 24 8

MAD 1BH

-0.85 51 82 24 8

3.43 SAN 1BH

-3.69

-3.61 0.08 52 83 2

9 MAD 1BH

-0.90 52 84 2

9 0.70 SAN 1BH

-3.75

-3.69 0.06 53 85 3

9 SAD 1BH

-1.60 54 86 5

9 1.63 MAN 1BH

-3.77

-3.68 0.09 54 87 5

9 SAD 131BH

-1.37 55 88 6

9 1.92 MAN 1BH

-3.75

-3.65 0.10 55 89 6

9 SAD 1BH

-0.83 56 90 7

9 MAD 1BH

-1.22 56 91 7

9 9.07 MAN 1BH

-3.69

-3.30 0.39 57 92 8

9 SAD 1BH

-0.77 57 93 8

9 2.61 SAN 1BH

-3.70

-3.60 0.10 58 94 11 9

MAD 1BH

-1.34 59 95 12 9

SAD 1BH

-0.84 59 96 12 9

5.99 SAN 1BH

-3.68

-3.48 0.20 Page 26 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 60 97 15 9

SAD 1BH

-0.86 60 98 15 9

1.54 SAN 1BH

-3.85

-3.78 0.07 61 99 18 9

MAD 1BH

-1.49 62 100 20 9

MAD 1BH

-0.76 62 101 20 9

4.65 MAN 1BH

-3.86

-3.68 0.18 63 102 21 9

MAD 1BH

-1.04 64 103 25 9

2.96 MAN 1BH

-3.58

-3.46 0.12 64 104 25 9

SAD 1BH

-0.85 65 105 2

10 SAD 1BH

-0.85 65 106 2

10 3.75 SAN 1BH

-3.70

-3.40 0.30 66 107 4

10 SAD 1BH

-1.39 66 108 4

10 1.61 SAN 1BH

-3.63

-3.50 0.13 67 109 5

10 SAD 1BH

-1.10 68 110 7

10 SAD 1BH

-0.84 68 111 7

10 1.19 SAN 1BH

-3.44

-3.38 0.06 69 112 8

10 SAD 1BH

-0.91 70 113 10 10 SAD 1BH

-0.98 71 114 11 10 SAD 1BH

-1.03 72 115 14 10 MAD 1BH

-0.90 72 116 14 10 5.06 MAN 1BH

-3.57

-3.42 0.15 73 117 15 10 MAD 1BH

-0.86 73 118 15 10 5.13 MAN 1BH

-3.60

-3.47 0.13 74 119 16 10 SAD 1BH

-0.82 74 120 16 10 2.12 SAN 1BH

-3.49

-3.35 0.14 75 121 27 10 MAD 1BH

-0.70 75 122 27 10 3.53 MAN 1BH

-3.75

-3.67 0.08 76 123 3

11 4.63 MAN 1BH

-3.72

-3.54 0.18 76 124 3

11 3.24 MAN 1BH

-0.84

-0.24 0.60 76 125 3

11 SAD 1BH

-1.61 77 126 5

11 5.16 MAN 1BH

-3.68

-3.53 0.15 77 127 5

11 2.17 MAN 1BH

-1.24

-1.14 0.10 78 128 6

11 1.51 MAN 1BH

-3.66

-3.51 0.15 78 129 6

11 SAD 1BH

-1.40 79 130 8

11 MAD 1BH

-0.73 80 131 10 11 SAD 1BH

-1.14 81 132 13 11 4.48 MAN 1BH

-3.64

-3.49 0.15 81 133 13 11 SAD 1BH

-0.78 82 134 15 11 MAD 1BH

-1.30 82 135 15 11 2.49 SAN 1BH

-3.59

-3.47 0.12 83 136 17 11 SAD 1BH

-0.85 83 137 17 11 3.62 SAN 1BH

-3.42

-3.31 0.11 84 138 18 11 SAD 1BH

-0.87 84 139 18 11 2.04 SAN 1BH

-3.79

-3.72 0.07 85 140 20 11 0.41 MAN 1BH

-3.59

-3.56 0.03 86 141 21 11 1.97 MAN 1BH

-3.49

-3.40 0.09 86 142 21 11 SAD 1BH

-0.70 87 143 23 11 MAD 1BH

-1.50 87 144 23 11 1.98 MAN 1BH

-3.69

-3.62 0.07 Page 27 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 88 145 26 11 SAD 1BH

-0.88 88 146 26 11 2.62 SAN 1BH

-3.47

-3.42 0.05 89 147 27 11 3.09 MAN 1BH

-3.65

-3.57 0.08 89 148 27 11 SAD 1BH

-0.92 90 149 29 11 2.80 MAN 1BH

-3.57

-3.44 0.13 90 150 29 11 SAD 1BH

-0.84 91 151 1

12 9.50 MAN 1BH

-3.75

-3.32 0.43 91 152 1

12 SAD 1BH

-1.32 92 153 2

12 SAD 1BH

-1.47 92 154 2

12 4.73 SAN 1BH

-3.75

-3.61 0.14 93 155 4

12 SAD 1BH

-1.06 93 156 4

12 1.35 SAN 1BH

-3.75

-3.68 0.07 94 157 5

12 4.31 MAN 1BH

-3.71

-3.44 0.27 94 158 5

12 SAD 1BH

-1.09 95 159 6

12 IRR 1BH

-1.43 96 160 8

12 MAD 1BH

-0.88 96 161 8

12 0.46 SAI 1BH

-3.56

-3.53 0.03 97 162 9

12 SAD 1BH

-1.33 97 163 9

12 0.86 SAN 1BH

-3.74

-3.70 0.04 98 164 11 12 SAD 1BH

-1.06 99 165 13 12 SAD 1BH

-0.90 100 166 15 12 MAD 1BH

-0.80 100 167 15 12 6.13 MAN 1BH

-3.81

-3.60 0.21 101 168 16 12 MAD 1BH

-0.85 102 169 17 12 SAD 1BH

-0.85 103 170 19 12 SAD 1BH

-0.82 104 171 20 12 MAD 1BH

-0.80 104 172 20 12 2.39 SAN 1BH

-3.69

-3.55 0.14 105 173 21 12 SAD 1BH

-0.71 106 174 23 12 1

MAD 1BH

-1.43 106 175 23 12 1.92 MAN 1BH

-3.64

-3.58 0.06 107 176 24 12 MAD 1BH

-0.75 107 177 24 12 0.88 MAN 1BH

-3.54

-3.46 0.08 108 178 26 12 SAD 1BH

-0.80 108 179 26 12 3.70 SAN 1BH

-3.55

-3.48 0.07 109 180 27 12 2.36 MAN 1BH

-3.69

-3.59 0.10 109 181 27 12 SAD 1BH

-0.86 110 182 29 12 SAD 1BH

-0.92 111 183 1

13 3.12 MAN 1BH

-3.74

-3.53 0.21 111 184 1

13 SAD 1BH

-0.86 112 185 3

13 SAD 1BH

-0.89 113 186 5

13 SAD 1BH

-1.48 114 187 6

13 MAD 1BH

-0.79 114 188 6

13 2.06 MAN 1BH

-3.62

-3.48 0.14 115 189 7

13 MAD 1BH

-1.03 115 190 7

13 6.29 MAN 1BH

-3.73

-3.57 0.16 116 191 8

13 MAD 1BH

-1.12 116 192 8

13 0.68 SAN 1BH

-3.83

-3.78 0.05 Page 28 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 117 193 11 13 MAD 1BH

-1.33 118 194 12 13 MAD 1BH

-0.86 118 195 12 13 1.43 SAN 1BH

-3.72

-3.58 0.14 119 196 13 13 SAD 1BH

-1.40 119 197 13 13 1.91 SAN 1BH

-3.34

-3.28 0.06 120 198 14 13 2.13 MAN 1BH

-3.54

-3.42 0.12 120 199 14 13 SAD 1BH

-1.33 121 200 15 13 MAD 1BH

-1.19 121 201 15 13 1.87 SAN 1BH

-3.59

-3.49 0.10 122 202 16 13 MAD 1BH

-0.82 122 203 16 13 0.79 SAN 1BH

-3.55

-3.49 0.06 123 204 20 13 MAD 1BH

-1.20 124 205 25 13 MAD 1BH

-0.88 124 206 25 13 2.64 SAN 1BH

-3.61

-3.50 0.11 125 207 27 13 MAD 1BH

-0.88 125 208 27 13 2.45 MAN 1BH

-3.60

-3.50 0.10 126 209 29 13 MAD 1BH

-0.82 127 210 1

14 3.52 MAN 1BH

-3.80

-3.56 0.24 127 211 1

14 SAD 1BH

-0.89 128 212 2

14 6.51 MAN 1BH

-3.75

-3.45 0.30 128 213 2

14 1.91 SAN 1BH

-1.07

-0.90 0.17 129 214 7

14 5.11 MAN 1BH

-3.75

-3.59 0.16 130 215 8

14 SAD 1BH

-0.72 131 216 9

14 MAD 1BH

-1.35 132 217 12 14 MAD 1BH

-0.86 133 218 13 14 SAD 1BH

-1.17 134 219 15 14 MAD 1BH

-1.21 135 220 18 14 MAD 1BH

-0.85 136 221 22 14 SAD 1BH

-1.17 137 222 23 14 SAD 1BH

-1.30 138 223 26 14 SAD 1BH

-0.78 139 224 27 14 SAD 1BH

-0.88 140 225 30 14 MAD 1BH

-0.86 141 226 2

15 4.16 MAN 1BH

-3.52

-3.23 0.29 141 227 2

15 SAD 1BH

-1.38 142 228 3

15 SAD 1BH

-1.26 143 229 4

15 MAD 1BH

-1.02 143 230 4

15 1.51 MAN 1BH

-3.65

-3.54 0.11 144 231 5

15 2.73 MAN 1BH

-3.59

-3.49 0.10 144 232 5

15 SAD 1BH

-1.17 145 233 6

15 SAD 1BH

-0.80 145 234 6

15 4.18 SAN 1BH

-3.41

-3.27 0.14 146 235 7

15 MAD 1BH

-0.81 146 236 7

15 2.94 MAN 1BH

-3.85

-3.71 0.14 147 237 8

15 SAD 1BH

-1.21 148 238 10 15 SAD 1BH

-1.37 149 239 11 15 SAD 1BH

-0.89 150 240 14 15 SAD 1BH

-1.26 Page 29 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE#

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 151 241 15 15 SAD 1BH

-0.90 151 242 15 15 3.35 SAN 1BH

-3.66

-3.48 0.18 152 243 17 15 SAD 1BH

-0.75 153 244 19 15 SAD 1BH

-1.21 153 245 19 15 3.46 SAN I1BH

-3.61

-3.43 0.18 154 246 20 15 SAD 1BH

-0.89 154 247 20 15 1.10 SAN 1BH

-3.71

-3.64 0.07 155 248 21 15 MAD 1BH

-0.87 155 249 21 15 1.13 MAN 1BH

-3.71

-3.61 0.10 156 250 22 15 SAD 1BH

-1.22 156 251 22 15 3.59 SAN 1BH

-3.36

-3.27 0.09 157 252 23 15 SAD 1BH

-1.18 157 253 23 15 1.66 SAN 1BH

-3.34

-3.27 0.07 158 254 26 15 3.74 MAN 1BH

-3.65

-3.47 0.18 158 255 26 15 SAD 1BH

-0.85 159 256 31 15 SAD 1BH

-0.95 159 257 31 15 1.90 SAN 1BH

-3.72

-3.67 0.05 160 258 2

16 MAD 1BH

-0.80 160 259 2

16 5.37 MAN 1BH

-3.61

-3.34 0.27 161 260 3

16 3.93 MAN 1BH

-3.68

-3.39 0.29 161 261 3

16 SAD 1BH

-1.16 162 262 5

16 SAD 1BH

-1.16 162 263 5

16 3.90 SAN 1BH

-3.70

-3.52 0.18 163 264 6

16 3.81 MAN 1BH

-3.71

-3.54 0.17 163 265 6

16 SAD 1BH

-0.90 164 266 7

16 5.20 MAN 1BH

-3.71

-3.42 0.29 164 267 7

16 SAD 1BH

-0.80 165 268 10 16 SAD 1BH

-0.88 166 269 13 16 MAD 1BH

-1.16 166 270 13 16 3.53 MAN 1BH

-3.71

-3.57 0.14 167 271 14 16 MAD 1BH

-1.35 167 272 14 16 4.10 SAN 1BH

-3.76

-3.50 0.26 168 273 15 16 4.83 MAN 1BH

-3.73

-3.50 0.23 168 274 15 16 SAD 1BH

-0.85 169 275 16 16 MAD 1BH

-0.80 169 276 16 16 3.28 SAN 1BH

-3.69

-3.55 0.14 170 277 19 16 MAD 1BH

-0.95 170 278 19 16 2.33 MAN 1BH

-3.60

-3.48 0.12 171 279 22 16 SAD 1BH

-0.94 172 280 28 16 3.94 MAN 1BH

-3.53

-3.48 0.05 172 281 28 16 SAD 1BH

-0.90 173 282 29 16 1.83 MAN 1BH

-1.27

-1.15 0.12 174 283 30 16 MAD 1BH

-0.85 175 284 31 16 MAD 1BH

-0.86 176 285 6

17 3.25 MAN 1BH

-3.57

-3.46 0.11 176 286 6

17 SAD 1BH

-0.92 177 287 7

17 3.10 MAN 1BH

-3.57

-3.44 0.13 177 288 7

17 SAD 1BH

-1.03 Page 30 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 178 289 10 17 SAD 1BH

-1.37 179 290 11 17 SAD 11BH

-1.32 180 291 12 17 MAD 1BH

-0.81 181 292 16 17 MAD 1BH

-1.00 182 293 20 17 MAD 1BH

-0.95 183 294 21 17 MAD 1BH3-

-0.75 184 295 26 17 MAD 1BH

-0.71 185 296 27 17 MAD 1BH

-0.70 186 297 31 17 SAD 1BH

-0.86 187 298 33 17 SAD 1BH

-0.90 188 299 2

18 SAD 1BH

-0.89 188 300 2

18 2.29 SAN 1BH

-3.60

-3.49 0.11 189 301 6

18 SAD 1BH

-0.98 189 302 6

18 2.91 SAN 1BH

-3.40

-3.27 0.13 190 303 10 18 MAD 1BH

-1.25 191 304 12 18 SAD 1BH

-0.89 192 305 14 18 SAD 1BH

-0.89 193 306 15 18 MAD 1BH

-0.91 194 307 16 18 SAD 1BH

-1.44 195 308 17 18 SAD 1BH

-0.92 196 309 18 18 MAD 1BH

-0.82 197 310 20 18 SAD 1BH

-0.85 198 311 21 18 MAD 1BH

-0.97 199 312 22 18 SAD 1BH

-1.15 199 313 22 18 1.83 SAN 1BH

-3.78

-3.74 0.04 200 314 24 18 MAD 1BH

-0.80 200 315 24 18 2.53 MAN 1BH

-3.83

-3.70 0.13 201 316 25 18 2.13 MAN 1BH

-3.45

-3.37 0.08 201 317 25 18 SAD 1BH

-2.11 201 318 25 18 2.01 SAN 1BH

-0.86

-0.76 0.10 202 319 26 18 SAD 1BH

-0.90 203 320 29 18 SAD 1BH

-1.04 204 321 30 18 SAD 1BH

-0.79 205 322 32 18 SAD 1BH

-0.85 206 323 34 18 MAD 1BH

-0.85 207 324 36 18 SAD 1BH

-0.85 208 325 2

19 SAD 1BH

-1.39 209 326 3

19 SAD 1BH

-0.93 209 327 3

19 1.81 SAN 1BH

-3.36

-3.26 0.10 210 328 4

19 SAD 1BH

-1.20 211 329 5

19 MAD 1BH

-0.91 212 330 7

19 MAD 1BH

-1.04 212 331 7

19 4.04 MAN 1BH

-3.56

-3.43 0.13 213 332 10 19 MAD 1BH

-0.92 214 333 11 19 MAD 1BH

-1.37 215 334 12 19 MAD 1BH

-1.20 216 335 13 19 MAD 1BH

-1.00 E= =

217 336 14 19 SAD 1BH

-0.85 1

1 Page 31 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 217 337 14 19 1.65 SAN 1BH

-3.56

-3.48 0.08 218 338 15 19 SAD 1BH

-1.12 219 339 17 19 MAD 1BH

-0.86 219 340 17 19 5.51 SAN 1BH

-3.62

-3.51 0.11 220 341 18 19 SAD 1BH

-0.91 221 342 20 19 SAD 1BH

-1.21 222 343 24 19 SAD 1BH

-0.90 223 344 26 19 MAD 1BH

-0.94 223 345 26 19 6.81 MAN 1BH

-3.49

-3.28 0.21 224 346 27 19 MAD 1BH

-1.10 224 347 27 19 3.04 SAN 1BH

-3.70

-3.52 0.18 225 348 28 19 SAD 1BH

-0.93 226 349 30 19 2.18 MAN 1BH

-3.65

-3.58 0.07 226 350 30 19 SAD 1BH

-1.37 227 351 31 19 MAD 1BH

-1.30 227 352 31 19 1.60 SAN 1BH

-3.72

-3.62 0.10 228 353 32 19 SAD 1BH

-1.42 228 354 32 19 2.12 SAN 1BH

-3.73

-3.63 0.10 229 355 2

20 SAD 1BH

-0.96 230 356 3

20 SAD 1BH

-0.96 231 357 6

20 4.84 MAN 1BH

-3.76

-3.57 0.19 231 358 6

20 SAD 1BH

-0.90 232 359 8

20 MAD 1BH

-0.98 232 360 8

20 3.64 MAN 1BH

-3.51

-3.40 0.11 233 361 11 20 SAD 1BH

-1.06 234 362 12 20 SAD 1BH

-0.88 235 363 14 20 SAD 1BH

-0.92 236 364 22 20 SAD 1BH

-0.86 237 365 24 20 MAD 1BH

-0.80 238 366 25 20 3.39 MAN 1BH

-3.83

-3.67 0.16 238 367 25 20 SAD 1BH

-0.82 239 368 26 20 1.10 MAI 1BH

-3.60

-3.53 0.07 239 369 26 20 SAD 1BH

-0.88 240 370 28 20 SAD 1BH

-0.80 241 371 31 20 SAD 1BH

-0.87 241 372 31 20 2.99 SAN 1BH

-3.39

-3.28 0.11 242 373 32 20 1.40 MAN 1BH

-3.79

-3.71 0.08 242 374 32 20 SAD 1BH

-1.12 243 375 36 20 MAD 1BH

-1.37 244 376 8

21 5.32 MAN 1BH

-3.57

-3.45 0.12 244 377 8

21 SAD 1BH

-1.15 245 378 10 21 SAD 1BH

-0.91 246 379 20 21 MAD 1BH

-0.88 246 380 20 21 0.96 SAN 1BH

-3.95

-3.89 0.06 247 381 22 21 MAD 1BH

-0.90 248 382 25 21 MAD 1BH

-0.85 249 383 26 21 1.90 MAN 1BH

-3.65

-3.57 0.08 249 384 26 21 SAD 1BH

-1.25 Page 32 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 250 385 28 21 SAD 1BH

-0.85 251 386 29 21 SAD 1BH

-0.85 251 387 29 21 2.79 SAN 1BH

-3.59

-3.48 0.11 252 388 30 21 SAD 1BH

-1.40 252 389 30 21 0.74 SAI 1BH

-3.70

-3.58 0.12 253 390 33 21 4.70 MAN 1BH

-3.58

-3.42 0.16 253 391 33 21 SAD 1BH

-1.26 254 392 34 21 MAD 1BH

-0.89 255 393 36 21 SAD 1BH

-1.25 256 394 37 21 SAD 1BH

-0.87 257 395 5

22 6.69 MAN 1BH

-3.86

-3.54 0.32 257 396 5

22 SAD 1BH

-0.84 258 397 6

22 3.60 MAN 1BH

-3.65

-3.53 0.12 258 398 6

22 SAD 1BH

-0.89 259 399 9

22 SAD 1BH

-1.16 260 400 10 22 MAD 1BH

-1.16 260 401 10 22 SAD 1BH

-0.90 261 402 12 22 SAD 1BH

-0.80 262 403 14 22 0.91 MAN 1BH

-1.19

-1.04 0.15 263 404 15 22 MAD 1BH

-0.87 264 405 17 22 2.35 MAN 1BH

-1.18

-1.01 0.17 265 406 19 22 MAD 1BH

-1.20 266 407 20 22 SAD 1BH

-0.88 267 408 23 22 SAD 1BH

-0.92 268 409 24 22 MAD 1BH

-0.85 269 410 26 22 MAD 1BH

-0.87 269 411 26 22 4.41 MAN 1BH

-3.60

-3.49 0.11 270 412 27 22 SAD 1BH

-0.87 271 413 28 22 1.80 MAN 1BH

-3.61

-3.54 0.07 271 414 28 22 SAD 1BH

-1.28 272 415 29 22 SAD 1BH

-0.85 273 416 30 22 MAD 1BH

-0.90 274 417 32 22 3.98 MAN 1BH

-3.69

-3.59 0.10 274 418 32 22 SAD 1BH

-1.39 274 419 32 22 0.56 SAN 1BH

-1.08

-1.04 0.04 275 420 36 22 SAD 1BH

-0.86 276 421 1

23 MAD 1BH

-1.00 276 422 1

23 8.42 MAN 1BH

-3.69

-3.53 0.16 277 423 2

23 MAD 1BH

-0.89 277 424 2

23 4.21 SAN 1BH

-3.42

-3.29 0.13 278 425 5

23 MAD 1BH

-1.40 278 426 5

23 1.66 SAN 1BH

-3.49

-3.42 0.07 279 427 9

23 3.00 MAN 1BH

-0.45

-0.13 0.32 279 428 9

23 SAD 1BH

-1.29 280 429 10 23 SAD 1BH

-0.87 281 430 15 23 MAD 1BH

-1.16 282 431 18 23 MAD 1BH

-0.99 283 432 20 23 SAD 1BH

-0.85 Page 33 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 284 433 21 23 MAD 1BH

-0.98 285 434 25 23 MAD 1BH

-0.78 286 435 26 23 MAD 1BH

-0.97 286 436 26 23 0.80 MAI 1BH

-3.61

-3.51 0.10 287 437 27 23 SAD 1BH

-1.17 287 438 27 23 1.81 SAN 1BH

-3.63

-3.50 0.13 288 439 29 23 SAD 1BH

-0.89 289 440 34 23 SAD 1BH

-1.17 290 441 35 23 MAD 1BH

-1.03 291 442 2

24 SAD 1BH

-1.35 292 443 4

24 SAD 1BH

-1.23 292 444 4

24 4.37 SAN 1BH

-3.70

-3.59 0.11 293 445 7

24 6.69 MAN 1BH

-3.67

-3.51 0.16 293 446 7

24 SAD 1BH

-1.32 294 447 8

24 3.59 MAN 1BH

-3.71

-3.55 0.16 294 448 8

24 SAD 1BH

-1.26 295 449 11 24 MAD 1BH

-1.16 296 450 16 24 MAD 1BH

-1.20 297 451 18 24 SAD 1BH

-0.80 298 452 19 24 MAD 1BH

-0.82 299 453 21 24 SAD 1BH

-0.85 300 454 22 24 MAD 1BH

-0.94 301 455 23 24 SAD 1BH

-0.94 302 456 25 24 SAD 1BH

-1.25 302 457 25 24 1.88 SAN 1BH

-3.73

-3.59 0.14 303 458 26 24 MAD 1BH

-0.85 304 459 28 24 3.24 MAN 1BH

-3.74

-3.64 0.10 304 460 28 24 SAD 1BH

-0.93 305 461 29 24 SAD 1BH

-1.14 306 462 31 24 2.80 MAN 1BH

-3.74

-3.61 0.13 306 463 31 24 SAD 1BH

-0.98 307 464 32 24 MAD 1BH

-0.94 307 465 32 24 1.34 MAN 1BH

-3.70

-3.63 0.07 308 466 33 24 5.19 MAN 1BH

-3.80

-3.67 0.13 308 467 33 24 SAD 1BH

-0.88 309 468 34 24 MAD 1BH

-0.83 310 469 35 24 SAD 1BH

-0.83 311 470 3

25 SAD 1BH

-0.92 312 471 5

25 SAD 1BH

-1.17 313 472 7

25 SAD 1BH

-1.30 313 473 7

25 1.92 SAN 1BH

-0.38

-0.18 0.20 314 474 11 25 MAD 1BH

-1.00 315 475 13 25 MAD 1BH

-0.93 316 476 15 25 SAD 1BH

-1.12 317 477 17 25 SAD 1BH

-1.21 318 478 18 25 SAD 1BH

-0.85 319 479 21 25 MAD 1BH

-0.86 320 480 24 25 4.38 MAN 1BH

-3.69

-3.57 0.12 Page 34 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 320 481 24 25 SAD 1BH

-1.00 321 482 25 25 MAD 1BH

-1.25 321 483 25 25 0.77 SAN 1BH

-3.74

-3.68 0.06 322 484 28 25 SAD 1BH

-1.06 322 485 28 25 3.14 SAN 1BH

-3.66

-3.55 0.11 323 486 30 25 MAD 1BH

-1.39 323 487 30 25 2.37 SAN 1BH

-3.54

-3.45 0.09 324 488 31 25 MAD 1BH

-0.85 324 489 31 25 0.69 SAN 1BH

-3.59

-3.48 0.11 325 490 1

26 SAD 1BH

-0.95 325 491 1

26 3.19 SAN 1BH

-3.81

-3.65 0.16 326 492 2

26 MAD 1BH

-0.91 327 493 3

26 MAD 1BH

-0.85 328 494 11 26 MAD 1BH

-0.90 329 495 14 26 SAD 1BH

-1.02 330 496 16 26 SAD 1BH

-1.26 331 497 21 26 SAD 1BH

-1.02 332 498 22 26 SAD 1BH

-1.22 333 499 24 26 SAD 1BH

-0.85 333 500 24 26 3.05 SAN 1BH

-3.64

-3.53 0.11 334 501 25 26 SAD 1BH

-1.13 334 502 25 26 1.67 SAN 1BH

-3.68

-3.58 0.10 335 503 27 26 SAD 1BH

-0.85 336 504 28 26 SAD 1BH

-0.93 336 505 28 26 1.88 SAN 1BH

-3.69

-3.62 0.07 337 506 30 26 2.83 MAN 1BH

-3.74

-3.63 0.11 337 507 30 26 SAD 1BH

-0.90 338 508 33 26 SAD 1BH

-0.90 339 509 34 26 SAD 1BH

-1.10 340 510 38 26 MAD 1BH

-0.88 341 511 1

27 SAD 1BH

-1.07 341 512 1

27 3.17 SAN 1BH

-3.76

-3.68 0.08 342 513 2

27 SAD 1BH

-1.20 343 514 3

27 SAD 1BH

-1.46 344 515 4

27 MAD 1BH

-0.93 344 516 4

27 6.31 MAN 1BH

-0.80

-0.19 0.61 345 517 6

27 SAD 1BH

-0.87 346 518 11 27 MAD 1BH

-0.85 347 519 13 27 SAD 1BH

-1.28 348 520 14 27 0.61 MAN 1BH

-0.49

-0.32 0.17 348 521 14 27 SAD 1BH

-0.92 349 522 16 27 SAD 1BH

-1.21 350 523 17 27 2.33 MAN 1BH

-1.22

-1.04 0.18 351 524 18 27 SAD 1BH

-1.33 352 525 19 27 MAD 1BH

-0.88 353 526 20 27 MAD 1BH

-0.84 354 527 22 27 SAD 1BH

-0.78 355 528 23 27 1 MAD 1BH

-0.84 Page 35 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 356 529 24 27 SAD 1BH

-0.95 357 530 25 27 SAD 1BH

-0.99 358 531 31 27 MAD 1BH

-0.79 359 532 33 27 1.31 MAN 1BH

-3.62

-3.49 0.13 359 533 33 27 SAD 1BH

-0.85 360 534 34 27 MAD 1BH

-0.85 361 535 37 27 MAD 1BH

-0.90 362 536 38 27 SAD 1BH

-0.82 363 537 39 27 SAD 1BH

-0.78 364 538 2

28 MAD 1BH

-0.88 365 539 4

28 SAD 1BH

-0.86 366 540 5

28 1.19 MAN 1BH

-1.21

-1.05 0.16 367 541 6

28 SAD 1BH

-1.30 368 542 10 28 SAD 1BH

-1.30 369 543 24 28 SAD 1BH

-0.92 370 544 28 28 2.16 MAN 1BH

-3.65

-3.56 0.09 370 545 28 28 SAD 1BH

-1.18 371 546 30 28 SAD 1BH

-1.15 371 547 30 28 4.09 SAN 1BH

-3.63

-3.46 0.17 372 548 31 28 MAD 1BH

-1.19 372 549 31 28 3.25 MAN 11BH

-3.70

-3.60 0.10 373 550 32 28 SAD 1BH

-0.96 373 551 32 28 4.32 SAN 1BH

-3.75

-3.66 0.09 374 552 34 28 MAD 1BH

-0.78 375 553 35 28 SAD 1BH

-0.85 376 554 36 28 SAD 1BH

-0.82 377 555 2

29 MAD 1BH

-1.04 378 556 3

29 SAD 11BH

-0.98 379 557 5

29 SAD 1BH

-0.89 380 558 8

29 MAD 1BH

-1.27 381 559 9

29 SAD 1BH

-0.90 382 560 17 29 MAD 1BH

-0.85 383 561 21 29 MAD 1BH

-0.85 384 562 24 29 MAD 1BH

-0.77 385 563 25 29 SAD 1BH

-1.26 386 564 28 29 MAD 1BH

-1.16 387 565 32 29 MAD 1BH

-0.75 387 566 32 29 2.41 MAN 1BH

-3.68

-3.58 0.10 388 567 36 29 MAD 1BH

-0.89 389 568 38 29 SAD 1BH

-0.84 390 569 1

30 MAD 1BH

-1.42 391 570 2

30 MAD 1BH

-0.88 392 571 5

30 SAD 1BH

-0.94 392 572 5

30 0.96 SAN 1BH

-3.80

-3.74 0.06 393 573 10 30 SAD 1BH

-1.12 394 574 19 30 MAD 1BH

-0.81 395 575 25 30 MAD 1BH

-0.86 396 576 26 30 SAD 1BH

-0.79 Page 36 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 397 577 28 30 MAD 1BH

-0.85 398 578 29 30 MAD 1BH

-0.88 399 579 30 30 MAD 1BH

-0.85 399 580 30 30 0.68 SAN 1BH

-3.92

-3.85 0.07 400 581 33 30 MAD 1BH

-0.80 400 582 33 30 2.28 SAN 1BH

-3.68

-3.54 0.14 401 583 35 30 MAD 1BH

-0.87 402 584 36 30 MAD 11BH

-1.00 403 585 38 30 SAD 1BH

-1.13 404 586 40 30 MAD 1BH

-0.82 405 587 42 30 SAD 11BH

-0.88 406 588 1

31 SAD 1BH

-1.21 406 589 1

31 4.23 SAN 1BH

-3.71

-3.59 0.12 407 590 2

31 MAD 1BH

-1.00 408 591 3

31 0.73 MAN 1BH

-1.22

-1.13 0.09 409 592 7

31 MAD 1BH

-1.41 410 593 8

31 SAD 1BH

-1.09 411 594 9

31 MAD 1BH

-0.83 412 595 31 31 SAD 1BH

-0.90 413 596 32 31 SAD 1BH

-1.36 414 597 35 31 SAD 1BH

-0.90 415 598 36 31 SAD 1BH

-0.82 416 599 38 31 MAD 1BH

-0.88 417 600 41 31 SAD 1BH

-0.89 418 601 42 31 SAD 1BH

-0.76 419 602 2

32 SAD 1BH

-0.87 420 603 4

32 SAD 1BH

-0.83 421 604 7

32 MAD 1BH

-1.04 422 605 9

32 MAD 1BH

-0.90 423 606 20 32 0.48 MAN 1BH

-0.82

-0.19 0.63 424 607 22 32 MAD 11BH

-0.88 425 608 27 32 SAD 1BH

-1.27 426 609 28 32 SAD 1 BH

-0.87 427 610 33 32 SAD 1BH

-1.26 428 611 35 32 MAD 1BH

-1.26 429 612 36 32 MAD 1BH

-0.90 430 613 37 32 MAD 1BH

-0.86 431 614 38 32 SAD 1BH

-0.82 432 615 39 32 MAD 1BH

-0.81 433 616 1

33 SAD 1BH

-0.85 433 617 1

33 3.55 SAN 1BH

-3.73

-3.53 0.20 434 618 11 33 SAD 1BH

-1.24 434 619 11 33 1.76 SAN 1BH

-3.71

-3.65 0.06 435 620 23 33 SAD 11BH

-0.88 436 621 25 33 SAD 1BH

-0.80 437 622 26 33 SAD 1BH

-0.85 438 623 28 33 SAD 11BH

-0.74 439 624 31 33 SAD 1BH

-0.84 Page 37 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 439 625 31 33 1.92 SAN 1BH

-3.70

-3.60 0.10 440 626 33 33 MAD 1BH

-1.26 440 627 33 33 1.49 MAN 1BH

-3.68

-3.61 0.07 441 628 34 33 MAD 1BH

-0.80 442 629 36 33 SAD 11BH

-0.82 443 630 37 33 MAD 1BH

-1.38 444 631 38 33 MAD 1BH

-0.79 445 632 1

34 5.16 MAN 1BH

-3.70

-3.48 0.22 445 633 1

34 SAD 1BH

-0.85 446 634 4

34 SAD 1BH

-1.14 447 635 5

34 MAD 1BH

-1.00 448 636 6

34 MAD 11BH

-0.86 449 637 9

34 SAD 1BH

-0.92 450 638 24 34 MAD 11BH

-0.89 451 639 31 34 MAD 1BH

-0.79 452 640 33 34 1.60 MAN 1BH

-3.74

-3.66 0.08 452 641 33 34 SAD 1BH

-1.26 453 642 35 34 MAD 1BH

-0.81 454 643 36 34 SAD 11BH

-0.98 455 644 37 34 MAD 1BH

-1.38 456 645 41 34 MAD 1BH

-1.22 457 646 43 34 SAD 1BH

-0.96 458 647 3

35 MAD 1BH

-0.81 459 648 9

35 MAD 1BH

-0.85 460 649 11 35 SAD 1BH

-1.28 461 650 12 35 SAD 1BH

-1.29 462 651 13 35 4.45 MAN 1BH

-1.26

-1.09 0.17 463 652 24 35 SAD 1BH

-1.25 464 653 25 35 SAD 1BH

-1.00 464 654 25 35 0.86 SAN 1BH

-3.62

-3.58 0.04 465 655 26 35 MAD 1BH

-0.77 466 656 29 35 SAD 1BH

-1.29 467 657 30 35 SAD 1BH

-1.31 468 658 34 35 SAD 1BH

-0.72 469 659 36 35 SAD 1BH

-0.79 470 660 37 35 SAD 1BH

-1.45 471 661 40 35 SAD 1BH

-0.76 472 662 2

36 SAD 1BH

-1.00 473 663 3

36 SAD 1BH

-1.30 474 664 10 36 SAD 1BH

-1.35 475 665 11 36 MAD 1BH

-0.86 476 666 12 36 SAD 1BH

-1.55 476 667 12 36 0.45 SAN 1BH

-3.65

-3.58 0.07 477 668 13 36 SAD 1BH

-1.01 478 669 20 36 1.96 MAN 1BH

-0.94

-0.79 0.15 479 670 21 36 SAD 1BH

-0.87 480 671 22 36 1.31 SAN 1BH

-1.14

-1.02 0.12 481 672 24 36 MAD 1BH

-0.80 Page 38 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 482 673 27 36 1.00 MAI 11BH

-3.82

-3.76 0.06 482 674 27 36 SAD 1BH

-1.26 483 675 28 36 SAD 1BH

-1.00 484 676 32 36 SAD 1BH

-0.77 485 677 36 36 SAD 11BH

-0.90 486 678 37 36 SAD 1BH

-1.00 487 679 38 36 MAD 1BH

-1.22 488 680 39 36 SAD 1BH

-0.79 489 681 2

37 SAD 1BH

-0.84 490 682 3

37 MAD 1BH

-0.68 491 683 4

37 SAD 1BH

-1.33 492 684 7

37 SAD 11BH

-0.82 493 685 9

37 SAD 1BH

-0.90 494 686 10 37 SAD 1BH

-0.90 495 687 11 37 MAD 1BH

-0.92 496 688 20 37 SAD 1BH

-0.80 497 689 23 37 SAD 1BH

-0.85 498 690 27 37 MAD 1BH

-1.25 498 691 27 37 4.98 MAN 1BH

-3.73

-3.60 0.13 499 692 31 37 SAD 1BH

-0.98 500 693 32 37 SAD 1BH

-1.20 501 694 34 37 SAD 1BH

-1.24 502 695 36 37 MAD 1BH

-1.27 503 696 37 37 SAD 1BH

-0.90 504 697 42 37 MAD 1BH

-0.74 505 698 1

38 MAD 1BH

-1.25 506 699 2

38 SAD 1BH

-1.02 507 700 5

38 SAD 1BH

-1.35 508 701 8

38 MAD 1BH

-0.93 509 702 10 38 SAD 1BH

-0.96 510 703 11 38 SAD 1BH

-0.88 510 704 11 38 0.27 SAN 1BH

-0.73

-0.01 0.72 511 705 12 38 SAD 1BH

-1.50 512 706 13 38 2.03 SAN 1BH

-3.73

-3.66 0.07 512 707 13 38 2.60 SAN 1BH

-1.31

-1.10 0.21 513 708 21 38 MAD 1BH

-0.84 514 709 23 38 MAD 1BH

-0.91 515 710 25 38 MAD 1BH

-0.74 516 711 26 38 1.54 MAN 1BH

-3.71

-3.62 0.09 516 712 26 38 SAD 1BH

-1.03 517 713 27 38 MAD 1BH

-0.99 518 714 28 38 SAD 1BH

-0.75 519 715 29 38 MAD 1BH

-0.85 520 716 32 38 SAD 1BH

-1.40 521 717 33 38 MAD 1BH

-0.83 522 718 36 38 MAD 1BH

-0.85 523 719 37 38 MAD 1BH

-1.22 524 720 39 38 MAD 1BH

-0.85 Page 39 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 525 721 40 38 SAD 1BH

-0.84 526 722 1

39 MAD 1BH

-0.87 527 723 2

39 SAD 1BH

-1.36 527 724 2

39 0.60 SAN 1BH

-3.75

-3.67 0.08 528 725 3

39 SAD 1BH

-0.85 529 726 7

39 SAD 1BH

-1.35 530 727 9

39 SAD 1BH

-1.24 531 728 11 39 MAD 1BH

-0.89 532 729 19 39 SAD 1BH

-1.29 533 730 24 39 SAD 1BH

-1.13 534 731 26 39 SAD 1BH

-1.22 535 732 28 39 MAD 1BH

-0.80 536 733 29 39 SAD 1BH

-0.95 537 734 32 39 MAD 1BH

-1.23 538 735 35 39 SAD 1BH

-1.13 539 736 40 39 MAD 1BH

-0.93 540 737 42 39 MAD 1BH

-0.79 541 738 7

40 MAD 1BH

-0.83 542 739 9

40 SAD 1BH

-1.27 543 740 11 40 SAD 1BH

-0.80 544 741 13 40 MAD 1BH

-1.56 545 742 20 40 SAD 1BH

-1.00 546 743 21 40 MAD 1BH

-1.26 547 744 24 40 MAD 1BH

-1.00 548 745 25 40 SAD 1BH

-0.85 549 746 26 40 MAD 1BH

-1.28 550 747 27 40 SAD 1BH

-0.73 551 748 28 40 2.10 MAN 1BH

-3.58

-3.52 0.06 551 749 28 40 SAD 1BH

-0.83 552 750 31 40 MAD 1BH

-1.10 553 751 32 40 MAD 1BH

-1.23 553 752 32 40 3.94 MAN 1BH

-1.15

-0.89 0.26 554 753 33 40 SAD 1BH

-1.20 555 754 34 40 MAD 1BH

-0.81 556 755 40 40 MAD 1BH

-0.82 557 756 1

41 SAD 1BH

-1.30 557 757 1

41 6.80 SAN 1BH

-3.61

-3.47 0.14 558 758 2

41 SAD 1BH

-0.93 559 759 4

41 5.05 MAN 1BH

-1.25

-1.08 0.17 560 760 5

41 1.84 MAN 1BH

-1.22

-1.11 0.11 561 761 8

41 MAD 1BH

-1.27 562 762 11 41 SAD 1BH

-1.37 563 763 14 41 0.37 MAN 1BH

-0.87

-0.13 0.74 564 764 20 41 SAD 1BH

-0.87 565 765 21 41 SAD 1BH

-0.86 566 766 22 41 MAD 1BH

-0.90 567 767 23 41 3.21 MAN 1BH

-3.69

-3.54 0.15 567 768 23 41 SAD 1BH

-0.98 Page 40 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 568 769 26 41 MAD 1BH

-0.88 568 770 26 41 3.42 SAN 1BH

-3.73

-3.59 0.14 569 771 28 41 1.12 MAN 1BH

-3.95

-3.86 0.09 569 772 28 41 SAD 1BH

-1.29 570 773 30 41 SAD 1BH

-0.86 571 774 31 41 SAD 1BH

-1.00 572 775 32 41 SAD 1BH

-0.95 573 776 34 41 SAD 1BH

-1.02 574 777 1

42 SAD 1BH

-1.36 574 778 1

42 1.64 SAN 1BH

-3.72

-3.62 0.10 575 779 4

42 SAD 1BH

-1.30 576 780 5

42 MAD 1BH

-0.92 577 781 11 42 SAD 1BH

-1.05 578 782 12 42 MAD 1BH

-1.17 579 783 20 42 SAD 1BH

-1.30 580 784 23 42 1 SAD 1BH

-0.88 581 785 24 42 SAD 1BH

-1.25 582 786 25 42 3.33 MAN 1BH

-3.73

-3.63 0.10 582 787 25 42 SAD 1BH

-0.85 583 788 28 42 SAD 1BH

-1.05 584 789 29 42 SAD 1BH

-0.92 585 790 31 42 MAD 1BH

-0.88 586 791 33 42 MAD 1BH

-0.91 587 792 35 42 MAD 1BH

-0.92 588 793 2

43 SAD 1BH

-0.91 589 794 4

43 MAD 1BH

-0.85 590 795 19 43 MAD 1BH

-0.88 591 796 21 43 SAD 1BH

-1.23 592 797 22 43 MAD 1BH

-0.84 593 798 25 43 MAD 1BH

-0.90 594 799 26 43 SAD 1BH

-0.93 595 800 30 43 SAD 1BH

-0.80 596 801 34 43 MAD 1BH

-0.89 597 802 35 43 SAD 1BH

-1.18 598 803 36 43 MAD 1BH

-1.00 599 804 42 43 SAD 1BH

-0.99 600 805 1

44 MAD 1BH

-1.32 600 806 1

44 4.47 SAN 1BH

-3.74

-3.66 0.08 601 807 3

44 SAD 1BH

-1.30 602 808 4

44 MAD 1BH

-1.25 602 809 4

44 0.67 SAN 1BH

-3.78

-3.71 0.07 603 810 5

44 MAD 1BH

-0.85 604 811 6

44 SAD 1BH

-1.30 605 812 7

44 SAD 1BH

-0.85 606 813 13 44 SAD 1BH

-0.93 607 814 15 44 SAD 1BH

-0.89 608 815 22 44 SAD 1BH

-0.90 609 816 23 44 MAD 1BH

-0.86 Page 41 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 610 817 25 44 MAD 1BH

-0.99 610 818 25 44 1.03 SAN 1BH

-3.74

-3.65 0.09 611 819 26 44 SAD 1BH

-0.90 612 820 29 44 MAD 1BH

-0.97 613 821 31 44 MAD 1BH

-1.02 614 822 32 44 MAD 1BH

-1.00 615 823 33 44 MAD 1BH

-0.90 616 824 40 44 SAD 1BH

-0.94 617 825 4

45 SAD 1BH

-0.86 618 826 6

45 SAD 1BH

-1.18 619 827 7

45 SAD 1BH

-0.90 620 828 8

45 SAD 1BH

-0.89 621 829 10 45 MAD 1BH

-0.89 622 830 11 45 SAD 1BH

-0.80 623 831 15 45 MAD 1BH

-1.00 624 832 16 45 SAD 1BH

-1.30 625 833 18 45 MAD 1BH

-1.23 625 834 18 45 1.02 MAN 1BH

-0.49

-0.20 0.29 626 835 20 45 MAD 1BH

-0.97 627 836 21 45 SAD 1BH

-1.22 628 837 22 45 MAD 11BH

-0.97 629 838 23 45 SAD 1BH

-1.33 630 839 24 45 MAD 1BH

-0.86 630 840 24 45 0.45 SAN 1BH

-3.78

-3.72 0.06 631 841 28 45 MAD 1BH

-0.96 632 842 32 45 MAD 1BH

-1.26 633 843 34 45 SAD 1BH

-1.07 634 844 5

46 SAD 1BH

-1.35 635 845 7

46 SAD 1BH

-1.43 636 846 17 46 SAD 1BH

-1.25 637 847 19 46 6.58 MAN 1BH

-3.59

-3.35 0.24 637 848 19 46 SAD 1BH

-1.18 638 849 24 46 MAD 1BH

-1.28 638 850 24 46 9.54 MAN 1BH

-0.67

-0.03 0.64 638 851 24 46 3.54 SAN 1BH

-3.64

-3.48 0.16 639 852 26 46 MAD 1BH

-0.98 640 853 27 46 2.59 MAN 1BH

-3.73

-3.63 0.10 640 854 27 46 SAD 11BH

-0.85 641 855 28 46 MAD 1BH

-1.28 641 856 28 46 1.99 MAN 1BH

-3.57

-3.49 0.08 642 857 34 46 MAD 1BH

-1.27 643 858 40 46 SAD 11BH

-0.93 644 859 1

47 9.68 MAN 1BH

-3.65

-3.38 0.27 644 860 1

47 SAD 1BH

-1.00 645 861 2

47 SAD 1BH

-0.87 646 862 3

47 MAD 1BH

-1.41 647 863 11 47 MAD 1BH

-1.18 648 864 17 47 SAD 1BH

-0.99 Page 42 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 649 865 19 47 MAD 1BH

-1.28 649 866 19 47 3.90 MAN 1BH

-3.69

-3.51 0.18 650 867 22 47 MAD 1BH

-1.27 651 868 25 47 MAD 1BH

-0.89 652 869 26 47 SAD 1BH

-1.25 653 870 27 47 SAD 1BH

-1.47 654 871 29 47 MAD 1BH

-0.99 655 872 30 47 MAD 1BH

-0.82 656 873 31 47 SAD 1BH

-1.31 657 874 35 47 1.50 MAN 1BH

-3.69

-3.53 0.16 657 875 35 47 SAD 1BH

-1.04 658 876 39 47 SAD 1BH

-0.84 659 877 1

48 6.68 MAN 1BH

-3.75

-3.45 0.30 659 878 1

48 SAD 1BH

-1.29 660 879 3

48 SAD 1BH

-1.34 661 880 5

48 SAD 1BH

-1.36 662 881 6

48 0.75 SAN 1BH

-1.18

-1.10 0.08 663 882 9

48 SAD 1BH

-1.36 664 883 13 48 MAD 1BH

-0.94 665 884 15 48 MAD 1BH

-0.96 665 885 15 48 1.37 MAN 1BH

-3.70

-3.66 0.04 666 886 16 48 SAD 1BH

-0.89 666 887 16 48 1.41 SAN 1BH

-3.66

-3.39 0.27 667 888 18 48 2.83 MAN 1BH

-0.49

-0.22 0.27 667 889 18 48 SAD 1BH

-1.34 668 890 20 48 MAD 1BH

-1.24 669 891 24 48 MAD 1BH

-0.85 670 892 25 48 SAD 1BH

-0.90 671 893 30 48 MAD 1BH

-1.16 672 894 31 48 MAD 1BH

-0.90 673 895 34 48 SAD 1BH

-0.85 674 896 36 48 MAD 1BH

-0.83 675 897 39 48 SAD 1BH

-0.90 676 898 1

49 MAD 1BH

-0.91 676 899 1

49 3.64 SAN 1BH

-3.72

-3.58 0.14 677 900 3

49 SAD 1BH

-1.36 678 901 4

49 MAD 1BH

-1.39 679 902 7

49 MAD 1BH

-1.39 680 903 9

49 SAD 1BH

-0.90 681 904 11 49 MAD 1BH

-1.36 682 905 20 49 MAD 1BH

-0.92 683 906 22 49 SAD 1BH

-0.86 684 907 23 49 SAD 1BH

-0.88 685 908 24 49 SAD 1BH

-0.87 686 909 27 49 MAD 1BH

-0.86 687 910 28 49 SAD 1BH

-1.33 688 911 29 49 MAD 1BH

-1.26 689 912 30 49 MAD 1BH

-0.91 Page 43 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 690 913 31 49 SAD 1BH

-1.26 691 914 36 49 SAD 1BH

-1.26 692 915 38 49 SAD 1BH

-0.81 693 916 40 49 SAD 1BH

-0.91 694 917 1

50 SAD 1BH

-0.90 694 918 1

50 2.18 SAN 11BH

-3.54

-3.42 0.12 695 919 3

50 SAD 1BH

-0.90 696 920 6

50 SAD 1BH

-1.41 697 921 9

50 MAD 1BH

-1.02 698 922 12 50 3.82 MAN 1BH

-1.24

-1.13 0.11 698 923 12 50 4.53 MAN 1BH

-0.55

-0.28 0.27 699 924 15 50 MAD 1BH

-0.89 700 925 19 50 MAD 1BH

-0.90 701 926 21 50 SAD 1BH

-1.30 702 927 22 50 SAD 1BH

-1.27 703 928 26 50 MAD 11BH

-0.92 704 929 28 50 SAD 1BH

-1.27 705 930 30 50 MAD 1BH

-1.10 706 931 33 50 MAD 1BH

-0.90 707 932 36 50 SAD 11BH

-0.77 708 933 1

51 1.87 SAN 1BH

-1.17

-1.09 0.08 709 934 2

51 SAD 1BH

-1.37 710 935 3

51 SAD 1BH

-1.07 711 936 6

51 MAD 1BH

-1.27 712 937 11 51 SAD 1BH

-1.75 713 938 12 51 MAD 1BH

-1.30 714 939 13 51 SAD 1BH

-1.41 715 940 16 51 MAD 1BH

-1.28 716 941 17 51 SAD 1BH

-0.89 717 942 20 51 MAD 1BH

-0.92 718 943 21 51 SAD 1BH

-1.16 719 944 23 51 MAD 1BH

-0.88 720 945 26 51 SAD 1BH

-1.34 721 946 27 51 MAD 1BH

-0.87 722 947 28 51 MAD 1BH

-0.92 723 948 29 51 MAD 1BH

-1.30 723 949 29 51 0.83 SAN 1BH

-3.75

-3.65 0.10 724 950 30 51 MAD 1BH

-0.93 725 951 32 51 MAD 1BH

-1.23 726 952 33 51 MAD 11BH

-0.92 727 953 34 51 MAD 11BH

-0.84 728 954 35 51 SAD 1BH

-0.86 729 955 36 51 SAD 1BH

-0.88 730 956 38 51 SAD 1BH

-1.32 731 957 39 51 MAD 1BH

-0.89 732 958 42 51 SAD 1BH

-0.88 733 959 5

52 MAD 1BH

-1.38 734 960 6

52 MAD 1BH

-0.96 Page 44 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 735 961 9

52 SAD 1BH

-1.34 736 962 10 52 SAD 11BH

-1.36 737 963 13 52 SAD 1BH

-1.65 738 964 15 52 MAD 1BH

-1.31 739 965 16 52 SAD 1BH

-0.88 740 966 17 52 SAD 1BH

-0.99 740 967 17 52 0.89 SAI 1BH

-0.52

-0.30 0.22 741 968 18 52 SAD 1BH

-0.90 742 969 19 52 MAD 1BH

-1.33 743 970 20 52 MAD 1BH

-0.89 743 971 20 52 1.95 SAN 1BH

-3.69

-3.65 0.04 744 972 21 52 SAD 11BH

-0.74 745 973 23 52 MAD 1BH

-0.91 745 974 23 52 0.61 SAN 1BH

-3.81

-3.75 0.06 746 975 24 52 MAD 1 BH

-0.83 746 976 24 52 1.16 SAN 1BH

-3.81

-3.75 0.06 747 977 25 52 SAD 1BH

-1.36 747 978 25 52 1.48 SAN 1BH

-3.86

-3.82 0.04 748 979 26 52 SAD 1 BH

-0.87 749 980 27 52 MAD 1BH

-0.94 750 981 28 52 MAD 1BH

-0.89 751 982 30 52 MAD 1BH

-1.34 752 983 33 52 SAD 1BH

-1.25 753 984 36 52 SAD 1BH

-1.05 754 985 37 52 SAD 1BH

-1.06 755 986 1

53 MAD 1BH

-1.43 755 987 1

53 0.91 SAI 1BH

-3.79

-3.69 0.10 756 988 2

53 SAD 1BH

-0.93 757 989 3

53 MAD 1BH

-1.40 758 990 4

53 2.16 MAN 1BH

-1.29

-1.16 0.13 759 991 6

53 MAD 1BH

-1.04 760 992 8

53 MAD 11BH

-0.85 761 993 11 53 SAD 1BH

-1.42 762 994 13 53 MAD 1BH

-1.33 763 995 14 53 MAD 1BH

-1.50 764 996 15 53 MAD 1BH

-0.90 765 997 16 53 SAD 1BH

-1.00 766 998 17 53 MAD IBH

-0.90 767 999 18 53 SAD 1BH

-1.10 768 1000 19 53 MAD 1BH

-0.91 769 1001 20 53 SAD 1BH

-1.30 770 1002 21 53 SAD 1BH

-0.95 771 1003 22 53 SAD 1BH

-0.85 772 1004 24 53 MAD 1BH

-0.85 773 1005 25 53 MAD 1BH

-1.05 774 1006 27 53 MAD 1BH

-0.88 774 1007 27 53 2.62 SAN 1BH

-3.75

-3.68 0.07 775 1008 28 53 SAD 1BH

-0.85 Page 45 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 776 1009 31 53 MAD 1BH

-0.84 777 1010 32 53 SAD 1BH

-0.89 778 1011 35 53 SAD 1BH

-0.84 779 1012 37 53 MAD 1BH

-0.81 780 1013 38 53 MAD 1BH

-0.85 781 1014 42 53 SAD 1BH

-0.89 782 1015 1

54 0.66 SAI 1BH

-3.83

-3.77 0.06 782 1016 1

54 1.00 SAN 1BH

-1.29

-1.18 0.11 783 1017 2

54 SAD 1BH

-1.48 784 1018 3

54 MAD 1BH

-1.06 785 1019 4

54 MAD 1BH

-0.90 786 1020 5

54 SAD 1BH

-1.09 787 1021 7

54 2.09 MAN 1BH

-1.34

-1.14 0.20 788 1022 9

54 MAD 1BH

-0.99 789 1023 10 54 SAD 1BH

-0.92 790 1024 13 54 MAD 11BH

-1.38 791 1025 14 54 SAD 1BH

-1.37 792 1026 16 54 SAD 1BH

-0.73 793 1027 17 54 MAD 1BH

-1.16 794 1028 18 54 SAD 1BH

-1.21 795 1029 20 54 SAD 1BH

-1.32 796 1030 23 54 MAD 1BH

-0.85 797 1031 24 54 SAD 1BH

-0.82 798 1032 27 54 SAD 1BH

-1.31 799 1033 31 54 MAD 1BH

-0.89 800 1034 33 54 MAD 1BH

-0.95 801 1035 3

55 SAD 1BH

-1.06 802 1036 5

55 MAD 1BH

-0.93 803 1037 6

55 MAD 1BH

-0.92 804 1038 7

55 SAD 11BH

-1.58 805 1039 12 55 SAD 11BH

-1.40 806 1040 15 55 MAD 1BH

-1.33 807 1041 17 55 SAD 1BH

-1.23 808 1042 18 55 MAD 1BH

-0.85 809 1043 19 55 MAD 11BH

-0.90 810 1044 20 55 MAD 1BH

-1.00 811 1045 22 55 SAD 1BH

-1.23 812 1046 24 55 MAD 1BH

-1.01 813 1047 26 55 MAD 1BH

-0.90 814 1048 27 55 SAD 1BH

-1.26 815 1049 29 55 SAD 1BH

-1.30 815 1050 29 55 1.80 SAN 1BH

-3.51

-3.39 0.12 816 1051 31 55 SAD 1BH

-0.85 817 1052 39 55 SAD 1BH

-0.88 818 1053 40 55 SAD 1BH

-0.88 819 1054 1

56 MAD 1BH

-1.00 820 1055 2

56 MAD 1BH

-1.23 820 1056 2

56 5.43 MAN 1BH

-0.49

-0.15 0.34 Page 46 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 821 1057 3

56 MAD 1BH

-0.99 822 1058 9

56 MAD 1BH

-1.27 823 1059 13 56 SAD 1BH

-0.85 824 1060 14 56 SAD 1BH

-1.46 824 1061 14 56 0.56 SAN 1BH

-0.50

-0.39 0.11 825 1062 15 56 MAD 1BH

-0.96 826 1063 17 56 MAD 1BH

-0.92 827 1064 18 56 SAD 11BH

-1.35 827 1065 18 56 1.29 SAN 11BH

-0.43

-0.26 0.17 828 1066 19 56 SAD 1BH

-0.99 829 1067 20 56 SAD 1BH

-1.28 830 1068 22 56 SAD 1BH

-1.35 831 1069 27 56 SAD 1BH

-0.88 832 1070 29 56 SAD 1BH

-1.31 833 1071 30 56 MAD 1BH

-0.85 834 1072 31 56 MAD 1BH

-0.86 835 1073 32 56 MAD 1BH

-0.85 836 1074 34 56 MAD 1BH

-0.85 837 1075 36 56 1 MAD 1BH

-1.00 838 1076 43 56 SAD 1BH

-1.05 839 1077 2

57 MAD 1BH

-1.43 840 1078 3

57 MAD 1BH

-1.29 841 1079 5

57 SAD 1BH

-1.50 842 1080 12 57 MAD 1BH

-1.38 843 1081 15 57 MAD 1BH

-1.37 843 1082 15 57 1.04 SAN 1BH

-3.75

-3.61 0.14 844 1083 18 57 MAD 1BH

-1.30 845 1084 19 57 SAD 1BH

-1.28 846 1085 25 57 SAD 1BH

-1.31 846 1086 25 57 1.48 SAN 1BH

-3.80

-3.72 0.08 847 1087 27 57 SAD 1BH

-1.11 847 1088 27 57 1.05 SAN 1BH

-3.63

-3.55 0.08 848 1089 29 57 SAD 1BH

-0.85 849 1090 32 57 MAD 1BH

-0.85 850 1091 34 57 MAD 1BH

-0.85 851 1092 36 57 MAD 1BH

-0.99 852 1093 40 57 MAD 1BH

-0.89 853 1094 3

58 SAD 1BH

-1.00 854 1095 4

58 MAD 1BH

-1.41 855 1096 12 58 SAD 1BH

-0.90 856 1097 14 58 1.66 MAN 1BH

-1.26

-1.20 0.06 857 1098 17 58 SAD 1BH

-1.28 858 1099 18 58 SAD 1BH

-1.32 859 1100 19 58 MAD 1BH

-0.95 860 1101 22 58 SAD 1BH

-0.85 861 1102 31 58 MAD 1BH

-1.40 862 1103 2

59 SAD 1BH

-1.00 863 1104 3

59 SAD 1BH

-1.29 Page 47 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 864 1105 6

59 MAD 1BH

-1.38 865 1106 7

59 MAD 1BH

-1.00 866 1107 8

59 5.83 MAN 1BH

-3.68

-2.30 1.38 866 1108 8

59 3.34 MAN 1BH

-1.32

-1.04 0.28 867 1109 9

59 MAD 1BH

-1.39 867 1110 9

59 4.21 MAN 1BH

-3.70

-2.28 1.42 868 1111 12 59 MAD 1BH

-1.44 869 1112 14 59 0.65 MAN 1BH

-1.32

-1.25 0.07 870 1113 17 59 SAD 1BH

-1.32 871 1114 18 59 MAD 1BH

-0.89 872 1115 19 59 MAD 1BH

-1.26 873 1116 20 59 SAD 1BH

-0.86 874 1117 21 59 SAD 1BH

-1.28 875 1118 23 59 SAD 1BH

-0.70 876 1119 26 59 SAD 1BH

-1.23 877 1120 28 59 SAD 1BH

-1.20 878 1121 29 59 SAD 1BH

-1.05 878 1122 29 59 1.54 SAN 1BH

-3.71

-3.64 0.07 879 1123 30 59 MAD 1BH

-0.92 880 1124 33 59 SAD 1BH

-1.39 881 1125 34 59 MAD 1BH

-0.87 882 1126 36 59 SAD 1BH

-0.92 883 1127 41 59 SAD 1BH

-0.86 884 1128 43 59 MAD 1BH

-0.90 885 1129 3

60 2.63 MAN 1BH

-1.25

-1.15 0.10 886 1130 8

60 MAD 1BH

-1.02 887 1131 12 60 MAD 1BH

-0.85 888 1132 13 60 MAD 1BH

-0.98 889 1133 15 60 SAD 1BH

-0.94 890 1134 17 60 MAD 1BH

-1.34 890 1135 17 60 1.35 SAN 1BH

-3.73

-3.70 0.03 891 1136 18 60 SAD 1BH

-1.29 892 1137 19 60 SAD 1BH

-1.30 893 1138 20 60 MAD 1BH

-1.10 894 1139 21 60 1.26 MAN 1BH

-3.70

-3.66 0.04 894 1140 21 60 SAD 1BH

-0.85 895 1141 23 60 MAD 1BH

-1.29 895 1142 23 60 4.50 MAN 1BH

-3.75

-3.54 0.21 896 1143 24 60 5.25 MAN 1BH

-3.64

-3.53 0.11 896 1144 24 60 SAD 1BH

-0.93 897 1145 25 60 MAD 1BH

-0.98 897 1146 25 60 3.44 SAN 1BH

-3.74

-3.49 0.25 898 1147 26 60 SAD 1BH

-0.90 899 1148 32 60 2.63 MAN 1BH

-3.84

-3.73 0.11 899 1149 32 60 SAD 1BH

-0.85 900 1150 33 60 5.20 MAN 1BH

-3.80

-3.59 0.21 900 1151 33 60 SAD 1BH

-0.85 901 1152 34 60 SAD 1BH

-0.84 Page 48 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 902 1153 36 60 SAD 1BH

-1.30 903 1154 38 60 MAD 1BH

-0.83 904 1155 42 60 MAD 1BH

-0.90 905 1156 43 60 MAD 1BH

-0.88 906 1157 8

61 SAD 1BH

-0.99 907 1158 10 61 1.07 MAN 1BH

-1.16

-1.08 0.08 908 1159 13 61 4.68 MAN 1BH

-0.66

-0.17 0.49 908 1160 13 61 SAD 1BH

-0.92 909 1161 14 61 MAD 1BH

-1.00 910 1162 18 61 SAD 1BH

-1.00 911 1163 19 61 SAD 1BH

-1.32 912 1164 20 61 SAD 1BH

-0.92 913 1165 22 61 2.68 MAN 1BH

-3.46

-3.37 0.09 913 1166 22 61 SAD 1BH

-0.85 914 1167 24 61 4.77 MAN 1BH

-3.71

-3.56 0.15 914 1168 24 61 SAD 1BH

-1.32 915 1169 27 61 MAD 1BH

-1.08 915 1170 27 61 6.61 MAN 1BH

-3.71

-3.50 0.21 916 1171 31 61 SAD 1BH

-3.50 916 1172 31 61 0.14 SVN 1BH

-1.50

-1.32 0.18 917 1173 32 61 SAD 1BH

-0.81 918 1174 34 61 MAD 1BH

-1.30 918 1175 34 61 1.27 SAN 1BH

-3.85

-3.78 0.07 919 1176 36 61 SAD 1BH

-0.89 920 1177 41 61 SAD 1BH

-0.85 921 1178 1

62 SAD 1BH

-1.41 921 1179 1

62 4.66 SAN 1BH

-3.74

-3.55 0.19 922 1180 3

62 SAD 1BH

-1.36 923 1181 6

62 SAD 1BH

-1.47 923 1182 6

62 1.22 SAN 1BH

-3.63

-3.51 0.12 924 1183 7

62 MAD 1BH

-0.96 925 1184 8

62 0.88 MAN 1BH

-1.32

-1.25 0.07 926 1185 9

62 MAD 1BH

-0.94 927 1186 11 62 MAD 1BH

-1.12 928 1187 12 62 1.20 SAN 1BH

-1.18

-1.05 0.13 929 1188 13 62 MAD 1BH

-1.34 930 1189 15 62 MAD 1BH

-1.00 930 1190 15 62 6.07 MAN 1BH

-3.71

-3.61 0.10 931 1191 17 62 MAD 1BH

-1.42 931 1192 17 62 4.76 SAN 1BH

-3.79

-3.65 0.14 932 1193 19 62 SAD 1BH

-0.88 933 1194 21 62 SAD 1BH

-1.10 934 1195 23 62 6.01 MAN 1BH

-3.75

-3.48 0.27 934 1196 23 62 SAD 1BH

-0.88 935 1197 27 62 MAD 1BH

-0.83 935 1198 27 62 2.15 SAN 1BH

-3.73

-3.55 0.18 936 1199 28 62 SAD 1BH

-0.91 936 1200 28 62 5.02 SAN 1BH

-3.77

-3.64 0.13 Page 49 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 937 1201 34 62 SAD 1BH

-0.86 938 1202 35 62 MAD 1BH

-1.35 939 1203 36 62 SAD 1BH

-1.35 940 1204 37 62 SAD 1BH

-0.90 941 1205 40 62 MAD 1BH

-0.90 942 1206 4

63 MAD 1BH

-0.93 943 1207 7

63 SAD 1BH

-1.40 944 1208 10 63 MAD 1BH

-0.92 944 1209 10 63 0.51 SAN 1BH

-3.75

-3.66 0.09 945 1210 11 63 1.12 MAN 1BH

-0.31

-0.18 0.13 945 1211 11 63 SAD 1BH

-1.39 946 1212 12 63 0.64 MAN 1BH

-0.45

-0.31 0.14 946 1213 12 63 SAD 1BH

-1.00 947 1214 13 63 MAD 1BH

-0.91 948 1215 15 63 SAD 1BH

-1.21 949 1216 17 63 MAD 1BH

-0.80 949 1217 17 63 1.31 SAN 1BH

-3.66

-3.62 0.04 950 1218 18 63 SAD 1BH

-0.89 951 1219 21 63 5.32 MAN 1BH

-3.70

-3.59 0.11 951 1220 21 63 SAD 1BH

-1.01 952 1221 23 63 SAD 1BH

-1.03 953 1222 24 63 MAD 1BH

-0.89 954 1223 26 63 4.54 MAN 1BH

-3.75

-3.66 0.09 954 1224 26 63 SAD 1BH

-0.81 955 1225 27 63 2.87 MAN 1BH

-3.75

-3.64 0.11 955 1226 27 63 SAD 1BH

-1.07 956 1227 29 63 MAD 1BH

-0.92 956 1228 29 63 4.19 MAN 1BH

-3.78

-3.56 0.22 957 1229 30 63 SAD 1BH

-0.91 957 1230 30 63 2.04 SAN 1BH

-3.65

-3.55 0.10 958 1231 31 63 MAD 1BH

-0.83 959 1232 34 63 5.07 MAN 1BH

-0.69

-0.14 0.55 959 1233 34 63 SAD 1BH

-1.32 960 1234 38 63 MAD 1BH

-0.85 961 1235 39 63 SAD 1BH

-0.90 962 1236 1

64 7.47 MAN 1BH

-3.75

-3.46 0.29 962 1237 1

64 SAD 1BH

-1.35 963 1238 4

64 1.88 MAN 1BH

-1.31

-1.21 0.10 964 1239 9

64 MAD 1BH

-1.03 965 1240 11 64 MAD 1BH

-1.59 965 1241 11 64 2.90 MAN 1BH

-0.65

-0.23 0.42 966 1242 13 64 MAD 1BH

-0.93 966 1243 13 64 0.74 MAN 1BH

-0.54

-0.26 0.28 967 1244 14 64 5.80 MAN 1BH

-3.65

-3.35 0.30 967 1245 14 64 1.10 MAN 1BH

-1.15

-1.04 0.11 968 1246 18 64 MAD 11BH

-0.87 968 1247 18 64 4.72 MAN 1BH

-3.58

-3.41 0.17 969 1248 19 64 SAD 1BH

-1.38 Page 50 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 970 1249 22 64 SAD 1BH

-1.35 971 1250 24 64 MAD 1BH

-0.87 971 1251 24 64 0.87 MAN 1BH

-3.69

-3.65 0.04 972 1252 26 64 2.68 MAN 1BH

-3.55

-3.39 0.16 972 1253 26 64 SAD 1BH

-0.90 973 1254 27 64 SAD 1BH

-0.84 974 1255 29 64 SAD 1BH

-0.80 974 1256 29 64 4.13 SAN 1BH

-3.77

-3.56 0.21 975 1257 35 64 SAD 1BH

-1.28 975 1258 35 64 1.16 SAN 1BH

-3.76

-3.70 0.06 976 1259 37 64 SAD 1BH

-1.34 977 1260 1

65 MAD 1BH

-1.25 977 1261 1

65 6.67 MAN 1BH

-3.75

-3.40 0.35 977 1262 1

65 1.75 MAN 1BH

-0.42

-0.22 0.20 978 1263 3

65 0.40 MAN 1BH

-0.95

-0.94 0.01 978 1264 3

65 2.61 SAN 1BH

-3.67

-3.59 0.08 979 1265 4

65 SAD 1BH

-1.40 979.

1266 4

65 2.48 SAN 1BH

-0.39

-0.27 0.12 980 1267 7

65 MAD 1BH

-1.00 980 1268 7

65 2.17 SAN 1BH

-3.61

-3.52 0.09 981 1269 9

65 MAD 1BH

-0.98 982 1270 13 65 MAD 1BH

-1.27 982 1271 13 65 4.15 MAN 1BH

-0.91

-0.25 0.66 983 1272 15 65 4.06 MAN 1BH

-3.67

-3.54 0.13 983 1273 15 65 SAD 1BH

-1.02 984 1274 17 65 MAD 1BH

-1.33 984 1275 17 65 2.86 SAN 1BH

-3.67

-3.60 0.07 985 1276 18 65 SAD 1BH

-1.36 985 1277 18 65 6.13 SAN IBH

-3.65

-3.43 0.22 986 1278 19 65 SAD 1BH

-0.84 986 1279 19 65 2.27 SAN 1BH

-3.58

-3.46 0.12 987 1280 20 65 6.76 MAN 1BH

-3.87

-3.66 0.21 987 1281 20 65 SAD 1BH

-1.00 988 1282 22 65 SAD 1BH

-0.76 989 1283 23 65 MAD 1BH

-0.92 989 1284 23 65 4.59 MAN 1BH

-3.82

-3.57 0.25 990 1285 26 65 MAD 1BH

-1.14 990 1286 26 65 5.49 MAN 1BH

-3.68

-3.54 0.14 991 1287 28 65 MAD 1BH

-0.83 991 1288 28 65 2.09 SAN 1BH

-3.60

-3.56 0.04 992 1289 30 65 MAD 1BH

-0.88 992 1290 30 65 5.70 MAN 1BH

-3.60

-3.50 0.10 993 1291 35 65 MAD 1BH

-0.90 994 1292 36 65 MAD 1BH

-0.91 995 1293 37 65 SAD 1BH

-0.86 996 1294 39 65 MAD 1BH

-0.87 997 1295 41 65 MAD 1BH

-0.88 998 1296 1

66 MAD 1BH

-0.93 Page 51 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 998 1297 1

66 8.22 MAN 1BH

-3.71

-3.38 0.33 999 1298 2

66 MAD 1BH

-0.89 999 1299 2

66 4.31 SAN 1BH

-3.67

-3.53 0.14 1000 1300 3

66 MAD 1BH

-1.30 1000 1301 3

66 1.40 SAN 1BH

-3.81

-3.69 0.12 1001 1302 4

66 MAD 1BH

-0.93 1001 1303 4

66 1.44 SAN 1BH

-3.79

-3.72 0.07 1002 1304 6

66 SAD 1BH

-1.22 1002 1305 6

66 3.62 SAN 1BH

-3.69

-3.56 0.13 1003 1306 8

66 MAD 1BH

-1.02 1004 1307 9

66 MAD 1BH

-0.92 1004 1308 9

66 1.20 SAN 1BH

-3.85

-3.76 0.09 1005 1309 11 66 SAD 1BH

-0.94 1006 1310 12 66 MAD 1BH

-1.33 1006 1311 12 66 3.52 MAN 1BH

-3.77

-3.67 0.10 1007 1312 14 66 2.32 MAN 1BH

-3.60

-3.53 0.07 1007 1313 14 66 SAD 1BH

-1.29 1008 1314 15 66 MAD 1BH

-1.41 1008 1315 15 66 5.81 MAN 1BH

-3.72

-3.48 0.24 1009 1316 19 66 SAD 1BH

-0.82 1010 1317 21 66 4.08 MAN 1BH

-3.77

-3.66 0.11 1010 1318 21 66 SAD 1BH

-1.24 1011 1319 22 66 SAD 1BH

-1.23 1012 1320 24 66 MAD 1BH

-1.18 1012 1321 24 66 4.38 SAN 1BH

-3.73

-3.63 0.10 1013 1322 28 66 SAD 1BH

-0.88 1014 1323 30 66 MAD 1BH 1-

-0.88 1014 1324 30 66 3.71 MAN 1BH 1-

-3.83

-3.73 0.10 1015 1325 33 66 MAD 1BH

-0.91 1015 1326 33 66 1.40 MAN 1BH

-3.89

-3.85 0.04 1016 1327 35 66 SAD 1BH

-1.35 1016 1328 35 66 0.60 SAN 1BH

-3.81

-3.75 0.06 1017 1329 36 66 MAD 1BH

-0.90 1018 1330 37 66 SAD 1BH

-0.89 1019 1331 41 66 MAD IBH

-0.89 1020 1332 1

67 MAD 1BH

-1.31 1020 1333 1

67 4.88 SAN 1BH

-3.72

-3.58 0.14 1021 1334 2

67 SAD 1BH

-1.42 1022 1335 3

67 MAD 1BH

-1.36 1023 1336 4

67 SAD 1BH

-1.17 1024 1337 6

67 SAD 1BH

-1.33 1025 1338 8

67 SAD 1BH

-0.86 1026 1339 9

67 MAD 1BH

-1.00 1027 1340 10 67 SAD 1BH

-0.94 1028 1341 11 67 SAD 1BH

-1.34 1029 1342 12 67 MAD 1BH

-1.36 1029 1343 12 67 1.53 SAN 1BH

-3.71

-3.64 0.07 1030 1344 13 67 0.27 MAN 1BH

-1.05

-0.89 0.16 Page 52 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1030 1345 13 67 1.05 SAN 1BH1-

-3.55

-3.48 0.07 1031 1346 15 67 MAD 1131-

-0.89 1031 1347 15 67 2.55 MAN 1131-

-3.66

-3.58 0.08 1032 1348 16 67 4.25 MAN 1131-

-3.73

-3.53 0.20 1033 1349 18 67 SAD 1131-

-1.00 1034 1350 19 67 SAD 1131-

-0.79 1035 1351 20 67 3.10 MAN 1131-

-3.74

-3.59 0.15 1035 1352 20 67 SAD 1B31-

-0.92 1036 1353 23 67 0.34 MAN 1131-

-1.35

-1.31 0.04 1036 1354 23 67 1.95 SAN 1 I131-

-3.62

-3.55 0.07 1037 1355 27 67 SAD 1131-

-0.90 1038 1356 28 67 SAD 1131-

-0.89 1039 1357 30 67 MAD 1131-

-1.25 1039 1358 30 67 5.44 SAN 1131-

-3.73

-3.63 0.10 1040 1359 34 67 MAD 1131-

-1.41 1041 1360 39 67 MAD 1131-

-0.84 1042 1361 2

68 MAD 1131-

-0.93 1042 1362 2

68 1.44 SAN 1131-

-3.62

-3.51 0.11 1043 1363 6

68 MAD 1131-

-0.92 1043 1364 6

68 3.92 SAN 113H

-3.66

-3.52 0.14 1044 1365 8

68 MAD 1131-

-0.85 1044 1366 8

68 3.93 MAN 1BH1-

-3.68

-3.58 0.10 1045 1367 9

68 MAD 1131-

-0.92 1046 1368 10 68 MAD 1131-

-0.85 1047 1369 12 68 4.60 MAN 1131-

-0.62

-0.17 0.45 1047 1370 12 68 SAD 1131-

-1.32 1048 1371 15 68 MAD 1131-

-1.44 1048 1372 15 68 2.97 SAN 1131-

-3.66

-3.59 0.07 1049 1373 17 68 MAD 113H

-1.25 1049 1374 17 68 1.33 SAN 1131-

-3.77

-3.67 0.10 1050 1375 18 68 MAD 1131-

-0.92 1050 1376 18 68 2.41 SAN 1131-

-3.63

-3.54 0.09 1051 1377 20 68 SAD 1131-

-0.85 1052 1378 21 68 SAD 1131-

-0.85 1052 11379 21 68 3.48 SAN 11B1-

-3.71

-3.61 0.10 1053 1380 24 68 2.52 MAN 1131-

-3.68

-3.60 0.08 1053 1381 24 68 SAD 1131-

-0.83 1054 1382 26 68 MAD 1131-

-0.85 1054 1383 26 68 1.79 SAN 113H-

-3.79

-3.75 0.04 1055 1384 30 68 MAD 1B31-

-0.89 1056 1385 36 68 SAD 1131-

-0.82 1057 1386 37 68 MAD 1131-

-1.05 1057 1387

.37 68 5.34 MAN 1131-

-0.58

-0.05 0.53 1058 1388 1

69 6.74 MAN 1131-

-3.75

-3.63 0.12 1058 1389 1

69 SAD 113H

-1.30 1059 1390 3

69 SAD 1BH1-

-1.01 1060 1391 4

69 MAD 1131-

-1.42 1061 1392 6

69 MAD 1131-

-1.73 Page 53 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1061 1393 6

69 SAD 1BH

-1.34 1061 1394 6

69 1.14 SAN 1BH

-3.62

-3.54 0.08 1062 1395 7

69 MAD 1BH

-1.74 1063 1396 8

69 SAD 1BH

-1.40 1063 1397 8

69 0.64 SAN 1BH

-1.99

-1.75 0.24 1064 1398 9

69 SAD 1BH

-0.85 1065 1399 14 69 SAD 1BH

-1.34 1066 1400 15 69 MAD 1BH

-1.47 1066 1401 15 69 4.34 MAN 1BH

-3.74

-3.63 0.11 1067 1402 17 69 SAD 1BH

-1.30 1067 1403 17 69 4.88 SAN 1BH

-3.74

-3.67 0.07 1068 1404 18 69 MAD 1BH

-0.85 1069 1405 21 69 SAD 1BH

-0.83 1070 1406 22 69 SAD 1BH

-0.85 1071 1407 23 69 SAD 1BH

-1.00 1072 1408 24 69 MAD 1BH

-0.84 1072 1409 24 69 3.85 MAN 1BH

-3.50

-3.34 0.16 1073 1410 25 69 SAD 1BH

-1.42 1073 1411 25 69 1.37 SAN 1BH

-3.72

-3.65 0.07 1074 1412 26 69 2.14 MAN 1BH

-3.72

-3.66 0.06 1074 1413 26 69 SAD 1BH

-1.41 1075 1414 28 69 SAD 1BH

-0.86 1075 1415 28 69 1.13 SAN 1BH

-3.81

-3.77 0.04 1076 1416 30 69 SAD 1BH

-0.75 1076 1417 30 69 1.40 SAN 1BH

-3.78

-3.74 0.04 1077 1418 32 69 5.33 MAN 1BH

-3.71

-3.58 0.13 1077 1419 32 69 SAD 1BH

-0.85 1078 1420 34 69 MAD 1BH

-0.85 1079 1421 35 69 SAD 1BH

-1.32 1080 1422 36 69 MAD 1BH

-0.85 1081 1423 37 69 MAD 1BH

-0.88 1082 1424 39 69 SAD 1BH

-0.85 1083 1425 2

70 SAD 1BH

-1.23 1083 1426 2

70 3.57 SAN 1BH

-3.67

-3.49 0.18 1084 1427 4

70 SAD 1BH

-1.42 1085 1428 7

70 SAD 1BH

-0.86 1086 1429 8

70 MAD 1BH

-0.85 1086 1430 8

70 3.63 SAN 1BH

-3.63

-3.44 0.19 1087 1431 10 70 MAD 1BH

-0.96 1088 1432 11 70 MAD 1BH

-0.87 1088 1433 11 70 4.86 SAN 1BH

-3.76

-3.59 0.17 1089 1434 14 70 SAD 1BH

-0.86 1089 1435 14 70 1.88 SAN 1BH

-3.68

-3.62 0.06 1090 1436 15 70 MAD 1BH

-0.97 1091 1437 19 70 MAD 1BH

-0.85 1092 1438 21 70 SAD 1BH

-0.85 1093 1439 22 70 SAD 1BH

-1.05 1094 1440 23 70 6.35 MAN 1BH

-3.78

-3.42 0.36 Page 54 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1094 1441 23 70 SAD 1BH

-0.92 1095 1442 24 70 SAD 1BH

-0.85 1095 1443 24 70 4.02 SAN 1BH

-3.66

-3.42 0.24 1096 1444 25 70 5.88 MAN 1BH

-3.77

-3.46 0.31 1096 1445 25 70 SAD 1BH

-1.49 1097 1446 30 70 SAD 1BH

-0.99 1097 1447 30 70 5.19 SAN 1BH

-3.73

-3.61 0.12 1098 1448 32 70 SAD 1BH

-0.88 1098 1449 32 70 1.38 SAN 1BH

-3.58

-3.54 0.04 1099 1450 37 70 MAD 1BH

-0.86 1100 1451 38 70 MAD 1BH

-1.07 1101 1452 1

71 SAD 1BH

-0.80 1101 1453 1

71 2.78 SAN 1BH

-3.68

-3.60 0.08 1102 1454 2

71 MAD 1BH

-0.92 1103 1455 6

71 MAD 1BH

-1.36 1104 1456 8

71 MAD 1BH

-1.36 1105 1457 12 71 SAD 1BH

-1.28 1106 1458 13 71 MAD 1BH

-1.00 1107 1459 15 71 MAD 1BH

-0.90 1108 1460 18 71 SAD 1BH

-0.95 1109 1461 20 71 SAD 1BH

-1.07 1110 1462 21 71 SAD 1BH

-1.42 1110 1463 21 71 1.39 SAN 1BH

-3.74

-3.70 0.04 1111 1464 24 71 SAD 1BH

-0.90 1112 1465 25 71 SAD 1BH

-0.90 1112 1466 25 71 1.69 SAN 11BH

-3.74

-3.67 0.07 1113 1467 29 71 SAD 1BH

-1.02 1113 1468 29 71 4.68 SAN 1BH

-3.60

-3.43 0.17 1114 1469 30 71 SAD 1BH

-1.30 1114 1470 30 71 3.60 SAN 1BH

-3.70

-3.60 0.10 1115 1471 31 71 SAD 1BH

-1.37 1115 1472 31 71 8.04 SAN 1BH

-3.76

-3.62 0.14 1116 1473 33 71 MAD 1BH

-0.87 1116 1474 33 71 4.09 MAN 1BH

-3.43

-3.23 0.20 1117 1475 35 71 MAD 1BH

-0.85 1118 1476 37 71 MAD 1BH

-0.85 1119 1477 1

72 MAD 1BH

-0.85 1120 1478 2

72 MAD 1BH

-1.37 1121 1479 3

72 SAD 1BH

-1.00 1121 1480 3

72 2.36 SAN 1BH

-3.53

-3.45 0.08 1122 1481 5

72 SAD 1BH

-1.41 1122 1482 5

72 1.42 SAN 1BH

-3.78

-3.65 0.13 1123 1483 6

72 SAD 1BH

-1.30 1124 1484 7

72 MAD 1BH

-0.93 1125 1485 9

72 SAD 1BH

-0.85 1126 1486 10 72 MAD 1BH

-0.93 1127 1487 12 72 SAD 1BH

-1.46 1128 1488 15 72 SAD 1BH

-1.29 Page 55 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1129 1489 16 72 SAD 1BH

-1.42 1130 1490 17 72 5.98 SAN 1BH

-3.71

-3.60 0.11 1130 1491 17 72 0.36 SAN 1BH

-1.39

-1.34 0.05 1131 1492 20 72 MAD IBH

-0.87 1132 1493 21 72 SAD 1BH

-0.86 1133 1494 23 72 SAD 1BH

-1.24 1133 1495 23 72 1.16 SAN 1BH

-3.79

-3.71 0.08 1134 1496 35 72 MAD 1BH

-1.01 1135 1497 36 72 MAD 1BH

-1.46 1136 1498 38 72 SAD 1BH

-1.31 1137 1499 1

73 3.43 MAN 1BH

-3.65

-3.48 0.17 1137 1500 1

73 SAD 1BH

-0.87 1138 1501 2

73 SAD 1BH

-0.95 1139 1502 3

73 2.80 MAN 1BH

-1.28

-1.16 0.12 1140 1503 4

73 SAD 1BH

-0.85 1141 1504 6

73 SAD 1BH

-0.82 1142 1505 7

73 SAD 1BH

-0.90 1143 1506 8

73 MAD 1BH

-1.02 1144 1507 12 73 MAD 1BH

-0.89 1145 1508 15 73 SAD 1BH

-0.99 1146 1509 17 73 MAD 1BH

-0.88 1147 1510 18 73 MAD 1BH

-1.45 1148 1511 19 73 MAD 1BH

-0.85 1149 1512 21 73 SAD 1BH

-0.85 1150 1513 22 73 MAD 1BH

-0.83 1150 1514 22 73 0.60 SAN 1BH

-3.42

-3.33 0.09 1151 1515 23 73 SAD 1BH

-0.82 1151 1516 23 73 3.99 SAN 1BH

-3.66

-3.52 0.14 1152 1517 34 73 SAD 1BH

-1.00 1153 1518 35 73 SAD 1BH

-0.82 1154 1519 37 73 MAD 1BH

-0.80 1155 1520 1

74 SAD 1BH

-1.41 1155 1521 1

74 1.62 SAN 1BH

-3.66

-3.62 0.04 1156 1522 2

74 SAD 1BH

-1.35 1157 1523 6

74 SAD 1BH

-1.32 1158 1524 7

74 MAD 1BH

-1.34 1159 1525 8

74 MAD 1BH

-0.85 1160 1526 10 74 SAD 1BH

-1.03 1161 1527 12 74 SAD 1BH

-0.94 1161 1528 12 74 1.30 SAN 1BH

-3.51

-3.47 0.04 1162 1529 13 74 SAD 1BH

-1.38 1163 1530 15 74 SAD 1BH

-1.37 1164 1531 16 74 SAD 1BH

-0.97 1164 1532 16 74 3.94 SAN 1BH

-3.73

-3.57 0.16 1165 1533 17 74 SAD 1BH

-0.78 1166 1534 18 74 MAD 1BH

-0.90 1167 1535 19 74 SAD 1BH

-1.41 1168 1536 20 74 MAD 1BH

-0.83 Page 56 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1169 1537 23 74 SAD 1BH

-0.90 1169 1538 23 74 1.25 SAN 1BH

-3.46

-3.40 0.06 1170 1539 29 74 SAD 1BH

-1.49 1170 1540 29 74 1.35 SAN 1BH

-3.75

-3.68 0.07 1171 1541 36 74 SAD 1BH

-0.85 1172 1542 37 74 SAD 1BH

-1.26 1173 1543 1

75 5.89 MAN 1BH

-3.66

-3.42 0.24 1173 1544 1

75 SAD 1BH

-0.98 1174 1545 2

75 MAD 1BH

-0.94 1175 1546 5

75 2.36 MAN 1BH

-1.29

-1.19 0.10 1176 1547 6

75 SAD 1BH

-0.97 1177 1548 8

75 MAD 1BH

-0.90 1177 1549 8

75 2.97 SAN 1BH

-3.69

-3.64 0.05 1178 1550 9

75 SAD 1BH

-0.85 1179 1551 10 75 MAD 1BH

-0.85 1180 1552 11 75 SAD 1BH

-1.36 1181 1553 16 75 MAD 1BH

-0.85 1181 1554 16 75 4.18 MAN 1BH

-3.65

-3.56 0.09 1182 1555 20 75 SAD 1BH

-1.15 1183 1556 21 75 SAD 1BH

-1.47 1184 1557 22 75 SAD 1BH

-1.46 1184 1558 22 75 1.92 SAN 1BH

-3.72

-3.63 0.09 1185 1559 23 75 SAD 1BH

-0.92 1185 1560 23 75 1.79 SAN 1BH

.-3.66

-3.56 0.10 1186 1561 25 75 MAD 1BH

-0.83 1186 1562 25 75 1.88 MAN 1BH

-3.54

-3.46 0.08 1187 1563 34 75 MAD 1BH

-0.88 1188 1564 35 75 MAD 1BH

-1.04 1189 1565 36 75 SAD 1BH

-0.85 1190 1566 3

76 SAD 1BH

-1.37 1191 1567 5

76 SAD 1BH

-1.31 1191 1568 5

76 3.12 SAN 1BH

-3.78

-3.67 0.11 1192 1569 6

76 MAD 1BH

-0.85 1192 1570 6

76 5.41 SAN 1BH

-3.69

-3.48 0.21 1193 1571 8

76 MAD 1BH

-0.85 1193 1572 8

76 3.52 SAN 1BH

-3.69

-3.65 0.04 1194 1573 10 76 MAD 1BH

-1.30 1195 1574 11 76 1.80 MAN 1BH

-0.50

-0.23 0.27 1195 1575 11 76 SAD 1BH

-1.38 1196 1576 13 76 SAD 1BH

-0.96 1196 1577 13 76 2.63 SAN 1BH

-3.50

-3.36 0.14 1197 1578 14 76 5.38 MAN 1BH

-3.70

-3.45 0.25 1197 1579 14 76 SAD 1BH

-0.85 1198 1580 15 76 MAD 1BH

-0.96 1198 1581 15 76 1.86 SAN 1BH

-3.53

-3.46 0.07 1199 1582 16 76 MAD 1BH

-0.85 1199 1583 16 76 8.37 MAN 131BH

-3.70

-3.41 0.29 1200 1584 18 76 SAD 1BH

-0.87 Page 57 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1201 1585 21 76 MAD 1BH

-0.86 1201 1586 21 76 5.31 MAN 1BH

-3.55

-3.44 0.11 1202 1587 24 76 4.67 MAN 1BH

-3.74

-3.61 0.13 1202 1588 24 76 SAD 1BH

-1.33 1203 1589 27 76 MAD 1BH

-0.83 1203 1590 27 76 9.41 MAN 1BH

-3.53

-3.39 0.14 1204 1591 28 76 SAD 1BH

-1.31 1204 1592 28 76 2.68 SAN 1BH

-3.88

-3.78 0.10 1205 1593 29 76 SAD 1BH

-0.85 1205 1594 29 76 4.52 SAN 1BH

-3.76

-3.65 0.11 1206 1595 33 76 MAD 1BH

-0.87 1206 1596 33 76 4.81 MAN 1BH

-3.55

-3.41 0.14 1207 1597 1

77 SAD 1BH

-0.85 1207 1598 1

77 5.92 SAN 1BH

-3.70

-3.36 0.34 1208 1599 3

77 MAD 1BH

-0.93 1208 1600 3

77 4.20 SAN 1BH

-3.77

-3.67 0.10 1209 1601 4

77 SAD 1BH

-1.33 1210 1602 6

77 MAD 1BH

-1.40 1210 1603 6

77 3.66 SAN 1BH

-3.76

-3.67 0.09 1211 1604 8

77 MAD 1BH

-0.85 1211 1605 8

77 3.51 SAN 1BH

-3.70

-3.62 0.08 1212 1606 9

77 SAD 1BH

-0.85 1213 1607 10 77 MAD 1BH

-1.33 1214 1608 13 77 SAD 1BH

-1.02 1215 1609 14 77 MAD 1BH

-0.87 1215 1610 14 77 1.69 SAN 1BH

-3.60

-3.53 0.07 1216 1611 15 77 MAD 1BH

-0.91 1217 1612 16 77 3.63 MAN 1BH

-3.66

-3.53 0.13 1217 1613 16 77 SAD 1BH

-0.87 1218 1614 19 77 SAD 1BH

-0.91 1219 1615 20 77 SAD 1BH

-1.41 1219 1616 20 77 3.27 SAN 1BH

-3.78

-3.64 0.14 1220 1617 30 77 SAD 1BH

-0.80 1221 1618 32 77 1.19 MAN 1BH

-0.60

-0.30 0.30 1221 1619 32 77 SAD 1BH

-0.80 1222 1620 4

78 MAD 1BH

-1.08 1222 1621 4

78 4.99 SAN 1BH

-3.72

-3.54 0.18 1223 1622 5

78 MAD 1BH

-1.44 1223 1623 5

78 3.75 SAN 1BH

-3.78

-3.71 0.07 1224 1624 6

78 MAD 1BH

-0.98 1224 1625 6

78 0.65 SAN 1BH

-3.76

-3.71 0.05 1225 1626 8

78 SAD 1BH

-1.00 1225 1627 8

78 0.66 SAN 1BH

-3.79

-3.73 0.06 1226 1628 9

78 MAD 1BH

-1.39 1226 1629 9

78 0.85 SAN 1BH

-3.84

-3.77 0.07 1227 1630 11 78 1.48 MAN 1BH

-1.28

-1.12 0.16 1228 1631 12 78 MAD 131BH

-0.80 1228 1632 12 78 2.18 SAN 1BH

-3.65

-3.56 0.09 Page 58 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1229 1633 13 78 MAD 1BH

-1.02 1229 1634 13 78 1.43 SAN 1BH

-3.59

-3.52 0.07 1230 1635 15 78 MAD 1BH

-0.85 1231 1636 17 78 SAD 1BH

-0.85 1231 1637 17 78 2.56 SAN 1BH

-3.65

-3.58 0.07 1232 1638 22 78 MAD 1BH

-0.94 1232 1639 22 78 4.15 MAN 1BH

-3.68

-3.53 0.15 1233 1640 23 78 4.88 MAN 1BH

-3.72

-3.61 0.11 1233 1641 23 78 SAD 1BH

-0.90 1234 1642 3

79 SAD 1BH

-1.11 1235 1643 4

79 SAD 1BH

-1.37 1236 1644 5

79 MAD 1BH

-1.37 1237 1645 6

79 MAD 1BH

-1.00 1237 1646 6

79 2.17 SAN IBH

-3.66

-3.61 0.05 1238 1647 7

79 1.59 MAN 1BH

-1.29

-1.20 0.09 1239 1648 10 79 SAD 1BH

-1.39 1240 1649 12 79 SAD 1BH

-1.42 1241 1650 14 79 MAD 1BH

-0.89 1241 1651 14 79 5.46 SAN 1BH

-3.70

-3.57 0.13 1242 1652 15 79 SAD 1BH

-1.00 1242 1653 15 79 0.93 SAN 1BH

-3.77

-3.71 0.06 1243 1654 21 79 4.12 MAN 1BH

-3.70

-3.57 0.13 1243 1655 21 79 SAD 1BH

-1.29 1244 1656 1

80 MAD 1BH

-1.00 1245 1657 2

80 MAD 1BH

-0.85 1246 1658 3

80 SAD 1BH

-1.31 1247 1659 7

80 MAD 1BH

-0.99 1248 1660 8

80 SAD 1BH

-1.31 1248 1661 8

80 0.90 SAN 1BH

-3.68

-3.61 0.07 1249 1662 11 80 MAD 1BH

-1.37 1250 1663 12 80 SAD 1BH

-1.26 1251 1664 18 80 MAD 1BH

-0.85 1251 1665 18 80 2.56 SAN 1BH

-3.87

-3.68 0.19 1252 1666 26 80 SAD 1BH

-0.80 1253 1667 27 80 SAD 1BH

-0.86 1254 1668 1

81 MAD 1BH

-0.90 1254 1669 1

81 3.67 MAN 1BH

-3.72

-3.48 0.24 1255 1670 2

81 MAD 1BH

-0.86 1256 1671 3

81 MAD 1BH

-1.09 1257 1672 5

81 MAD 1BH

-0.96 1257 1673 5

81 3.94 SAN 1BH

-3.52

-3.38 0.14 1258 1674 8

81 SAD 1BH

-1.20 1259 1675 9

81 MAD 1BH

-0.86 1260 1676 10 81 SAD 1BH

-0.91 1261 1677 13 81 SAD IBH

-0.85 1262 1678 17 81 SAD 1BH

-0.85 1263 1679 21 81 SAD 1BH

-1.30 1263 1680 21 81 3.27 SAN 1BH

-3.77

-3.70 0.07 Page 59 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1264 1681 24 81 SAD 1BH

-0.84 1265 1682 27 81 SAD 1BH

-1.02 1266 1683 1

82 SAD 1BH

-1.40 1266 1684 1

82 3.25 SAN 1BH

-3.74

-3.43 0.31 1267 1685 2

82 MAD 1BH

-0.85 1268 1686 3

82 MAD 1BH

-1.05 1269 1687 5

82 MAD 1BH

-0.93 1270 1688 6

82 SAD 1BH

-1.00 1271 1689 8

82 MAD 1BH

-0.85 1272 1690 9

82 MAD 1BH

-0.88 1273 1691 10 82 SAD 1BH

-0.91 1274 1692 11 82 SAD 1BH

-1.36 1275 1693 12 82 SAD 1BH

-1.44 1276 1694 14 82 MAD 1BH

-0.85 1277 1695 15 82 SAD 1BH

-0.85 1277 1696 15 82 1.48 SAN 1BH

-3.66

-3.56 0.10 1278 1697 16 82 SAD 1BH

-0.85 1278 1698 16 82 5.24 SAN 1BH

-3.75

-3.56 0.19 1279 1699 19 82 SAD 1BH

-0.85 1280 1700 25 82 2.48 MAN 1BH

-3.67

-3.60 0.07 1280 1701 25 82 SAD 1BH

-0.98 1281 1702 26 82 SAD 1BH

-1.37 1281 1703 26 82 1.02 SAN 1BH

-3.98

-3.92 0.06 1282 1704 2

83 SAD 1BH

-0.94 1282 1705 2

83 0.49 SAN 1BH

-3.83

-3.74 0.09 1283 1706 4

83 SAD 1BH

-1.30 1284 1707 6

83 MAD 11BH

-0.87 1284 1708 6

83 1.32 SAN 1BH

-3.75

-3.65 0.10 1285 1709 7

83 SAD 1BH

-0.85 1286 1710 8

83 MAD 1BH

-0.99 1287 1711 9

83 MAD 1BH

-1.52 1288 1712 10 83 SAD 1BH

-0.95 1289 1713 11 83 SAD 1BH

-1.00 1290 1714 14 83 SAD 1BH

-1.00 1291 1715 18 83 MAD 1BH

-0.85 1292 1716 21 83 MAD 1BH

-0.85 1293 1717 2

84 MAD 1BH

-0.85 1293 1718 2

84 1.43 SAN 1BH

-3.71

-3.65 0.06 1294 1719 4

84 SAD 1BH

-1.37 1295 1720 7

84 SAD 1BH

-1.10 1296 1721 9

84 SAD 1BH

-1.42 1297 1722 10 84 MAD 1BH

-1.02 1298 1723 14 84 MAD 1BH

-0.91 1299 1724 20 84 SAD 1BH

-0.80 1300 1725 1

85 MAD 1BH

-0.85 1301 1726 3

85 MAD 1BH

-0.85 1301 1727 3

85 0.71 SAN 1BH

-3.80

-3.73 0.07 1302 1728 5

85 MAD 1BH

-0.94 Page 60 of 169

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1302 1729 5

85 2.12 SAN 1BH

-3.43

-3.37 0.06 1303 1730 7

85 SAD 1BH

-1.49 1304 1731 11 85 1.73 MAN 1BH

-3.84

-3.76 0.08 1304 1732 11 85 SAD 1BH

-1.26 1305 1733 13 85 MAD 1BH

-1.39 1305 1734 13 85 2.57 SAN 1BH

-3.73

-3.63 0.10 1306 1735 1

86 MAD 1BH

-0.85 1307 1736 2

86 SAD 1BH

-0.99 1308 1737 6

86 SAD 1BH

-0.88 1309 1738 7

86 MAD 1BH

-0.85 1309 1739 7

86 2.94 MAN 1BH

-0.61

-0.25 0.36 1310 1740 10 86 SAD 1BH

-1.05 1310 1741 10 86 1.67 SCN 1BH

-3.49

-3.40 0.09 1311 1742 16 86 MAD 1BH

-0.80 1311 1743 16 86 0.73 SAN 1BH

-3.68

-3.62 0.06 1312 1744 21 86 MAD 1BH

-0.88 1313 1745 22 86 SAD 1BH

-0.81 1314 1746 12 87 MAD 1BH

-0.96 1315 1747 1

88 MAD 1BH

-0.95 1316 1748 7

88 MAD 1BH

-1.07 1317 1749 8

88 SAD 1BH

-0.85 1318 1750 9

88 MAD 1BH

-0.85 1319 1751 10 88 SAD 1BH

-0.86 1320 1752 11 88 MAD 1BH

-1.01 1321 1753 13 88 SAD 1BH

-0.85 1322 1754 7

89 MAD 1BH

-0.92 1323 1755 8

89 SAD 1BH

-0.88 1324 1756 9

89 SAD 1BH

-1.23 1324 1757 9

89 0.95 SAN 1BH

-1.05

-1.01 0.04 1325 1758 10 89 MAD 1BH

-1.25 1326 1759 12 89 MAD 1BH

-0.85 1327 1760 6

90 MAD 1BH

-0.80 1328 1761 8

90 MAD 1BH

-1.04 1329 1762 4

91 SAD 1BH

-0.80 1330 1763 6

91 SAD 1BH

-1.17 1331 1764 8

91 MAD 1BH

-0.96 1332 1765 9

92 SAD 1BH

-1.00 Page 61 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 1

6 MAD 1BH

-0.88 1

2 1

6 3.42 SAN 1BH

-3.85

-3.62 0.23 2

3 4

6 SAD 1BH

-0.90 3

4 16 6

SAD 1BH

-0.92 4

5 1

7 MAD 1BH

-0.80 4

6 1

7 5.62 MAN 1BH 3-

-3.68

-3.59 0.09 5

7 4

7 MAD 1BH 3-

-1.13 6

8 14 7

SAD 1BH 3-

-0.91 7

9 15 7

SAD 1BH 1-

-1.05 8

10 1

8 SAD 1BH 3-

-0.85 9

11 4

8 SAD 1BH 3-

-1.40 10 12 16 8

MAD 1BH

-0.83 11 13 4

9 SAD 1BH 1-

-0.85 12 14 6

9 SAD 1BH 1-

-0.84 13 15 21 9

SAD 1BH

-0.94 14 16 1

10 1.24 SAN 1BH

-2.10

-2.01 0.09 15 17 14 10 MAD 1BH

-0.90 16 18 17 10 SAD 1BH

-0.91 17 19 19 10 SAD 1BH

-0.95 18 20 20 10 SAD 1BH

-0.89 19 21 1

11 MAD 1BH

-0.88 20 22 4

11 SAD 1BH

-0.93 21 23 9

11 SAD 1BH

-0.98 22 24 21 11 SAD 1BH

-1.42 23 25 1

12 MAD 1BH

-0.94 23 26 1

12 2.18 SAN 1BH

-3.74

-3.67 0.07 24 27 15 12 MAD 1BH

-0.85 25 28 1

13 SAD 1BH

-0.89 26 29 4

13 SAD 1BH

-0.85 27 30 15 13 SAD 1BH

-1.11 28 31 16 13 MAD 1BH

-0.88 29 32 20 13 SAD 1BH

-0.85 30 33 22 13 SAD 1BH

-0.90 30 34 22 13 0.67 SAI 1BH

-0.38

-0.27 0.11 31 35 24 13 2.81 MAN 1BH

-0.66

-0.11 0.55 31 36 24 13 SAD 1BH

-1.46 32 37 25 13 SAD 1BH

-0.99 33 38 27 13 SAD 1BH

-0.80 34 39 4

14 1.07 SAN 1BH

-2.38

-2.31 0.07 35 40 9

14 MAD 1BH

-0.80 36 41 13 14 SAD 1BH

-0.88 37 42 15 14 MAD 1BH

-0.93 38 43 1

15 MAD 1BH

-0.85 39 44 2

15 1.03 SAN 1BH

-2.41

-2.30 0.11 40 45 9

15 SAD 1BH

-1.16 41 46 14 15 SAD 1BH

-1.06 42 47 15 15 SAD 1BH

-0.89 43 48 19 15 SAD 1BH

-0.89 Page 62 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 44 49 24 15 4.00 MAN 1BH

-1.55

-1.16 0.39 45 50 25 15 SAD 1BH

-1.49 46 51 1

16 0.72 MCN 1BH

-3.61

-3.30 0.31 46 52 1

16 SAD 1BH

-0.91 47 53 4

16 MAD 1BH

-0.85 48 54 9

16 SAD 1BH

-0.90 49 55 12 16 SAD 1BH 1-

-0.94 50 56 15 16 SAD 1BH

-0.89 51 57 16 16 SAD 1BH 1-

-0.91 52 58 17 16 MAD 1BH

-0.92 53 59 25 16 SAD 1BH

-1.07 54 60 27 16 SAD 1BH

-1.17 55 61 4

17 MAD 1BH

-1.30 56 62 16 17 MAD 1BH

-0.93 57 63 18 17 MAD 1BH

-0.96 58 64 20 17 SAD 1BH

-0.91 59 65 22 17 SAD 1BH

-1.04 60 66 23 17 SAD 1BH

-1.00 61 67 25 17 1.45 SAN 1BH

-1.05

-0.99 0.06 62 68 31 17 MAD 1BH

-0.95 63 69 1

18 3.70 MAN 1BH

-2.13

-2.00 0.13 64 70 2

18 0.99 MAN 1BH

-2.34

-2.24 0.10 65 71 3

18 SAD 1BH

-0.91 66 72 4

18 MAD 1BH

-1.19 67 73 9

18 SAD 1BH

-1.45 68 74 14 18 MAD 1BH

-1.37 68 75 14 18 0.86 MAI 1BH

-0.40

-0.12 0.28 69 76 15 18 SAD 1BH

-0.94 70 77 20 18 SAD 1BH

-1.10 71 78 29 18 0.18 SAN 1BH

-1.03

-0.96 0.07 72 79 4

19 1.26 SAN 1BH

-2.30

-1.99 0.31 73 80 7

19 MAD 1BH

-0.82 74 81 9

19 SAD 1BH

-0.84 74 82 9

19 0.43 SAN 1BH

-0.20

-0.04 0.16 75 83 12 19 MAD 1BH

-0.80 76 84 13 19 SAD 1BH

-0.96 77 85 15 19 MAD 1BH

-1.08 78 86 16 19 MAD 1BH

-0.80 78 87 16 19 0.96 SAN 1BH

-0.37

-0.24 0.13 79 88 21 19 0.83 SVN 1BH

-2.55

-2.34 0.21 80 89 25 19 SAD 1BH

-0.92 81 90 28 19 SAD 1BH

-0.87 82 91 31 19 MAD 1BH

-0.89 83 92 33 19 MAD 1BH

-0.92 83 93 33 19 0.17 SAI 1BH

-0.56

-0.40 0.16 84 94 3

20 0.95 SAN 1BH

-2.17

-2.11 0.06 85 95 7

20 SAD 1BH

-0.85 86 96 9

20 MAD 1BH

-0.98 Page 63 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 87 97 14 20 SAD 1BH

-0.91 88 98 24 20 4.56 MAN 1BH

-0.93

-0.16 0.77 88 99 24 20 SAD 1BH

-1.32 89 100 25 20 MAD 1BH

-0.90 90 101 29 20 SAD 1BH

-1.47 91 102 30 20 MAD 1BH

-0.90 92 103 31 20 MAD 1BH

-0.83 93 104 33 20 SAD 1BH

-0.96 94 105 35 20 MAD 1BH

-1.00 94 106 35 20 2.46 MAN 1BH

-3.41

-3.12 0.29 95 107 37 20 SAD 1BH

-1.14 96 108 1

21 2.97 MAN 1BH

-2.15

-2.03 0.12 97 109 2

21 SAD 1BH

-0.99 98 110 4

21 1.63 MAN 1BH

-2.40

-2.31 0.09 99 111 6

21 SAD 1BH

-0.82 100 112 7

21 SAD 1BH

-0.94 101 113 9

21 MAD 1BH

-0.81 102 114 10 21 SAD 1BH

-1.34 103 115 17 21 SAD 1BH

-0.90 104 116 19 21 SAD 1BH

-0.87 105 117 20 21 SAD 1BH

-0.86 106 118 25 21 SAD 1BH

-1.04 107 119 31 21 SAD 1BH

-1.40 108 120 32 21 1.08 MAI 1BH

-0.72

-0.05 0.67 108 121 32 21 SAD 1BH

-0.99 109 122 1

22 MAD 1BH

-0.99 110 123 5

22 SAD 1BH

-0.89 111 124 7

22 SAD 1BH

-1.27 112 125 12 22 SAD 1BH

-0.85 113 126 13 22 MAD 1BH

-0.90 113 127 13 22 1.93 MAN 1BH

-0.53

-0.39 0.14 114 128 14 22 MAD IBH

-0.96 115 129 15 22 SAD 1BH

-0.85 116 130 18 22 2.20 SAN 1BH

-1.43

-1.23 0.20 117 131 19 22 SAD 1BH

-1.24 118 132 23 22 SAD 1BH

-1.31 118 133 23 22 1.25 SAN 1BH

-0.50

-0.32 0.18 119 134 24 22 SAD 1BH

-1.06 120 135 26 22 0.26 MAN 1BH

-1.42

-1.35 0.07 121 136 28 22 SAD 1BH

-1.47 122 137 33 22 SAD 1BH

-1.28 123 138 35 22 MAD 1BH

-0.90 123 139 35 22 1.90 MAN 1BH

-3.58

-3.46 0.12 124 140 1

23 MAD 1BH

-0.96 125 141 7

23 MAD 1BH

-0.94 126 142 9

23 MAD 1BH

-0.88 127 143 12 23 SAD 1BH

-0.85 128 144 14 23 SAD 1BH

-0.93 Page 64 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 129 145 20 23 SAD 1BH

-0.89 130 146 21 23 SAD 1BH

-0.90 131 147 26 23 SAD 1BH

-1.53 132 148 31 23 MAD 1BH

-0.93 133 149 32 23 SAD 1BH

-1.24 134 150 33 23 MAD 1BH

-0.90 135 151 35 23 MAD 1BH

-0.96 135 152 35 23 2.48 MAN 1BH

-3.69

-3.47 0.22 136 153 37 23 1.48 MAN 113-BH

-3.65

-3.51 0.14 136 154 37 23 SAD 1BH

-0.95 137 155 1

24 SAD 1BH

-1.36 138 156 7

24 SAD 1BH

-0.98 139 157 14 24 0.14 MAN 1BH

-1.14

-1.09 0.05 140 158 15 24 MAD 1BH

-0.90 141 159 19 24 MAD 1BH

-0.96 142 160 20 24 SAD 1BH

-0.86 143 161 22 24 MAD 1BH

-0.87 144 162 27 24 MAD 1BH

-1.57 145 163 28 24 3.27 MAN 1BH

-1.31

-1.09 0.22 146 164 32 24 SAD 1BH

-1.10 147 165 33 24 MAD 1BH

-1.00 148 166 34 24 SAD 1BH

-1.02 149 167 35 24 1.50 MAN 1BH

-3.56

-3.44 0.12 149 168 35 24 SAD 1BH

-1.32 150 169 37 24 SAD 1BH

-1.04 150 170 37 24 1.46 SAN 1BH

-3.67

-3.54 0.13 151 171 1

25 MAD 1BH

-0.85 151 172 1

25 2.22 SAN 1BH

-3.75

-3.68 0.07 152 173 7

25 SAD 1BH

-1.31 153 174 9

25 SAD 1BH

-0.85 154 175 12 25 MAD 1BH

-0.91 155 176 14 25 SAD 1BH

-1.33 156 177 21 25 SAD 1BH

-1.51 157 178 23 25 2.39 MAN 1BH

-1.48

-1.27 0.21 158 179 26 25 0.60 SAN 1BH

-1.27

-1.16 0.11 159 180 27 25 SAD 1BH

-0.94 160 181 28 25 4.35 MAN 1BH

-0.86

-0.18 0.68 160 182 28 25 SAD 1BH

-1.27 161 183 31 25 SAD 1BH

-1.00 162 184 32 25 SAD 1BH

-1.40 163 185 33 25 SAD 1BH

-1.00 164 186 35 25 2.39 MAN 1BH

-0.68

-0.19 0.49 164 187 35 25 SAD 1BH

-1.56 164 188 35 25 2.29 SAN 1BH

-3.59

-3.40 0.19 165 189 37 25 1.72 MAN 1BH

-3.66

-3.52 0.14 165 190 37 25 SAD 1BH

-0.85 166 191 38 25 2.48 SAN 1BH

-3.75

-3.63 0.12 167 192 1

26 SAD 1BH

-1.47 1

1 Page 65 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 167 193 1

26 3.28 SAN 1BH

-3.81

-3.67 0.14 167 194 1

26 0.24 SAN 1BH

-0.53

-0.32 0.21 168 195 3

26 SAD 1BH

-0.87 169 196 7

26 MAD 1BH

-0.98 170 197 9

26 MAD 1BH

-0.85 171 198 14 26 SAD 1BH

-0.91 172 199 15 26 MAD 1BH

-0.90 173 200 17 26 MAD 1BH

-0.87 174 201 19 26 MAD 1BH

-1.67 175 202 20 26 SAD 1BH

-1.01 176 203 21 26 SAD 1BH

-1.36 176 204 21 26 0.62 SAN 1BH

-0.36

-0.13 0.23 177 205 25 26 0.43 SAN 1BH

-1.31

-0.78 0.53 178 206 28 26 SAD 1BH

-0.96 179 207 31 26 SAD 1BH

-0.93 180 208 32 26 SAD 11BH

-1.30 181 209 33 26 SAD 1BH

-1.33 182 210 1

27 SAD 131BH

-0.99 182 211 1

27 3.45 SAN 1BH

-3.75

-3.58 0.17 183 212 2

27 MAD 1BH

-0.92 183 213 2

27 1.70 SAN 1BH

-3.58

-3.50 0.08 184 214 3

27 SAD 1BH

-0.90 185 215 5

27 SAD 1BH

-0.85 186 216 7

27 SAD 1BH

-0.96 186 217 7

27 0.18 SAN 1BH

-0.53

-0.46 0.07 187 218 12 27 MAD 1BH

-0.90 188 219 13 27 MAD 1BH

-1.29 189 220 15 27 SAD 131BH

-1.59 190 221 20 27 SAD 113-BH

-1.52 191 222 24 27 SAD 1131BH

-1.35 192 223 25 27 SAD 1BH

-1.22 193 224 27 27 SAD 1BH

-1.08 194 225 31 27 MAD 1BH

-1.29 195 226 33 27 MAD 1BH

-0.95 196 227 35 27 SAD 1BH

-0.99 196 228 35 27 1.02 SAN 1BH

-3.70

-3.57 0.13 197 229 3

28 SAD 1BH

-0.98 197 230 3

28 3.60 SAN 11BH

-3.72

-3.55 0.17 198 231 7

28 MAD 1BH

-1.51 199 232 22 28 SAD 1BH

-1.00 200 233 24 28 SAD 1BH

-1.40 201 234 25 28 MAD 1BH

-1.06 202 235 30 28 MAD 1BH

-1.05 203 236 31 28 SAD 1BH

-1.34 203 237 31 28 0.46 SAI 1BH

-0.99

-0.92 0.07 204 238 33 28 SAD 1BH

-0.96 205 239 38 28 SAD 1BH

-2.18 205 240 38 28 2.52 SAN 1BH

-3.79

-3.66 0.13 Page 66 of 169

TABLE 8 STEAMGENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 206 241 1

29

____MAD 1131-

-1.35 207 242 3

29 SAD 1131-

-0.94 207 243 3

29 3.17 SAN 113H

-3.45

-3.21 0.24 208 244 7

29

____SAD 1131-

-1.18 209 245 9

29 MAD 1131-

-0.94 210 246 21 29

____MAD 11BH-

-0.91 211 247 24 29

____SAD 1131-

-1.57 212 248 26 29 MAD 1BH

-1.44 213 249 27 29 MAD 1B31-

-1.23 213 250 27 29 4.01 MAN 1131-

-0.67

-0.13 0.54 214 251 28 29 SAD 1131-

-0.85 215 252 31 29 MAD 1131-1_

-0.90 216 253 32 29 SAD 113H

-1.52 217 254 33 29 SAD 1131-

-0.98 218 255 34 29 0.78 SAN 1131-

-3.73

-3.64 0.09 218 256 34 29 0.65 SAN 1131-

-3.73

-3.64 0.09 218 257 34 29 0.26 SAN 113H

-1.35

-1.29 0.06 219 258 4

30 SAD 113H

-0.90 220 259 5

30 MAD 1131-

-1.24 220 260 5

30 0.35 SAN 1131-

-0.38

-0.16 0.22 221 261 7

30 SAD 1131-

-1.05 222 262 9

30

____SAD 1131-

-1.61 223 263 18 30

____MAD 1131-

-0.98 224 1264 28 30 0.47 SAN 1131-BH

-1.43

-1.37 0.06 225 265 31 30

____SAD 11311BH

-0.80 226 266 32 30

____MAD 1131BH

-1.40 227 267 33 30

____MAD 1131-BH

-0.90 228 268 35 30 1.25 MAN 1131-BH

-3.56

-3.40 0.16 228 269 35 30 SAD 1131-H

-1.40 229 270 40 30 SAD 1131H-1_

-1.07 230 271 3

31 3.05 MAN 1131-BH

-1.56

-1.10 0.46 231 272 4

31 0.54 SAN 1131-

-1.42

-1.35 0.07 232 273 5

31 SAD ____1BH

-1.02 232 274 5

31 0.12 SAN 1131-

-0.65

-0.46 0.19 233 275 6

31 MAD 113H-

-0.87 233 276 6

31 0.48 MAN 1BH __

-0.74

-0.24 0.50 234 277 7

31 SAD 113H

-0.92 235 278 9

31 MAD 113H

-0.94 236 279 10 31 2.27 MAN 1131-

-1.48

-1.29 0.19 236 280 10 31 1.49 SAN 1131-

-0.78

-0.37 0.41 237 281 27 31 SAD 11BH-

-1.25 238 282 28 31 SAD 11B1-

-1.47 239 283 29 31 SAD 1131-

-1.25 240 284 31 31 SAD 1131-1_

-0.90 241 285 32 31 SAD 1131-1_

-1.40 242 286 35 31 1.38 MAN 1131-1_

-3.53

-3.42 0.11 242 287 35 31 SAD 1131-1_

-1.53 243 288 39 31

____SAD 1131-

-1.15 Page 67 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 244 289 1

32 MAD 1BH

-1.34 244 290 1

32 2.92 MAN 11BH

-3.75

-3.52 0.23 245 291 2

32 SAD 1BH

-0.91 246 292 3

32 SAD 1BH

-0.90 247 293 6

32 SAD 11BH

-1.00 248 294 9

32 MAD 1BH

-1.18 249 295 11 32 SAD 1BH

-0.90 250 296 20 32 1.31 MAN 1BH 3-

-1.25

-1.14 0.11 251 297 21 32 SAD 1BH

-1.36 252 298 22 32 SVD 11BH

-2.08 253 299 27 32 0.47 SAN 1BH

-1.39

-1.33 0.06 254 300 28 32 SAD 1BH

-1.17 255 301 31 32 2.65 SAN IBH

-1.50

-1.29 0.21 256 302 32 32 SAD 1BH

-1.44 257 303 33 32 MAD 11BH

-1.46 258 304 35 32 SAD 1BH

-1.00 259 305 43 32 SAD 1BH

-1.25 259 306 43 32 1.53 SAN 1BH

-3.69

-3.61 0.08 260 307 1

33 MAD 11BH

-0.94 260 308 1

33 5.62 MAN 1BH

-3.67

-3.37 0.30 261 309 3

33 SAD 1BH

-0.95 262 310 6

33 MAD 1BH

-0.89 263 311 7

33 MAD 1BH

-0.95 264 312 9

33 MAD 1BH

-0.92 265 313 18 33 SAD 1BH

-1.41 266 314 23 33 SAD 1BH

-1.53 267 315 25 33 SAD 1BH

-0.90 268 316 31 33 MAD 1BH

-0.98 268 317 31 33 0.35 MAI 1BH

-0.46

-0.13 0.33 269 318 32 33 MAD 1BH

-1.49 270 319 33 33 SAD 1BH

-1.00 271 320 38 33 SAD 1BH

-2.03 271 321 38 33 1.44 SAN 1BH

-3.75

-3.67 0.08 272 322 1

34 MAD 11BH

-0.91 272 323 1

34 4.86 MAN 1BH

-3.60

-3.46 0.14 273 324 3

34 MAD 11BH

-0.85 274 325 5

34 SAD 11BH

-0.92 275 326 6

34 SAD 11BH

-0.85 276 327 7

34 SAD 1BH

-1.25 277 328 23 34 MAD 1BH

-0.95 278 329 28 34 2.72 MAN 1BH

-1.43

-1.32 0.11 279 330 30 34 0.86 SAN 1BH

-1.56

-1.47 0.09 280 331 33 34 SAD 1BH

-0.97 281 332 36 34 SAD 1BH

-0.99 282 333 37 34 MAD 11BH

-0.95 282 334 37 34 1.09 MAN 11BH

-3.46

-3.39 0.07 283 335 38 34 SAD 11BH

-2.04 283 336 38 34 1.57 SAN 1BH

-3.52

-3.41 0.11 Page 68 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 284 337 1

35 SAD 1BH

-0.85 285 338 3

35 SAD 1BH

-1.36 286 339 6

35 SAD 1BH

-0.85 287 340 7

35 MAD 1BH

-0.96 288 341 9

35 SAD 1BH

-0.94 289 342 22 35 SAD 1BH

-0.90 290 343 23 35 MAD 1BH

-0.92 291 344 27 35 SAD 1BH

-1.04 292 345 28 35 4.10 MAN 1BH

-1.60

-1.30 0.30 293 346 29 35 SAD 1BH

-1.27 294 347 30 35 SAD 1BH

-1.38 295 348 35 35 MAD 1BH

-1.00 296 349 38 35 MAD 1BH

-1.06 296 350 38 35 1.08 MAN 1BH

-2.59

-2.53 0.06 297 351 1

36 3.33 MAN 1BH

-3.74

-3.55 0.19 297 352 1

36 SAD 1BH

-1.30 298 353 3

36 SAD 1BH

-0.85 299 354 5

36 SAD 1BH

-0.90 300 355 7

36 SAD 1BH

-1.35 301 356 9

36 MAD 1BH

-0.93 302 357 12 36 SAD 1BH

-0.95 303 358 20 36 MAD 1BH

-1.47 304 359 21 36 MAD 1BH

-0.94 305 360 23 36 5.23 MAN 1BH

-1.46

-1.31 0.15 306 361 27 36 SAD 11BH

-1.48 307 362 29 36 SAD 11BH

-1.22 308 363 32 36 0.47 SAN 11BH

-0.99

-0.75 0.24 309 364 36 36 MAD 1BH

-1.09 309 365 36 36 0.46 SAN 1BH

-0.53

-0.22 0.31 310 366 38 36 0.82 MAN 1BH

-2.59

-2.52 0.07 310 367 38 36 SAD 1BH

-1.08 310 368 38 36 1.02 SAN 1BH

-3.88

-3.79 0.09 311 369 1

37 MAD 1BH

-0.94 311 370 1

37 5.78 MAN 1BH

-3.74

-3.47 0.27 312 371 2

37 SAD 1BH

-1.25 313 372 3

37 SAD 1BH

-0.80 314 373 5

37 SAD 1BH

-0.90 315 374 7

37 SAD 1BH

-0.80 316 375 9

37 SAD 1BH

-0.88 317 376 18 37 MAD 1BH

-0.82 318 377 20 37 SAD 1BH

-1.48 319 378 21 37 MAD 1BH

-1.23 320 379 22 37 SAD 1BH

-0.94 321 380 23 37 SAD 1BH

-1.51 322 381 24 37 1.24 SAN 1BH

-1.55

-1.48 0.07 323 382 30 37 SAD 1BH

-1.29 324 383 35 37 MAD 1BH

-1.03 325 384 36 37 MAD 1BH

-1.06 Page 69 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 326 385 37 37 SAD 11BH

-1.40 327 386 3

38 SAD 1BH

-0.85 328 387 11 38 SAD 1BH

-0.85 329 388 15 38 SAD 1BH

-0.91 330 389 19 38 1.56 MAN 1131BH

-1.40

-1.18 0.22 331 390 23 38 SAD 113-BH

-1.00 332 391 38 38 1.16 MAN 113-BH

-2.66

-2.58 0.08 332 392 38 38 SAD 131BH

-1.05 333 393 42 38 SAD 1BH

-1.11 334 394 3

39 SAD 1BH

-1.41 335 395 4

39 0.83 SVN 1BH

-1.21

-0.88 0.33 336 396 5

39 MAD 1BH

-0.93 337 397 6

39 SAD 1BH 1-

-0.90 338 398 9

39 SAD 1BH

-1.50 339 399 20 39 SAD 1BH 1-

-1.11 340 400 21 39 MAD 1BH 1-

-1.07 341 401 23 39 SAD 1BH

-1.50 342 402 30 39 SAD 1BH 3-

-0.89 343 403 33 39 SAD 1BH

-1.31 344 404 35 39 SAD 1BH

-1.00 345 405 37 39 SAD 1BH

-1.33 345 406 37 39 0.64 SAN 1BH

-3.59

-3.48 0.11 346 407 38 39 0.92 SAN 1BH

-3.51

-3.42 0.09 346 408 38 39 0.85 SAN 1BH

-2.71

-2.65 0.06 347 409 40 39 SAD 1BH

-1.02 348 410 3

40 SAD 1BH

-1.08 349 411 4

40 SAD 1BH

-0.80 350 412 6

40 SAD 1BH

-1.07 351 413 9

40 SAD 1BH

-0.85 352 414 12 40 SAD 1BH

-1.03 352 415 12 40 2.02 SAN 1BH

-3.65

-3.55 0.10 353 416 20 40 SAD 1BH

-1.41 354 417 21 40 SAD 1BH

-1.36 355 418 22 40 MAD 1BH

-0.95 356 419 23 40 SAD 1BH

-1.00 357 420 30 40 MAD 1BH

-0.94 358 421 32 40 SAD 1BH

-1.52 359 422 33 40 SAD 1BH

-1.00 360 423 3

41 SAD 1BH

-0.95 361 424 4

41 1.38 SAN 1BH

-3.76

-3.65 0.11 362 425 6

41 SAD 1BH

-0.85 363 426 9

41 SAD 1BH

-0.85 364 427 11 41 SAD 1BH

-1.05 365 428 19 41 SAD 1BH

-1.54 366 429 20 41 MAD 1BH

-0.84 367 430 23 41 MAD 1BH

-1.22 368 431 27 41 2.81 MAN 1BH

-1.51

-1.40 0.11 369 432 28 41 0.88 MAN 1BH

-3.74

-3.64 0.10 Page 70 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 369 433 28 41 SAD 1BH

-0.92 370 434 29 41 SAD 1BH

-1.28 371 435 30 41 SAD 1BH

-0.99 372 436 33 41 MAD 1BH

-1.41 373 437 34 41 SAD 1BH

-0.95 374 438 2

42 SAD 1BH

-1.32 374 439 2

42 2.59 SAN 1BH

-3.79

-3.64 0.15 375 440 5

42 SAD 1BH

-0.85 376 441 9

42 MAD 1BH

-0.85 377 442 10 42 SAD 1BH

-1.10 378 443 13 42 SAD 1BH

-1.28 379 444 21 42 MAD 1BH

-0.95 380 445 23 42 SAD 113-BH

-1.07 381 446 24 42 SAD 1BH

-1.71 382 447 28 42 0.61 SAN 1BH

-1.55

-1.46 0.09 383 448 29 42 SAD 1BH

-1.50 384 449 30 42 SAD 1BH

-0.99 385 450 32 42 0.47 SAN 1BH

-1.40

-1.29 0.11 386 451 33 42 1.86 MAN 1BH

-1.28

-1.14 0.14 387 452 34 42 0.20 MAN 1BH

-1.06

-0.97 0.09 388 453 35 42 SAD 1BH

-1.13 388 454 35 42 0.27 SAN 1BH

-0.51

-0.34 0.17 389 455 38 42 MAD 1BH

-1.11 390 456 41 42 SAD 131BH

-1.08 391 457 1

43 6.91 MAN 1BH

-3.75

-3.39 0.36 391 458 1

43 SAD 1BH

-1.63 391 459 1

43 0.55 SAN 1BH

-0.63

-0.49 0.14 392 460 3

43 SAD 1BH

-1.22 393 461 5

43 SAD 1BH

-0.85 394 462 7

43 MAD 1BH

-0.87 395 463 12 43 SAD 1BH

-1.17 396 464 13 43 SAD 1BH

-1.18 397 465 21 43 SAD 1BH

-0.94 398 466 30 43 SAD 1BH

-1.07 399 467 33 43 1.95 MAN 1BH

-1.53

-1.28 0.25 400 468 37 43 1.77 MAN 1BH

-1.59

-1.31 0.28 400 469 37 43 1.87 MAN 1BH

-0.41

-0.25 0.16 401 470 38 43 MAD 1BH

-1.00 402 471 2

44 SAD 1BH

-0.83 403 472 3

44 MAD 1BH

-0.89 404 473 5

44 SAD 1BH

-0.79 405 474 6

44 SAD 1BH

-1.07 406 475 7

44 MAD 1BH

-0.94 407 476 14 44 SAD 1BH

-1.58 408 477 17 44 0.77 MAN 1BH

-1.39

-1.28 0.11 409 478 18 44 SAD 1BH

-0.93 410 479 20 44 MAD 1BH

-1.16 411 480 22 44 MAD 1BH

-1.05 Page 71 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 412 481 23 44 MAD 1BH

-1.52 413 482 27 44 SAD 1BH

-1.55 414 483 30 44 SAD 1BH

-1.50 415 484 33 44 SAD 1BH

-1.36 416 485 35 44 0.46 SAN 1BH

-1.45

-1.17 0.28 417 486 37 44 SAD 1BH

-1.14 418 487 38 44 SAD 1BH

-1.03 418 488 38 44 0.66 SAN 1BH

-3.79

-3.72 0.07 419 489 42 44 SAD 1BH

-1.01 420 490 1

45 MAD 1BH

-0.75 420 491 1

45 5.37 MAN 1BH

-3.74

-3.42 0.32 421 492 2

45 MAD 1BH

-0.97 421 493 2

45 2.22 SAN 1BH

-3.53

-3.34 0.19 422 494 3

45 MAD 1BH

-0.78 422 495 3

45 1.25 SAN 1BH

-3.69

-3.66 0.03 423 496 6

45 SAD 1BH

-1.34 424 497 11 45 SAD 1BH

-0.80 425 498 12 45 SAD 1BH

-0.90 426 499 13 45 1.79 SAN 1BH

-1.25

-1.08 0.17 427 500 15 45 MAD 1BH

-1.52 428 501 19 45 MAD 1BH

-0.90 429 502 23 45 SAD 1BH

-1.00 430 503 26 45 SAD 1BH

-0.99 431 504 27 45 SAD 1BH

-1.05 432 505 28 45 MAD 1BH

-1.57 433 506 29 45 SAD 1BH

-1.40 434 507 33 45 SAD 1BH

-0.99 435 508 34 45 MAD 1BH

-1.40 436 509 3

46 SAD 1BH

-0.81 437 510 6

46 SAD 1BH

-0.85 438 511 7

46 SAD 1BH

-0.85 439 512 9

46 SAD 1BH

-1.03 440 513 10 46 SAD 1BH

-1.18 441 514 12 46 SAD 1BH

-1.38 442 515 16 46 MAD 1BH

-1.35 443 516 18 46 SAD 1BH

-0.95 444 517 19 46 SAD 1BH

-1.47 445 518 26 46 2.72 MAN 1BH

-1.55

-1.34 0.21 446 519 28 46 0.49 SAN 1BH

-1.38

-1.28 0.10 447 520 34 46 MAD 1BH

-1.12 448 521 38 46 MAD 1BH

-1.00 449 522 1

47 SAD 1BH

-1.19 449 523 1

47 1.61 SAN 1BH

-3.75

-3.65 0.10 450 524 3

47 SAD 1BH

-1.10 451 525 4

47 SAD 1BH

-0.83 452 526 5

47 MAD 1BH

-0.81 453 527 6

47 SAD 1BH

-1.29 454 528 15 47 SAD 1BH

-0.95 Page 72 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 455 529 20 47 SAD 1BH

-0.93 456 530 22 47 SAD 1BH

-0.96 457 531 28 47 SAD 1BH

-0.99 458 532 33 47 MAD 1BH

-1.05 459 533 34 47 SAD 1BH

-0.98 460 534 35 47 SAD 1BH

-1.09 461 535 42 47 SAD 1BH

-0.98 462 536 1

48 SAD 1BH

-1.07 463 537 2

48 2.78 MAN 1BH

-1.10

-1.02 0.08 464 538 3

48 MAD 1BH

-1.17 464 539 3

48 1.01 SAN 1BH

-3.65

-3.58 0.07 465 540 6

48 SAD 1BH

-1.00 466 541 9

48 MAD 1BH 1-

-0.89 466 542 9

48 3.99 SAN 1BH 1-

-3.69

-3.47 0.22 467 543 10 48 MAD 1BH

-0.89 467 544 10 48 2.02 SAN 1BH

-3.75

-3.65 0.10 468 545 15 48 SAD 1BH

-0.91 469 546 21 48 SAD 1BH

-1.00 470 547 23 48 3.84 MAN 1BH

-1.60

-1.23 0.37 471 548 28 48 3.32 MAN 1BH

-1.54

-1.17 0.37 472 549 29 48 SAD 1BH

-1.59 473 550 30 48 MAD 1BH

-1.05 473 551 30 48 0.54 MAN 1BH

-0.42

-0.26 0.16 474 552 37 48 3.56 MAN 1BH

-3.79

-3.63 0.16 474 553 37 48 1.07 MAN 1BH

-0.46

-0.26 0.20 474 554 37 48 SAD 1BH

-1.43 475 555 1

49 4.85 SAN 1BH

-3.75

-3.55 0.20 475 556 1

49 1.51 SAN 1BH

-1.18

-1.11 0.07 476 557 4

49 2.13 MAN 1BH

-3.74

-3.63 0.11 476 558 4

49 SAD 1BH

-1.28 477 559 5

49 SAD 1BH

-0.89 477 560 5

49 3.85 SAN 1BH

-3.64

-3.49 0.15 478 561 6

49 SAD 1BH

-0.93 478 562 6

49 3.53 SAN 1BH

-3.71

-3.60 0.11 479 563 8

49 SAD 1BH

-1.04 479 564 8

49 1.93 SAN 1BH

-3.75

-3.66 0.09 480 565 9

49 SAD 1BH

-1.32 480 566 9

49 1.87 SAN 131BH

-3.55

-3.41 0.14 481 567 10 49 SAD 1BH

-1.35 481 568 10 49 2.30 SAN 1BH

-3.75

-3.55 0.20 482 569 11 49 MAD 1BH

-1.36 483 570 12 49 2.50 MAN 1BH

-1.05

-0.90 0.15 483 571 12 49 2.15 SAN 1BH

-0.18

-0.01 0.17 484 572 14 49 3.25 MAN 1BH

-1.24

-1.02 0.22 485 573 16 49 MAD 1BH

-0.94 486 574 20 49 MAD 1BH

-0.96 487 575 22 49 MAD 1BH

-0.93 488 576 23 49 4.83 MAN 1BH

-1.64

-1.20 0.44 Page 73 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 489 577 24 49 MAD 1BH

-0.98 490 578 27 49 SAD 1BH

-1.15 491 579 28 49 1.91 SAN 1BH

-1.36

-1.28 0.08 492 580 32 49 3.53 MAN 1BH

-1.65

-1.23 0.42 493 581 34 49 SAD 1BH

-1.06 494 582 40 49 SAD 1BH

-1.19 495 583 41 49 2.91 MAN 1BH

-1.37

-1.21 0.16 496 584 1

50 10.21 MAN 1BH

-3.75

-3.44 0.31 496 585 1

50 SAD 1BH

-1.44 497 586 2

50 SAD 1BH

-1.15 497 587 2

50 1.40 SAN 1BH

-3.80

-3.71 0.09 498 588 3

50 SAD 131BH

-0.99 498 589 3

50 1.51 SAN 1BH

-3.70

-3.60 0.10 499 590 11 50 SAD 1BH

-1.18 500 591 13 50 MAD 131BH

-1.05 501 592 18 50 MAD 131BH

-0.94 502 593 22 50 SAD 1BH

-0.99 503 594 24 50 2.92 MAN 1BH

-1.42

-1.31 0.11 504 595 25 50 1.28 SAN 1BH

-2.39

-2.34 0.05 505 596 28 50 0.92 SAN 1BH

-1.36

-1.28 0.08 506 597 29 50 SAD 1BH

-1.60 507 598 30 50 SAD 1BH

-1.22 508 599 31 50 SAD 1BH

-1.00 509 600 32 50 3.69 MAN 1BH

-1.45

-1.11 0.34 510 601 33 50 2.55 MAN 1BH

-1.46

-1.40 0.06 511 602 34 50 SAD 1BH

-1.55 511 603 34 50 0.87 SAN 1BH

-3.65

-3.58 0.07 512 604 35 50 SAD 1BH

-1.56 512 605 35 50 0.89 SAN 1BH

-3.61

-3.54 0.07 513 606 37 50 SAD 1BH

-0.89 513 607 37 50 1.08 SAN 1BH

-3.59

-3.51 0.08 514 608 1

51 7.22 MAN 1BH

-3.70

-3.51 0.19 514 609 1

51 SAD 1BH

-1.13 515 610 3

51 2.59 MAN 1BH

-3.64

-3.53 0.11 515 611 3

51 SAD 1BH

-1.35 516 612 6

51 MAD 1BH

-1.02 517 613 10 51 2.27 MAN 1BH

-3.75

-3.65 0.10 517 614 10 51 SAD 1BH

-1.19 518 615 12 51 SAD 1BH

-1.17 519 616 13 51 MAD 1BH

-1.21 520 617 14 51 SAD 1BH

-1.06 521 618 16 51 SAD 1BH

-1.22 522 619 19 51 MAD 1BH

-1.03 523 620 21 51 SAD 1BH

-1.33 524 621 27 51 SAD 1BH

-0.95 525 622 28 51 SAD 1BH

-1.47 526 623 31 51 SAD 1BH

-1.03 527 624 32 51 3.27 SAN 1BH

-1.40

-1.26 0.14 Page 74 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 528 625 33 51 MAD 1BH

-0.90 529 626 37 51 0.86 MAN 1BH

-0.55

-0.28 0.27 529 627 37 51 SAD 1BH

-1.57 529 628 37 51 1.01 SAN 1BH

-3.71

-3.62 0.09 530 629 3

52 SAD 1BH

-1.35 531 630 9

52 SAD 1BH

-1.15 531 631 9

52 3.13 SAN 1BH

-3.66

-3.54 0.12 532 632 10 52 SAD 1BH

-1.07 532 633 10 52 1.98 SAN 1BH

-3.75

-3.65 0.10 533 634 12 52 SAD 1BH

-1.18 534 635 14 52 MAD 1BH

-1.02 535 636 19

  • 52 MAD 1BH

-0.97 536 637 20 52 SAD 1BH

-1.28 537 638 27 52 MAD 1BH

-0.92 538 639 28 52 2.24 MAN 1BH

-1.40

-1.29 0.11 539 640 32 52 MAD 1BH

-0.89 540 641 33 52 2.66 SAN 1BH

-1.54

-1.23 0.31 541 642 34 52 1.70 MAN 1BH

-3.80

-3.70 0.10 541 643 34 52 SAD 1BH

-0.90 542 644 37 52 SAD 1BH

-0.96 542 645 37 52 1.52 SAN 1BH

-3.63

-3.52 0.11 543 646 7

53 SAD 1BH

-1.02 543 647 7

53 2.23 SAN 1BH

-3.64

-3.54 0.10 544 648 14 53 SAD 1BH

-1.09 545 649 15 53 SAD 1BH

-0.87 546 650 18 53 SAD 1BH

-1.33 547 651 19 53 SAD 1BH

-1.12 548 652 21 53 MAD 1BH

-1.00 549 653 24 53 SAD 131BH

-1.46 550 654 25 53 0.85 SAN 1BH

-1.60

-1.47 0.13 551 655 32 53 SAD 1BH

-1.35 552 656 33 53 SAD 1BH

-1.34 553 657 34 53 1.83 MAN 1BH

-3.32

-3.20 0.12 553 658 34 53 SAD 1BH

-1.05 554 659 37 53 MAD 1BH

-0.93 554 660 37 53 2.53 MAN 1BH

-3.70

-3.50 0.20 555 661 40 53 3.52 MAN 1BH

-0.79

-0.15 0.64 555 662 40 53 SAD 1BH

-1.36 556 663 1

54 4.74 MAN 1BH

-3.75

-3.55 0.20 556 664 1

54 2.27 MAN 1BH

-1.00

-0.84 0.16 557 665 5

54 3.12 MAN 11BH

-3.62

-3.45 0.17 557 666 5

54 SAD 1BH

-1.03 558 667 7

54 SAD 131BH

-1.06 558 668 7

54 1.26 SAN 113-BH

-3.64

-3.57 0.07 559 669 9

54 MAD 1BH

-1.18 560 670 10 54 SAD 1131BH

-1.24 561 671 13 54 SAD 1BH

-1.31 562 672 14 54 MAD 1BH

-0.96 Page 75 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 563 673 15 54 SAD 1BH

-1.07 564 674 22 54 MAD 1BH

-1.28 565 675 23 54 1.46 SAN 11BH

-1.45

-1.37 0.08 566 676 24 54 SAD 1131BH

-1.46 567 677 25 54 SAD 1131BH

-1.33 568 678 27 54 SAD 11BH

-1.45 569 679 30 54 MAD 11BH

-0.85 570 680 32 54 MAD 11BH 3

-0.94 571 681 34 54 3.69 MAN 1BH 1-

-3.73

-3.58 0.15 571 682 34 54 1.82 SAN 11BH 3

-1.00

-0.92 0.08 572 683 37 54 SAD 1BH

-1.41 572 684 37 54 1.07 SAN 11BH 3

-3.71

-3.62 0.09 573 685 38 54 MAD 11BH 3

-1.04 574 686 1

55 0.18 SAN 1BH 1-

-0.77

-0.62 0.15 575 687 2

55 SAD 1BH 1-

-0.96 576 688 5

55 SAD 1BH 1-

-0.93 577 689 7

55 SAD 1BH

-1.10 577 690 7

55 2.00 SAN 1BH

-3.63

-3.56 0.07 578 691 9

55 SAD 1BH

-1.36 578 692 9

55 1.47 SAN 11BH

-3.61

-3.57 0.04 579 693 10 55 2.10 MAN 1BH

-1.23

-1.07 0.16 580 694 11 55 SAD 1BH

-0.97 581 695 16 55 SAD 1BH

-1.09 582 696 17 55 SAD 1BH

-1.19 583 697 18 55 MAD 1BH

-0.92 584 698 20 55 SAD 1BH

-1.23 585 699 23 55 0.65 SAN 131BH

-1.50

-1.44 0.06 586 700 24 55 SAD 131BH

-1.53 587 701 28 55 0.17 SVN 131BH

-2.49

-2.27 0.22 587 702 28 55 0.07 SVN 1BH

-1.56

-1.38 0.18 588 703 29 55 SAD 1BH

-1.39 589 704 32 55 SAD 1BH

-1.30 590 705 33 55 2.80 SAN 1BH

-1.54

-1.34 0.20 591 706 34 55 MAD 1BH

-1.04 591 707 34 55 4.00 MAN 1BH

-3.60

-3.35 0.25 592 708 1

56 3.92 MAN 1BH

-3.63

-3.51 0.12 592 709 1

56 SAD 11BH

-0.92 593 710 2

56 MAD 1BH

-0.96 593 711 2

56 2.15 MAN 1BH

-3.75

-3.60 0.15 594 712 5

56 SAD 1BH

-1.00 595 713 6

56 SAD 1BH

-1.26 596 714 7

56 SAD 1BH

-1.36 597 715 9

56 SAD 1BH

-1.28 598 716 10 56 MAD 1BH

-1.20 598 717 10 56 0.43 SAN 1BH

-3.84

-3.80 0.04 599 718 11 56 MAD 1BH

-1.19 600 719 12 56 MAD 1BH

-1.24 601 720 13 56 SAD 1BH

-1.41 Page 76 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 602 721 14 56 SAD 1BH

-1.02 603 722 16 56 SAD 1BH

-1.25 604 723 18 56 SAD 1BH

-0.80 605 724 27 56 SAD 1BH

-1.60 606 725 28 56 SAD 1BH

-1.55 607 726 29 56 SAD 1BH

-1.50 608 727 32 56 SAD 1BH

-1.28 609 728 34 56 4.18 MAN 1BH

-3.63

-3.41 0.22 609 729 34 56 SAD 1BH

-1.07 610 730 2

57 SAD 1BH

-0.81 611 731 3

57 1.94 MAN 1BH

-3.60

-3.52 0.08 611 732 3

57 SAD 1BH

-1.28 612 733 5

57 SAD 1BH

-1.37 612 734 5

57 1.44 SAN 1BH

-3.80

-3.65 0.15 613 735 7

57 1.83 SAN 1BH

-3.66

-3.55 0.11 613 736 7

57 2.95 SAN 1BH

-1.15

-1.01 0.14 614 737 10 57 SAD 1BH

-1.24 615 738 12 57 SAD 1BH

-0.88 616 739 14 57 MAD 1BH

-1.04 617 740 15 57 SAD 1BH

-1.06 618 741 18 57 MAD 1BH

-0.92 619 742 20 57 SAD 1BH

-1.05 620 743 23 57 SAD 1BH

-1.51 621 744 25 57 SAD 1BH

-1.44 622 745 27 57 SAD 1BH

-1.37 623 746 28 57 MAD 1BH

-1.41 624 747 29 57 MAD 1BH

-1.09 625 748 30 57 MAD 1BH

-1.11 626 749 32 57 SAD 1BH

-1.28 627 750 35 57 SAD 1BH

-1.00 628 751 36 57 SAD 1BH

-1.02 629 752 37 57 2.48 MAN 1BH

-3.77

-3.56 0.21 629 753 37 57 SAD 1BH

-0.85 630 754 39 57 SAD 1BH

-0.97 630 755 39 57 0.87 SAN 1BH

-3.59

-3.46 0.13 631 756 1

58 SAD 1BH

-1.30 632 757 3

58 SAD 1BH

-1.27 632 758 3

58 3.09 SAN 1BH

-3.78

-3.57 0.21 633 759 7

58 MAD 1BH

-1.21 633 760 7

58 1.37 SAN 1BH

-3.62

-3.51 0.11 634 761 10 58 SAD 1BH

-0.96 634 762 10 58 1.34 SAN 1BH

-3.75

-3.69 0.06 635 763 12 58 SAD 1BH

-1.00 636 764 14 58 SAD 1BH

-1.31 637 765 15 58 SAD 1BH

-0.97 638 766 16 58 SAD 1BH

-1.20 639 767 20 58 SAD 1BH

-1.40 640 768 21 58 SAD 1BH

-1.01 Page 77 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 641 769 22 58 SAD 1BH

-1.07 642 770 24 58 SAD 1BH

-1.51 643 771 27 58 SAD 1BH

-1.40 644 772 33 58 MAD 1BH

-0.90 645 773 37 58 1.79 MAN 1BH

-3.68

-3.55 0.13 645 774 37 58 2.62 SAN 1BH

-1.51

-1.32 0.19 646 775 2

59 SAD 11BH

-0.94 646 776 2

59 0.83 SAN 1BH

-3.71

-3.68 0.03 647 777 4

59 2.47 MAN 1BH

-3.77

-3.66 0.11 647 778 4

59 SAD 1BH

-1.26 648 779 5

59 SAD 1BH

-1.42 648 780 5

59 1.37 SAN 131BH

-3.63

-3.56 0.07 649 781 6

59 MAD 1131BH

-1.00 650 782 7

59 MAD 1BH

-0.96 650 783 7

59 1.62 SAN 1BH

-3.63

-3.53 0.10 651 784 11 59 MAD 1BH

-0.97 652 785 12 59 SAD 1BH

-1.08 653 786 13 59 SAD 1BH 1-

-1.01 654 787 16 59 MAD 1BH 3-

-1.16 654 788 16 59 0.61 SAN 1BH 3-

-0.43

-0.30 0.13 655 789 17 59 SAD 1BH 1-

-1.04 656 790 18 59 SAD 1BH

-1.03 657 791 19 59 SAD 1BH 1-

-1.01 658 792 22 59 SAD 1BH 3-

-1.43 659 793 23 59 0.54 SAN 1BH 1-

-1.47

-1.25 0.22 660 794 24 59 SAD 1BH

-1.51 661 795 25 59 SAD 1BH 1-

-1.40 662 796 27 59 SAD 1BH 1-

-1.41 663 797 28 59 3.14 MAN 1BH 1-

-1.55

-1.19 0.36 664 798 29 59 3.02 MAN 1BH

-0.69

-0.21 0.48 664 799 29 59 SAD 1BH

-1.51 665 800 30 59 1.98 MAN 1BH

-1.40

-1.32 0.08 666 801 31 59 SAD 1BH

-1.07 667 802 32 59 MAD 1BH

-0.85 668 803 34 59 1.69 MAN 1BH

-3.60

-3.49 0.11 668 804 34 59 SAD 1BH

-1.39 669 805 37 59 1.73 MAN 1BH

-3.93

-3.74 0.19 669 806 37 59 SAD 1BH

-1.01 670 807 5

60 SAD 1BH

-1.35 671 808 6

60 SAD 1BH

-1.34 671 809 6

60 1.14 SAN 1BH

-3.66

-3.55 0.11 672 810 7

60 SAD 1BH

-1.35 672 811 7

60 3.09 SAN 1BH

-3.67

-3.54 0.13 673 812 10 60 SAD 1BH

-1.17 673 813 10 60 1.46 SAN 11BH

-3.60

-3.48 0.12 674 814 11 60 SAD 1BH

-1.03 675 815 12 60 1.31 MVN 1BH

-2.51

-2.27 0.24 675 816 12 60 SAD 1BH

-0.99 Page 78 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 676 817 13 60 3.24 MAN 11BH

-0.67

-0.08 0.59 676 818 13 60 SAD 11BH-

-1.43 677 819 14 60 SAD 11BH-

-1.08 678 1820 15 160 1.65 MAN 113H-

-0.43

-0.18 0.25 678 821 15 60 SAD 11BH-

-1.26 679 822 16 60 SAD 1131-

-0.94 680 823 17 60 SAD 11BH-

-0.99 681 824 18 60 SAD 11BH-

-1.42 682 825 19 60 MAD 113H-

-1.41 683 826 23 60 SAD 1131-

-1.48 684 827 27 60 SAD 11BH-

-1.26 685 828 29 60 SAD 113H-

-1.41 686 829 32 60 2.15 SAN 1BH31-1

-1.41

-1.34 0.07 687 830 33 60 MAD 1131-1_

-1.03 688 831 37 60 SAD 1131-1_

-1.45 689 832 6

61 SAD 1131-1_

-0.80 689 833 6

61 2.98 SAN 1131-1_

-3.69

-3.58 0.11 690 834 7

61 MAD 1131-

-1.26 690 835 7

61 4.99 SAN 11BH-

-3.65

-3.54 0.11 691 836 9

61

____SAD 113H-

-1.03 691 837 9

61 1.47 SAN 11BH-

-3.59

-3.52 0.07 692 838 10 61 MAD 113H-

-0.93 692 839 10 61 0.91 MAN 113H-

-3.64

-3.61 0.03 693 840 11 61 SAD IBH

-1.05 693 841 11 61 2.08 SAN 113H-

-3.64

-3.51 0.13 694 842 12 61

____SAD 1131-

-1.29 695 843 13 61

____MAD 113H

-1.53 696 844 14 61

____MAD 1BH

-1.11 697 845 15 61

____SAD 1131-

-0.85 698 846 16 61

____SAD 11BH-

-1.10 699 847 17 61

____MAD 11H1-1

-1.08 700 848 18 61

____MAD 1131-

-1.43 701 849 19 61

____SAD 113H-

-1.02 702 850 20 61 SAD 1131-

-1.35 703 851 21 61 SAD 113H-

-0.91 704 852 25 61 SAD 11BH-

-1.50 705 853 26 61 SAD 113H-

-1.14 706 854 27 61

____MAD 113H-

-1.44 706 855 27 61 2.50 MAN 113H-

-0.63

-0.11 0.52 707 856 32 61

____SAD 1131H

-1.47 708 857 33 61 MAD 113H-

-0.93 709 858 37 61 SAD 113H-

-0.85 710 859 39 61

____SAD 113H-

-0.98 711 860 1

62

____MAD 1131-

-1.07 711 861 1

62 16.29 MAN 11BH-

-3.75

-3.60 0.15 712 862 5

62 MAD 1131-

-1.62 713 863 7

62

____SAD 113H-

-1.23 713 864 17 62 1.57 SAN 1131H

-3.58

-3.52 0.06 Page 79 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 714 865 10 62 SAD 1BH

-1.38 715 866 11 62 SAD 1BH

-1.15 715 867 11 62 1.46 SAN 1BH

-3.60

-3.53 0.07 716 868 12 62 SAD 1BH

-1.42 717 869 14 62 SAD 1BH

-0.99 718 870 15 62 SAD 1BH

-0.99 719 871 16 62 MAD 1BH

-1.17 719 872 16 62 2.47 MAN 1BH

-0.54

-0.34 0.20 720 873 18 62 SAD 1BH

-1.34 721 874 23 62 MAD 1BH

-1.55 722 875 24 62 SAD 1BH

-1.36 723 876 25 62 1.73 MAN 1BH

-3.11

-2.93 0.18 723 877 25 62 SAD 1BH

-1.45 723 878 25 62 6.50 SAN 1BH

-0.77

-0.14 0.63 724 879 27 62 SAD 1BH

-0.95 725 880 29 62 SAD 1BH

-1.16 726 881 31 62 MAD 1BH

-1.03 727 882 34 62 3.35 MAN 1BH

-3.71

-3.55 0.16 727 883 34 62 SAD 1BH

-1.46 728 884 37 62 2.39 MAN 1BH

-3.66

-3.32 0.34 728 885 37 62

  • 1.53 SAN 1BH

-1.40

-1.25 0.15 729 886 42 62 3.70 MAN 1BH

-0.81

-0.14 0.67 729 887 42 62 SAD 1BH

-1.26 729 888 42 62 1.06 SAN 1BH

-3.59

-3.53 0.06 730 889 1

63 SAD 1BH

-1.24 730 890 1

63 3.85 SAN 1BH

-3.62

-3.52 0.10 731 891 7

63 SAD 1BH

-1.19 731 892 7

63 2.93 SAN 1BH

-3.78

-3.67 0.11 732 893 9

63 MAD 1BH

-1.02 732 894 9

63 1.74 SAN 1BH

-3.47

-3.39 0.08 733 895 10 63 SAD 1BH

-0.85 733 896 10 63 0.94 SAN 1BH

-3.72

-3.62 0.10 734 897 12 63 SAD 131BH

-1.41 735 898 13 63 SAD 1131BH

-1.05 736 899 15 63 SAD 1BH

-0.98 737 900 18 63 2.94 MAN 1BH

-3.59

-3.52 0.07 737 901 18 63 0.08 MAN 113-BH

-1.10

-1.01 0.09 738 902 21 63 SAD 1131BH

-1.09 739 903 23 63 SAD 11BH

-1.16 740 904 24 63 SAD 1BH

-1.38 741 905 25 63 0.44 SAN 1BH

-1.55

-1.47 0.08 742 906 31 63 SAD 131BH

-1.08 743 907 33 63 SAD 1BH

-1.52 744 908 37 63 2.05 MAN 131BH

-3.75

-3.55 0.20 744 909 37 63 1.51 SAN 1BH

-1.42

-1.39 0.03 745 910 42 63 SAD 1BH

-1.15 746 911 1

64 1.07 MAN 1BH

-3.68

-3.54 0.14 746 912 1

64 SAD 1BH

-1.21 Page 80 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 747 913 4

64 SAD 1BH

-1.14 748 914 6

64 SAD 131BH

-1.02 748 915 6

64 3.64 SAN 1BH

-3.73

-3.48 0.25 749 916 7

64 6.37 SAN 131BH

-3.66

-3.38 0.28 749 917 7

64 0.61 SAN 1BH

-1.71

-1.50 0.21 750 918 9

64 2.45 SAN 131BH

-3.63

-3.49 0.14 750 919 9

64 3.32 SAN 1BH13-

-1.20

-1.08 0.12 751 920 11 64 SAD 1BH13-

-0.96 752 921 13 64 MAD 1BH

-0.98 753 922 15 64 SAD 1BH

-1.06 754 923 18 64 SAD 1BH

-1.30 755 924 19 64 MAD 1BH

-1.26 756 925 21 64 0.63 SAN 1BH

-1.39

-1.32 0.07 757 926 27 64 SAD 1BH

-0.89 758 927 32 64 MAD 1BH

-1.50 759 928 33 64 MAD 1BH

-0.88 760 929 34 64 0.79 MAN 1BH

-3.67

-3.37 0.30 760 930 34 64 0.47 MAN 131BH

-1.51

-1.28 0.23 761 931 37 64 0.63 MAN 1BH

-3.75

-3.38 0.37 761 932 37 64 SAD 1BH

-1.18 762 933 6

65 MAD 1BH

-1.27 763 934 7

65 1.07 MAN 1BH

-3.62

-3.45 0.17 763 935 7

65 SAD 1BH

-0.72 764 936 8

65 SAD 1BH

-1.18 764 937 8

65 2.79 SAN 1BH

-3.63

-3.49 0.14 765 938 10 65 2.05 MAN 131BH

-1.20

-1.09 0.11 765 939 10 65 0.80 SAN 1BH

-3.60

-3.51 0.09 766 940 11 65 SAD 1BH

-1.33 767 941 12 65 1.60 MAN 1BH

-1.35

-1.09 0.26 767 942 12 65 1.60 SAI 1BH

-1.25

-1.16 0.09 768 943 13 65 MAD 1BH 3-

-0.99 769 944 17 65 SAD f BH 13-

-1.01 770 945 25 65 SAD 1BH 3-

-0.98 771 946 26 65 SAD 1BH

-1.26 772 947 27 65 1.97 SAN 1BH 3-

-1.40

-1.32 0.08 773 948 31 65 MAD 1BH 1-

-0.93 774 949 33 65 SAD 1BH 1-

-1.49 775 950 34 65 4.68 MAN 1BH 1-

-3.95

-3.66 0.29 775 951 34 65 SAD 1BH

-1.23 776 952 9

66 2.73 MAN 1BH

-3.74

-3.46 0.28 776 953 9

66 SAD 1BH

-1.15 777 954 10 66 SAD 1BH

-1.00 778 955 11 66 2.87 MAN 1BH

-1.26

-1.07 0.19 779 956 13 66 SAD 1BH 1-

-1.28 780 957 14 66 0.37 MAN 1BH

-1.05

-0.98 0.07 781 958 15 66 MAD 1BH

-0.99 782 959 18 66 1.72 MAN 1BH

-2.70

-2.55 0.15 782 960 18 66 SAD 1BH

-1.00 Page 81 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 783 961 20 66 MAD 1BH

-1.27 784 962 21 66 MAD 1BH

-1.03 785 963 22 66 SAD 11BH

-1.47 786 964 31 66 SAD 11BH

-1.50 787 965 32 66 MAD 11BH

-0.96 788 966 34 66 SAD 11BH

-0.90 789 967 37 66 3.03 MAN 1BH

-3.74

-3.52 0.22 789 968 37 66 SAD 1BH

-1.31 789 969 37 66 0.25 SVN 1BH

-1.37

-1.18 0.19 790 970 3

67 MAD 1BH

-1.08 791 971 7

67 SAD 1BH

-1.31 792 972 9

67 4.29 MAN 1BH 1-

-1.41

-0.98 0.43 792 973 9

67 0.96 SAN 1BH 1-

-3.67

-3.54 0.13 793 974 17 67 SAD 1BH

-1.39 794 975 19 67 SAD 1BH

-0.98 795 976 20 67 SAD 11BH

-1.27 796 977 21 67 SAD 1BH

-0.88 797 978 27 67 3.90 MAN 1BH

-1.33

-1.11 0.22 798 979 30 67 0.49 SAN 1BH

-1.49

-1.39 0.10 799 980 31 67 SAD 1BH

-1.00 800 981 34 67 4.51 MAN 1BH

-3.65

-3.42 0.23 800 982 34 67 SAD 1 BH

-1.48 801 983 37 67 4.22 MAN 1BH

-3.75

-3.46 0.29 801 984 37 67 0.69 MAN 1BH

-0.44

-0.22 0.22 801 985 37 67 SAD 1BH

-1.45 802 986 8

68 0.24 MAN 1BH

-1.07

-0.95 0.12 802 987 8

68 5.56 SAN 1BH

-3.62

-3.48 0.14 803 988 9

68 3.08 MAN 31-BH1

-0.64

-0.04 0.60 803 989 9

68 SAD 131BH

-1.59 804 990 10 68 SAD 1BH

-1.24 805 991 11 68 SAD 1BH

-0.89 806 992 13 68 SAD 1BH

-1.17 807 993 14 68 MAD 1BH

-0.92 808 994 19 68 SAD 1BH

-0.82 809 995 21 68 MAD 1BH

-1.33 810 996 25 68 MAD 1BH

-1.04 811 997 27 68 4.27 SAN 1BH

-1.43

-1.31 0.12 812 998 29 68 SAD 1BH

-0.98 813 999 30 68 MAD 1BH

-0.92 814 1000 31 68 SAD 1BH

-0.90 815 1001 32 68 SAD 1BH

-1.32 816 1002 33 68 SAD 1BH

-1.27 817 1003 34 68 MAD 1BH

-1.09 817 1004 34 68 4.75 MAN 1BH

-3.74

-3.49 0.25 818 1005 37 68 7.48 MAN 1BH

-3.83

-3.48 0.35 818 1006 37 68 2.50 MAN 1BH

-1.50

-1.31 0.19 819 1007 3

69 SAD 1BH

-0.97 819 1008 3

69 1.61 SAN 1BH

-3.51

-3.40 0.11 Page 82 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 820 1009 6

69 SAD 1BH

-0.94 821 1010 7

69 SAD 1BH

-0.75 822 1011 9

69 1.48 MAN 1BH

-3.80

-3.66 0.14 822 1012 9

69 SAD 1BH

-1.34 823 1013 13 69 MAD 1BH

-0.93 824 1014 14 69 SAD 1BH

-0.99 825 1015 15 69 MAD 1BH

-0.94 826 1016 16 69 MAD 1BH

-1.30 827 1017 17 69 0.37 SAN 1BH

-1.09

-1.00 0.09 828 1018 18 69 MAD 131BH

-1.10 829 1019 19 69 SAD 1BH

-0.85 830 1020 21 69 SAD 131BH

-0.86 831 1021 25 69 1.76 MAN 1BH

-1.30

-1.16 0.14 832 1022 27 69 SAD 1BH

-1.51 833 1023 31 69 SAD 1131BH

-1.46 834 1024 32 69 SAD 1131BH

-1.15 835 1025 34 69 MAD 113-BH

-0.99 835 1026 34 69 1.84 SAN 113-BH

-3.52

-3.37 0.15 836 1027 37 69 3.38 MAN 1BH

-3.78

-3.57 0.21 836 1028 37 69 SAD 1BH

-1.43 837 1029 3

70 SAD 1BH

-0.99 838 1030 4

70 SAD 1BH

-1.06 839 1031 9

70 1.95 SAN 1BH

-3.64

-3.52 0.12 839 1032 9

70 0.32 SAN 1BH

-1.14

-1.09 0.05 840 1033 10 70 SAD 1131BH

-1.10 840 1034 10 70 2.37 SAN 131BH

-3.74

-3.61 0.13 841 1035 11 70 SAD 1131BH

-0.95 841 1036 11 70 0.57 SAN 1BH

-3.69

-3.62 0.07 842 1037 13 70 SAD 1BH

-0.91 843 1038 14 70 MAD 1BH

-1.00 844 1039 16 70 SAD 1BH

-1.07 845 1040 18 70 SAD 1BH 3-

-1.05 846 1041 19 70 SAD 1BH 1-

-0.99 847 1042 21 70 SAD 11BH 3

-1.47 848 1043 22 70 SAD 1BH 1-

-1.19 849 1044 23 70 SAD 1BH 1-

-1.14 850 1045 27 70 3.05 SAN 1BH 1-

-1.54

-1.34 0.20 851 1046 31 70 2.26 MAN 1BH

-0.49

-0.22 0.27 851 1047 31 70 0.27 SAN IBH

-1.05

-0.93 0.12 852 1048 4

71 SAD 1BH

-0.90 852 1049 4

71 0.62 SAI 1BH

-0.32

-0.09 0.23 853 1050 5

71 SAD 1BH

-0.81 854 1051 9

71 MAD 1BH 1-

-0.90 854 1052 9

71 3.17 SAN 1BH

-3.77

-3.48 0.29 855 1053 10 71 MAD 1BH

-1.02 856 1054 12 71 MAD 1BH

-1.11 857 1055 13 71 MAD 1BH

-0.98 858 1056 14 71 SAD 1BH

-1.36 Page 83 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 859 1057 15 71 SAD 1BH

-1.04 860 1058 18 71 SAD 1131BH

-1.28 861 1059 22 71 MAD 1BH

-1.24 861 1060 22 71 3.77 MAN 1BH

-3.73

-3.43 0.30 862 1061 23 71 MAD 1BH

-1.42 862 1062 23 71 3.68 MAN 1BH

-3.75

-3.58 0.17 863 1063 28 71 SAD 1BH

-0.80 864 1064 32 71 SAD 1131BH

-1.17 865 1065 35 71 SAD 1BH

-0.97 866 1066 37 71 SAD 1BH

-1.05 866 1067 37 71 0.87 SAN 1BH

-3.88

-3.82 0.06 867 1068 8

72 SAD 1BH

-1.28 867 1069 8

72 2.10 SAN 11BH

-3.90

-3.85 0.05 868 1070 9

72 MAD 1BH

-1.20 868 1071 9

72 1.38 SAN 1BH

-3.66

-3.59 0.07 869 1072 11 72 MAD 1BH

-1.28 870 1073 12 72 5.00 MAN 1BH

-1.12

-1.01 0.11 871 1074 13 72 SAD 1BH

-1.37 872 1075 15 72 SAD 1BH

-1.09 873 1076 20 72 MAD 1BH

-0.98 874 1077 27 72 MAD 1BH

-1.32 875 1078 31 72 SAD 1BH

-0.91 876 1079 34 72 SAD 11BH

-1.01 876 1080 34 72 2.97 SAN 1BH 3-

-3.74

-3.64 0.10 877 1081 9

73 SAD 1BH 3-

-1.27 878 1082 13 73 MAD 1BH 3-

-1.30 879 1083 23 73 SAD 1BH

-1.00 880 1084 25 73 SAD 1BH

-1.49 881 1085 31 73 SAD 1BH

-1.01 882 1086 4

74 MAD 1BH

-0.90 882 1087 4

74 1.51 MAN 1BH 1-

-3.65

-3.57 0.08 883 1088 9

74 SAD 1BH

-1.01 884 1089 12 74 4.04 MAN 1BH

-0.78

-0.40 0.38 884 1090 12 74 SAD 1BH

-1.34 885 1091 13 74 SAD 1BH 1-

-1.00 886 1092 14 74 MAD 1BH 1-

-1.34 887 1093 18 74 4.26 MAN 1BH

-0.70

-0.05 0.65 887 1094 18 74 SAD 1BH

-0.94 888 1095 24 74 SAD 1BH

-1.54 889 1096 25 74 SAD 1BH

-0.97 890 1097 27 74 MAD 1BH

-1.14 891 1098 34 74 SAD 1BH

-0.99 892 1099 4

75 2.99 MAN 1BH

-3.69

-3.56 0.13 892 1100 4

75 SAD 1BH

-1.39 893 1101 9

75 SAD 1BH

-1.02 893 1102 9

75 4.38 SAN 1BH

-3.59

-3.50 0.09 894 1103 10 75 MAD 1BH

-1.24 895 1104 13 75 2.71 SAN 1BH

-1.26

-1.05 0.21 Page 84 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 896 1105 15 75 MAD 1BH

-1.30 897 1106 17 75 SAD 1BH

-1.07 898 1107 19 75 SAD 1BH

-0.99 899 1108 27 75 MAD 1BH

-0.90 900 1109 4

76 MAD 1BH

-0.85 900 1110 4

76 1.61 SAN 1BH

-3.52

-3.44 0.08 901 1111 8

76 SAD 1BH

-1.29 901 1112 8

76 0.69 SAN 1BH

-3.86

-3.79 0.07 902 1113 9

76 SAD 1BH

-1.18 902 1114 9

76 3.54 SAN 1BH

-3.49

-3.40 0.09 903 1115 10 76 SAD 1BH

-1.00 904 1116 13 76 SAD 1BH

-1.48 905 1117 14 76 MAD 1BH

-0.89 906 1118 18 76 SAD 131BH

-1.42 907 1119 20 76 SAD 1BH

-1.38 908 1120 26 76 MAD 1BH

-1.50 909 1121 8

77 SAD 1BH

-1.26 910 1122 9

77 SAD 1BH

-0.85 911 1123 11 77 SAD 1BH

-1.39 912 1124 13 77 3.74 SAN 1BH

-1.25

-1.17 0.08 913 1125 14 77 4.63 MAN 131BH

-0.49

-0.12 0.37 913 1126 14 77 SAD 1BH

-1.30 914 1127 15 77 SAD 1BH

-1.33 915 1128 16 77 MAD 1BH

-1.27 916 1129 19 77 SAD 1BH

-0.84 917 1130 23 77 SAD 1BH

-1.00 918 1131 25 77 SAD 1BH

-0.94 919 1132 9

78 MAD 1BH

-1.03 920 1133 12 78 SAD 1BH

-0.95 921 1134 14 78 SAD 1BH

-0.85 922 1135 15 78 MAD 1BH

-0.92 922 1136 15 78 1.06 MAI 1BH

-0.69

-0.23 0.46 923 1137 16 78 SAD 1BH

-0.88 924 1138 17 78 SAD 1BH

-1.40 925 1139 19 78 SAD 131BH

-0.98 926 1140 25 78 SAD 131BH

-1.02 927 1141 26 78 3.51 MAN 131BH

-1.14

-0.90 0.24 928 1142 27 78 SAD 113-BH

-0.95 929 1143 17 79 MAD 1BH

-1.12 930 1144 19 79 SAD 131BH

-1.20 931 1145 20 79 SAD 131BH

-0.80 932 1146 22 79 SAD 1BH

-1.31 933 1147 25 79 SAD 1BH

-1.36 934 1148 26 79 SAD 1BH

-1.49 935 1149 9

80 4.76 MAN 1BH

-3.73

-3.59 0.14 935 1150 9

80 3.07 MAN 1BH

-1.26

-1.14 0.12 936 1151 10 80 MAD 1BH

-1.36 936 1152 10 80 1.06 SAN 1BH

-3.75

-3.69 0.06 Page 85 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 937 1153 12 80 MAD 1BH

-1.36 938 1154 14 80 SAD 1BH

-0.91 939 1155 16 80 SAD 1BH

-0.73 940 1156 18 80 SAD 1BH

-1.02 941 1157 22 80 MAD 1BH

-1.00 942 1158 23 80 SAD 1BH

-1.40 943 1159 26 80 SAD 1BH

-0.95 944 1160 4

81 SAD 1BH

-0.85 944 1161 4

81 0.65 SAN 1BH

-3.66

-3.54 0.12 945 1162 9

81 MAD 1BH

-1.30 945 1163 9

81 0.99 SAN 1BH

-3.67

-3.53 0.14 946 1164 10 81 SAD 1BH

-1.00 947 1165 11 81 SAD 1BH

-1.11 948 1166 12 81 SAD 1BH

-0.88 949 1167 15 81 MAD 1BH

-0.94 950 1168 17 81 SAD 1BH

-11.06 951 1169 19 81 SAD 1BH

-0.96 952 1170 9

82 MAD 1BH

-1.04 953 1171 10 82 MAD 1BH

-0.89 953 1172 10 82 0.54 MAN 1BH

-3.59

-3.50 0.09 954 1173 12 82 SAD 1BH

-1.30 955 1174 13 82 MAD 1BH

-1.00 956 1175 19 82 MAD 1BH

-0.99 957 1176 22 82 SAD IBH

-1.04 958 1177 3

83 SAD 1BH

-0.93 959 1178 4

83 SAD 1BH

-0.85 959 1179 4

83 1.75 SAN IBH

-3.69

-3.58 0.11 960 1180 5

83 MAD 1BH

-0.80 961 1181 13 83 MAD 1BH

-1.00 962 1182 14 83 MAD 1BH

-0.95 962 1183 14 83 0.60 SAN 1BH

-2.43

-2.39 0.04 963 1184 15 83 SAD 1BH

-0.90 964 1185 16 83 SAD 1BH

-0.91 965 1186 17 83 SAD 1BH

-0.86 966 1187 23 83 SAD 1BH

-0.91 967 1188 25 83 MAD 1BH

-1.02 968 1189 26 83 SAD 1BH

-0.90 969 1190 7

84 SAD 1BH

-0.86 969 1191 7

84 1.49 SAN 1BH

-3.60

-3.54 0.06 970 1192 9

84 SAD 1BH

-0.96 971 1193 10 84 SAD 1BH

-1.48 972 1194 12 84 SAD 1BH

-0.95 973 1195 13 84 SAD 1BH

-0.95 974 1196 14 84 MAD 1BH

-0.88 975 1197 15 84 SAD 1BH

-1.48 976 1198 16 84 SAD 1BH

-0.95 977 1199 17 84 MAD 1BH

-0.98 978 1200 18 84 MAD 1BH

-0.92 Page 86 of 169

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 979 1201 19 84 SAD 1BH

-0.99 980 1202 20 84 SAD 1BH

-0.92 981 1203 22 84 SAD 1BH

-0.95 982 1204 10 85 SAD 1BH

-0.92 983 1205 12 85 SAD 11BH

-1.45 984 1206 13 85 SAD 1BH

-1.16 985 1207 19 85 SAD 1BH

-0.91 986 1208 21 85 SAD 1BH

-0.98 987 1209 4

86 SAD 1BH

-0.80 988 1210 10 86 SAD 1BH

-0.80 989 1211 12 86 SAD 1BH

-0.92 990 1212 14 86 MAD 1BH

-0.89 991 1213 16 86 SAD 1BH

-1.11 992 1214 17 86 MAD 1BH

-0.87 993 1215 18 86 0.10 SCD IBH

-1.02 994 1216 21 86 SAD 1BH

-0.98 995 1217 10 87 SAD 1BH

-0.97 996 1218 12 87 SAD 1BH

-0.93 997 1219 14 87 SAD 1BH

-0.83 998 1220 15 87 SAD 1BH

-1.05 999 1221 17 87 SAD 1BH

-1.42 999 1222 17 87 1.39 SAN 1BH

-1.01

-0.97 0.04 1000 1223 12 88 SAD 1BH

-0.94 1001 1224 15 88 5.06 MAN 1BH

-3.71

-3.51 0.20 1001 1225 15 88 SAD 1BH

-0.86 1002 1226 18 89 SAD IBH

-0.95 Page 87 of 169

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 4

2 MAD 2BH

-3.06 1

2 4

2 3.56 MAN 2BH

-2.38

-1.98 0.40 2

3 3

3 1.32 MAN 2BH

-0.81

-0.75 0.06 2

4 3

3 SAD 2BH

-3.53 2

5 3

3 1.93 SAN 2BH

-5.78

-5.71 0.07 3

6 13 9

1.78 MAN 2BH

-0.81

-0.67 0.14 3

7 13 9

SAD 2BH

-3.27 3

8 13 9

2.93 SAN 2BH

-5.70

-5.57 0.13 4

9 12 10 2.09 MAN 2BH

-0.81

-0.68 0.13 4

10 12 10 SAD 2BH

-3.25 4

11 12 10 3.41 SAN 2BH

-5.74

-5.47 0.27 5

12 20 10 SAD 2BH

-3.33 5

13 20 10 0.82 SAN 2BH

-0.77

-0.70 0.07 6

14 2

11 6.66 MAN 2BH

-5.66

-5.49 0.17 6

15 2

11 1.88 MAN 2BH

-0.96

-0.71 0.25 6

16 2

11 SAD 21H

-2.90 7

17 7

12 3.92 MAN 2BH

-5.62

-5.46 0.16 7

18 7

12 SAD 2BH

-3.07 7

19 7

12 1.12 SAN 2BH

-0.91

-0.85 0.06 8

20 14 12 5.43 MAN 2BH

-5.67

-5.39 0.28 8

21 14 12 3.37 MAN 2BH

-3.26

-2.90 0.36 8

22 14 12 2.13 SAN 2BH

-0.94

-0.70 0.24 9

23 22 12 SAD 2BH

-3.40 9

24 22 12 1.40 SAN 2BH

-5.65

-5.57 0.08 9

25 22 12 0.68 SAN 2BH

-0.85

-0.79 0.06 10 26 2

13 8.88 MAN 2BH

-5.67

-5.48 0.19 10 27 2

13 4.59 MAN 2BH

-3.35

-2.85 0.50 10 28 2

13 0.92 SAN 2BH

-0.85

-0.79 0.06 11 29 4

14 MAD 2BH

-3.22 11 30 4

14 3.27 MAN 2BH

-5.57

-5.42 0.15 11 31 4

14 0.95 SAN 2BH

-0.73

-0.65 0.08 12 32 5

14 2.90 MAN 2BH

-5.73

-5.50 0.23 12 33 5

14 SAD 2BH

-4.14 12 34 5

14 1.33 SAN 2BH

-0.79

-0.72 0.07 13 35 13 15 3.55 MAN 2BH

-3.43

-3.02 0.41 13 36 13 15 2.12 SAN 2BH

-0.94

-0.74 0.20 14 37 16 15 2.03 MAN 2BH

-3.20

-3.07 0.13 14 38 16 15 8.41 SAN 2BH

-5.70

-5.25 0.45 14 39 16 15 2.87 SAN 2BH

-0.94

-0.70 0.24 15 40 18 15 2.32 MAN 2BH

-3.05

-2.93 0.12 15 41 18 15 1.28 SAN 2BH

-0.90

-0.72 0.18 16 42 1

16 8.62 MAN 2BH

-5.62

-5.32 0.30 16 43 1

16 SAD 2BH

-3.34 16 44 1

16 1.43 SAN 2BH

-0.74

-0.61 0.13 17 45 8

16 5.16 MAN 2BH

-5.83

-5.63 0.20 17 46 8

16 0.40 SAI 2BH

-3.22

-3.15 0.07 17 47 8

16 1.97 SAN 2BH

-0.86

-0.76 0.10 18 48 17 16 SAD 2BH

-3.28 Page 88 of 169

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 18 49 17 16 0.83 SAN 2BH

-5.70

-5.66 0.04 18 50 17 16 1.73 SAN 2BH

-0.82

-0.73 0.09 19 51 24 16 MAD 2BH

-3.39 19 52 24 16 5.71 MAN 2BH

-5.81

-5.67 0.14 19 53 24 16 1.24 SAN 2BH

-0.80

-0.73 0.07 20 54 1

17 3.72 MAN 2BH

-3.44

-3.00 0.44 20 55 1

17 1.22 MAN 2BH

-0.88

-0.80 0.08 21 56 2

17 4.96 MAN 2BH

-5.60

-5.45 0.15 21 57 2

17 SAD 2BH

-3.40 21 58 2

17 2.97 SAN 2BH

-0.74

-0.62 0.12 22 59 18 17 SAD 2BH

-3.29 22 60 18 17 3.28 SAN 2BH

-0.68

-0.58 0.10 23 61 19 17 SAD 2BH

-3.32 23 62 19 17 3.65 SAN 2BH

-0.77

-0.67 0.10 24 63 25 17 MAD 2BH

-3.75 24 64 25 17 5.21 MAN 2BH

-5.67

-5.27 0.40 24 65 25 17 5.59 MAN 2BH

-2.77

-2.60 0.17 24 66 25 17 1.64 MAN 2BH

-0.61

-0.50 0.11 25 67 3

18 2.01 SAN 2BH

-3.23

-3.15 0.08 25 68 3

18 0.90 SAN 2BH

-2.46

-2.38 0.08 25 69 3

18 2.11 SAN 2BH

-0.88

-0.73 0.15 26 70 13 18 SAD 2BH

-3.30 26 71 13 18 1.56 SAN 2BH

-0.91

-0.84 0.07 27 72 31, 18 SAD 2BH

-3.22 27 73 31 18 0.80 SAN 2BH

-0.80

-0.73 0.07 28 74 33 18 1.64 MAN 2BH

-5.76

-5.66 0.10 28 75 33 18 0.94 MAN 2BH

-3.22

-3.14 0.08 28 76 33 18 0.91 MAN 2BH

-2.22

-2.12 0.10 29 77 1

19 1.48 MAN 2BH

-5.70

-5.48 0.22 29 78 1

19 5.65 MAN 2BH

-3.21

-3.10 0.11 29 79 1

19 1.86 SAN 2BH 1-

-0.80

-0.70 0.10 30 80 6

19 5.50 MAN 2BH

-5.54

-5.33 0.21 30 81 6

19 SAD 2BH

-3.47 30 82 6

19 1.36 SAN 2BH

-0.82

-0.73 0.09 31 83 8

19 2.73 MAN 2BH

-5.65

-5.54 0.11 31 84 8

19 SAD 2BH

-3.32 31 85 8

19 1.77 SAN 2BH

-0.79

-0.72 0.07 32 86 22 19 MAD 2BH

-2.93 32 87 22 19 5.88 MAN 2BH

-5.75

-5.52 0.23 32 88 22 19 2.25 SAN 2BH

-0.79

-0.69 0.10 33 89 23 19 SAD 2BH

-3.06 33 90 23 19 2.13 SAN 2BH

-0.83

-0.76 0.07 34 91 33 19 2.29 MAN 2BH

-0.87

-0.74 0.13 34 92 33 19 SAD 2BH

-3.38 35 93 4

20 SAD 2BH

-2.95 35 94 4

20 1.87 SAN 2BH

-0.89

-0.78 0.11 36 95 13 20 3.01 MAN 2BH

-3.29

-3.07 0.22 36 96 13 20 1.88 MAN 2BH

-0.97

-0.85 0.12 Page 89 of 169

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 37 97 16 20 SAD 2BH

-3.20 37 98 16 20 3.39 SAN 2BH

-0.80

-0.70 0.10 38 99 17 20 1.69 MAN 2BH

-3.03

-2.91 0.12 38 100 17 20 3.82 SAN 2BH

-0.87

-0.73 0.14 39 101 18 20 1.72 MAN 2BH

-5.64

-5.48 0.16 39 102 18 20 SAD 2BH

-3.29 39 103 18 20 2.19 SAN 2BH

-0.71

-0.63 0.08 40 104 19 20 1.04 MAN 2BH

-0.76

-0.71 0.05 40 105 19 20 SAD 2BH

-3.40 40 106 19 20 1.86 SAN 2BH

-5.70

-5.62 0.08 40 107 19 20 0.85 SAN 2BH

-2.42

-2.34 0.08 41 108 29 20 1,00 MAN 2BH

-3.19

-3.07 0.12 41 109 29 20 0.62 SAN 2BH

-5.52

-5.49 0.03 41 110 29 20 1.13 SAN 2BH

-0.79

-0.72 0.07 42 111 35 20 SAD 2BH

-3.27 42 112 35 20 2.38 SAN 2BH

-0.78

-0.66 0.12 43 113 37 20 MAD 2BH

-3.35 43 114 37 20 2.19 MAN 2BH

-0.85

-0.77 0.08 44 115 6

21 6.32 MAN 2BH

-5.58

-5.31 0.27 44 116 6

21 0.58 SAN 2BH

-3.23

-3.16 0.07 44 117 6

21 0.94 SAN 2BH

-2.70

-2.60 0,10 44 118 6

21 0.66 SAN 2BH

-2.54

-2.44 0.10 44 119 6

21 3.39 SAN 2BH

-0.86

-0.76 0.10 45 120 11 21 SAD 2BH

-3.21 45 121 11 21 1.43 SAN 2BH

-0.82

-0.74 0.08 46 122 12 21 MAD 2BH

-3.27 46 123 12 21 1.17 SAN 2BH

-0.88

-0.84 0.04 47 124 16 21 1.24 MAN 2BH

-3.21

-3.07 0.14 47 125 16 21 4.60 SAN 2BH

-5.68

-5.53 0.15 47 126 16 21 3.26 SAN 2BH

-0.85

-0.71 0.14 48 127 17 21 1.66 MAN 2BH

-3.15

-3.04 0.11 48 128 17 21 2.71 SAN 2BH

-5.62

-5.52 0.10 48 129 17 21 1.24 SAN 2BH

ý-0.80

-0.70 0.10 49 130 23 21 MAD 2BH

-3.41 49 131 23 21 1.71 MAN 2BH

-5.69

-5.58 0.11 49 132 23 21 1.70 MAN 2BH

-0.95

-0.80 0.15 50 133 27 21 1.32 MAN 2BH

-0.73

-0.65 0.08 50 134 27 21 SAD 2BH

-3.47 50 135 27 21 1.34 SAN 2BH

-5.55

-5.44 0.11 51 136 31 21 SAD 2BH

-3.27 51 137 31 21 4.91 SAN 2BH

-5.57

-5.33 0.24 51 138 31 21 3.68 SAN 2BH

-0.82

-0.70 0.12 52 139 1

22 10.10 MAN 2BH

-5.73

-5.27 0.46 52 140 1

22 4.07 MAN 22BH

-3.22

-3.11 0.11 52 141 1

22 1.01 MAN 2BH

-0.73

-0.66 0.07 53 142 2

22 3.38 MAN 2BH

-2.96

-2.81 0.15 53 143 2

22 2.54 MAN 2BH

-0.71

-0.57 0.14 54 144 8

22 6.34 MAN 2BH

-5.64

-5.53 0.11 Page 90 of 169

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 54 145 8

22 2.41 MAN 2BH

-3.30

-3.09 0.21 54 146 8

22 3.01 SAN 2BH

-0.92

-0.81 0.11 55 147 37 22 MAD 2BH

-3.49 55 148 37 22 1.72 MAN 2BH

-0.83

-0.75 0.08 56 149 3

23 5.10 MAN 2BH

-3.15

-3.01 0.14 56 150 3

23 1.15 MAN 2BH

-0.82

-0.74 0.08 57 151 8

23 MAD 2BH

-3.30 57 152 8

23 3.38 MAN 2BH

-5.68

-5.54 0.14 57 153 8

23 1.20 SAN 2BH

-0.79

-0.75 0.04 58 154 12 23 MAD 2BH

-3.21 58 155 12 23 3.35 SAN 2BH

-0.79

-0.68 0.11 59 156 14 23 2.49 MAN 2BH

-3.23

-3.09 0.14 59 157 14 23 2.72 MAN 2BH

-0.89

-0.78 0.11 60 158 17 23 MAD 2BH

-3.30 60 159 17 23 5.57 SAN 2BH

-0.82

-0.72 0.10 61 160 24 23 MAD 2BH

-2.83 61 161 24 23 4.88 MAN 2BH

-5.73

-5.55 0.18 61 162 24 23 1.93 MAN 2BH

-0.83

-0.76 0.07 62 163 30 23 MAD 2BH

-2.97 62 164 30 23 2.66 MAN 2BH

-0.89

-0.74 0.15 62 165 30 23 2.73 SAN 2BH

-5.58

-5.44 0.14 63 166 39 23 MAD 2BH

-3.38 63 167 39 23 2.97 SAN 2BH

-0.84

-0.68 0.16 64 168 12 24 2.97 MAN 2BH

-3.36

-3.07 0.29 64 169 12 24 3.78 MAN 2BH

-0.80

-0.63 0.17 65 170 30 24 MAD 2BH

-3.31 65 171 30 24 3.93 MAN 2BH

-5.62

-5.49 0.13 65 172 30 24 2.99 MAN 2BH

-0.72

-0.65 0.07 66 173 37 24 SAD 21BH

-3.32 66 174 37 24 1.24 SAN 2BH

-0.80

-0.73 0.07 67 175 6

25 MAD 2BH

-3.20 67 176 6

25 1.16 SAN 2BH

-0.83

-0.80 0.03 68 177 8

25 SAD 2BH

-3.49 68 178 8

25 0.86 SAN 2BH

-0.76

-0.70 0.06 69 179 10 25 SAD 2BH

-3.29 69 180 10 25 0.96 SAN 2BH

-0.90

-0.83 0.07 70 181 14 25 MAD 2BH

-3.29 70 182 14 25 2.64 MAN 2BH

-0.76

-0.59 0.17 70 183 14 25 0.50 SAN 2BH

-2.41

-2.34 0.07 71 184 16 25 2.97 SAN 2BH

-3.19

-3.09 0.10 71 185 16 25 1.41 SAN 2BH

-0.73

-0.64 0.09 72 186 20 25 MAD 2BH

-3.26 72 187 20 25 1.28 MAN 2BH

-0.76

-0.70 0.06 73 188 5

26 SAD 2BH

-3.27 73 189 5

26 1.84 SAN 2BH

-0.80

-0.72 0.08 74 190 7

26 MAD 2BH

-3.32 74 191 7

26 0.95 MAN 2BH

-2.64

-2.39 0.25 74 192 7

26 1.62 MAN 2BH

-0.92

-0.84 0.08 Page 91 of 169

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 75 193 8

26 1.73 MAN 2BH

-0.70

-0.65 0.05 75 194 8

26 SAD 2BH

-3.25 75 195 8

26 1.20 SAN 2BH

-5.62

-5.54 0.08 76 196 10 26 MAD 2BH

-2.91 76 197 10 26 2.32 SAN 2BH

-0.72

-0.63 0.09 77 198 15 26 MAD 2BH

-2.85 77 199 15 26 3.86 SAN 2BH

-5.73

-5.61 0.12 77 200 15 26 2.35 SAN 2BH

-0.72

-0.67 0.05 78 201 18 26 SAD 2BH

-3.60 78 202 18 26 1.92 SAN 2BH

-5.84

-5.72 0.12 78 203 18 26 2.89 SAN 2BH

-0.84

-0.69 0.15 79 204 9

27 SAD 2BH

-3.23 79 205 9

27 1.01 SAN 2BH

-0.70

-0.66 0.04 80 206 26 27 MAD 2BH

-3.27 80 207 26 27 1.81 MAN 2BH

-0.84

-0.75 0.09 81 208 27 27 MAD 2BH

-3.30 81 209 27 27 2.10 MAN 2BH

-0.74

-0.63 0.11 82 210 32 27 1.79 MAN 2BH

-5.47

-5.36 0.11 82 211 32 27 1.54 SAN 2BH

-3.03

-2.89 0.14 82 212 32 27 1.97 SAN 2BH

-0.70

-0.57 0.13 83 213 35 27 1.39 MAN 2BH

-0.98

-0.89 0.09 83 214 35 27 SAD 2BH

-3.06 84 215 36 27 MAD 2BH

-3.18 84 216 36 27 1.58 SAN 2BH

-0.91

-0.82 0.09 85 217 1

28 3.40 MAN 2BH

-3.20

-3.07 0.13 85 218 1

28 3.12 SAN 2BH

-0.73

-0.63 0.10 86 219 3

28 3.51 MAN 2BH

-3.27

-3.13 0.14 86 220 3

28 2.51 SAN 2BH

-0.88

-0.78 0.10 87 221 15 28 1.16 SAN 2BH

-3.29

-3.20 0.09 87 222 15 28 3.50 SAN 2BH

-1.00

-0.73 0.27 88 223 17 28 MAD 2131-1

-3.17 88 224 17 28 2.09 SAN 2BH

-0.89

-0.82 0.07 89 225 18 28 SAD 2BH

-3.23 89 226 18 28 0.77 SAN 2BH

-5.85

-5.76 0.09 89 227 18 28 2.59 SAN 2BH

-0.87

-0.75 0.12 90 228 19 28 3.99 MAN 2BH

-3.32

-3.18 0.14 90 229 19 28 4.72 MAN 2BH

-0.84

-0.72 0.12 91 230 21 28 3.62 MAN 2BH

-3.35

-3.21 0.14 91 231 21 28 2.84 SAN 2BH

-0.85

-0.76 0.09 92 232 33 28 2.14 MAN 2BH

-5.71

-5.60 0.11 92 233 33 28 SAD 2BH

-3.03 92 234 33 28 2.42 SAN 2BH

-0.85

-0.75 0.10 93 235 7

29 0.91 MAN 2BH

-3.22

-3.12 0.10 93 236 7

29 1.67 SAN 2BH

-0.78

-0.68 0.10 94 237 11 29 SAD 2BH

-2.80 95 238 19 29 MAD 2BH

-3.30 95 239 19 29 2.27 SAN 2BH

-5.79

-5.59 0.20 95 240 19 29 2.12 SAN 2BH

-0.76

-0.65 0.11 Page 92 of 169

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 96 241 22 29 MAD 2BH

-3.09 96 242 22 29 2.93 SAN 2BH

-0.82

-0.75 0.07 97 243 23 29 MAD 2BH

-3.26 97 244 23 29 0.96 MAN 2BH

-0.86

-0.76 0.10 98 245 27 29 MAD 2BH

-3.27 98 246 27 29 1.94 MAN 2BH

-0.88

-0.75 0.13 99 247 31 29 MAD 2BH

-3.29 99 248 31 29 3.67 MAN 2BH

-5.61

-5.43 0.18 99 249 31 29 1.77 MAN 2BH

-0.60

-0.49 0.11 100 250 35 29 SAD 2BH

-2.86 100 251 35 29 1.66 SAN 2BH

-0.76

-0.69 0.07 101 252 6

30 3.93 MAN 2BH

-3.37

-3.19 0.18 101 253 6

30 2.19 SAN 2BH

-0.94

-0.77 0.17 102 254 15 30 MAD 2BH

-2.90 103 255 6

31 2.64 SAN 2BH

-3.24

-3.11 0.13 103 256 6

31 2.51 SAN 2BH

-0.75

-0.69 0.06 104 257 10 31 SAD 2BH

-3.26 104 258 10 31 0.61 SAN 2BH

-2.38

-2.26 0.12 104 259 10 31 1.32 SAN 2BH

-0.77

-0.70 0.07 105 260 15 31 MAD 2BH

-2.94 106 261 37 31 MAD 2BH

-3.23 106 262 37 31 0.94 SAN 2BH

-5.77

-5.63 0.14 106 263 37 31 0.90 SAN 2BH

-0.91

-0.84 0.07 107 264 1

32 3.96 MAN 2BH

-3.29

-3.07 0.22 107 265 1

32 4.93 SAN 2BH

-0.87

-0.71 0.16 107 266 1

32 1.32 SCN 2BH

-4.90

-4.55 0.35 108 267 3

32 MAD 2BH

-3.50 108 268 3

32 4.05 SAN 2BH

-0.96

-0.87 0.09 109 269 5

32 SAD 2BH

-3.45 109 270 5

32 1.32 SAN 2BH

-0.79

-0.69 0.10 110 271 6

32 5.91 MAN 2BH

-3.28

-3.12 0.16 110 272 6

32 2.82 SAN 2BH

-0.89

-0.75 0.14 111 273 12 32 SAD 2BH

-2.90 ill 274 12 32 1.27 SAN 2BH

-5.47

-5.39 0.08 112 275 24 32 MAD 2BH

-3.29 112 276 24 32 2.45 SAN 2BH

-0.88

-0.78 0.10 113 277 26 32 2.28 MAN 2BH

-5.65

-5.54 0.11 113 278 26 32 2.00 MAN 2BH

-0.82

-0.74 0.08 113 279 26 32 SAD 2BH

-3.18 114 280 30 32 2.69 SAN 2BH

-3.29

-3.15 0.14 114 281 30 32 2.38 SAN 2BH

-0.79

-0.72 0.07 115 282 32 32 5.30 MAN 2BH

-5.76

-5.59 0.17 115 283 32 32 1.14 MAN 2BH

-3.22

-3.11 0.11 115 284 32 32 1.28 SAN 2BH

-0.86

-0.79 0.07 116 285 4

33 SAD 2BH

-3.30 116 286 4

33 1.81 SAN 2BH

-0.83

-0.72 0.11 117 287 7

33 2.60 MAN 2BH

-3.28

-3.16 0.12 117 288 7

33 1.44 MAN 2BH

-0.91

-0.82 0.09 Page 93 of 169

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 117 289 7

33 0.64 SAN 213H

-5.75

-5.69 0.06 118 290 15 33 SAD 213H

-2.85 119 291 21 33 2.16 MAN 2B3H

-3.22

-3.11 0.11 119 292 21 33 0.82 SAN 213H-

-0.87

-0.76 0.11 120 293 7

34 SAD 2BH1-

-3.42 120 294 7

34 2.59 SAN 213H-

-0.92

-0.84 0.08 121 295 8

34 2.48 MAN 213H

-3.26

-3.11 0.15 121 296 8

34 5.90 SAN 2B3H

-0.89

-0.76 0.13 122 297 12 34 SAD 2B3H

-2.75 123 298 34 34 0.52 MAN 213H

-3.52

-2.96 0.56 123 299 34 34 2.59 MAN 2131-

-0.84

-0.73 0.11 124 300 4

35 MAD 2BH1-

-2.95 124 301 4

35 1.90 SAN 2BH

-0.80

-0.72 0.08 125 302 5

35 MAD 213H

-3.18 125 303 5

35 0.73 SAN 213H

-0.86

-0.79 0.07 126 304 8

35 1.96 MAN 213H

-3.19

-3.06 0.13 126 305 8

35 0.94 SAN 213H

-0.84

-0.74 0.10 127 306 20 35

____MAD 213H

-2.86 128 307 27 35 MAD 2131-

-3.20 128 308 27 35 3.34 MAN 2131-

-0.89

-0.76 0.13 129 309 4

36 MAD 213H

-3.37 129 310 4

36 2.29 SAN 213H

-0.91

-0.81 0.10 130 311 6

36 12.79 MAN 213H

-3.19

-3.04 0.15 130 312 6

36 3.51 SAN 213H

-0.93

-0.78 0.15 131 313 25 36 2.47 MAN 213H

-0.85

-0.70 0.15 131 314 25 36 SAD 2131-

-3.40 132 315 29 36 SAD 2131-

-3.31 132 316 29 36 2.00 SAN 213H

-0.94

-0.84 0.10 133 317 35 36 MAD 213H

-2.86 133 318 35 36 2.15 SAN 213H

-0.84

-0.76 0.08 134 319 6

37 1.76 MAN 2131-

-3.13

-3.02 0.11 134 320 6

37 0.89 SAN 2131-

-0.88

-0.81 0.07 135 321 17 37 MAD 213H

-2.90 136 322 21 137 0.95 MAN 2B3H

-3.07

-2.97 0.10 136 323 21 37 1.84 SAN 2131-

-0.82

-0.69 0.13 137 324 33 37 1.42 MAN 213H-

-0.79

-0.72 0.07 137 325 33 37 SAD 213H

-2.88 138 326 24 38 SAD 213H

-3.18 138 327 24 38 4.14 SAN 2B3H

-0.77

-0.41 0.36 139 328 35 38 MAD 2131-

-3.26 139 329 35 38 2.21 MAN 2131-

-0.77

-0.70 0.07 140 330 4

39 3.43 MAN 213H

-3.28

-3.17 0.11 140 331 4

39 1.70 SAN 213H

-0.88

-0.82 0.06 141 332 14 39 SAD 2131-

-2.91 142 333 15 39 SAD 2131-

-2.91 142 334 15 39 2.21 SAN 213H

-1.01

-0.95 0.06 143 335 20 39 1.99 MAN 213H

-3.16

-3.09 0.07 143 336 20 39 10.70 SAN 2131-

-0.80--

-0.68 0.12 Page 94 of 169

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 144 337 21 39 1.45 SAN 2BH

-3.49

-3.42 0.07 144 338 21 39 3.94 SAN 2BH

-0.90

-0.79 0.11 145 339 30 39 MAD 2BH

-3.17 145 340 30 39 2.38 SAN 2BH

-0.84

-0.75 0.09 146 341 2

40 SAD 2BH

-3.36 146 342 2

40 2.87 SAN 2BH

-0.98

-0.81 0.17 147 343 6

40 SAD 2BH

-3.30 147 344 6

40 1.90 SAN 2BH

-0.85

-0.69 0.16 148 345 10 40 1.88 MAN 2BH

-3.12

-2.97 0.15 148 346 10 40 2.12 SAN 2BH

-0.88

-0.67 0.21 149 347 29 40 1.58 MAN 2BH

-5.75

-5.66 0.09 149 348 29 40 SAD 2BH

-3.30 149 349 29 40 1.79 SAN 2BH

-0.83

-0.73 0.10 150 350 3

41 1.30 MAN 2BH

-0.77

-0.66 0.11 150 351 3

41 SAD 2BH

-3.31 151 352 12 41 2.47 MAN 2BH

-3.09

-2.96 0.13 151 353 12 41 2.30 MAN 2BH

-0.84

-0.72 0.12 152 354 3

42 MAD 2BH

-3.22 152 355 3

42 0.87 SAN 2BH

-0.81

-0.72 0.09 153 356 8

42 MAD 2BH

-3.23 153 357 8

42 1.68 MAN 2BH

-0.76

-0.67 0.09 154 358 15 42 2.21 MAN 2BH

-3.19

-3.06 0.13 154 359 15 42 1.42 MAN 2BH

-0.86

-0.79 0.07 155 360 17 42 SAD 2BH

-2.80 155 361 17 42 1.84 SAN 2BH

-0.81

-0.68 0.13 156 362 7

43 1.94 MAN 2BH

-3.21

-3.11 0.10 156 363 7

43 0.75 SAN 2BH

-0.78

-0.69 0.09 157 364 8

43 2.46 SAN 2BH

-3.17

-3.04 0.13 157 365 8

43 2.26 SAN 2BH

-0.81

-0.69 0.12 158 366 12 43 1.67 MAN 2BH

-0.76

-0.64 0.12 158 367 12 43 SAD 2BH

-2.93 159 368 8

44 SAD 2BH

-2.90 159 369 8

44 1.02 SAN 2BH

-0.77

-0.69 0.08 160 370 12 44 SAD 2BH

-2.95 160 371 12 44 0.91 SAN 2BH

-0.84

-0.77 0.07 161 372 19 44 1.70 MAN 2BH

-1.94

-1.77 0.17 161 373 19 44 SAD 2BH

-3.50 162 374 9

45 2.10 MAN 2BH

-3.01

-2.84 0.17 162 375 9

45 1.32 MAN 2BH

-0.93

-0.86 0.07 163 376 3

46 0.30 MAN 2BH

-3.02

-2.96 0.06 163 377 3

46 2.62 SAN 2BH

-0.81

-0.66 0.15 164 378 6

46 MAD 2BH

-3.55 164 379 6

46 2.79 SAN 2BH

-0.81

-0.66 0.15 165 380 9

46 SAD 2BH

-3.58 165 381 9

46 0.16 SAN 2BH

-1.99

-1.21 0.78 166 382 20 46 2.43 MAN 2BH

-5.72

-5.69 0.03 166 383 20 46 1.23 MAN 2BH

-3.11

-3.01 0.10 166 384 20 46 SAD 2BH

-1.50 1

1 1

Page 95 of 169

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 167 385 22 46 3.91 MAN 2BH

-2.34

-2.06 0.28 167 386 22 46 1.47 MAN 2BH

-1.85

-1.41 0.44 167 387 22 46 SAD 2BH

-3.24 168 388 6

47 0.31 SAN 2BH

-2.76

-2.02 0.74 169 389 9

47 1.19 MAN 2BH

-3.12

-2.97 0.15 169 390 9

47 1.40 MAN 2BH

-0.79

-0.70 0.09 169 391 9

47 SAD 2BH

-2.75 170 392 12 47 2.79 MAN 2BH

-3.40

-3.11 0.29 170 393 12 47 0.24 SAN 2BH

-2.90

-2.75 0.15 170 394 12 47 1.45 SAN 2BH

-1.03

-0.95 0.08 171 395 23 47 MAD 2BH

-3.19 171 396 23 47 2.14 SAN 2BH

-5.61

-5.57 0.04 171 397 23 47 1.51 SAN 2BH

-0.85

-0.77 0.08 172 398 24 47 MAD 2BH

-3.32 172 399 24 47 0.83 SAN 2BH

-5.75

-5.69 0.06 172 400 24 47 1.51 SAN 2BH

-0.93

-0.86 0.07 173 401 36 47 MAD 2BH

-3.10 173 402 36 47 1.79 SAN 2BH

-0.81

-0.71 0.10 174 403 12 48 MAD 2BH

-3.31 174 404 12 48 1.75 SAN 2BH

-0.59

-0.49 0.10 175 405 13 49 2.58 MAN 2BH

-3.35

-3.01 0.34 175 406 13 49 1.75 SAN 2BH

-0.91

-0.82 0.09 176 407 14 49 2.96 MAN 2BH

-3.29

-3.16 0.13 176 408 14 49 0.15 SAN 2BH

-2.75

-2.43 0.32 176 409 14 49 3.02 SAN 2BH

-0.84

-0.74 0.10 177 410 17 49 SAD 2BH

-2.88 178 411 2

50 12.86 MAN 2BH

-3.35

-2.88 0.47 178 412 2

50 2.67 SAN 2BH

-0.78

-0.71 0.07 179 413 7

50 8.38 MAN 2BH

-3.36

-3.04 0.32 179 414 7

50 7.99 MAN 2BH

-3.36

-3.04 0.32 179 415 7

50 1.76 MAN 2BH

-0.83

-0.73 0.10 179 416 7

50 1.29 MAN 2BH

-0.83

-0.73 0.10 180 417 8

50 0.49 MAN 2BH

-2.96

-2.90 0.06 180 418 8

50 2.94 SAN 2BH

-0.80

-0.67 0.13 181 419 25 50 SAD 2BH

-3.26 181 420 25 50 2.15 SAN 2BH

-0.80

-0.67 0.13 182 421 5

51 3.58 MAN 2BH

-3.25

-3.09 0.16 182 422 5

51 2.04 MAN 2BH

-0.80

-0.68 0.12 183 423 8

51 9.37 MAN 2BH

-3.42

-2.94 0.48 183 424 8

51 SAN 2BH

-0.87

-0.71 0.16 184 425 14 51 SAD 2BH

-3.35 184 426 14 51 6.93 SAN 2BH

-2.49

-1.66 0.83 184 427 14 51 3.21 SAN 2BH

-0.79

-0.49 0.30 185 428 18 51 MAD 2BH

-3.30 185 429 18 51 2.00 MAN 2BH

-1.97

-1.85 0.12 186 430 19 51 SAD 2BH

-3.21 186 431 19 51 0.88 SAN 2BH

-0.78

-0.72 0.06 187 432 2

52 7.34 MAN 2BH

-3.38

-3.03 0.35 Page 96 of 169

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 187 433 2

52 1.25 SAN 2BH

-0.80

-0.77 0.03 188 434 4

52 1.39 MAN 2BH

-3.23

-3.12 0.11 188 435 4

52 1.11 SAN 2BH

-0.75

-0.70 0.05 189 436 7

52 SAD 2BH

-3.31 189 437 7

52 1.20 SAN 2BH

-0.69

-0.63 0.06 190 438 12 52 SAD 2BH

-3.04 190 439 12 52 SAD 2BH

-1.81 190 440 12 52 0.61 SAN 2BH

-2.42

-2.28 0.14 191 441 22 52 SAD 2BH

-3.27 191 442 22 52 1.88 SAN 2BH

-0.83

-0.73 0.10 192 443 7

53 7.70 MAN 2BH

-2.83

-2.22 0.61 192 444 7

53 1.21 SAN 2BH

-3.18

-3.10 0.08 192 445 7

53 1.78 SAN 2BH

-0.77

-0.68 0.09 193 446 10 53 3.56 MAN 2BH

-3.34

-3.17 0.17 193 447 10 53 2.26 SAN 2BH

-0.76

-0.72 0.04 194 448 15 54 MAD 2BH

-2.94 194 449 15 54 SAD 2BH

-0.80 194 450 15 54 0.30 SAN 2BH

-2.88

-2.24 0.64 195 451 19 54 1.82 MAN 2BH

-3.14

-3.06 0.08 195 452 19 54 2.48 SAN 2BH

-0.76

-0.69 0.07 196 453 29 54 MAD 2BH

-3.32 196 454 29 54 1.86 SAN 2BH

-0.88

-0.76 0.12 197 455 2

55 SAD 2BH

-3.01 198 456 23 55 MAD 2BH

-3.19 198 457 23 55 2.39 SAN 2BH

-0.78

-0.69 0.09 199 458 7

56 MAD 2BH

-3.08 199 459 7

56 3.08 SAN 2BH

-0.83

-0.71 0.12 200 460 8

56 MAD 2BH

-2.91 201 461 10 56 4.50 MAN 2BH

-3.39

-2.91 0.48 201 462 10 56 1.20 SAN 2BH

-0.62

-0.57 0.05 202 463 4

57 1.55 MAN 2BH

-0.74

-0.64 0.10 202 464 4

57 SAD 2BH

-3.28 203 465 6

57 1.97 MAN 2BH

-3.34

-3.20 0.14 203 466 6

57 SAN 2BH

-0.84

-0.76 0.08 204 467 7

57 MAD 2BH

-3.36 204 468 7

57 3.59 MAN 2BH

-0.76

-0.66 0.10 205 469 8

57 3.82 MAN 2BH

-3.21

-2.84 0.37 205 470 8

57 11.78 MAN 2BH

-2.75

-2.02 0.73 205 471 8

57 3.15 MAN 2BH

-0.76

-0.52 0.24 206 472 2

58 SAD 2BH

-3.39 206 473 2

58 1.99 SAN 2BH

-0.52

-0.42 0.10 207 474 11 58 SAD 2BH

-3.20 207 475 11 58 0.50 SAN 2BH

-0.81

-0.74 0.07 208 476 16 58 3.63 MAN 2BH

-3.11

-2.82 0.29 208 477 16 58 1.99 MAN 2BH

-0.65

-0.56 0.09 209 478 21 58 1.77 MAN 2BH

-3.18

-3.05 0.13 209 479 21 58 1.78 SAN 2BH

-0.87

-0.75 0.12 210 480 1

59 MAD 2BH

-3.34 Page 97 of 169

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 210 481 1

59 3.51 SAN 2BH

-0.95

-0.76 0.19 211 482 13 59 3.74 MAN 2BH

-3.27

-3.02 0.25 211 483 13 59 1.03 SAN 2BH

-0.93

-0.86 0.07 212 484 31 59 MAD 2BH

-3.34 212 485 31 59 1.07 SAN 2BH

-0.83

-0.68 0.15 213 486 6

60 MAD 2BH

-3.35 213 487 6

60 SAD 2BH

-1.11 213 488 6

60 2.55 SAN 2BH

-5.69

-5.61 0.08 214 489 9

60 MAD 2BH

-3.23 214 490 9

60 1.71 SAN 2BH

-0.77

-0.71 0.06 215 491 16 60 3.19 MAN 2BH

-5.75

-5.62 0.13 215 492 16 60 3.17 MAN 2BH

-3.05

-2.95 0.10 215 493 16 60 3.59 MAN 2BH

-0.97

-0.85 0.12 216 494 2

61 2.15 MAN 2BH

-3.47

-3.17 0.30 216 495 2

61 7.12 MAN 2BH

-0.92

-0.66 0.26 217 496 3

61 2.74 MAN 2BH

-3.99

-3.87 0.12 217 497 3

61 0.97 MAN 2BH

-3.34

-3.23 0.11 217 498 3

61 2.34 SAN 2BH

-0.82

-0.72 0.10 218 499 4

61 SAD 2BH

-3.26 218 500 4

61 0.50 SAN 2BH

-0.85

-0.74 0.11 219 501 5

61 1.64 MAN 2BH

-3.34

-3.17 0.17 219 502 5

61 3.18 SAN 2BH

-0.88

-0.74 0.14 220 503 17 61 1.99 MAN 2BH

-3.26

-3.11 0.15 220 504 17 61 3.25 SAN 2BH

-0.91

-0.81 0.10 221 505 2

62 1.57 MAN 2BH13-

-3.32

-3.22 0.10 221 506 2

62 0.98 SAN 2BH

-0.82

-0.75 0.07 222 507 4

62 MAD 2BH

-2.84 222 508 4

62 3.16 SAN 2BH

-5.57

-5.36 0.21 222 509 4

62 3.62 SAN 2BH

-1.03

-0.57 0.46 223 510 5

62 1.11 MAN 2BH

-3.26

-3.17 0.09 223 511 5

62 0.58 SAN 2BH

-0.89

-0.83 0.06 224 512 14 62 7.33 MAN 2BH

-5.84

-5.66 0.18 224 513 14 62 2.64 MAN 2BH

-3.31

-3.12 0.19 224 514 14 62 1.21 SAN 2BH

-0.85

-0.75 0.10 225 515 25 62 6.02 MAN 2BH

-0.66

-0.02 0.64 225 516 25 62 6.30 SAN 2BH

-5.80

-5.52 0.28 225 517 25 62 0.40 SAN 2BH

-3.24

-3.17 0.07 225 518 25 62 2.78 SAN 2BH

-1.05

-0.81 0.24 226 519 3

63 3.32 MAN 2BH

-3.43

-3.27 0.16 226 520 3

63 6.52 SAN 2BH

-0.90

-0.77 0.13 227 521 5

63 1.70 MAN 2BH

-3.32

-3.24 0.08 227 522 5

63 1.40 SAN 2BH

-0.99

-0.88 0.11 228 523 8

63 0.36 MAN 2BH

-3.27

-3.14 0.13 228 524 8

63 3.08 MAN 2BH

-0.89

-0.78 0.11 229 525 14 63 MAD 2BH

-3.73 229 526 14 63 3.12 MAN 2BH

-0.80

-0.68 0.12 230 527 16 63 5.81 MAN 2BH

-5.75

-5.56 0.19 230 528 16 63 SAD 2BH

-3.33 Page 98 of 169

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 230 529 16 63 3.71 SAN 2BH

-0.84

-0.74 0.10 231 530 28 63 MAD 2BH

-3.30 231 531 28 63 1.08 MAN 2BH

-0.89

-0.84 0.05 231 532 28 63 6.01 SAN 2BH

-5.70

-5.54 0.16 232 533 36 63 SAD 2BH

-2.89 232 534 36 63 1.51 SAN 2BH

-0.74

-0.64 0.10 233 535 5

64 3.59 MAN 2BH

-3.73

-3.16 0.57 233 536 5

64 1.01 SAN 2BH

-0.98

-0.87 0.11 234 537 7

64 2.42 MAN 2BH

-3.38

-3.17 0.21 234 538 7

64 1.08 SAN 2BH

-0.92

-0.85 0.07 235 539 8

64 SAD 2BH

-3.05 235 540 8

64 2.58 SAN 2BH

-0.64

-0.54 0.10 236 541 12 64 2.45 MAN 2BH

-3.10

-3.01 0.09 236 542 12 64 2.32 SAN 2BH

-5.70

-5.63 0.07 236 543 12 64 2.71 SAN 2BH

-0.88

-0.72 0.16 237 544 34 64 MAD 2BH

-3.22 237 545 34 64 1.72 SAN 2BH

-0.83

-0.73 0.10 238 546 5

65 3.32 MAN 2BH

-3.38

-3.16 0.22 238 547 5

65 3.37 SAN 2BH

-0.95

-0.81 0.14 239 548 10 65 MAD 2BH

-3.24 239 549 10 65 2.65 MAN 2BH

-2.44

-2.29 0.15 239 550 10 65 2.64 MAN 2BH

-0.67

-0.61 0.06 240 551 14 65 2.47 MAN 2BH

-5.74

-5.63 0.11 240 552 14 65 SAD 2BH

-3.19 240 553 14 65 0.82 SAN 2BH

-0.84

-0.77 0.07 241 554 16 65 3.32 MAN 2BH

-1.05

-0.56 0.49 241 555 16 65 SAD 2BH

-3.23 242 556 25 65 SAD 2BH

-2.79 242 557 25 65 2.40 SAN 2BH

-5.78

-5.64 0.14 242 558 25 65 1.85 SAN 2BH

-0.86

-0.79 0.07 243 559 40 65 MAD 2BH

-3.32 243 560 40 65 1.37 SAN 2BH

-0.69

-0.35 0.34 244 561 5

66 4.55 MAN 2BH

-3.19

-2.97 0.22 244 562 5

66 7.88 SAN 2BH

-5.68

-5.45 0.23 244 563 5

66 1.44 SAN 2BH

-0.79

-0.75 0.04 245 564 7

66 3.09 MAN 2BH

-5.63

-5.50 0.13 245 565 7

66 1.25 MAN 2BH

-0.99

-0.83 0.16 245 566 7

66 SAD 2BH

-3.27 246 567 16 66 7.52 SAN 2BH

-5.66

-5.46 0.20 246 568 16 66 0.96 SAN 2BH

-3.95

-3.88 0.07 246 569 16 66 1.41 SAN 2BH

-0.74

-0.66 0.08 247 570 17 66 SAD 2BH

-3.40 247 571 17 66 2.34 SAN 2BH

-5.69

-5.59 0.10 247 572 17 66 2.34 SAN 2BH

-0.87

-0.76 0.11 248 573 14 67 SAD 2BH

-3.02 249 574 24 67 MAD 2BH

-2.19 249 575 24 67 1.49 MAN 2BH

-3.18

-3.03 0.15 249 576 24 67 1.21 MAN 2BH

-0.85

-0.78 0.07 Page 99 of 169

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 249 577 24 67 3.36 SAN 2BH

-5.74

-5.64 0.10 250 578 25 67 4.43 MAN 2BH

-5.79

-5.58 0.21 250 579 25 67 0.95 SAN 2BH

-0.82

-0.75 0.07 251 580 5

68 4.53 MAN 2BH

-3.53

-3.21 0.32 251 581 5

68 7.29 SAN 2BH

-5.91

-5.58 0.33 251 582 5

68 1.75 SAN 2BH

-0.99

-0.90 0.09 252 583 19 68 SAD 2BH

-2.85 252 584 19 68 2.01 SAN 2BH

-0.76

-0.69 0.07 253 585 11 69 0.95 SAN 2BH

-3.25

-3.18 0.07 253 586 11 69 3.35 SAN 2BH

-0.91

-0.81 0.10 254 587 33 69 SAD 2BH

-3.48 254 588 33 69 5.45 SAN 2BH

-5.74

-5.50 0.24 254 589 33 69 1.55 SAN 2BH

-0.88

-0.74 0.14 255 590 5

70 2.59 MAN 2BH

-3.45

-3.23 0.22 255 591 5

70 5.65 SAN 2BH

-5.74

-5.45 0.29 255 592 5

70 0.84 SAN 2BH

-1.05

-0.90 0.15 256 593 9

70 MAD 2BH

-3.20 256 594 9

70 1.24 SAN 2BH

-5.69

-5.58 0.11 256 595 9

70 2.12 SAN 2BH

-0.99

-0.84 0.15 257 596 13 70 MAD 2BH

-3.40 257 597 13 70 1.61 MAN 2BH

-0.89

-0.81 0.08 257 598 13 70 2.98 SAN 2BH

-5.68

-5.63 0.05 258 599 7

71 MAD 2BH

-3.55 258 600 7

71 1.32 SAN 2BH

-5.76

-5.66 0.10 258 601 7

71 1.95 SAN 2BH

-0.87

-0.81 0.06 259 602 9

71 SAD 2BH

-3.46 259 603 9

71 2.96 SAN 2BH

-0.81

-0.71 0.10 260 604 34 71 MAD 2BH

-3.33 260 605 34 71 3.33 MAN 2BH

-2.80

-2.07 0.73 261 606 4

72 SAD 2BH

-3.00 261 607 4

72 2.46 SAN 2BH

-5.68

-5.64 0.04 261 608 4

72 1.04 SAN 2BH

-0.97

-0.89 0.08 262 609 8

72 1.28 MAN 2BH

-3.20

-3.12 0.08 262 610 8

72 1.71 SAN 2BH

-0.89

-0.82 0.07 263 611 11 72 2.13 MAN 2BH

-3.25

-3.15 0.10 263 612 11 72 1.47 SAN 2BH

-0.84

-0.70 0.14 264 613 25 72 SAD 21B3H

-2.84 264 614 25 72 2.47 SAN 2BH

-5.50

-5.40 0.10 265 615 5

73 1.68 MAN 2BH

-3.19

-3.06 0.13 265 616 5

73 1.95 SAN 2BH13-

-5.63

-5.51 0.12 265 617 5

73 0.88 SAN 2BH

-0.89

-0.80 0.09 266 618 9

73 SAD 2BH

-2.80 267 619 11 73 0.93 MAN 2BH

-3.27

-3.18 0.09 267 620 11 73 1.57 MAN 2BH

-0.93

-0.79 0.14 268 621 16 73 MAD 2BH

-2.86 268 622 16 73 1.68 SAN 2BH

-0.78

-0.68 0.10 269 623 4

74 MAD

2BH3,

-3.43 269 624 4

74 1.04 SAN 2BH

-0.81

-0.74 0.07 Page 100 of 169

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 270 625 9

74 MAD 2BH

-3.31 270 626 9

74 3.11 SAN 2BH

-0.98

-0.82 0.16 271 627 25 74 2.10 MAN 2BH

-5.75

-5.66 0.09 271 628 25 74 SAD 2BH

-2.85 271 629 25 74 0.86 SAN 2BH

-0.85

-0.78 0.07 272 630 28 74 1.05 SAN 2BH

-5.66

-5.59 0.07 272 631 28 74 0.81 SAN 2BH

-2.94

-2.88 0.06 272 632 28 74 1.48 SAN 2BH

-1.00

-0.91 0.09 273 633 4

75 SAD 2BH

-3.34 273 634 4

75 2.58 SAN 2BH

-0.80

-0.73 0.07 274 635 17 75 MAD 2BH

-3.40 274 636 17 75 4.24 MAN 2BH

-5.71

-5.61 0.10 274 637 17 75 0.92 SAN 2BH

-2.57

-2.36 0.21 274 638 17 75 1.71 SAN 2BH

-0.81

-0.70 0.11 275 639 11 77 0.86 MAI 2BH

-0.91

-0,80 0.11 275 640 11 77 SAD 2BH

-3.44 276 641 2

78 SAD 2BH

-2.98 276 642 2

78 SAD 2BH

-0.97 277 643 3

78 MAD 2BH

-3.53 277 644 3

78 2.16 SAN 2BH

-0.84

-0.71 0.13 278 645 7

78 4.76 MAN 2BH

-5.75

-5.62 0.13 278 646 7

78 4.21 MAN 2BH

-3.37

-3.23 0.14 278 647 7

78 1.12 MAN 2BH

-0.90

-0.81 0.09 279 648 8

79 SAD 2BH

-2.93 279 649 8

79 1.89 SAN 2BH

-5.74

-5.68 0.06 279 650 8

79 0.97 SAN 2BH

-0.80

-0.76 0.04 280 651 19 79 MAD 2BH

-3.52 280 652 19 79 2.73 SAN 2BH

-5.78

-5.69 0.09 280 653 19 79 2.25 SAN 2BH

-0.79

-0.69 0.10 281 654 28 80 2.40 SAN 2BH

-3.41

-3.27 0.14 281 655 28 80 2.50 SAN 2BH

-1.00

-0.90 0.10 282 656 11 81 2.12 MAN 2BH

-0.87

-0.76 0.11 282 657 11 81 SAD 2BH

-3.45 283 658 13 83 MAD 2BH

-2.85 283 659 13 83 SAD 2BH

-0.90 284 660 11 84 MAD 2BH

-3.45 284 661 11 84 1.08 SAN 2BH

-5.83

-5.77 0.06 284 662 11 84 1.36 SAN 2BH

-0.57

-0.51 0.06 285 663 12 84 MAD 2BH

-2.90 285 664 12 84 2.87 MAN 2BH

-2.43

-2.31 0.12 285 665 12 84 2.78 SAN 2BH

-0.92

-0.82 0.10 286 666 9

85 MAD 2BH

-3.35 286 667 9

85 2.78 SAN 2BH

-5.75

-5.67 0.08 286 668 9

85 1.32 SAN 2BH

-0.88

-0.81 0.07 Page 101 of 169

TABLE 10 STEAM GENERATOR 22 - HISTORICAL F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 18 14 3.83 MAN 2BH

-3.22

-2.89 0.33 1

2 18 14 2.52 SAN 2BH

-0.87

-0.72 0.15 2

3 4

15 2.41 MAN 2BH

-2.24

-1.74 0.50 2

4 4

15 SAD 2BH

-3.25 3

5 13 16 6.52 MAN 2BH

-2.51

-1.62 0.89 3

6 13 16 SAD 2BH

-3.32 4

7 18 16 0.77 MAN 2BH

-2.36

-2.20 0.16 4

8 18 16 SAD 2BH

-3.34 4

9 18 16 1.20 SAN 2BH

-0.70

-0.60 0.10 5

10 1

17 3.00 MAN 2BH

-4.27

-4.03 0.24 5

11 1

17 0.94 MAN 2BH

-0.79

-0.63 0.16 6

12 1

20 2.74 MAN 2BH

-4.13

-3.95 0.18 6

13 1

20 3.69 MAN 2BH

-0.80

-0.68 0.12 7

14 18 20 5.96 MAN 2BH

-2.70

-1.88 0.82 7

15 18 20 SAD 2BH

-3.57 7

16 18 20 0.70 SAN 2BH

-0.75

-0.69 0.06 8

17 20 20 MAD 2BH

-3.33 8

18 20 20 3.41 MAN 2BH

-0.72

-0.62 0.10 9

19 25 22 MAD 2BH

-3.17 9

20 25 22 1.11 SAN 2BH

-0.82

-0.7r3 0.09 10 21 32 22 SAD 2BH

-3.22 11 22 16 23 3.49 MAN 2BH

-2.63

-1.86 0.77 11 23 16 23 SAD 2BH

-3.23 12 24 16 25 SAD 2BH

-3.27 12 25 16 25 3.21 SAN 2BH

-0.86

-0.56 0.30 13 26 19 25 SAD 2BH

-3.24 13 27 19 25 0.22 SAN 2BH

-0.41

-0.37 0.04 14 28 18 26 SAD 2BH

-3.27 14 29 18 26 4.17 SAN 2BH

-0.98

-0.51 0.47 15 30 22 26 SAD 2BH

-3.56 15 31 22 26 0.76 SAN 2BH

-2.03

-1.96 0.07 16 32 24 26 MAD 2BH

-3.39 16 33 24 26 4.06 MAN 2BH

-2.73

-2.17 0.56 16 34 24 26 2.55 SAN 2BH

-0.97

-0.82 0.15 17 35 27 26 2.16 MAN 2BH

-2.28

-1.76 0.52 17 36 27 26 SAD 2BH

-3.50 17 37 27 26 1.95 SAN 2BH

-0.72

-0.65 0.07 18 38 20 28 SAD 2BH

-3.21 18 39 20 28 1.65 SAN 2BH

-0.82

-0.67 0.15 19 40 23 28 SAD 2BH

-3.34 19 41 23 28 0.92 SAN 2BH

-0.87

-0.80 0.07 20 42 29 29 MAD 2BH

-3.58 20 43 29 29 11.59 MAN 2BH

-2.93

-1.96 0.97 21 44 3

30 3.73 MAN 2BH

-2.46

-1.83 0.63 21 45 3

30 SAD 2BH

-2.90 22 46 21 30 SAD 2BH

-3.29 22 47 21 30 2.84 SAN 2BH

-0.85

-0.76 0.09 23 48 27 30 MAD 2BH

-3.34 Page 102 of 169

TABLE 10

~STEAM GENERATOR 22 - HISTORICAL F*2____

TUBE #

IND #

ROW COL VOLTS POT LOCATION ELEV-FROM ELEV-TO LENGTH 23 49 27 30 3.48 SAN 213H-

-2.15

-1.80 0.35 24 50 15 31 3.09 MAN 213H

-3.26

-3.04 0.22 24 51 15 31

____SAD 213H

-0.31 25 52 17 33 SAD 2B3H

-3.08 26 53 20 33 MAD 2131-

-2.74 27 54 9

34 MAD 2B3H

-2.97 27 55 9

34 1.04 SAN 2B31-

-0.91

-0.68 0.23 28 56 17 34 SAD 2B3H

-2.82 29 57 22 34 MAD 213H

-3.27 29 58 22 34 3.64 MAN 213H

-2.31

-1.83 0.48 29 59 22 34 1.00 MAN 2B3H

-0.72

-0.62 0.10 30 60 14 35 2.06 SAN 2BH1-

-3.11

-2.97 0.14 31 61 18 35 MAD 213H

-2.95 32 62 19 35 SAD 2B31-

-3.18 33 63 37 35 SAD 213H

-3.48 33 64 37 35 SAD 213H

-0.88 33 65 37 35 0.67 SAN 2131-

-5.69

-5.55 0.14 34 66 35 36 2.05 MAN 213H

-2.53

-1.85 0.68 34 67 35 36

____SAD 2B31-

-3.51 34 68 35 36 0.98 SAN 2B3H

-1.77

-1.70 0.07 35 69 11 37

____SAD 2131-

-2.91 36 70 12 37 SAD I 2B3H

-3.28 37 71 13 37 SAD 213H

-2.99 38 72 14 37 SAD 2131-

-2.90 39 73 17 37 SAD 2B3H

-2.84 40 74 33 37 MAD 2B31-

-3.44 40 75 33 37 3.23 MAN 2BH1-

-2.30

-1.77 0.53 41 76 9

38 MAD 213H

-2.89 42 77 33 38 MAD 213H

-3.50 42 78 33 38 6.37 MAN 2BH1-

-2.69

-2.02 0.67 42 79 33 38 0.85 MAN 2B3H

-0.70

-0.07 0.63 43 80 37 38 SAD 2B31-

-3.37 43 81 37 38 1.80 SAN 213H

-0.95

-0.69 0.26 44 82 13 39

____MAD 213H

-2.94 45 83 18 39 SAD 2B31-

-3.16 46 84 19 39 SAD 213H

-3.21 47 85 15 40 SAD 213H

-2.90 48 86 18 40 MAD 2B31-

-3.00 49 87 5

41 1.64 MAN 213H

-2.35

-1.76 0.59 49 88 5

41 SAD 2B3H

-3.17 50 89 7

41 SAD 213H

-2.83 51 90 21 41 SAD 2B3H

-3.58 51 91 21 41 11.87 SAN 213H-

-0.71

-0.59 0.12 52 92 22 41 SAD 213H

-3.47 52 93 22 41 1.72 SAN 2BH

-0.83

-0.67 0.16 53 94 37 41 MAD 2B31-

-3.45 53 95 37 41 0.80 MAN 213H

-1.93

-1.57 0.36 53 96 37 41 1.12 SAN 213H

-5.75

-5.69 0.06 Page 103 of 169

TABLE 10 STEAM GENERATOR 22 - HISTORICAL F*2 TUBE#

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 54 97 18 42 SAD 2BH

-2.85 55 98 6

43 MAD 2BH

-2.85 56 99 9

43 MAD 2BH

-2.82 57 100 16 43 SAD 2BH

-3.01 58 101 17 43 SAD 2BH

-2.76 59 102 19 43 MAD 2BH

-2.75 60 103 20 43 1.28 SAN 2BH

-3.28

-3.17 0.11 61 104 22 43 MAD 2BH

-3.44 61 105 22 43 2.55 SAN 2BH

-0.76

-0.66 0.10 62 106 23 43 MAD 2BH

-3.02 63 107 27 43 MAD 2BH

-3.06 63 108 27 43 1.04 MAN 2BH

-2.10

-1.92 0.18 64 109 9

44 SAD 2BH

-2.71 65 110 10 44 SAD 2BH

-2.85 66 111 11 44 SAD 2BH

-2.74 67 112 13 44 1.86 MAN 2BH

-3.18

-2.98.

0.20 67 113 13 44 1.28 SAN 2BH

-0.87

-0.83 0.04 68 114 9

45 MAD 2BH

-2.85 69 115 10 45 MAD 2BH

-2.75 70 116 16 45 SAD 2BH

-2.85 71 117 37 45 SAD 2BH

-3.48 72 118 39 45 0.56 MAN 2BH

-2.21

-1.92 0.29 72 119 39 45 SAD 2BH

-3.15 73 120 1

46 4.28 MAN 2BH

-5.67

-5.45 0.22 73 121 1

46 SAD 2BH

-2.80 74 122.

14 46 1.86 MAN 2BH

-2.05

-1.57 0.48 74 123 14 46 SAD 2BH

-3.20 75 124 17 46 3.65 MAN 2BH

-5.73

-5.61 0.12 75 125 17 46 1.34 MAN 2BH

-0.87

-0.79 0.08 75 126 17 46 0.42 SAN 2BH

-3.16

-2.99 0.17 76 127 20 46 SAD 2BH

-3.00 77 128 22 46 SAD 2BH

-2.98 78 129 23 46 SAD 2BH

-3.38 79 130 9

47 MAD 2BH

-2.78 80 131 11 47 MAD 2BH

-2.80 81 132 12 47 SAD 2BH

-4.43 81 133 12 47 1.54 SAN 2BH

-0.80

-0.71 0.09 82 134 18 47 MAD 2BH

-3.37 83 135 21 47 SAD 2BH

-3.20 84 136 23 47 MAD 2BH

-2.98 85 137 17 48 SAD 2BH

-3.25 86 138 19 48 SAD 2BH

-2.86 87 139 27 48 SAD 2BH

-3.08 88 140 3

49 2.29 MAN 2BH

-2.04

-1.80 0.24 88 141 3

49 0.41 SAN 2BH

-3.13

-3.06 0.07 88 142 3

49 2.06 SAN 2BH

-0.75

-0.64 0.11 89 143 13 49 SAD 2BH

-3.53 89 144 13 49 2.63 SAN 2BH

-0.69

-0.58 0.11 Page 104 of 169

TABLE 10 STEAM GENERATOR 22 - HISTORICAL F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 90 145 18 49 3.03 MAN 2BH

-3.25

-3.10 0.15 90 146 18 49 1.82 SAN 2BH

-0.89

-0.79 0.10 91 147 10 50 SAD 2BH

-2.97 91 148 10 50 2.59 SAN 2BH

-5.85

-5.74 0.11 92 149 20 50 SAD 2BH

-2.87 93 150 23 50 MAD 2BH

-2.97 93 151 23 50 2.41 MAN 2BH

-0.81

-0.66 0.15 94 152 26 50 MAD 2BH

-3.14 95 153 27 50 MAD 2BH

-3.51 95 154 27 50 0.97 MAN 2BH

-0.74

-0.60 0.14 96 155 8

51 SAD 2BH

-3.12 97 156 9

51 MAD 2BH

-3.22 97 157 9

51 1.59 MAN 2BH

-2.42

-2.17 0.25 97 158 9

51 3.33 SAN 2BH

-5.64

-5.52 0.12 98 159 11 51 SAD 2BH

-3.16 99 160 18 51 MAD 2BH

-3.37 99 161 18 51 1.61 SAN 2BH

-0.69

-0.54 0.15 100 162 20 51 MAD 2BH

-3.03 100 163 20 51 1.80 SAN 2BH

-2.02

-1.89 0.13 101 164 7

52 SAD 2BH

-2.97 101 165 7

52 2.68 SAN 2BH

-0.75

-0.56 0.19 102 166 18 52 SAD 2BH

-3.10 103 167 24 52 3.77 MAN 2BH

-3.41

-2.99 0.42 104 168 29 52 1.55 SAN 2BH

-3.46

-3.39 0.07 104 169 29 52 1.38 SAN 2BH

-2.23

-2.17 0.06 104 170 29 52 2.64 SAN 2BH

-0.55

-0.40 0.15 105 171 1

53 MAD 2BH

-3.00 105 172 1

53 4.13 MAN 2BH

-5.74

-5.58 0.16 106 173 10 53 MAD 2BH

-3.29 106 174 10 53 2.05 SAN 2BH

-5.91

-5.82 0.09 107 175 12 53 3.33 SAN 2BH

-3.01

-2.94 0.07 107 176 12 53 3.22 SVN 2BH

-4.39

-4.03 0.36 108 177 13 53 5.59 MAN 2BH

-3.29

-2.84 0.45 108 178 13 53 1.57 SAN 2BH

-0.66

-0.59 0.07 109 179 16 53 1.76 MAN 2BH

-2.11

-1.90 0.21 109 180 16 53 SAD 2BH

-3.48 110 181 20 53 MAD 2BH

-3.16 111 182 30 53 10.36 MAN 2BH

-3.10

-2.11 0.99 111 183 30 53 SAD 2BH

-3.60 111 184 30 53 2.30 SAN 2BH

-0.64

-0.56 0.08 112 185 11 54 SAD 2BH

-3.05 113 186 12 54 MAD 2BH

-3.04 114 187 18 54 MAD 2BH

-3.41 114 188 18 54 1.73 SAN 2BH

-0.84

-0.68 0.16 115 189 28 54 7.85 MAN 2BH

-2.73

-1.88 0.85 115 190 28 54 SAD 2BH

-3.41 116 191 13 55 13.08 MAN 2BH

-3.46

-2.77 0.69 116 192 13 55 1.66 SAN 2BH

-0.98

-0.90 0.08 Page 105 of 169

TABLE 10 STEAM GENERATOR 22 - HISTORICAL F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 117 193 19 55 MAD 2BH

-3.25 117 194 19 55 0.92 SAN 2BH

-0.76

-0.69 0.07 118 195 37 55 MAD 2BH

-3.46 118 196 37 55 1.87 MAN 2BH

-5.84

-5.70 0.14 118 197 37 55 2.84 MAN 2BH

-2.67

-2.12 0.55 119 198 20 56 SAD 2BH

-3.21 120 199 37 56 1.99 MAN 2BH

-5.66

-5.49 0.17 120 200 37 56 SAD 2BH

-3.00 121 201 13 57 MAD 2BH

-3.31 121 202 13 57 2.08 MAN 2BH

-0.77

-0.65 0.12 122 203 2

58 SAD 2BH

-3.23 123 204 11 58 SAD 2BH

-3.08 124 205 23 58 3.79 MAN 2BH

-3.52

-3.41 0.11 124 206 23 58 0.91 SAN 2BH

-0.71

-0.65 0.06 125 207 21 59 MAD 2BH

-2.90 126 208 9

60 0.43 MAN 2BH

-2.32

-2.18 0.14 126 209 9

60 1.94 SAN 2BH

-5.57

-5.48 0.09 126 210 9

60 0.40 SAN 2BH

-1.65

-1.49 0.16 127 211 20 60 SAD 2BH

-3.25 128 212 22 61 1.47 MAN 2BH

-3.33

-3.23 0.10 128 213 22 61 1.59 MAN 2BH

-0.76

-0.69 0.07 129 214 13 62 MAD 2BH

-3.26 129 215 13 62 3.22 MAN 2BH

-2.57

-1.83 0.74 130 216 15 65 1.05 MAN 2BH

-2.98

-2.80 0.18 130 217 15 65 2.86 SAN 2BH

-0.75

-0.28 0.47 131 218 24 65 2.27 MAN 2BH

-3.46

-3.35 0.11 131 219 24 65 1.01 SAN 2BH

-0.82

-0.76 0.06 132 220 36 65 2.58 MAN 2BH

-5.70

-5.54 0.16 132 221 36 65 10.40 MAN 2BH

-2.49

-1.89 0.60 132 222 36 65 SAD 2BH

-3.56 133 223 37 65 3.46 MAN 2BH

-5.79

-5.55 0.24 133 224 37 65 SAD 2BH

-3.28 133 225 37 65 1.36 SAN 2BH

-0.80

-0.65 0.15 134 226 24 66 1.32 SAN 2BH

-3.53

-3.40 0.13 134 227 24 66 1.80 SAN 2BH

-0.92

-0.82 0.10 135 228 10 67 MAD 2BH.

-3.03 136 229 16 67 2.56 MAN 2BH

-0.78

-0.69 0.09 136 230 16 67 2.36 SAN 2BH

-3.06

-3.00 0.06 137 231 24 69 0.22 MAN 2BH

-3.41

-3.32 0.09 137 232 24 69 1.80 SAN 2BH

-0.76

-0.58 0.18 137 233 24 69 0.84 SAN 2BH

-0.14

-0.01 0.13 138 234 32 70 MAD 2BH

-3.39 138 235 32 70 5.99 MAN 2BH

-2.60

-1.77 0.83 139 236 17 71 MAD 2BH

-3.35 139 237 17 71 2.16 MAN 2BH

-0.79

-0.69 0.10 140 238 20 71 6.19 MAN 2BH

-5.65

-5.37 0.28 140 239 20 71 SAD 2BH

-3.29 140 240 20 71 1.88 SAN 2BH

-0.83

-0.64 0.19 Page 106 of 169

TABLE 10 STEAM GENERATOR 22 - HISTORICAL F*2 TUBE#

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 141 241 12 73 2.41 MAN 2BH

-3.15

-3.00 0.15 141 242 12 73 2.43 SAN 2BH

-0.77

-0.66 0.11 142 243 15 73 1.22 MAN 2BH

-3.20

-3.08 0.12 142 244 15 73 1.43 MAN 2BH

-0.87

-0.79 0.08 143 245 18 73 1.25 MAN 2BH

-0.91

-0.83 0.08 143 246 18 73 SAD 2BH

-3.30 144 247 15 74 MAD 2BH

-3.29 144 248 15 74 2.64 SAN 2BH

-0.97

-0.89 0.08 145 249 14 75 MAD 2BH

-3.33 145 250 14 75 3.19 MAN 2BH

-0.87

-0.76 0.11 146 251 22 75 4.21 MAN 2BH

-2.59

-1.73 0.86 146 252 22 75 SAD 2BH

-3.12 147 253 11 76 2.24 SAN 2BH

-3.25

-3.10 0.15 147 254 11 76 3.69 SAN 2BH

-0.80

-0.68 0.12 148 255 17 76 MAD 2BH

-3.13 148 256 17 76 1.96 MAN 2BH

-0.82

-0.68 0.14 149 257 12 77 MAD 2BH

-3.49 149 258 12 77 1.37 MAN 2BH

-0.75

-0.67 0.08 150 259 18 77 MAD 2BH

-3.43 150 260 18 77 1.76 MAN 2BH

-0.82

-0.69 0.13 151 261 22 77 1.88 MAN 2BH

-0.93

-0.83 0.10 151 262 22 77 4.19 SAN 2BH

-3.48

-3.40 0.08 152 263 11 78 SAD 2BH

-3.36 152 264 11 78 0.70 SAN 2BH

-2.03

-1.97 0.06 153 265 18 78 1.68 MAN 2BH

-0.68

-0.56 0.12 153 266 18 78 SAD 2BH

-3.38 154 267 23 78 8.87 MAN 2BH

-2.79

-1.97 0.82 154 268 23 78 SAD 2BH

-3.46 155 269 12 79 2.02 MAI 2BH

-3.17

-3.04 0.13 155 270 12 79 6.03 MAI 2BH

-2.80

-2.28 0.52 155 271 12 79 1.79 MAN 2BH

-0.92

-0.75 0.17 156 272 14 79 5.38 MAN 2BH

-5.70

-5.55 0.15 156 273 14 79 1.04 MAN 2BH

-3.16

-3.03 0.13 156 274 14 79 1.78 MAN 2BH

-0.78

-0.71 0.07 157 275 15 79 MAD 2BH

-3.29 157 276 15 79 5.79 MAN 2BH

-5.59

-5.37 0.22 157 277 15 79 1.75 SAN 2BH

-0.66

-0.59 0.07 158 278 13 80 4.93 MAN 2BH

-3.06

-2.80 0.26 158 279 13 80 1.84 SAN 2BH

-0.60

-0.45 0.15 159 280 13 81 SAD 2BH

-3.38 159 281 13 81 1.27 SAN 2BH

-2.03

-1.86 0.17 160 282 18 81 SAD 2BH

-3.26 160 283 18 81 1.45 SAN 2BH

-0.74

-0.65 0.09 161 284 22 81 1.58 SAN 2BH

-3.48

-3.38 0.10 161 285 22 81 1.91 SAN 2BH

-0.88

-0.79 0.09 162 286 26 81 MAD 2BH

-3.34 162 287 26 81 4.20 MAN 2BH

-2.42

-1.95 0.47 163 288 17 82 MAD 2BH

-3.30 Page 107 of 169

TABLE 10 STEAM GENERATOR 22 - HISTORICAL F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 163 289 17 82 4.73 SAN 2BH

-0.85

-0.69 0.16 164 290 13 86 1.59 MAN 2BH

-0.78

-0.72 0.06 164 291 13 86 SAD 2BH

-3.32 165 292 15 86 MAD 2BH

-3.42 165 293 15 86 4.68 MAN 2BH

-2.51

-1.93 0.58 166 294 14 88 3.91 MAN 2BH

-2.62

-1.88 0.74 166 295 14 88 SAD 2BH

-3.42 Page 108 of 169

TABLE 11 STEAM GENERATOR 21 - HISTORICAL EF*

TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 11 14 1.99 MAN EBH

-13.75

-13.57 0.18 1

2 11 14 1.94 MAN EBH

-9.47

-9.37 0.10 1

3 11 14 2.83 SAN EBH

-11.63

-11.31 0.32 2

4 4

18 4.19 MAN EBH

-13.94

-13.72 0.22 2

5 4

18 3.97 SAN EBH

-11.72

-11.05 0.67 2

6 4

18 2.52 SAN EBH

-9.49

-9.44 0.05 3

7 2

21 1.70 MAN EBH

-10.81

-10.66 0.15 3

8 2

21 4.65 MAN EBH

-9.20

-8.66 0.54 3

9 2

21 SAD EBH

-14.11 3

10 2

21 1.39 SAN EBH

-11.35

-11.21 0.14 4

11 9

21 0.25 MAN EBH

-13.81

-13.70 0.11 4

12 9

21 5.57 SAN EBH

-11.37

-11.07 0.30 4

13 9

21 3.61 SAN EBH

-9.23

-9.13 0.10 5

14 3

24 SAD EBH

-14.03 5

15 3

24 3.02 SAN EBH

-11.17

-11.03 0.14 5

16 3

24 3.08 SAN EBH

-9.08

-8.94 0.14 6

17 6

24 4.31 MAN EBH

-16.34

-16.16 0.18 6

18 6

24 0.27 MAN EBH

-13.78

-13.69 0.09 6

19 6

24 2.55 MAN EBH

-9.37

-9.26 0.11 6

20 6

24 2.64 SAN EBH

-11.49

-11.39 0.10 7

21 4

26 0.88 MAN EBH

-9.16

-9.06 0.10 7

22 4

26 SAD EBH

-13.43 7

23 4

26 4.36 SAN EBH

-11.46

-11.37 0.09 8

24 9

30 2.40 SAN EBH

-16.39

-16.24 0.15 8

25 9

30 0.12 SAN EBH

-13.74

-13.59 0.15 8

26 9

30 4.42 SAN EBH

-11.14

-10.89 0.25 8

27 9

30 3.47 SAN EBH

-9.39

-9.21 0.18 9

28 17 32 SAD EBH

-13.48 9

29 17 32 1.26 SAN EBH

-15.94

-15.81 0.13 10 30 22 33 SAD EBH

-13.90 10 31 22 33 3.65 SAN EBH

-10.83

-10.76 0.07 10 32 22 33 1.60 SAN EBH

-8.86

-8.72 0.14 11 33 27 33 1.64 MAN EBH

-13.88

-13.75 0.13 11 34 27 33 0.99 SAN EBH

-11.48

-11.41 0.07 11 35 27 33 1.84 SAN EBH

-9.32

-9.24 0.08 12 36 3

34 1.38 MAI EBH

-9.36

-9.26 0.10 12 37 3

34 3.69 MAN EBH

-13.89

-13.72 0.17 12 38 3

34 1.46 SAN EBH

-11.56

-11.46 0.10 13 39 13 34 MAD EBH

-13.48 14 40 8

36 0.28 MAN EBH

-13.61

-13.54 0.07 14 41 8

36 1.85 SAN EBH

-11.40

-11.30 0.10 14 42 8

36 2.25 SAN EBH

-9.24

-9.15 0.09 15 43 22 38 MAD EBH

-12.50 15 44 22 38 MAD EBH

-11.00 15 45 22 38 SAD EBH

-13.57 16 46 17 41 SAD EBH

-13.48 17 47 33 41 MAD EBH

-14.24 17 48 33 41 1.16 MAN EBH

-11.47

-11.39 0.08 Page 109 of 169

TABLE 11 STEAM GENERATOR 21 - HISTORICAL EF*

TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 17 49 33 41 1.60 SAN EBH

-9.41

-9.34 0.07 18 50 9

42 1.16 MAN EBH

-10.83

-10.80 0.03 18 51 9

42 SAD EBH

-13.80 18 52 9

42 2.76 SAN EBH

-9.38

-9.30 0.08 19 53 6

43 MAD EBH

-13.31 19 54 6

43 SAD EBH

-13.48 19 55 6

43 SAD EBH

-11.20 20 56 28 43 SAD EBH

-13.51 20 57 28 43 0.65 SAN EBH

-13.33

-10.77 2.56 21 58 9

44 MAD EBH

-13.55 21 59 9

44 2.67 SAN EBH

-11.42

-11.34 0.08 21 60 9

44 1.69 SAN EBH

-9.47

-9.37 0.10 22 61 10 44 2.44 MAN EBH

-13.60

-13.44 0.16 22 62 10 44 SAD EBH

-13.53 22 63 10 44 1.44 SAN EBH

-9.26

-9.19 0.07 23 64 1

46 0.58 MAN EBH

-13.38

-11.80 1.58 23 65 1

46 SAD EBH

-13.41 23 66 1

46 2.36 SAN EBH

-16.27

-16.12 0.15 23 67 1

46 0.60 SAN EBH

-0.05

-0.01 0.04 24 68 10 48 0.92 MAN EBH

-13.48

-13.40 0.08 24 69 10 48 2.31 SAN EBH

-8.83

-8.76 0.07 25 70 28 48 0.22 SAN EBH

-12.98

-9.92 3.06 26 71 14 50 1.97 MAN EBH

-13.70

-13.62 0.08 26 72 14 50 0.11 SAN EBH

-12.89

-12.49 0.40 26 73 14 50 3.52 SAN EBH

-9.41

-9.21 0.20 27 74 20 50 SAD EBH

-13.88 27 75 20 50 0.14 SAN EBH

-10.77

-10.54 0.23 28 76 11 52 2.28 MAN EBH

-9.42

-9.30 0.12 28 77 11 52 SAD EBH

-13.97 28 78 11 52 1.62 SAN EBH

-11.28

-11.19 0.09 29 79 28 55 SAD EBH

-13.90 29 80 28 55 0.43 SAN EBH

-13.44

-10.27 3.17 30 81 5

58 0.37 MAN EBH'

-14.03

-13.87 0.16 30 82 5

58 2.89 SAN EBH

-11.58

-11.46 0.12 30 83 5

58 3.02 SAN EBH

-9.50

-9.36 0.14 31 84 12 65 2.89 MAN EBH

-16.21

-16.04 0.17 31 85 12 65 0.23 MAN EBH

-13.73

-13.62 0.11 31 86 12 65 1.73 MAN EBH

-11.48

-11.34 0.14 31 87 12 65 2.55 SAN EBH

-9.18

-9.01 0.17 32 88 10 71 2.16 MAN EBH

-13.95

-13.81 0.14 32 89 10 71 0.80 MAN EBH

-9.26

-9.18 0.08 32 90 10 71 1.30 SAN EBH

-11.63

-11.52 0.11 33 91 22 72 SAD EBH

-13.52 33 92 22 72 0.44 SAN EBH

-13.52

-10.32 3.20 34 93 10 73 SAD EBH

-14.00 34 94 10 73 2.11 SAN EBH

-11.51

-11.38 0.13 34 95 10 73 1.75 SAN EBH

-9.51

-9.40 0.11 Page 110 of 169

TABLE 12 STEAM GENERATOR 22 - HISTORICAL EF*

TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 21 22 4.91 MAN EBH

-9.42

-9.00 0.42 1

2 21 22 SAD EBH

-14.14 2

3 13 41 MAD EBH

-14.15 2

4 13 41 1.00 SAN EBH

-10.53

-10.46 0.07 3

5 12 42 SAD EBH

-13.64 3

6 12 42 2.91 SAN EBH

-11.48

-11.39 0.09 3

7 12 42 3.45 SAN EBH

-9.67

-9.35 0.32 4

8 15 43 2.53 MAN EBH

-10.70

-10.48 0.22 4

9 15 43 SAD EBH

-13.84 4

10 15 43 0.25 SAN EBH

-12.28

-12.21 0.07 4

11 15 43 0.73 SAN EBH

-9.00

-8.96 0.04 5

12 1

44 MAD EBH

-13.87 5

13 1

44 5.87 MAN EBH

-16.21

-16.07 0.14 5

14 1

44 0.64 SAN EBH

-9.54

-9.43 0.11 6

15 16 44 SAD EBH

-14.03 6

16 16 44 3.78 SAN EBH

-8.80

-8.72 0.08 7

17 17 45 5.16 MAN EBH

-13.86

-13.34 0.52 7

18 17 45 1.92 SAN EBH

-9.35

-9.27 0.08 8

19 15 56 MAD EBH

-13.80 8

20 15 56 2.90 MAN EBH

-11.29

-11.22 0.07 8

21 15 56 1.29 MAN EBH

-9.33

-9.13 0.20 9

22 16 65 MAD EBH

-13.67 9

23 16 65 1.10 MAN EBH

-9.30

-9.22 0.08 10 24 17 80 SAD EBH

-13.90 10 25 17 80 2.31 SAN EBH

-11.17

-11.08 0.09 10 26 17 80 0.82 SAN EBH

-9.97

-9.81 0.16 Page 111 of 169

TABLE 13 STEAM GENERATOR 21 - NEW F*1 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 1

2 4.29 MAN 1BH

-3.48

-3.27 0.21 1

2 1

2 SAD 1BH

-0.95 1

3 1

2 0.84 SAI TRH 0.05 0.09 0.04 1

4 1

2 5.59 SAN TRH

-2.48

-2.27 0.21 2

5 7

6 0.75 MAN 1BH

-1,04

-0.85 0.19 2

6 7

6 1.42 SAN 1BH

-3.52

-3.48 0.04 2

7 7

6 0.71 MAI TRH

-0.04 0.15 0.19 2

8 7

6 1.62 SAN TRH

-2.52

-2.48 0.04 3

9 3

8 MAD 1BH

-1.03 3

10 3

8 0.88 SAN 1BH

-3.45

-3.38 0.07 3

11 3

8 0.45 MAI TRH

-0.03 0.15 0.18 3

12 3

8 0.40 SAN TRH

-2.45

-2.38 0.07 4

13 17 9

SAD 11H

-1.08 4

14 17 9

0.30 SAI TRH 0.08 0.16 0.08 5

15 23 9

MAD 1BH

-0.86 5

16 23 9

0.61 MAI TRH 0.14 0.23 0.09 6

17 9

11 SAD 1BH

-0.91 6

18 9

11 0.78 SAI TRH

-0.10

-0.03 0.07 7

19 18 12 SAD IBH

-0.98 7

20 18 12 0.37 SAI TRH 0.02 0.08 0.06 8

21 28 12 MAD IBH

-0.92 8

22 28 12 5.15 MAN 1BH

-3.57

-3.27 0.30 8

23 28 12 1.15 MAI TRH 0.08 0.19 0.11 8

24 28 12 4.75 MAN TRH

-2.57

-2.27 0.30 9

25 28 13 SAD 1BH

-0.90 9

26 28 13 0.50 SAI TRH 0.10 0.16 0.06 10 27 10 14 SAD 1BH

-0.99 10 28 10 14 0.39 SAI TRH 0.01 0.05 0.04 11 29 16 14 0.33 SAN 1BH

-0.92

-0.85 0.07 11 30 16 14 0.35 SAI TRH 0.09 0.16 0.07 12 31 25 15 MAD 1BH

-0.96 12 32 25 15 2.02 MAN 1BH

-3.60

-3.51 0.09 12 33 25 15 0.61 MAI TRH 0.04 0.12 0.08 12 34 25 15 0.83 MAN TRH

-2.60

-2.51 0.09 13 35 30 15 SAD 1BH

-0.92 13 36 30 15 0.28 SAI TRH 0.08 0.14 0.06 14 37 20 16 MAD 1BH

-0.96 14 38 20 16 0.67 MAN 1BH

-3.56

-3.51 0.05 14 39 20 16 0.70 MAI TRH

-0.04 0.04 0.08 14 40 20 16 0.62 MAN TRH

-2.56

-2.51 0.05 15 41 23 16 MAD IBH

-1.02 15 42 23 16 0.54 MAI TRH

-0.02 0.02 0.04 16 43 34 16 SAD 1BH

-0.95 16 44 34 16 0.29 SAI TRH 0.05 0.14 0.09 17 45 5

17 MAD 1BH

-0.98 17 46 5

17 2.42 MAN 1BH

-3.56

-3.43 0.13 17 47 5

17 0.54 MAI TRH 0.02 0.16 0.14 17 48 5

17 2.88 MAN TRH

-2.56

-2.43 0.13 Page 112 of 169

TABLE 13 STEAM GENERATOR 21 - NEW F*1 TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 18 49 24 17 MAD 1BH

-0.96 18 50 24 17 0.78 MAI TRH 0.04 0.09 0.05 19 51 7

18 SAD 1BH

-0.92 19 52 7

18 3.40 SAN 1BH

-3.51

-3.32 0.19 19 53 7

18 0.37 SAI TRH 0.08 0.14 0.06 19 54 7

18 3.37 SAN TRH

-2.51

-2.32 0.19 20 55 29 19 MAD 1BH

-0.90 20 56 29 19 0.28 MAI TRH 0.10 0.17 0.07 21 57 34 19 SAD 1BH

-0.88 21 58 34 19 0.54 SAI TRH 0.12 0.16 0.04 22 59 25 22 MAD 1BH

-0.95 22 60 25 22 0.72 MAI TRH 0.05 0.17 0.12 23 61 35 22 MAD 1BH

-0.92 23 62 35 22 0.37 MAI TRH 0.08 0.26 0.18 24 63 4

23 SAD 1BH

-0.92 24 64 4

23 0.63 SAI TRH 0.08 0.15 0.07 25 65 32 23 SAD 1BH

-0.96 25 66 32 23 2.02 SAN 1BH

-3.37

-3.24 0.13 25 67 32 23 0.36 SAI TRH 0.04 0.08 0.04 25 68 32 23 2.27 SAN TRH

-2.37

-2.24 0.13 26 69 29 25 MAD 1BH

-0.91 26 70 29 25 1.88 SAN 1BH

-3.38

-3.25 0.13 26 71 29 25 0.48 MAI TRH 0.09 0.18 0.09 26 72 29 25 0.56 SAN TRH

-2.38

-2.25 0.13 27 73 32 25 SAD 1BH

-0.97 27 74 32 25 1.18 SAN 1BH

-3.68

-3.62 0.06 27 75 32 25 1.39 SAI TRH

-2.68

-2.62 0.06 27 76 32 25 0.59 SAI TRH 0.03 0.11 0.08 28 77 33 25 MAD 1BH

-0.91 28 78 33 25 5.50 MAN 1BH

-3.39

-3.20 0.19 28 79 33

.25 0.31 MAI TRH 0.09 0.19 0.10 28 80 33 25 4.21 MAN TRH

-2.39

-2.20 0.19 29 81 34 25 SAD 1BH

-0.88 29 82 34 25 0.22 SAI TRH 0.12 0.21 0.09 30 83 9

26 SAD 1BH

-0.91 30 84 9

26 0.63 SAI TRH 0.09 0.16 0.07 31 85 29 26 MAD 1BH

-0.93 31 86 29 26 1.21 SAN 1BH

-3.66

-3.52 0.14 31 87 29 26 0.86 MAI TRH 0.07 0.17 0.10 32 88 31 26 SAD 1BH

-0.94 32 89 31 26 0.45 SAI TRH 0.06 0.12 0.06 33 90 32 26 MAD 1BH

-0.98 33 91 32 26 1.23 MAN 1BH

-3.57

-3.49 0.08 33 92 32 26 1.02 MAI TRH

-0.02 0.07 0.09 33 93 32 26 0.98 MAN TRH

-2.57

-2.49 0.08 34 94 37 26 SAD 1BH

-0.98 34 95 37 26 0.60 SAI TRH 0.02 0.19 0.17 35 96 20 29 SAD IBH

-0.92 Page 113 of 169

TABLE 13 STEAM GENERATOR 21 - NEW F*1 TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 35 97 20 29 0.71 SAI TRH 0.08 0.20 0.12 36 98 30 29 SAD 1BH

-0.97 36 99 30 29 0.83 SAI TRH 0.03 0.13 0.10 37 100 33 29 MAD 1BH

-0.94 37 101 33 29 1.62 SAN 1BH

-3.43

-3.30 0.13 37 102 33 29 0.58 MAI TRH 0.06 0.22 0.16 37 103 33 29 0.87 SAN TRH

-2.43

-2.30 0.13 38 104 34 29 SAD 1BH

-0.87 38 105 34 29 0.36 SAI TRH 0.13 0.19 0.06 39 106 37 29 MAD 1BH

-0.98 39 107 37 29 0.78 MAI TRH 0.02 0.19 0.17 40 108 30 31 SAD 1BH

-0.92 40 109 30 31 0.44 SAI TRH 0.08 0.13 0.05 41 110 33 31 MAD 1BH

-0.94 41 111 33 31 0.71 MAI TRH 0.06 0.26 0.20 42 112 10 32 SAD IBH

-0.78 42 113 10 32 0.26 SAI TRH 0.22 0.30 0.08 43 114 29 32 SAD 1BH

-0.91 43 115 29 32 0.51 SAI TRH 0.09 0.15 0.06 44 116 31 32 MAD IBH

-0.97 44 117 31 32 0.56 MAI TRH

-0.03 0.02 0.05 45 118 9

33 MAD 1BH

-0.89 45 119 9

33 0.45 MAI TRH 0.11 0.23 0.12 46 120 29 33 SAD 11BH

-0.96 46 121 29 33 0.64 SAI TRH 0.04 0.17 0.13 47 122 30 33 MAD 1BH

-0.99 47 123 30 33 0.38 MAI TRH

-0.01 0.05 0.06 48 124 39 34 MAD 1BH

-0.85 48 125 39 34 0.67 MAI TRH

-0.15

-0.04 0.11 49 126 32 35 MAD 1BH

-0.94 49 127 32 35 0.79 MAI TRH 0.06 0.18 0.12 50 128 35 35 MAD 1BH

-0.97 50 129 35 35 0.61 MAI TRH 0.03 0.12 0.09 51 130 31 36 SAD 1BH

-0.93 51 131 31 36 0.32 SAI TRH 0.07 0.16 0.09 52 132 34 36 MAD 1BH

-0.96 52 133 34 36 0.81 MAI TRH

-0.04 0.08 0.12 53 134 43 36 0.25 SAN IBH

-0.93

-0.82 0.11 53 135 43 36 0.47 SAI TRH 0.07 0.18 0.11 54 136 4

40 SAD 1BH

-0.95 54 137 4

40 0.56 SAI TRH 0.05 0.12 0.07 55 138 35 40 MAD 1BH

-0.92 55 139 35 40 0.94 MAI TRH 0.08 0.22 0.14 56 140 36 40 SAD 1BH

-0.96 56 141 36 40 0.64 SAI TRH 0.04 0.12 0.08 57 142 25 41 MAD 1BH

-0.93 57 143 25 41 4.46 SAN IBH

-3.50

-3.33 0.17 57 144 25 41 0.67 MAI TRH 0.07 0.17 0.10 Page 114 of 169

TABLE 13 STEAM GENERATOR 21 - NEW F*I TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 57 145 25 41 3.27 SAN TRH

-2.50

-2.33 0.17 58 146 29 41 MAD 1BH

-0.99 58 147 29 41 1.49 SAN 1BH

-3.53

-3.46 0.07 58 148 29 41 1.26 MAI TRH

-0.01 0.12 0.13 58 149 29 41 1.09 SAI TRH

-2.53

-2.46 0.07 59 150 34 42 MAD 11BH

-0.87 59 151 34 42 0.54 MAI TRH 0.13 0.20 0.07 60 152 45 42 SAD 1BH

-0.93 60 153 45 42 0.55 SAI TRH 0.07 0.16 0.09 61 154 27 43 SAD 1BH

-1.00 61 155 27 43 0.88 SAI TRH 0.00 0.12 0.12 62 156 29 43 MAD 1BH

-0.96 62 157 29 43 0.50 MAI TRH 0.04 0.13 0.09 63 158 33 43 MAD 1BH

-0.98 63 159 33 43 1.00 MAI TRH 0.02 0.15 0.13 64 160 40 43 MAD IBH

-0.96 64 161 40 43 0.36 MAI TRH 0.04 0.17 0.13 65 162 43 43 SAD IBH

-0.95 65 163 43 43 0.42 SAI TRH 0.05 0.22 0.17 66 164 2

44 SAD 1BH

-0.89 66 165 2

44 0.42 SAI TRH 0.11 0.15 0.04 67 166 41 44 MAD 1BH

-0.93 67 167 41 44 0.54 MAI TRH 0.07 0.14 0.07 68 168 33 46 SAD 1BH

-1.00 68 169 33 46 0.34 SAI TRH 0.00 0.12 0.12 69 170 41 46 MAD 1BH

-0.91 69 171 41 46 0.79 MAI TRH 0.09 0.22 0.13 70 172 10 47 SAD 1131BH

-0.88 70 173 10 47 0.49 SAI TRH 0.12 0.29 0.17 71 174 32 47 SAD 1BH

-0.90 71 175 32 47 0.46 SAI TRH 0.10 0.16 0.06 72 176 2

49 MAD 1BH

-0.91 72 177 2

49 0.69 MAI TRH 0.09 0.22 0.13 73 178 16 49 MAD 1BH

-0.91 73 179 16 49 0.63 MAI TRH 0.09 0.18 0.09 74 180 35 49 MAD 1BH

-0.93 74 181 35 49 0.31 MAI TRH 0.07 0.16 0.09 75 182 42 49 MAD 1BH

-0.88 75 183 42 49 0.76 MAI TRH 0.11 0.18 0.07 76 184 27 50 MAD 1BH

-0.89 76 185 27 50 0.43 MAI TRH 0.11 0.19 0.08 77 186 32 50 MAD 1BH

-0.92 77 187 32 50 0.60 MAI TRH 0.08 0.19 0.11 78 188 35 50 MAD 1BH

-0.94 78 189 35 50 0.37 MAI TRH

-0.06 0.03 0.09 79 190 39 50 MAD 1BH

-0.96 79 191 39 50 0.53 MAI TRH

-0.04 0.07 0.11 80 192 33 53 SAD 1BH

-0.85 Page 115 of 169

TABLE 13 STEAM GENERATOR 21 - NEW F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 80 193 33 53 0.50 SAI TRH 0.15 0.21 0.06 81 194 23 56 MAD 1BH

-0.94 81 195 23 56 0.60 MAI TRH 0.06 0.18 0.12 82 196 38 57 SAD IBH

-0.92 82 197 38 57 0.84 SAI TRH 0.08 0.26 0.18 83 198 16 59 SAD 1BH

-0.87 83 199 16 59 0.54 SAI TRH 0.13 0.20 0.07 84 200 31 60 MAD 1BH

-0.87 84 201 31 60 0.73 MAI TRH 0.13 0.30 0.17 85 202 31 62 0.91 MAN 1BH

-3.50

-3.40 0.10 85 203 31 62 SAD 1BH

-0.85 85 204 31 62 0.96 MAI TRH

-2.50

-2.40 0.10 85 205 31 62 0.54 SAI TRH 0.15 0.30 0.15 86 206 33 62 MAD 1BH

-0.90 86 207 33 62 5.22 SAN 1BH

-3.71

-3.49 0.22 86 208 33 62 0.63 MAI TRH 0.10 0.26 0.16 86 209 33 62 5.12 SAN TRH

-2.71

-2.49 0.22 87 210 23 64 4.81 MAN 1BH

-3.60

-3.47 0.13 87 211 23 64 0.50 SAN 1BH

-0.89

-0.72 0.17 87 212 23 64 5.11 MAN TRH

-2.60

-2.47 0.13 87 213 23 64 0.63 SAI TRH 0.11 0.28 0.17 88 214 40 64 MAD IBH

-0.87 88 215 40 64 0.58 MAI TRH 0.13 0.22 0.09 89 216 27 65 MAD 1BH

-0.90 89 217 27 65 2.84 SAN 1BH

-3.66

-3.45 0.21 89 218 27 65 0.76 MAI TRH 0.10 0.25 0.15 89 219 27 65 3.60 SAN TRH

-2.66

-2.45 0.21 90 220 33 65 MAD 1BH

-0.89 90 221 33 65 2.24 MAN IBH

-3.58

-3.49 0.09 90 222 33 65 0.80 MAI TRH 0.11 0.26 0.15 90 223 33 65 2.49 MAN TRH

-2.58

-2.49 0.09 91 224 34 65 MAD 1BH

-0.89 91 225 34 65 0.44 MAI TRH 0.11 0.26 0.15 92 226 1

68 5.80 MAN 1BH

-3.42

-3.30 0.12 92 227 1

68 SAD 1BH

-0.88 92 228 1

68 5.36 MAN TRH

-2.42

-2.30 0.12 92 229 1

68 0.58 SAI TRH 0.12 0.21 0.09 93 230 3

68 MAD IBH

-0.94 93 231 3

68 0.75 SAN 1BH

-3.53

-3.50 0.03 93 232 3

68 0.60 MAI TRH 0.06 0.18 0.12 93 233 3

68 0.57 SAI TRH

-2.53

-2.50 0.03 94 234 27 68 4.98 MAN 1BH

-3.68

-3.49 0.19 94 235 27 68 0.36 MAN 1BH

-0.87

-0.74 0.13 94 236 27 68 0.87 MAI TRH 0.13 0.26 0.13 94 237 27 68 5.59 SAN TRH

-2.68

-2.49 0.19 95 238 2

69 MAD 1BH

-0.97 95 239 2

69 2.63 SAN 1BH

-3.47

-3.33 0.14 95 240 2

69 0.84 MAI TRH 0.03 0.13 0.10 Page 116 of 169

TABLE 13 STEAM GENERATOR 21 - NEW F~l____

TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 95 241 2

69 2.66 SAN TRH

-2.47

-2.33 0.14 96 242 31 70 MAD 113H

-0.87 96 243 31 70 3.70 MAN 113H

-3.51

-3.34 0.17 96 244 31 70 0.52 1MAI TRH 0.13 0.24 0.11 96 245 31 70 3.46 MAN TRH

-2.51

-2.34 0.17 97 246 14 71 MAD 113H

-0.94 97 247 14 71 0.66 MAN 113H

-3.56

-3.52 0.04 97 248 14 71 0.72 MAI TRH 0.06 0.16 0.10 98 249 26 72 MAD 113H

-0.86 98 2 5 0 26 72 1.17 SAN 113H

-3.56

-3.52 0.04 98 251 26 72 0.66 MAI TRH 0.14 0.23 0.09 98 252 26 72 1.20 SAN TRH

-2.56

-2.52 0.04 99 253 27 72

____MAD 113H

-0.82 99 254 27 72 4.11 MAN 113H

-3.62

-3.45 0.17 99 2 55 27 72 0.52 MAI TRH 0.18 0.22 0.04 99 256 27 72 4.15 MAN TRH

-2.62

-2.45 0.17 100 257 33 72 MAD 1131-

-0.87 100 258 33 72 2.15 MAN 1131-

-3.59

-3.52 0.07 100 259 33 72 0.47 MAI TRH 0.13 0.24 0.11 100 260 33 72 2.20 MAN TRH

-2.59

-2.52 0.07 101 261 29 73 MAD 1131-

-0.90 101 262 29 73 0.53 MAI TRH ___

0.10 0.21 0.11 102 263 22 74 MAD IBH

-0.80 102 264 22 74 0.48 MAI TRH ___

0.20 0.27 0.07 103 265 26 74 MAD 1131-

-0.84 103 266 26 74 3.08 SAN 1131-

-3.46

-3.26 0.20 103 267 26 74 0.61 MAI TRH 0.16 0.23 0.07 103 268 26 74 3.37 SAN TRH

-2.46

-2.26 0.20 104 269 31 74

____MAD 1131-

-0.86 104 270 31 74 1.59 SAN 1131-

-3.44

-3.32 0.12 104 271 31 74 0.51 MAI TRH __

0.14 0.27 0.13 104 272 31 74 1.54 SAl TRH

-2.44

-2.32 0.12 105 273 32 74 MAD 113H

-0.87 105 274 32 74 5.11 SAN 1131-

-3.58

-3.39 0.19 105 275 32 74 0.69 MAI TRH 0.13 0.20 0.07 105 276 32 74 4.98 SAN TRH

-2.58

-2.39 0.19 106 277 33 74 MAD 113H

-0.84 106 278 33 74 3.44 SAN 1131-

-3.62

-3.47 0.15 106 279 33 74 0.50-MAI TRH 0.16 0.28 0.12 106 280 33 74 3.16 SAN TRH

-2.62

-2.47 0.15 107 281 7

75

____MAD 1131-1

-0.91 107 282 7

75 0.62 MAI TRH__

0.09 0.27 0.18 108 283 28 75 2.17 MAN 1131-

-3.61

-3.49 0.12 108 284 28 75 SAD 1131-

-1.11 108 285 28 75 2.17 MAN TRH

-2.61

-2.49 0.12 108 286 28 75 0.83 SAl TRH 0.11 0.14 0.03 109 287 1

76 MAD 1131-

-0.88 109 288 1

76 5.53 1SAN 1131-

-3.72

-3.41

0.3:17 Page 117 of 169

TABLE 13 STEAM GENERATOR 21 - NEW F*I TUBE #

IND #

ROW COL VOLTS POT LOCATION ELEV-FROM ELEV-TO LENGTH 109 289 1

76 0.43 MAI TRH 0.12 0.24 0.12 109 290 1

76 5.98 SAN TRH

-2.72

-2.41 0.31 110 291 4

76 MAD 1BH

-0.97 110 292 4

76 0.54 MAI TRH 0.03 0.11 0.08 111 293 12 76 MAD 1BH

-1.15 111 294 12 76 0.83 MAI TRH 0.15 0.24 0.09 112 295 17 76 MAD IBH

-0.76 112 296 17 76 2.07 SAN 1BH

-3.56

-3.49 0.07 112 297 17 76 0.77 MAI TRH 0.24 0.29 0.05 112 298 17 76 2.60 SAN TRH

-2.56

-2.49 0.07 113 299 30 76 MAD 1BH

-0.83 113 300 30 76 1.45 SAN 1BH

-3.54

-3.41 0.13 113 301 30 76 0.69 MAI TRH 0.17 0.25 0.08 113 302 30 76 1.89 SAI TRH

-2.54

-2.41 0.13 114 303 35 76 MAD 1BH

-0.85 114 304 35 76 0.43 MAI TRH 0.15 0.22 0.07 115 305 35 77 SAD 1BH

-0.92 115 306 35 77 0.85 SAI TRH 0.08 0.15 0.07 116 307 25 78 MAD 1BH

-0.79 116 308 25 78 3.49 MAN 1BH

-3.51

-3.43 0.08 116 309 25 78 0.60 MAI TRH 0.21 0.30 0.09 116 310 25 78 3.88 MAN TRH

-2.51

-2.43 0.08 117 311 29 78 MAD 1BH

-0.78 117 312 29 78 4.13 SAN 1BH

-3.49

-3.42 0.07 117 313 29 78 0.59 MAI TRH 0.22 0.34 0.12 117 314 29 78 3.99 SAN TRH

-2.49

-2.42 0.07 118 315 22 79 3.61 MAN 1BH

-3.46

-3.33 0.13 118 316 22 79 SAD 1BH

-0.91 118 317 22 79 3.43 MAN TRH

-2.46

-2.33 0.13 118 318 22 79 0.69 SAI TRH 0.09 0.14 0.05 119 319 27 79 3.94 MAN 1BH

-3.55

-3.45 0.10 119 320 27 79 SAD 1BH

-0.92 119 321 27 79 3.93 MAN TRH

-2.55

-2.45 0.10 119 322 27 79 0.75 SAI TRH 0.08 0.16 0.08 120 323 10 80 MAD 1BH

-0.85 120 324 10 80 0.74 MAI TRH 0.15 0.26 0.11 121 325 22 80 SAD 1BH

-0.75 121 326 22 80 1.08 SAI TRH 0.25 0.32 0.07 122 327 6

81 MAD 1BH

-0.91 122 328 6

81 0.78 MAI TRH 0.09 0.24 0.15 123 329 22 81 SAD 1BH

-0.89 123 330 22 81 3.27 SAN 1BH

-3.51

-3.35 0.16 123 331 22 81 0.57 SAI TRH 0.11 0.18 0.07 123 332 22 81 3.33 SAN TRH

-2.51

-2.35 0.16 124 333 4

82 SAD 1BH

-0.96 124 334 4

82 0.58 SAI TRH 0.04 0.12 0.08 125 335 17 82 MAD 1BH

-0.74 125 336 17 82 2.32 SAN 1BH

-3.55

-3.45 0.10 Page 118 of 169

TABLE 13 STEAM GENERATOR 21 - NEW F*1 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 125 337 17 82 0.38 MAI TRH 0.26 0.35 0.09 125 338 17 82 2.36 SAN TRH

-2.55

-2.45 0.10 126 339 23 82 MAD 1BH

-0.87 126 340 23 82 5.78 MAN 1BH

-3.55

-3.44 0.11 126 341 23 82 0.37 MAI TRH 0.13 0.26 0.13 126 342 23 82 5.57 MAN TRH

-2.55

-2.44 0.11 127 343 1

83 MAD 1BH

-0.88 127 344 1

83 5.02 SAN 1BH

-3.71

-3.35 0.36 127 345 1

83 0.63 MAI TRH 0.12 0.24 0.12 127 346 1

83 5.49 SAN TRH

-2.71

-2.35 0.36 128 347 17 83 SAD 1BH

-1.02 128 348 17 83 1.45 SAN 1BH

-3.54

-3.47 0.07 128 349 17 83 0.47 SAI TRH

-0.02 0.12 0.14 128 350 17 83 1.62 SAN TRH

-2.54

-2.47 0.07 129 351 22 83 SAD 1BH

-0.88 129 352 22 83 0.68 SAI TRH 0.12 0.17 0.05 130 353 25 83 SAD 1BH

-0.86 130 354 25 83 0.62 SAI TRH 0.14 0.22 0.08 131 355 1

84 SAD 1BH

-0.93 131 356 1

84 3.68 SAN 113-BH

-3.66

-3.50 0.16 131 357 1

84 0.49 SAI TRH 0.07 0.15 0.08 131 358 1

84 3.69 SAN TRH

-2.66

-2.50 0.16 132 359 6

84 MAD 1BH

-0.83 132 360 6

84 0.53 MAI TRH

-0.17 0.04 0.21 133 361 8

84 SAD 1BH

-0.93 133 362 8

84 0.83 SAI TRH 0.07 0.17 0.10 134 363 2

85 MAD 1BH

-0.91 134 364 2

85 0.65 MAI TRH 0.09 0.27 0.18 135 365 6

85 MAD 1BH

-0.90 135 366 6

85 0.98 MAI TRH 0.10 0.22 0.12 136 367 14 85 SAD 1BH

-0.95 136 368 14 85 0.22 SAI TRH 0.05 0.13 0.08 137 369 18 85 MAD 1BH

-0.90 137 370 18 85 0.93 MAI TRH 0.10 0.22 0.12 138 371 8

86 SAD 1BH

-0.95 138 372 8

86 0.56 SAI TRH 0.05 0.21 0.16 139 373 6

87 0.71 SAN 1BH

-0.92

-0.78 0.14 139 374 6

87 0.80 SAI TRH 0.08 0.22 0.14 140 375 8

87 MAD 1BH

-1.00 140 376 8

87 0.70 MAI TRH 0.00 0.26 0.26 141 377 11 87 MAD 1BH

-0.97 141 378 11 87 0.37 MAI TRH 0.03 0.15 0.12 142 379 2

88 MAD 1BH

-0.97 142 380 2

88 0.58 MAI TRH 0.03 0.28 0.25 143 381 3

88 MAD 1BH

-0.93 143 382 3

88 0.71 MAI TRH 0.07 0.26 0.19 144 383 6

88 MAD 1BH

-0.97 144 384 6

88 0.93 MAI TRH 0.03 0.23 0.20 Page 119 of 169

TABLE 13 STEAM GENERATOR 21 - NEW F*I TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 145 385 19 88 SAD 11BH

-0.88 145 386 19 88 0.51 SAI TRH 0.12 0.24 0.12 146 387 6

89 MAD 1BH

-0.92 146 388 6

89 1 0.61 MAI TRH 0.08 0.21 0.13 Page 120 of 169

TABLE 14 STEAM GENERATOR 22 - NEW F*I TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 17 5

SAD IBH

-0.92 1

2 17 5

0.71 SAI TRH 0.08 0.15 0.07 2

3 18 5

0.33 SAN IBH

-0.94

-0.84 0.10 2

4 18 5

0.52 SAI TRH 0.06 0.16 0.10 3

5 9

7 SAD 1BH

-0.89 3

6 9

7 0.38 SAI TRH 0.10 0.16 0.06 4

7 4

10 MAD 1BH

-0.92 4

8 4

10 0.31 MAI TRH 0.04 0.14 0.10 5

9 4

12 SAD 1BH

-0.90 5

10 4

12 0.36 SAI TRH 0.10 0.19 0.09 6

11 3

13 SAD 1BH

-0.91 6

12 3

13 0.35 SAI TRH 0.03 0.12 0.09 7

13 31 13 MAD 1BH

-0.91 7

14 31 13 0.46 MAI TRH 0.09 0.17 0.08 8

15 6

14 SAD 1BH

-0.93 8

16 6

14 0.52 SAI TRH 0.09 0.22 0.13 9

17 7

14 SAD IBH

-0.88 9

18 7

14 0.67 SAI TRH 0.08 0.18 0.10 10 19 16 14 SAD 1BH

-0.89 10 20 16 14 0.51 SAI TRH 0.10 0.16 0.06 11 21 22 15 SAD 1BH

-1.06 11 22 22 15 1.25 SAI TRH

-0.06 0.03 0.09 12 23 20 16 SAD 1BH

-0.88 12 24 20 16 0.48 SAI TRH 0.10 0.17 0.07 13 25 21 16 SAD IBH

-0.85 13 26 21 16 0.42 SAI TRH 0.11 0.24 0.13 14 27 22 16 SAD 1BH

-0.99 14 28 22 16 0.51 SAI TRH

-0.05 0.08 0.13 15 29 3

17 MAD IBH

-0.95 15 30 3

17 0.51 MAI TRH 0.05 0.18 0.13 16 31 9

17 SAD 1BH

-0.89 16 32 9

17 0.58 SAI TRH 0.11 0.15 0.04 17 33 10 17 SAD IBH

-0.90 17 34 10 17 0.35 SAI TRH 0.10 0.17 0.07 18 35 21 17 MAD 1BH

-1.01 18 36 21 17 0.58 MAI TRH

-0.01 0.13 0.14 19 37 29 17 MAD IBH

-0.95 19 38 29 17 0.58 MAI TRH 0.05 0.12 0.07 20 39 12 18 SAD 1BH

-1.00 20 40 12 18 1.24 SAI TRH 0.00 0.08 0.08 21 41 20 19 SAD 1BH

-0.96 21 42 20 19 0.92 SAI TRH 0.04 0.19 0.15 22 43 10 20 MAD 1BH

-0.91 22 44 10 20 0.58 MAI TRH 0.09 0.21 0.12 23 45 13 20 MAD 1BH

-0.99 23 46 13 20 0.22 MAI TRH

-0.01 0.10 0.11 24 47 16 20 MAD 1BH

-0.91 24 48 16 20 0.61 MAI TRH 0.09 0.22 0.13 Page 121 of 169

TABLE 14 STEAM GENERATOR 22 - NEW F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 25 49 17 20 SAD 1BH

-0.88 25 50 17 20 0.37 SAI TRH 0.12 0.22 0.10 26 51 19 20 SAD 1BH

-0.88 26 52 19 20 0.27 SAI TRH 0.12 0.19 0.07 27 53 14 21 SAD IBH

-0.95 27 54 14 21 0.72 SAI TRH 0.05 0.15 0.10 28 55 15 21 MAD 1BH

-0.98 28 56 15 21 0.53 MAI TRH 0.02 0.08 0.06 29 57 28 21 MAD 1BH

-0.92 29 58 28 21 0.57 MAI TRH 0.08 0.18 0.10 30 59 6

22 SAD 1BH

-0.91 30 60 6

22 0.20 SAI TRH 0.09 0.14 0.05 31 61 17 22 MAD 1BH

-0.96 31 62 17 22 0.24 MAI TRH

-0.03 0.16 0.19 32 63 3

23 SAD 1BH

-0.94 32 64 3

23 0.30 SAI TRH 0.06 0.20 0.14 33 65 18 23 MAD IBH

-0.92 33 66 18 23 0.93 MAI TRH 0.08 0.30 0.22 34 67 34 23 SAD 1BH

-0.93 34 68 34 23 0.39 SAI TRH

-0.07 0.03 0.10 35 69 9

24 MAD 1BH

-0.93 35 70 9

24 0.41 MAI TRH 0.07 0.24 0.17 36 71 18 24 MAD 1BH

-0.93 36 72 18 24 0.56 MAI TRH 0.07 0.17 0.10 37 73 22 25 SAD 1BH

-0.93 37 74 22 25 0.36 SAI TRH 0.07 0.15 0.08 38 75 2

26 SAD 1BH

-0.90 38 76 2

26 0.66 SAI TRH 0.10 0.20 0.10 39 77 22 27 MAD 1BH

-0.93 39 78 22 27 0.46 MAI TRH 0.07 0.14 0.07 40 79 32 27 MAD 1BH

-0.94 40 80 32 27 0.57 MAI TRH 0.06 0.20 0.14 41 81 2

28 SAD 1BH

-0.81 41 82 2

28 2.69 SAN 1BH

-3.48

-3.31 0.17 41 83 2

28 0.55 SAI TRH 0.09 0.19 0.10 41 84 2

28 3.38 SAN TRH

-2.48

-2.31 0.17 42 85 18 29 SAD 1BH

-0.91 42 86 18 29 0.46 SAI TRH 0.09 0.22 0.13 43 87 38 29 1.12 MAN 1BH

-2.60

-2.49 0.11 43 88 38 29 1.00 MAI TRH

-1.08

-0.97 0.11 44 89 2

30 MAD 1BH

-0.80 44 90 2

30 2.92 SAN 11BH

-3.54

-3.26 0.28 44 91 2

30 0.50 MAI TRH 0.05 0.20 0.15 44 92 2

30 2.84 SAN TRH

-2.54

-2.26 0.28 45 93 6

30 MAD 1BH

-0.79 45 94 6

30 0.31 MAI TRH 0.04 0.19 0.15 46 95 25 31 SAD IBH

-0.83 46 96 25 31 0.69 SAI TRH 0.04 0.17 0.13 Page 122 of 169

TABLE 14 STEAM GENERATOR 22 - NEW F*I TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 47 97 38 31 1.12 SAN 1BH

-2.05

-1.90 0.15 47 98 38 31 1.06 SAI TRH

-1.05

-0.90 0.15 48 99 4

32 SAD 1BH

-0.93 48 100 4

32 0.48 SAI TRH 0.07 0.16 0.09 49 101 5

32 SAD 1BH

-0.95 49 102 5

32 0.25 SAI TRH 0.05 0.13 0.08 50 103 25 32 MAD I1BH

-0.91 50 104 25 32 0.76 MAN 1BH

-1.42

-1.37 0.05 50 105 25 32 0.94 MAI TRH

-0.03 0.01 0.04 51 106 5

33 SAD 1BH

-0.63 51 107 5

33 0.23 SAI TRH 0.14 0.27 0.13 52 108 4

34 SAD 1BH

-0.83 52 109 4

34 0.34 SAI TRH 0.08 0.17 0.09 53 110 24 34 SAD 1BH

-0.95 53 111 24 34 0.40 SAI TRH

-0.05 0.10 0.15 54 112 4

35 SAD 1BH

-0.84 54 113 4

35 SAD 1BH

-0.81 54 114 4

35 0.46 SAN 1BH

-3.29

-3.21 0.08 54 115 4

35 0.59 SAI TRH

-2.29

-2.21 0.08 54 116 4

35 0.30 SAI TRH 0.16 0.20 0.04 55 117 6

36 MAD 1BH

-0.96 55 118 6

36 0.51 MAI TRH 0.04 0.16 0.12 56 119 28 36 MAD 1BH

-0.83 56 120 28 36 0.41 MAI TRH 0.09 0.17 0.08 57 121 6

38 MAD 113-BH

-0.79 57 122 6

38 0.33 MAI TRH 0.12 0.27 0.15 58 123 28 38 MAD 1BH

-0.96 58 124 28 38 0.54 MAI TRH

-0.02 0.04 0.06 59 125 24 39 SAD 1BH

-0.88 59 126 24 39 0.40 SAI TRH 0.06 0.12 0.06 60 127 5

40 MAD 1BH

-0.79 60 128 5

40 0.35 MAI TRH 0.13 0.25 0.12 61 129 24 40 SAD 1BH

-0.89 61 130 24 40 0.48 SAI TRH 0.00 0.11 0.11 62 131 28 40 SAD 1BH

-0.97 62 132 28 40 0.67 SAI TRH

-0.03 0.03 0.06 63 133 38 40 MAD IBH

-1.01 63 134 38 40 0.66 MAI TRH

-0.01 0.08 0.09 64 135 26 41 SAD 1BH

-0.84 64 136 26 41 0.38 SAI TRH 0.10 0.16 0.06 65 137 3

42 MAD 1BH

-0.80 65 138 3

42 0.31 MAI TRH 0.08 0.22 0.14 66 139 6

42 MAD 1BH

-0.89 66 140 6

42 0.25 MAI TRH 0.11 0.25 0.14 67 141 7

42 MAD 1BH

-0.80 67 142 7

42 0.74 MAI TRH 0.11 0.19 0.08 68 143 2

43 SAD 1BH

-0.98 68 144 2

43 2.45 SAN 1BH

-3.48

-3.37 0.11 Page 123 of 169

TABLE 14 STEAM GENERATOR 22 - NEW F*I TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 68 145 2

43 0.94 SAI TRH 0.02 0.11 0.09 68 146 2

43 2.55 SAN TRH

-2.48

-2.37 0.11 69 147 26 43 MAD 1BH

-0.86 69 148 26 43 0.64 MAI TRH 0.04 0.14 0.10 70 149 28 43 SAD 1BH

-0.97 70 150 28 43 0.63 SAI TRH

-0.03 0.03 0.06 71 151 26 44 SAD 1BH

-0.85 71 152 26 44 0.43 SAI TRH 0.07 0.15 0.08 72 153 7

45 SAD IBH

-0.86 72 154 7

45 0.59 SAI TRH 0.11 0.21 0.10 73 155 38 45 SAD 1BH

-1.03 73 156 38 45 0.45 SAI TRH

-0.03 0.04 0.07 74 157 2

46 MAD 1BH

-0.81 74 158 2

46 1.06 MAI TRH 0.06 0.21 0.15 75 159 4

46 SAD 1BH

-0.93 75 160 4

46 0.39 SAI TRH 0.07 0.14 0.07 76 161 7

47 MAD 1131BH

-0.88 76 162 7

47 0.42 MAI TRH 0.12 0.21 0.09 77 163 2

49 SAD 1BH

-0.90 77 164 2

49 0.48 SAI TRH 0.10 0.17 0.07 78 165 6

50 SAD 1BH

-0.81 78 166 6

50 4.21 SAN 1BH

-3.66

-3.55 0.11 78 167 6

50 0.39 SAI TRH 0.19 0.26 0.07 78 168 6

50 3.56 SAN TRH

-2.87

-2.76 0.11 79 169 21 50 SAD 1BH

-0.86 79 170 21 50 0.47 SAI TRH 0.14 0.19 0.05 80 171 38 50 SAD 1BH

-1.02 80 172 38 50 0.74 SAI TRH

-0.02 0.05 0.07 81 173 5

51 MAD 1BH

-0.94 81 174 5

51 0.60 MAI TRH 0.06 0.15 0.09 82 175 5

52 MAD 1BH

-0.97 82 176 5

52 0.36 MAI TRH 0.03 0.14 0.11 83 177 6

52 MAD 1BH13-

-0.98 83 178 6

52 2.05 MAI TRH

-0.01 0.05 0.06 84 179 11 52 SAD 1BH

-0.98 84 180 11 52 1.18 SAI TRH 0.02 0.05 0.03 85 181 6

53 MAD 1B1H

-0.94 85 182 6

53 3.01 SAN 1BH

-3.78

-3.65 0.13 85 183 6

53 0.82 MAI TRH 0.06 0.17 0.11 85 184 6

53 3.10 SAN TRH

-2.78

-2.65 0.13 86 185 9

53 SAD 1BH

-0.92 86 186 9

53 0.97 SAN 11BH

-3.63

-3.47 0.16 86 187 9

53 0.69 SAI TRH 0.08 0.21 0.13 86 188 9

53 1.07 SAN TRH

-2.63

-2.47 0.16 87 189 6

54 SAD 1BH

-0.94 87 190 6

54 0.45 SAI TRH 0.06 0.15 0.09 88 191 29 54 SAD 1BH 1-

-0.92 88 192 29 54 0.49 SAI TRH 0.08 0.15 0.07 Page 124 of 169

TABLE 14 STEAM GENERATOR 22 - NEW F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 89 193 6

55 SAD 1BH

-1.00 89 194 6

55 3.75 SAN 1BH

-3.61

-3.48 0.13 89 195 6

55 0.86 SAI TRH 0.00 0.15 0.15 89 196 6

55 3.68 SAN TRH

-2.61

-2.48 0.13 90 197 30 55 MAD IBH

-0.93 90 198 30 55 0.62 MAI TRH 0.07 0.20 0.13 91 199 21 56 MAD 1BH

-0.88 91 200 21 56 1.38 MAI TRH 0.12 0.20 0.08 92 201 9

57 SAD 1BH

-0.90 92 202 9

57 0.37 SAI TRH 0.10 0.18 0.08 93 203 6

58 MAD 1BH

-0.98 93 204 6

58 3.59 SAN 1BH

-3.82

-3.71 0.11 93 205 6

58 0.60 MAI TRH 0.02 0.25 0.23 93 206 6

58 3.61 SAN TRH

-2.82

-2.71 0.11 94 207 9

58 MAD 1BH

-0.93 94 208 9

58 1.78 SAN 1BH

-3.61

-3.50 0.11 94 209 9

58 0.92 MAI TRH 0.07 0.25 0.18 94 210 9

58 1.78 SAN TRH

-2.61

-2.50 0.11 95 211 28 58 SAD 1BH

-0.92 95 212 28 58 0.39 SAI TRH 0.08 0.18 0.10 96 213 29 58 SAD 1BH

-0.98 96 214 29 58 0.43 SAI TRH 0.02 0.05 0.03 97 215 32 58 SAD IBH

-0.91 97 216 32 58 0.52 SAI TRH 0.09 0.18 0.09 98 217 34 58 5.44 MAN 1BH

-3.59

-3.24 0.35 98 218 34 58 SAD 1BH

-1.01 98 219 34 58 3.25 MAN TRH

-2.59

-2.24 0.35 98 220 34 58 0.51 SAI TRH

-0.01 0.06 0.07 99 221 8

59 SAD 1BH

-1.01 99 222 8

59 0.72 SAI TRH

-0.01 0.03 0.04 100 223 25 60 SAD 1BH

-1.00 100 224 25 60 0.56 SAI TRH 0.00 0.07 0.07 101 225 2

61 SAD 1BH

-0.91 101 226 2

61 0.34 SAI TRH 0.09 0.10 0.01 102 227 19 63 MAD 1BH

-0.90 102 228 19 63 1.19 MAI TRH 0.10 0.21 0.11 103 229 27 63 SAD 1BH

-0.97 103 230 27 63 0.22 SAI TRH

-0.03 0.07 0.10 104 231 41 63 SAD IBH

-0.97 104 232 41 63 0.49 SAI TRH

-0.03 0.04 0.07 105 233 3

64 1.17 MAN IBH

-3.50

-3.41 0.09 105 234 3

64 SAD 1BH

-0.94 105 235 3

64 1.33 MAI TRH

-2.50

-2.41 0.09 105 236 3

64 1.46 SAI TRH

-0.06 0.02 0.08 106 237 10 64 MAD 1BH

-0.91 106 238 10 64 0.47 MAI TRH 0.09 0.15 0.06 107 239 14 65 SAD 1BH

-0.85 107 240 14 65 0.50 SAI TRH 0.15 0.19 0.04 Page 125 of 169

TABLE 14 STEAM GENERATOR 22 - NEW F*I TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 108 241 27 66 MAD 1BH

-1.02 108 242 27 66 0.66 MAI TRH

-0.02 0.13 0.15 109 243 28 66 SAD 1BH

-0.90 109 244 28 66 0.40 SAI TRH 0.10 0.17 0.07 110 245 29 66 SAD 1BH

-1.00 110 246 29 66 0.21 SAI TRH 0.00 0.14 0.14 111 247 11 67 MAD IBH

-0.95 111 248 11 67 0.46 MAI TRH 0.05 0.13 0.08 112 249 15 67 MAD 1BH

-0.90 112 250 15 67 0.28 MAI TRH 0.10 0.14 0.04 113 251 26 67 SAD 1BH

-1.01 113 252 26 67 0.76 SAI TRH

-0.01 0.06 0.07 114 253 3

68 SAD IBH

-0.88 114 254 3

68 0.51 SAI TRH 0.12 0.16 0.04 115 255 6

68 SAD 1BH

-0.93 115 256 6

68 0.36 SAI TRH 0.07 0.17 0.10 116 257 16 68 MAD 1BH

-0.93 116 258 16 68 0.52 MAI TRH 0.07 0.20 0.13 117 259 17 68 MAD 1BH

-0.92 117 260 17 68 0.64 MAI TRH 0.08 0.22 0.14 118 261 22 68 SAD 1BH

-0.93 118 262 22 68 0.37 SAI TRH 0.07 0.15 0.08 119 263 26 68 SAD 1BH

-1.05 119 264 26 68 0.58 SAI TRH

-0.05 0.03 0.08 120 265 28 68 MAD 11H

-1.02 120 266 28 68 0.55 MAI TRH

-0.02 0.19 0.21 121 267 6

70 SAD 1BH

-0.92 121 268 6

70 0.49 SAI TRH 0.08 0.17 0.09 122 269 20 70 MAD 1BH

-0.91 122 270 20 70 0.42 MAI TRH 0.09 0.16 0.07 123 271 34 70 SAD 1BH

-1.03 123 272 34 70 0.57 SAI TRH

-0.03 0.06 0.09 124 273 24 71 MAD IBH

-0.96 124 274 24 71 3.49 MAN 1BH

-3.36

-3.21 0.15 124 275 24 71 0.71 MAI TRH 0.04 0.08 0.04 124 276 24 71 2.86 MAN TRH

-2.36

-2.21 0.15 125 277 4

72 MAD 1BH

-0.90 125 278 4

72 0.71 MAI TRH 0.10 0.18 0.08 126 279 5

72 SAD 1BH

-0.85 126 280 5

72 2.48 SAN 11BH

-3.50

-3.40 0.10 126 281 5

72 0.71 SAI TRH 0.15 0.22 0.07 126 282 5

72 3.26 SAN TRH

-2.50

-2.40 0.10 127 283 18 72 SAD 1BH

-0.85 127 284 18 72 0.53 SAI TRH 0.15 0.20 0.05 128 285 26 73 MAD 1BH

-1.06 128 286 26 73 0.96 MAI TRH

-0.06 0.02 0.08 129 287 29 73 MAD 1BH

-1.06 129 288 29 73 0.53 MAI TRH

-0.06 0.01 0.07 Page 126 of 169

TABLE 14 STEAM GENERATOR 22 - NEW F*I TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 130 289 32 73 MAD 1BH

-1.05 130 290 32 73 0.45 MAI TRH

-0.05 0.01 0.06 131 291 20 74 SAD 1BH

-0.90 131 292 20 74 0.43 SAI TRH 0.10 0.16 0.06 132 293 11 75 SAD 1BH

-0.84 132 294 11 75 0.35 SAI TRH 0.16 0.25 0.09 133 295 18 75 MAD 1BH

-0.94 133 296 18 75 0.88 MAI TRH 0.06 0.18 0.12 134 297 20 75 MAD 1BH

-0.96 134 298 20 75 0.55 MAI TRH 0.04 0.20 0.16 135 299 31 75 SAD 1BH

-1.02 135 300 31 75 0.53 SAI TRH

-0.02 0.05 0.07 136 301 27 76 SAD 1BH

-1.03 136 302 27 76 0.70 SAI TRH

-0.03 0.08 0.11 137 303 27 77 SAD 1BH

-1.04 137 304 27 77 0.58 SAI TRH 0.04 0.20 0.16 138 305 1

78 7.42 MAN 1BH

-3.69

-3.29 0.40 138 306 1

78 SAD 1BH

-0.92 138 307 1

78 8.83 MAN TRH

-2.69

-2.29 0.40 138 308 1

78 0.42 SAI TRH 0.08 0.20 0.12 139 309 4

78 SAD 1BH

-0.94 139 310 4

78 1.94 SAN 1BH

-3.60

-3.43 0.17 139 311 4

78 0.61 SAI TRH 0.06 0.13 0.07 139 312 4

78 2.28 SAN TRH

-2.60

-2.43 0.17 140 313 13 78 SAD 1BH

-1.08 140 314 13 78 1.01 SAI TRH

-0.08 0.04 0.12 141 315 24 78 SAD 1BH

-1.05 141 316 24 78 0.59 SAI TRH

-0.05 0.02 0.07 142 317 3

79 3.97 MAN 1BH

-3.65

-3.52 0.13 142 318 3

79 SAD 1BH

-0.95 142 319 3

79 4.52 MAN TRH

-2.65

-2.52 0.13 142 320 3

79 0.52 SAI TRH 0.05 0.17 0.12 143 321 4

80 MAD 1BH

-0.98 143 322 4

80 1.68 MAN 1BH

-3.57

-3.40 0.17 143 323 4

80 0.40 MAI TRH 0.02 0.16 0.14 143 324 4

80 1.86 MAN TRH

-2.57

-2.40 0.17 144 325 5

81 MAD 1BH

-0.93 144 326 5

81 2.68 SAN 1BH

-3.68

-3.51 0.17 144 327 5

81 0.54 MAI TRH 0.07 0.22 0.15 144 328 5

81 3.14 SAN TRH

-2.68

-2.51 0.17 145 329 18 83 SAD 1BH

-0.92 145 330 18 83 0.48 SAI TRH 0.08 0.22 0.14 146 331 5

85 SAD 1BH

-0.87 146 332 5

85 0.33 SAI TRH 0.13 0.17 0.04 147 333 5

88 SAD 1BH

-0.89 147 334 5

88 0.66 SAI TRH 0.11 0.24 0.13 148 335 7

88 SAD 1BH

-0.94 148 336 7

88 0.32 SAI TRH 0.06 0.12 0.06 Page 127 of 169

TABLE 14 STEAM GENERATOR 22 - NEW F*I TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 149 337 8

88 MAD 1BH

-1.00 149 338 8

88 0.57 MAI TRH 0.00 0.19 0.19 150 339 5

90 SAD 1BH

-0.95 150 340 5

90 0.33 SAI TRH 0.05 0.18 0.13 151 341 8

91 SAD 1BH

-0.99 151 342 8

91 0.37 SAI TRH 0.01 0.10 0.09 Page 128 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE #

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 17 7

MAD 2BH13-

-3.16 1

2 17 7

0.74 MAN 2BH

-0.78

-0.69 0.09 1

3 17 7

1.90 SAN 2BH

-5.65

-5.57 0.08 1

4 17 7

MAD 1BH

-1.16 1

5 17 7

0.43 MAI 1BH 1.22 1.31 0.09 1

6 17 7

1.67 SAN 1BH

-3.65

-3.57 0.08 2

7 4

9 MAD 2BH

-3.48 2

8 4

9 6.23 MAN 2BH

-5.72

-5.55 0.17 2

9 4

9 0.95 SAN 2BH

-0.85

-0.78 0.07 2

10 4

9 MAD 1BH

-1.48 2

11 4

9 6.28 MAN 1BH

-3.72

-3.55 0.17 2

12 4

9 0.53 SAI 1BH 1.15 1.22 0.07 3

13 19 10 SAD 2BH

-3.05 3

14 19 10 2.22 SAN 2BH

-5.64

-5.44 0.20 3

15 19 10 2.30 SAN 2BH

-0.79

-0.70 0.09 3

16 19 10 SAD 1BH

-1.05 3

17 19 10 1.12 SAI 1BH 1.21 1.30 0.09 3

18 19 10 2.23 SAN 1BH

-3.64

-3.44 0.20 4

19 1

11 7.58 MAN 21H

-5.73

-5.56 0.17 4

20 1

11 SAD 2BH

-3.48 4

21 1

11 0.72 SAN 2BH

-0.82

-0.78 0.04 4

22 1

11 8.24 MAN 1BH

-3.73

-3.56 0.17 4

23 1

11 SAD 1BH

-1.48 4

24 1

11 0.61 SAI 1BH 1.18 1.22 0.04 5

25 14 11 MAD 2BH

-3.12 5

26 14 11 0.66 SAN 2BH

-0.86

-0.82 0.04 5

27 14 11 MAD 1BH

-1.12 5

28 14 11 0.30 SAI 1BH 1.14 1.18 0.04 6

29 24 11 MAD 2BH

-3.30 6

30 24 11 4.20 MAN 2BH

-5.70

-5.62 0.08 6

31 24 11 5.00 MAN 2BH

-2.56

-1.89 0.67 6

32 24 11 MAD 1BH

-1.30 6

33 24 11 6.19 MAI IBH

-0.56 0.11 0.67 6

34 24 11 4.30 MAN IBH

-3.70

-3.62 0.08 7

35 21 13 SAD 2BH

-3.24 7

36 21 13 1.71 SAN 2BH

-5.48

-5.39 0.09 7

37 21 13 1.06 SAN 2BH

-0.91

-0.87 0.04 7

38 21 13 SAD 1BH

-1.24 7

39 21 13 0.73 SAI 1BH 1.09 1.13 0.04 7

40 21 13 1.49 SAN 1BH

-3.48

-3.39 0.09 8

41 1

15 2.46 MAN 2BH

-3.23

-3.08 0.15 8

42 1

15 1.12 SAN 2BH

-0.78

-0.72 0.06 8

43 1

15 2.83 MAN 1BH

-1.23

-1.08 0.15 8

44 1

15 0.72 SAI 1BH 1.22 1.28 0.06 9

45 4

16 3.60 MAN 2BH

-5.67

-5.51 0.16 9

46 4

16 2.28 MAN 2BH

-3.31

-3.10 0.21 9

47 4

16 0.27 SAN 2BH

-2.36

-2.22 0.14 9

48 4

16 0.76 SAN 2BH

-0.97

-0.87 0.10 Page 129 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 9

49 4

16 3.89 MAN 1BH

-3.67

-3.51 0.16 9

50 4

16 2.06 MAN 1BH

-1.31

-1.10 0.21 9

51 4

16 0.41 SAI 1BH 1.03 1.13 0.10 9

52 4

16 0.27 SAN IBH

-0.36

-0.22 0.14 10 53 18 16 4.55 MAN 2BH

-5.71

-5.48 0.23 10 54 18 16 SAD 2BH

-3.24 10 55 18 16 1.86 SAN 2BH

-0.86

-0.80 0.06 10 56 18 16 4.73 MAN 1BH

-3.71

-3.48 0.23 10 57 18 16 SAD 1BH

-1.24 10 58 18 16 0.76 SAI 1BH 1.14 1.20 0.06 11 59 13 17 SAD 2BH

-3.31 11 60 13 17 0.73 SAN 2BH

-0.89

-0.80 0.09 11 61 13 17 SAD 1BH

-1.31 11 62 13 17 0.41 SAI 1BH 1.11 1.20 0.09 12 63 22 17 0.70 MAN 2BH

-0.80

-0.71 0.09 12 64 22 17 SAD 2BH

-3.35 12 65 22 17 SAD 1BH

-1.35 12 66 22 17 0.53 SAI 1BH 1.20 1.29 0.09 13 67 5

18 3.89 MAN 2BH

-3.29

-2.89 0.40 13 68 5

18 0.57 SAN 2BH

-5.68

-5.64 0.04 13 69 5

18 0.97 SAN 2BH

-0.75

-0.65 0.10 13 70 5

18 3.90 MAN IBH

-1.29

-0.89 0.40 13 71 5

18 0.62 SAI 1BH

-3.68

-3.64 0.04 13 72 5

18 0.90 SAI 1BH 1.25 1.35 0.10 14 73 11 18 SAD 2BH

-3.40 14 74 11 18 0.81 SAN 2BH

-0.85

-0.79 0.06 14 75 11 18 SAD 1BH

-1.40 14 76 11 18 0.39 SAI 1BH 1.15 1.21 0.06 15 77 16 19 3.19 MAN 2BH

-5.51

-5.43 0.08 15 78 16 19 0.72 MAN 2BH

-0.81

-0.77 0.04 15 79 16 19 SAD 2BH

-3.20 15 80 16 19 3.11 MAN 1BH

-3.51

-3.43 0.08 15 81 16 19 SAD 1BH

-1.20 15 82 16 19 0.25 SAi 1BH 1.19 1.23 0.04 16 83 7

20 4.97 MAN 2BH

-5.74

-5.48 0.26 16 84 7

20 4.08 MAN 2BH

-3.30

-3.02 0.28 16 85 7

20 1.62 SAN 2BH

-0.85

-0.73 0.12 16 86 7

20 6.92 MAN 1BH

-3.74

-3.48 0.26 16 87 7

20 4.11 MAN 1BH

-1.30

-1.02 0.28 16 88 7

20 0.90 SAI 1BH 1.15 1.27 0.12 17 89 9

20 1.28 MAN 2BH

-0.80

-0.64 0.16 17 90 9

20 SAD 2BH

-3.16 17 91 9

20 SAD 1BH

-1.16 17 92 9

20 0.72 SAI 1BH 1.20 1.36 0.16 18 93 20 20 SAD 2BH

-3.23 18 94 20 20 0.94 SAN 2BH

-5.56

-5.49 0.07 18 95 20 20 0.96 SAN 2BH

-0.80

-0.73 0.07 18 96 20 20 SAD 1BH

-1.23 Page 130 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE#

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 18 97 20 20 0.65 SAI 1BH 1.20 1.27 0.07 18 98 20 20 1.33 SAN IBH

-3.56

-3.49 0.07 19 99 23 20 MAD 2BH

-3.42 19 100 23 20 2.71 MAN 2BH

-5.47

-5.39 0.08 19 101 23 20 0.69 SAN 2BH

-0.82

-0.75 0.07 19 102 23 20 MAD 1BH

-1.42 19 103 23 20 2.54 MAN 1BH

-3.47

-3.39 0.08 19 104 23 20 0.38 SAI 1BH 1.18 1.25 0.07 20 105 30 20 2.83 MAN 21H

-0.70

-0.56 0.14 20 106 30 20 SAD 2BH

-3.40 20 107 30 20 0.99 MAI 1BH 1.30 1.44 0.14 20 108 30 20 SAD 1BH

-1.40 21 109 13 21 FPC 1BH 0.30 21 110 13 21 SAD 1BH

-0.87 21 111 13 21 SAD 2BH

-2.87 21 112 13 21 0.36 SAI TRH 0.13 0.21 0.08 22 113 19 21 SAD 2BH

-3.03 22 114 19 21 1.09 SAN 2BH

-0.87

-0.80 0.07 22 115 19 21 SAD 1BH

-1.03 22 116 19 21 0.57 SAI 1BH 1.13 1.20 0.07 23 117 4

22 1.69 MAN 2BH

-3.20

-3.09 0.11 23 118 4

22 2.21 MAN 2BH

-0.75

-0.67 0.08 23 119 4

22 1.58 MAI 1BH 1.25 1.33 0.08 23 120 4

22 2.14 MAN 1BH

-1.20

-1.09 0.11 24 121 13 22 MAD 2BH

-3.20 24 122 13 22 1.55 MAN 2BH

-0.87

-0.77 0.10 24 123 13 22 MAD 1BH

-1.20 24 124 13 22 0.65 SAI 1BH 1.13 1.23 0.10 25 125 18 22 SAD 2BH

-3.16 25 126 18 22 1.91 SAN 2BH

-0.81

-0.71 0.10 25 127 18 22 SAD 1BH

-1.16 25 128 18 22 0.78 SAI 1BH 1.19 1.29 0.10 26 129 21 22 MAD 2BH

-3.31 26 130 21 22 1.65 SAN 2BH

-0.75

-0.68 0.07 26 131 21 22 MAD 1BH

-1.31 26 132 21 22 0.92 SAI 1BH 1.25 1.32 0.07 27 133 22 22 SAD 2BH

-2.85 27 134 22 22 2.25 SAN 2BH

-0.80

-0.71 0.09 27 135 22 22 SAD 1BH

-0.85 27 136 22 22 1.03 SAI 1BH 1.20 1.29 0.09 28 137 6

23 5.68 MAN 2BH

-5.58

-5.41 0.17 28 138 6

23 1.44 MAN 2BH

-3.08

-2.98 0.10 28 139 6

23 0.97 SAN 2BH

-0.84

-0.77 0.07 28 140 6

23 6.70 MAN 1BH

-3.58

-3.41 0.17 28 141 6

23 1.85 MAN 1BH

-1.08

-0.98 0.10 28 142 6

23 0.65 SAI 1BH 1.16 1.23 0.07 29 143 37 23 SAD 2BH

-3.38 29 144 37 23 0.63 SAN 2BH

-0.68

-0.61 0.07 Page 131 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 29 145 37 23 SAD 1BH

-1.38 29 146 37 23 0.53 SAI 1BH 1.32 1.39 0.07 30 147 38 23 MAD 2BH

-3.29 30 148 38 23 3.04 MAN 2BH

-0.85

-0.71 0.14 30 149 38 23 MAD 1BH

-1.29 30 150 38 23 1.16 MAI 1BH 1.15 1.29 0.14 31 151 9

24 1.71 SAN 2BH

-3.18

-3.06 0.12 31 152 9

24 0.85 SAN 2BH

-0.84

-0.74 0.10 31 153 9

24 0.66 SAI 1BH 1.16 1.26 0.10 31 154 9

24 2.21 SAN IBH

-1.18

-1.06 0.12 32 155 13 24 SAD 2BH

-3.01 32 156 13 24 0.68 SAN 2BH

-0.72

-0.64 0.08 32 157 13 24 SAD 1BH

-1.01 32 158 13 24 0.36 SAI 1BH 1.28 1.36 0.08 33 159 15 24 SAD 2BH

-2.89 33 160 15 24 0.89 SAN 2BH

-0.79

-0.69 0.10 33 161 15 24 SAD 1BH

-0.89 33 162 15 24 0.43 SAI 1BH 1.21 1.31 0.10 34 163 20 24 MAD 2BH

-3.34 34 164 20 24 1.52 MAN 2BH

-0.96

-0.84 0.12 34 165 20 24 MAD 1BH

-1.34 34 166 20 24 0.89 MAI 1BH 1.04 1.16 0.12 35 167 9

25 SAD 2BH

-2.82 35 168 9

25 1.28 SAN 2BH

-0.79

-0.71 0.08 35 169 9

25 SAD 1BH

-0.82 35 170 9

25 0.58 SAI 1BH 1.21 1.29 0.08 36 171 38 25 MAD 2BH

-2.89 36 172 38 25 0.93 SAN 2BH

-0.77

-0.70 0.07 36 173 38 25 MAD 1BH

-0.89 36 174 38 25 0.62 SAI 1BH 1.23 1.30 0.07 37 175 13 26 MAD 2BH

-3.27 37 176 13 26 0.90 MAN 2BH

-0.75

-0.64 0.11 37 177 13 26 MAD 1BH

-1.27 37 178 13 26 0.78 MAI 1BH 1.25 1.36 0.11 38 179 17 26 2.55 MAN 2BH

-5.72

-5.59 0.13 38 180 17 26 0.91 MAN 2BH

-0.68

-0.60 0.08 38 181 17 26 1.44 SAN 2BH

-3.19

-3.02 0.17 38 182 17 26 0.41 MAI 1BH 1.32 1.40 0.08 38 183 17 26 3.13 MAN 1BH

-3.72

-3.59 0.13 38 184 17 26 1.55 SAN 1BH

-1.19

-1.02 0.17 39 185 19 26 MAD 2BH

-3.27 39 186 19 26 2.65 SAN 2BH

-0.65

-0.54 0.11 39 187 19 26 MAD 1BH

-1.27 39 188 19 26 0.95 SAI 1BH 1.35 1.46 0.11 40 189 5

27 1.93 SAN 2BH

-4.12

-3.66 0.46 40 190 5

27 4.29 SAN 2BH

-0.87

-0.70 0.17 40 191 5

27 1.38 SAI 1BH 1.13 1.30 0.17 40 192 5

27 2.07 SAN 1BH

-2.12

-1.66 0.46 Page 132 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 41 193 8

27 0.77 SAN 2BH

-3.16

-3.06 0.10 41 194 8

27 1.30 SAN 2BH

-0.79

-0.71 0.08 41 195 8

27 1.09 SAI 1BH 1.21 1.29 0.08 41 196 8

27 0.96 SAN 1BH

-1.16

-1.06 0.10 42 197 8

28 SAD 2BH

-3.20 42 198 8

28 0.99 SAN 2BH

-0.61

-0.50 0.11 42 199 8

28 SAD 1BH

-1.20 42 200 8

28 0.84 SAI IBH 1.39 1.50 0.11 43 201 20 28 SAD 2BH

-3.25 43 202 20 28 1.28 SAN 2BH

-0.63

-0.53 0.10 43 203 20 28 SAD 1BH

-1.25 43 204 20 28 0.86 SAI 1BH 1.37 1.47 0.10 44 205 39 28 SAD 2BH

-3.32 44 206 39 28 1.71 SAN 2BH

-0.81

-0.71 0.10 44 207 39 28 SAD 1BH

-1.32 44 208 39 28 0.80 SAI 1BH 1.19 1.29 0.10 45 209 10 29 MAD 2BH

-3.31 45 210 10 29 1.23 MAN 2BH

-0.82

-0.72 0.10 45 211 10 29 MAD 1BH

-1.31 45 212 10 29 0.61 MAI 1BH 1.18 1.28 0.10 46 213 26 29 SAD 2BH

-3.22 46 214 26 29 2.25 SAN 2BH

-5.72

-5.64 0.08 46 215 26 29 1.18 SAN 2BH

-0.80

-0.74 0.06 46 216 26 29 SAD 1BH

-1.22 46 217 26 29 0.51 SAI 1BH 1.20 1.26 0.06 46 218 26 29 1.79 SAN 1BH

-3.72

-3.64 0.08 47 219 3

30 MAD 2BH

-3.26 47 220 3

30 0.88 SAN 2BH

-0.76

-0.69 0.07 47 221 3

30 MAD 1BH

-1.26 47 222 3

30 0.68 SAI 1BH 1.24 1.31 0.07 48 223 4

30 2.05 MAN 2BH

-5.87

-5.76 0.11 48 224 4

30 2.87 MAN 2BH

-3.21

-3.08 0.13 48 225 4

30 3.65 MAN 2BH

-2.48

-2.23 0.25 48 226 4

30 5.80 MAN 2BH

-0.24

-0.08 0.16 48 227 4

30 2.62 MAI 1BH 1.76 1.92 0.16 48 228 4

30 3.64 MAN 1BH

-3.87

-3.76 0.11 48 229 4

30 4.67 MAN 1BH

-1.21

-1.08 0.13 48 230 4

30 2.63 MAN 1BH

-0.48

-0.23 0.25 49 231 22 30 MAD 2BH

-3.20 49 232 22 30 0.14 SAN 2BH

-0.87

-0.75 0.12 49 233 22 30 MAD 1BH

-1.20 49 234 22 30 1.44 SAI 1BH 1.13 1.25 0.12 50 235 31 30 MAD 2BH

-3.38 50 236 31 30 1.59 MAN 2BH

-5.69

-5.64 0.05 50 237 31 30 0.94 MAN 2BH

-0.81

-0.74 0.07 50 238 31 30 MAD 1BH

-1.38 50 239 31 30 0.28 MAI 1BH 1.19 1.26 0.07 50 240 31 30 1.33 MAN 1BH

-3.69

-3.64 0.05 Page 133 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 51 241 5

31 SAD 2BH

-3.51 51 242 5

31 SAD 2BH

-3.08 51 243 5

31 1.21 SAN 2BH

-0.82

-0.75 0.07 51 244 5

31 SAD 1BH

-1.51 51 245 5

31 SAD 1BH

-1.08 51 246 5

31 0.55 SAI 1BH 1-1.18 1.25 0.07 52 247 11 31 FPC 1BH 1-0.30 52 248 11 31 SAD 1BH

-0.89 52 249 11 31 SAD 2BH

-2.89 52 250 11 31 0.57 SAI TRH 0.11 0.19 0.08 53 251 26 31 SAD 2BH

-2.84 53 252 26 31 1.16 SAN 2BH

-0.76

-0.69 0.07 53 253 26 31 SAD 1BH

-0.84 53 254 26 31 0.47 SAI 1BH 1.24 1.31 0.07 54 255 27 31 1.54 MAN 2BH

-0.87

-0.74 0.13 54 256 27 31 SAD 2BH

-3.29 54 257 27 31 0.76 MAI 1BH 1.13 1.26 0.13 54 258 27 31 SAD 1BH

-1.29 55 259 8

32 SAD 2BH

-2.97 55 260 8

32 1.96 SAN 2BH

-0.86

-0.74 0.12 55 261 8

32 SAD 1BH

-0.97 55 262 8

32 1.54 SAI 1BH 1.14 1.26 0.12 56 263 13 33 FPC 1BH 0.30 56 264 13 33 MAD IBH

-0.90 56 265 13 33 MAD 2BH

-2.90 56 266 13 33 0.63 MAI TRH 0.10 0.21 0.11 57 267 24 33 SAD 2BH

-3.31 57 268 24 33 1.40 SAN 2BH

-0.82

-0.76 0.06 57 269 24 33 SAD 1BH

-1.31 57 270 24 33 0.70 SAI 1BH 1.18 1.24 0.06 58 271 2

34 SAD 2BH

-3.24 58 272 2

34 0.60 SAN 2BH

-0.79

-0.72 0.07 58 273 2

34 SAD 1BH

-1.24 58 274 2

34 0.37 SAI 1BH 1.21 1.28 0.07 59 275 28 34 SAD 2BH

-2.88 59 276 28 34 2.49 SAN 2BH

-0.77

-0.71 0.06 59 277 28 34 SAD 1BH

-0.88 59 278 28 34 0.94 SAI 1BH 1.23 1.29 0.06 60 279 29 34 MAD 2BH

-3.22 60 280 29 34 1.45 SAN 2BH

-0.83

-0.70 0.13 60 281 29 34 MAD 1BH

-1.22 60 282 29 34 0.60 SAI 1BH 1.17 1.30 0.13 61 283 2

35 SAD 2BH

-3.27 61 284 2

35 0.55 SAN 2BH

-0.77

-0.74 0.03 61 285 2

35 SAD 1BH

-1.27 61 286 2

35 0.32 SAI 1BH 1.23 1.26 0.03 62 287 21 35 MAD 2BH

-3.21 62 288 21 35 0.66 MAN 2BH

-0.78

-0.71 0.07 Page 134 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 62 289 21 35 MAD 1BH

-1.21 62 290 21 35 0.51 SAI 1BH 1.22 1.29 0.07 63 291 33 35 SAD 2BH

-2.90 63 292 33 35 0.75 SAN 2BH

-0.75

-0.68 0.07 63 293 33 35 SAD IBH

-0.90 63 294 33 35 0.36 SAI 1BH 1.25 1.32 0.07 64 295 9

36 SAD 2BH

-3.42 64 296 9

36 0.77 SAN 2BH

-0.87

-0.81 0.06 64 297 9

36 SAD 1BH

-1.42 64 298 9

36 0.73 SAI IBH 1.13 1.19 0.06 65 299 23 36 MAD 2BH

-3.30 65 300 23 36 0.81 SAN 2BH

-0.74

-0.71 0.03 65 301 23 36 MAD 1BH

-1.30 65 302 23 36 0.35 SAI 1BH 1.26 1.29 0.03 66 303 8

37 1.37 MAN 2BH

-2.91

-2.85 0.06 66 304 8

37 1.51 SAN 2BH

-0.83

-0.73 0.10 66 305 8

37 1.52 MAN 1BH

-0.91

-0.85 0.06 66 306 8

37 0.82 SAI 1BH 1.17 1.27 0.10 67 307 22 37 SAD 2BH

-2.80 67 308 22 37 3.31 SAN 2BH

-0.87

-0.68 0.19 67 309 22 37 SAD 1BH

-0.80 67 310 22 37 1.56 SAI 1BH 1.13 1.32 0.19 68 311 25 37 0.41 MAN 2BH

-5.66

-5.49 0.17 68 312 25 37 SAD 2BH

-3.20 68 313 25 37 1.19 SAN 2BH

-0.82

-0.72 0.10 68 314 25 37 SAD 1BH

-1.20 68 315 25 37 0.77 SAI 1BH 1.18 1.28 0.10 69 316 28 37 MAD 2BH

-2.84 69 317 28 37 0.92 MAN 2BH

-0.65

-0.57 0.08 69 318 28 37 MAD 1BH

-0.84 69 319 28 37 0.40 MAI 1BH 1.35 1.43 0.08 70 320 30 38 MAD 213H

-3.11 70 321 30 38 0.64 SAN 2BH

-0.76

-0.69 0.07 70 322 30 38 MAD 11BH-

-1.11 70 323 30 38 0.31 SAI 1BH 1.24 1.31 0.07 71 324 31 38 SAD 2BH

-3.25 71 325 31 38 1.10 SAN 2BH

-0.86

-0.79 0.07 71 326 31 38 SAD 1BH

-1.25 71 327 31 38 0.77 SAI 1BH 1.14 1.21 0.07 72 328 25 39 3.58 MAN 2BH

-5.64

-5.48 0.16 72 329 25 39 1.01 MAN 2BH

-3.20

-3.12 0.08 72 330 25 39 1.26 SAN 2BH

-0.73

-0.64 0.09 72 331 25 39 3.19 MAN 1BH

-3.64

-3.48 0.16 72 332 25 39 0.66 MAN 1BH

-1.20

-1.12 0.08 72 333 25 39 0.83 SAI 1BH 1.27 1.36 0.09 73 334 33 39 SAD 2BH

-3.19 73 335 33 39 2.69 SAN 2BH

-0.79

-0.70 0.09 73 336 33 39 SAD 1BH

-1.19 Page 135 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 73 337 33 39 0.82 SAI 1BH 1.21 1.30 0.09 74 338 36 39 0.75 MAN 2BH

-0.80

-0.72 0.08 74 339 36 39 SAD 2BH

-3.43 74 340 36 39 0.43 MAI 1BH 1.20 1.28 0.08 74 341 36 39 SAD 1BH

-1.43 75 342 3

40 MAD 2BH

-3.26 75 343 3

40 0.63 SAN 2BH

-0.81

-0.78 0.03 75 344 3

40 MAD 1BH

-1.26 75 345 3

40 0.52 SAI 1BH 1.19 1.22 0.03 76 346 30 40 SAD 2BH

-2.80 76 347 30 40 0.93 SAN 2BH

-0.78

-0.71 0.07 76 348 30 40 SAD 1BH

-0.80 76 349 30 40 0.69 SAI 1BH 1.22 1.29 0.07 77 350 7

41 2.35 MAN 2BH

-3.24

-3.10 0.14 77 351 7

41 0.70 MAN 2BH

-0.87

-0.80 0.07 77 352 7

41 0.40 MAI 1BH 1.13 1.20 0.07 77 353 7

41 2.58 MAN 1BH

-1.24

-1.10 0.14 78 354 10 42 SAD 2BH

-3.28 78 355 10 42 0.59 SAN 2BH

-0.80

-0.76 0.04 78 356 10 42 SAD 1BH

-1.28 78 357 10 42 0.47 SAI 1BH 1.20 1.24 0.04 79 358 36 42 MAD 2BH

-3.37 79 359 36 42 2.14 MAN 2BH

-0.72

-0.56 0.16 79 360 36 42 MAD 1BH

-1.37 79 361 36 42 1.21 MAI 1BH 1.28 1.44 0.16 80 362 5

43 1.30 SAN 2BH

-3.20

-3.06 0.14 80 363 5

43 0.90 SAN 2BH

-0.80

-0.73 0.07 80 364 5

43 0.53 SAI IBH 1.20 1.27 0.07 80 365 5

43 1.44 SAN 1BH

-1.20

-1.06 0.14 81 366 23 43 1.72 MAN 2BH

-3.25

-3.06 0.19 81 367 23 43 0.84 SAN 2BH

-5.65

-5.54 0.11 81 368 23 43 1.22 SAN 2112BH

-0.85

-0.76 0.09 81 369 23 43 1.96 MAN 131BH

-1.25

-1.06 0.19 81 370 23 43 0.92 SAI 1BH

-3.76

-3.70 0.06 81 371 23 43 0.85 SAI 1BH 1.15 1.24 0.09 82 372 32 43 SAD 2BH

-3.10 82 373 32 43 0.59 SAN 2BH

-0.83

-0.77 0.06 82 374 32 43 SAD 1BH

-1.10 82 375 32 43 0.29 SAI 1BH 1.17 1.23 0.06 83 376 21 44 SAD 2BH

-3.30 83 377 21 44 1.13 SAN 2BH

-0.79

-0.70 0.09 83 378 21 44 SAD 1BH

-1.30 83 379 21 44 0.57 SAI 1BH 1.21 1.30 0.09 84 380 1

45 SAD 2BH

-3.36 84 381 1

45 2.51 SAN 2BH

-5.74

-5.68 0.06 84 382 1

45 1.40 SAN 2BH

-0.75

-0.65 0.10 84 383 1

45 SAD 1BH

-1.36 84 384 1

45 0.69 SAI 1BH 1.25 1.35 0.10 Page 136 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 84 385 1

45 2.57 SAN 1BH

-3.74

-3.68 0.06 85 386 14 45 SAD 2BH

-2.84 85 387 14 45 0.68 SAN 2BH

-0.92

-0.86 0.06 85 388 14 45 SAD 1BH

-0.84 85 389 14 45 0.35 SAI 1BH 1.08 1.14 0.06 86 390 17 45 FPC 1BH 0.30 86 391 17 45 SAD 1BH

-0.88 86 392 17 45 SAD 2BH

-2.88 86 393 17 45 0.42 SAI TRH 0.12 0.19 0.07 87 394 4

46 0.93 MAN 2BH

-3.24

-3.10 0.14 87 395 4

46 1.23 MAN 2BH

-0.82

-0.76 0.06 87 396 4

46 0.64 MAI 1BH 1.18 1.24 0.06 87 397 4

46 1.21 MAN 1131BH

-1.24

-1.10 0.14 88 398 8

46 1.86 MAN 2BH

-3.26

-3.02 0.24 88 399 8

46 2.32 SAN 2BH

-0.77

-0.54 0.23 88 400 8

46 1.99 MAN 1BH

-1.26

-1.02 0.24 88 401 8

46 1.70 SAI 1BH 1-1.23 1.46 0.23 89 402 10 46 MAD 2BH

-3.49 89 403 10 46 1.35 SAN 2BH

-0.82

-0.78 0.04 89 404 10 46 MAD 1BH

-1.49 89 405 10 46 0.50 SAI 1BH 1.18 1.22 0.04 90 406 14 46 2.06 MAN 2BH

-3.15

-3.04 0.11 90 407 14 46 0.64 MAN 2BH

-0.81

-0.76 0.05 90 408 14 46 0.44 MAI 1BH 1.19 1.23 0.04 90 409 14 46 2.86 MAN 1BH

-1.15

-1.04 0.11 91 410 21 46 SAD 2BH

-3.25 91 411 21 46 0.59 SAN 2BH

-0.82

-0.74 0.08 91 412 21 46 SAD 11BH-

-1.25 91 413 21 46 0.55 SAI 1BH 1.18 1.26 0.08 92 414 4

47 3.43 MAN 2BH

-3.42

-3.04 0.38 92 415 4

47 2.02 SAN 2BH

-0.98

-0.89 0.09 92 416 4

47 3.48 MAN 1BH

-1.42

-1.04 0.38 92 417 4

47 1.14 SAI 1BH 1.02 1.11 0.09 93 418 8

47 0.58 MAN 2BH

-0.84

-0.75 0.09 93 419 8

47 0.54 SAN 2BH

-3.15

-3.05 0.10 93 420 8

47 0.49 SAI 1BH 1.16 1.25 0.09 93 421 8

47 0.63 SAN 1BH

-1.15

-1.05 0.10 94 422 34 47 SAD 2BH

-3.20 94 423 34 47 1.30 SAN 2BH

-0.83

-0.76 0.07 94 424 34 47 SAD 11BH

-1.20 94 425 34 47 0.75 SAI 1BH 1.18 1.24 0.06 95 426 37 47 SAD 2BH

-3.60 95 427 37 47 0.78 SAN 2BH

-0.86

-0.77 0.09 95 428 37 47 SAD 1BH

-1.60 95 429 37 47 0.61 SAI 1BH 1.14 1.23 0.09 96 430 11 48 MAD 2BH

-3.41 96 431 11 48 0.88 SAN 2BH

-0.84

-0.77 0.07 96 432 11 48 MAD 1BH

-1.41 Page 137 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 96 433 11 48 0.64 SAI 1BH 1.16 1.23 0.07 97 434 22 48 MAD 2BH

-3.15 97 435 22 48 1.08 MAN 2BH

-0.81

-0.71 0.10 97 436 22 48 MAD IBH

-1.15 97 437 22 48 0.84 MAI 1BH 1.19 1.29 0.10 98 438 6

49 FPC 1BH 0.30 98 439 6

49 MAD 1BH

-1.12 98 440 6

49 MAD 2BH

-3.04 98 441 6

49 0.73 MAI TRH

-0.04 0.12 0.16 99 442 12 49 MAD 2BH

-3.45 99 443 12 49 1.63 MAN 2BH

-2.35

-2.18 0.17 99 444 12 49 1.75 SAN 2BH

-0.85

-0.75 0.10 99 445 12 49 MAD 1BH

-1.45 99 446 12 49 1.73 MAN 1BH

-0.35

-0.18 0.17 99 447 12 49 0.89 SAI 1BH 1.15 1.25 0.10 100 448 4

50 4.23 MAN 2BH

-3.35

-3.06 0.29 100 449 4

50 0.43 SAN 2BH

-0.70

-0.67 0.03 100 450 4

50 4.02 MAN 1BH

-1.35

-1.06 0.29 100 451 4

50 0.31 SAI 1BH 1.30 1.33 0.03 101 452 5

50 4.88 MAN 2BH

-3.29

-3.11 0.18 101 453 5

50 2.54 SAN 2BH

-0.87

-0.74 0.13 101 454 5

50 5.08 MAN 1BH

-1.29

-1.11 0.18 101 455 5

50 1.25 SAI 1BH 1.13 1.26 0.13 102 456 10 50 2.66 MAN 2BH

-3.28

-3.15 0.13 102 457 10 50 1.34 SAN 2BH

-0.78

-0.69 0.09 102 458 10 50 2.59 MAN 1BH

-1.28

-1.15 0.13 102 459 10 50 0.61 SAI 1BH 1.22 1.31 0.09 103 460 24 50 MAD 2BH

-3.29 103 461 24 50 6.57 MAN 2BH

-2.74

-2.18 0.56 103 462 24 50 1.00 SAN 2BH

-0.82

-0.73 0.09 103 463 24 50 MAD 1BH

-1.29 103 464 24 50 6.99 MAN 1BH

-0.74

-0.18 0.56 103 465 24 50 0.49 SAI 1BH 1.18 1.27 0.09 104 466 37 50 SAD IBH

-2.90 104 467 37 50 1.60 SAN 1BH

-0.96

-0.86 0.10 104 468 37 50 SAD 1BH

-0.90 104 469 37 50 1.04 SAI IBH 1.04 1.14 0.10 105 470 4

51 0.98 MAN 2BH

-3.24

-3.15 0.09 105 471 4

51 0.72 SAN 2BH

-0.89

-0.83 0.06 105 472 4

51 0.94 MAN 1BH

-1.24

-1.15 0.09 105 473 4

51 0.51 SAI 1BH 1.11 1.17 0.06 106 474 15 51 SAD 2BH

-3.28 106 475 15 51 1.21 SAN 2BH

-0.76

-0.72 0.04 106 476 15 51 SAD IBH

-1.28 106 477 15 51 0.45 SAI 1BH 1.24 1.28 0.04 107 478 37 51 MAD 2BH

-3.31 107 479 37 51 2.14 SAN 2BH

-0.89

-0.75 0.14 107 480 37 51 1 MAD 1BH

-1.31 Page 138 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE#

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 107 481 37 51 0.77 SAI 1BH 1.11 1.25 0.14 108 482 1

52 1.11 SAN 2BH

-3.16

-3.07 0.09 108 483 1

52 0.67 SAN 2BH

-0.67

-0.64 0.03 108 484 1

52 0.47 SAI 1BH 1.33 1.36 0.03 108 485 1

52 0.97 SAN 1BH

-1.16

-1.07 0.09 109 486 3

52 2.16 MAN 2BH

-3.29

-3.18 0.11 109 487 3

52 1.49 SAN 2BH

-0.84

-0.75 0.09 109 488 3

52 2.26 MAN 1BH

-1.29

-1.18 0.11 109 489 3

52 0.68 SAI 1BH 1.16 1.25 0.09 110 490 12 53 SAD 2BH

-3.23 110 491 12 53 1.64 SAN 2BH

-0.87

-0.78 0.09 110 492 12 53 SAD 11BH

-1.23 110 493 12 53 0.51 SAI 1BH 1.13 1.22 0.09 111 494 34 54 SAD 2BH

-3.29 111 495 34 54 1.48 SAN 2BH

-0.84

-0.75 0.09 111 496 34 54 SAD 11BH

-1.29 111 497 34 54 1.07 SAI 1BH 1.16 1.25 0.09 112 498 1

55 FPC 1BH 0.30 112 499 1

55 MAD 1BH

-0.94 112 500 1

55 MAD 2BH

-2.94 112 501 1

55 0.66 MAI TRH 0.06 0.14 0.08 113 502 9

55 MAD 2BH

-2.94 113 503 9

55 2.11 SAN 2BH

-0.86

-0.74 0.12 113 504 9

55 MAD 1BH

-0.94 113 505 9

55 0.74 SAI 1BH 1.14 1.26 0.12 114 506 25 55 SAD 2BH

-3.17 114 507 25 55 0.84 SAN 2BH3"

-0.85

-0.76 0.09 114 508 25 55 0.75 SAN 2BH

-0.85

-0.76 0.09 114 509 25 55 SAD 1BH

-1.17 114 510 25 55 0.48 SAI 1BH 1.15 1.24 0.09 115 511 33 55 SAD 2BH

-2.90 115 512 33 55 1.10 SAN 2BH

-0.85

-0.78 0.07 115 513 33 55 SAD 1BH

-0.90 115 514 33 55 0.63 SAI 1BH 1.15 1.22 0.07 116 515 4

56 MAD 2BH

-3.54 116 516 4

56 4.02 SAN 2BH

-0.82

-0.72 0.10 116 517 4

56 MAD 1BH

-1.54 116 518 4

56 1.12 SAI 1BH 1.18 1.28 0.10 117 519 14 57 SAD 2BH

-3.30 117 520 14 57 0.61 SAN 2BH

-0.53

-0.39 0.14 117 521 14 57 SAD 1BH

-1.30 117 522 14 57 0.35 SAI 1BH 1.47 1.61 0.14 118 523 17 57 0.62 MAN 2BH

-0.44

-0.35 0.09 118 524 17 57 SAD 2BH

-3.30 118 525 17 57 SAD 1BH

-1.30 118 526 17 57 0.54 SAI 1BH 1.56 1.65 0.09 119 527 21 57 MAD 2BH

-2.87 119 528 21 57 0.85 SAN 2BH

-0.83

-0.74 0.09 Page 139 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 119 529 21 57 MAD 1BH

-0.87 119 530 21 57 0.61 SAI 1BH 1.17 1.26 0.09 120 531 1

58 FPC 1BH 0.30 120 532 1

58 SAD 1BH

-0.91 120 533 1

58 SAD 2BH

-2.91 120 534 1

58 3.82 SAN 1BH

-3.65

-3.54 0.11 120 535 1

58 3.58 SAN 2BH

-5.65

-5.54 0.11 120 536 1

58 0.42 SAI TRH 0.09 0.13 0.04 120 537 1

58 3.49 SAN TRH

-2.65

-2.54 0.11 121 538 7

58 FPC 1BH 0.30 121 539 7

58 SAD 1BH

-0.94 121 540 7

58 SAD 2BH

-2.94 121 541 7

58 2.14 SAN 1BH

-3.51

-3.43 0.08 121 542 7

58 2.11 SAN 2BH

-5.51

-5.43 0.08 121 543 7

58 0.48 SAI TRH 0.06 0.17 0.11 121 544 7

58 1.70 SAN TRH

-2.51

-2.43 0.08 122 545 23 58 SAD 2BH

-3.32 122 546 23 58 1.87 SAN 2BH

-0.79

-0.73 0.06 122 547 23 58 SAD 1BH

-1.32 122 548 23 58 0.60 SAI 1BH 1.21 1.27 0.06 123 549 29 58 SAD 2BH

-2.85 123 550 29 58 0.80 SAN 2BH

-0.88

-0.81 0.07 123 551 29 58 SAD 1BH

-0.85 123 552 29 58 0.34 SAI 1BH 1.12 1.19 0.07 124 553 10 59 1.28 MAN 2BH

-3.26

-3.15 0.11 124 554 10 59 0.95 MAN 2BH

-0.79

-0.69 0.10 124 555 10 59 0.59 MAI 1BH 1.21 1.31 0.10 124 556 10 59 1.45 MAN 1BH

-1.26

-1.15 0.11 125 557 7

60 1.27 MAN 2BH

-0.83

-0.77 0.06 125 558 7

60 2.49 SAN 2BH

-3.19

-2.96 0.23 125 559 7

60 0.50 SAI 1BH 1.17 1.23 0.06 125 560 7

60 2.54 SAN 1BH

-1.19

-0.96 0.23 126 561 14 60 3.64 MAN 2BH

-3.32

-3.16 0.16 126 562 14 60 1.41 SAN 2BH

-0.87

-0.77 0.10 126 563 14 60 3.74 MAN 1BH

-1.32

-1.16 0.16 126 564 14 60 0.67 SAI 1BH 1.13 1.23 0.10 127 565 37 60 5.00 MAN 2BH

-2.60

-1.89 0.71 127 566 37 60 SAD 2BH

-3.26 127 567 37 60 4.81 MAI 1BH

-0.60 0.11 0.71 127 568 37 60 SAD 1BH

-1.26 128 569 6

61 MAD 2BH

-3.95 128 570 6

61 1.91 MAN 2BH

-0.78

-0.72 0.06 128 571 6

61 MAD 1BH

-1.95 128 572 6

61 0.54 SAI 1BH 1.22 1.28 0.06 129 573 23 61 4.29 MAN 2BH

-5.65

-5.53 0.12 129 574 23 61 1.73 MAN 2BH

-2.43

-2.29 0.14 129 575 23 61 1.25 MAN 2BH

-0.82

-0.68 0.14 129 576 23 61 SAD 2BH

-3.35 Page 140 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 129 577 23 61 1.50 MAI 1BH

-0.43

-0.29 0.14 129 578 23 61 0.65 MAI 1BH 1.18 1.32 0.14 129 579 23 61 4.94 MAN 1BH

-3.65

-3.53 0.12 129 580 23 61 SAD 1BH

-1.35 130 581 33 61 MAD 2BH

-3.42 130 582 33 61 4.36 MAN 2BH

-5.75

-5.54 0.21 130 583 33 61 0.65 SAN 2BH

-0.88

-0.81 0.07 130 584 33 61 MAD 1B1H

-1.42 130 585 33 61 4.51 MAN 1BH

-3.85

-3.60 0.25 130 586 33 61 0.50 SAI 1BH 1-1.12 1.19 0.07 131 587 37 61 SAD 2BH

-3.33 131 588 37 61 1.17 SAN 2BH

-0.71

-0.64 0.07 131 589 37 61 SAD 1BH

-1.33 131 590 37 61 0.49 SAI 1BH 1.29 1.36 0.07 132 591 38 62 SAD 2BH

-3.32 132 592 38 62 1.05 SAN 2BH

-0.86

-0.76 0.10 132 593 38 62 SAD 1BH

-1.32 132 594 38 62 0.57 SAI 1BH 1.14 1.24 0.10 133 595 9

63 0.97 MAN 2BH

-0.74

-0.67 0.07 133 596 9

63 SAD 2BH

-3.34 133 597 9

63 SAD 1BH

-1.34 133 598 9

63 0.45 SAI 1BH 1.26 1.33 0.07 134 599 25 63 MAD 2BH

-3.30 134 600 25 63 4.57 MAN 2BH

-5.67

-5.49 0.18 134 601 25 63 1.25 SAN 2BH

-0.83

-0.71 0.12 134 602 25 63 MAD 1BH

-1.30 134 603 25 63 5.37 MAN 1BH

-3.85

-3.57 0.28 134 604 25 63 0.50 SAI 1BH 1.17 1.29 0.12 135 605 37 63 MAD 2BH

-3.38 135 606 37 63 1.34 MAN 2BH

-0.87

-0.78 0.09 135 607 37 63 MAD 1BH

-1.38 135 608 37 63 0.68 MAI 1BH 1.13 1.22 0.09 136 609 3

64 1.61 MAN 2BH

-3.30

-3.22 0.08 136 610 3

64 1.38 MAN 2BH

-0.86

-0.74 0.12 136 611 3

64 0.72 MAI 1BH 1.14 1.26 0.12 136 612 3

64 1.71 MAN 1BH

-1.30

-1.22 0.08 137 613 6

64 1.04 MAN 2BH

-3.27

-3.13 0.14 137 614 6

64 2.07 SAN 2BH

-0.82

-0.76 0.06 137 615 6

64 1.13 MAN 1BH

-1.27

-1.13 0.14 137 616 6

64 1.15 SAI 1BH 1.18 1.34 0.16 138 617 10 64 MAD 2BH

-3.28 138 618 10 64 1.36 SAN 2BH

-0.81

-0.75 0.06 138 619 10 64 MAD 1BH

-1.28 138 620 10 64 0.39 SAI 1BH 1.19 1.25 0.06 139 621 15 64 3.72 MAN 2BH

-5.70

-5.50 0.20 139 622 15 64 SAD 2BH

-3.25 139 623 15 64 1.26 SAN 2BH

-0.80

-0.73 0.07 139 624 15 64 4.13 MAN 1BH

-3.70

-3.50 0.20 Page 141 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 139 625 15 64 SAD 1BH

-1.25 139 626 15 64 0.76 SAI 1BH 1.20 1.27 0.07 140 627 2

65 4.28 MAN 2BH

-5.73

-5.61 0.12 140 628 2

65 SAD 2BH

-3.42 140 629 2

65 1.60 SAN 2BH

-0.80

-0.73 0.07 140 630 2

65 SAD 1BH

-1.42 140 631 2

65 0.73 SAI 1BH 1.20 1.27 0.07 140 632 2

65 3.45 SAN 1BH

-3.73

-3.61 0.12 141 633 8

65 1.34 SAN 2BH

-3.29

-3.23 0.06 141 634 8

65 1.09 SAN 2BH

-0.78

-0.71 0.07 141 635 8

65 0.84 SAI 1BH 1.22 1.29 0.07 141 636 8

65 1.41 SAN 1BH

-1.29

-1.23 0.06 142 637 18 66 0.91 MAN 2BH

-5.60

-5.45 0.15 142 638 18 66 0.97 MAN 2BH

-0.86

-0.78 0.08 142 639 18 66 SAD 2BH

-3.36 142 640 18 66 0.73 MAI 11BH

-3.60

-3.45 0.15 142 641 18 66 0.53 MAI 1BH 1.14 1.22 0.08 142 642 18 66 SAD 1BH

-1.36 143 643 25 66 5.34 MAN 2BH

-5.77

-5.52 0.25 143 644 25 66 SAD 2BH

-3.26 143 645 25 66 1.48 SAN 2BH

-0.81

-0.77 0.04 143 646 25 66 4.40 MAN 1BH

-3.77

-3.52 0.25 143 647 25 66 SAD 1BH

-1.26 143 648 25 66 0.53 SAI 1BH 1.19 1.23 0.04 144 649 5

67 MAD 2BH

-3.35 144 650 5

67 1.12 SAN 2BH

-2.35

-2.30 0.05 144 651 5

67 0.99 SAN 2BH

-0.79

-0.71 0.08 144 652 5

67 MAD 1BH

-1.35 144 653 5

67 0.40 SAI 1BH 1.21 1.29 0.08 144 654 5

67 0.71 SAN 1BH

-0.35

-0.30 0.05 145 655 21 67 MAD 2BH

-3.30 145 656 21 67 0.72 MAN 2BH

-0.88

-0.76 0.12 145 657 21 67 2.98 SAN 2BH

-5.74

-5.64 0.10 145 658 21 67 MAD 1BH

-1.30 145 659 21 67 0.46 MAI 1BH 1.12 1.24 0.12 145 660 21 67 3.14 SAN 1BH

-3.74

-3.64 0.10 146 661 26 67 1.56 MAN 2BH

-5.72

-5.68 0.04 146 662 26 67 SAD 2BH

-3.21 146 663 26 67 0.89 SAN 2BH

-0.85

-0.73 0.12 146 664 26 67 1.63 MAN 1BH

-3.72

-3.68 0.04 146 665 26 67 SAD 1BH

-1.21 146 666 26 67 0.63 SAI 1BH 1.15 1.27 0.12 147 667 7

68 2.91 MAN 2BH

-3.31

-3.04 0.27 147 668 7

68 3.57 SAN 2BH

-5.69

-5.59 0.10 147 669 7

68 1.49 SAN 2BH

-0.83

-0.77 0.06 147 670 7

68 2.93 MAN 1BH

-1.31

-1.04 0.27 147 671 7

68 0.48 SAI 1BH 1.17 1.23 0.06 147 672 7

68 3.41 SAN 1BH

-3.69

-3.59 0.10 Page 142 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 148 673 13 68 MAD 2BH

-3.39 148 674 13 68 4.36 SAN 2BH

-5.62

-5.48 0.14' 148 675 13 68 1.60 SAN 2BH

-0.83

-0.75 0.08 148 676 13 68 MAD 1BH

-1.39 148 677 13 68 0.59 SAI 1BH 1.17 1.25 0.08 148 678 13 68 4.92 SAN 1BH

-3.62

-3.48 0.14 149 679 14 68 MAD 2BH

-3.35 149 680 14 68 1.14 SAN 2BH

-5.75

-5.68 0.07 149 681 14 68 0.85 SAN 2BH

-0.76

-0.66 0.10 149 682 14 68 MAD 1BH

-1.35 149 683 14 68 0.51 SAI 1BH 1.24 1.34 0.10 149 684 14 68 1.62 SAN 1BH

-3.75

-3.68 0.07 150 685 5

69 1.50 MAN 21H

-0.81

-0.70 0.11 150 686 5

69 SAD 2BH

-3.35 150 687 5

69 3.68 SAN 2BH

-5.74

-5.67 0.07 150 688 5

69 0.67 MAI 1BH 1.19 1.30 0.11 150 689 5

69 SAD 1BH

-1.35 150 690 5

69 3.66 SAN 1BH

-3.74

-3.67 0.07 151 691 13 69 2.94 MAN 2BH

-2.63

-2.20 0.43 151 692 13 69 SAD 2BH

-3.34 151 693 13 69 1.16 SAN 2BH

-5.74

-5.69 0.05 151 694 13 69 0.65 SAN 2BH

-0.75

-0.65 0.10 151 695 13 69 2.99 MAN 1BH

-0.63

-0.20 0.43 151 696 13 69 SAD 1BH

-1.34 151 697 13 69 0.31 SAI 1BH 1.25 1.35 0.10 151 698 13 69 1.63 SAN 1BH

-3.74

-3.69 0.05 152 699 16 69 5.64 MAN 2BH

-5.75

-5.49 0.26 152 700 16 69 SAD 2BH

-3.35 152 701 16 69 1.04 SAN 2BH

-0.81

-0.71 0.10 152 702 16 69 6.99 MAN 1BH

-3.75

-3.49 0.26 152 703 16 69 SAD 1BH

-1.35 152 704 16 69 0.45 SAI 1BH 1.19 1.29 0.10 153 705 20 69 MAD 2BH

-3.41 153 706 20 69 1.97 MAN 2BH

-0.89

-0.76 0.13 153 707 20 69 MAD 1BH

-1.41 153 708 20 69 0.61 MAI 1BH 1.11 1.24 0.13 154 709 6

70 4.44 MAN 2BH

-5.70

-5.51 0.19 154 710 6

70 SAD 2BH

-3.41 154 711 6

70 1.56 SAN 2BH

-0.82

-0.76 0.06 154 712 6

70 4.32 MAN 1BH

-3.70

-3.51 0.19 154 713 6

70 SAD 1BH

-1.41 154 714 6

70 0.92 SAI 1BH 1.18 1.24 0.06 155 715 16 70 MAD 2BH

-3.40 155 716 16 70 0.82 MAN 2BH

-0.79

-0.69 0.10 155 717 16 70 2.51 SAN 2BH

-5.65

-5.52 0.13 155 718 16 70 MAD 1BH

-1.40 155 719 16 70 0.52 SAI 1BH 1.21 1.31 0.10 155 720 16 70 2.58 SAN 1BH

-3.65

-3.52 0.13 Page 143 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 156 721 17 70 MAD 2BH

-2.78 156 722 17 70 4.68 MAN 2BH

-2.66

-2.11 0.55 156 723 17 70 0.66 SAN 2BH

-0.77

-0.68 0.09 156 724 17 70 MAD 1BH

-0.78 156 725 17 70 4.62 MAN 1BH

-0.66

-0.11 0.55 156 726 17 70 0.47 SAI IBH 1.23 1.32 0.09 157 727 4

71 MAD 2BH

-2.96 157 728 4

71 0.43 SAN 2BH

-0.82

-0.77 0.05 157 729 4

71 MAD 1BH

-0.96 157 730 4

71 0.43 SAI 1BH 1.18 1.23 0.05 158 731 5

71 MAD 2BH

-3.41 158 732 5

71 1.55 SAN 2BH

-0.81

-0.69 0.12 158 733 5

71 MAD 1BH

-1.41 158 734 5

71 0.83 SAI 1BH 1.19 1.31 0.12 159 735 16 71 SAD 2BH

-2.87 159 736 16 71 1.45 SAN 2BH

-5.98

-5.90 0.08 159 737 16 71 1.18 SAN 2BH

-0.71

-0.63 0.08 159 738 16 71 SAD 1BH

-0.87 159 739 16 71 0.77 SAI 1BH 1.29 1.36 0.07 159 740 16 71 1.55 SAN 1BH

-3.98

-3.90 0.08 160 741 17 71 MAD 2BH

-3.34 160 742 17 71 2.90 SAN 2BH

-5.76

-5.66 0.10 160 743 17 71 1.21 SAN 2BH

-0.70

-0.63 0.07 160 744 17 71 MAD 1BH

-1.34 160 745 17 71 0.62 SAI 1BH 1.30 1.37 0.07 160 746 17 71 2.98 SAN 1BH

-3.76

-3.66 0.10 161 747 22 71 MAD 2BH

-2.86 161 748 22 71 1.69 SAN 2BH 1-

-5.70

-5.60 0.10 161 749 22 71 0.89 SAN 2BH

-0.68

-0.61 0.07 161 750 22 71 MAD 1BH

-0.86 161 751 22 71 0.44 SAI 1BH 1.32 1.39 0.07 161 752 22 71 1.75 SAN 1BH

-3.70

-3.60 0.10 162 753 18 72 MAD 21H

-3.48 162 754 18 72 0.85 MAN 2BH

-0.73

-0.67 0.06 162 755 18 72 1.14 SAN 2BH 1-

-5.79

-5.73 0.06 162 756 18 72 MAD 1BH

-1.48 162 757 18 72 0.54 MAI 1BH 1.27 1.33 0.06 163 758 25 73 6.65 MAN 2BH

-5.79

-5.47 0.32 163 759 25 73 SAD 2BH

-3.09 163 760 25 73 1.00 SAN 2BH

-0.74

-0.68 0.06 163 761 25 73 6.86 MAN 1BH

-3.79

-3.47 0.32 163 762 25 73 SAD 1BH

-1.09 163 763 25 73 0.47 SAI 1BH 1.26 1.32 0.06 164 764 3

74 2.75 MAN 2BH

-3.19

-3.08 0.11 164 765 3

74 0.74 MAN 2BH

-0.83

-0.77 0.06 164 766 3

74 0.45 MAI 1BH 1.17 1.23 0.06 164 767 3

74 2.56 SAN 1BH

-1.19

-1.08 0.11 165 768 11 74 2.47 MAN 2BH

-3.24

-3.07 0.17 Page 144 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE #

IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 165 769 11 74 1.14 MAN 2BH

-0.83

-0.73 0.10 165 770 11 74 0.57 MAI 1BH 1.17 1.27 0.10 165 771 11 74 2.28 MAN 1BH

-1.24

-1.07 0.17 166 772 34 74 SAD 2BH

-3.01 166 773 34 74 1.78 SAN 2BH

-0.79

-0.72 0.07 166 774 34 74 SAD 1BH

-1.01 166 775 34 74 0.61 SAI 1BH 1.21 1.28 0.07 167 776 2

76 SAD 2BH

-3.38 167 777 2

76 0.81 SAN 2BH

-0.83

-0.76 0.07 167 778 2

76 SAD 1BH

-1.38 167 779 2

76 0.48 SAI 1BH 1.17 1.24 0.07 168 780 7

76 MAD 2BH

-3.41 168 781 7

76 4.33 SAN 2BH

-5.70

-5.50 0.20 168 782 7

76 0.72 SAN 2BH

-0.77

-0.68 0.09 168 783 7

76 MAD 1BH

-1.41 168 784 7

76 0.53 SAI 1BH 1.23 1.32 0.09 168 785 7

76 4.43 SAN 1BH

-3.70

-3.50 0.20 169 786 9

76 MAD 2BH

-3.39 169 787 9

76 0.82 MAN 2BH

-0.81

-0.75 0.06 169 788 9

76 MAD 1BH

-1.39 169 789 9

76 0.49 MAI 1BH 1.19 1.25 0.06 170 790 5

77 0.97 MAN 2BH

-0.84

-0.73 0.11 170 791 5

77 SAD 2BH

-3.77 170 792 5

77 4.75 SAN 2BH

-5.75

-5.58 0.17 170 793 5

77 0.66 MAI 1BH 1.16 1.27 0.11 170 794 5

77 SAD 1BH

-1.77 170 795 5

77 4.99 SAN 1BH

-3.75

-3.58 0.17 171 796 7

77 0.53 MAN 2BH

-0.68

-0.59 0.09 171 797 7

77 1.71 SAN 2BH

-5.71

-5.64 0.07 171 798 7

77 2.42 SAN 2BH

-3.29

-3.20 0.09 171 799 7

77 0.32 SAI 1BH 1.32 1.41 0.09 171 800 7

77 1.60 SAN 1BH

-3.71

-3.64 0.07 171 801 7

77 2.52 SAN 1BH

-1.29

-1.20 0.09 172 802 22 77 8.12 MAN 2BH

-5.84

-5.46 0.38 172 803 22 77 SAD 2BH

-3.16 172 804 22 77 1.85 SAN 2BH

-0.79

-0.70 0.09 172 805 22 77 3.80 MAN IBH

-3.84

-3.46 0.38 172 806 22 77 SAD 1BH

-1.16 172 807 22 77 1.01 SAI 1BH 1.21 1.30 0.09 173 808 2

79 MAD 2BH

-3.45 173 809 2

79 1.38 MAN 2BH

-5.77

-5.72 0.05 173 810 2

79 1.00 SAN 2BH

-0.84

-0.78 0.06 173 811 2

79 MAD 1BH

-1.45 173 812 2

79 1.33 MAN 1BH

-3.77

-3.72 0.05 173 813 2

79 0.76 SAI 1BH 1.16 1.22 0.06 174 814 11 79 1.42 MAN 2BH

-0.76

-0.68 0.08 174 815 11 79 SAD 2BH

-3.47 174 816 11 79 0.92 MAI 1BH 1.24 1.32 0.08 Page 145 of 169

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 174 817 11 79 SAD 1BH

-1.47 175 818 4

80 FPC 1BH 0.30 175 819 4

80 MAD 1BH

-0.95 175 820 4

80 MAD 2BH

-2.95 175 821 4

80 0.65 MAI TRH 0.05 0.15 0.10 176 822 5

80 SAD 2BH

-3.56 176 823 5

80 0.88 SAN 2BH

-0.81

-0.78 0.03 176 824 5

80 SAD 11BH

-1.56 176 825 5

80 0.37 SAI 1BH 1.19 1.22 0.03 177 826 9

80 0.86 MAN 2BH

-0.82

-0.75 0.07 177 827 9

80 SAD 2BH

-3.38 177 828 9

80 SAD 1BH

-1.38 177 829 9

80 0.41 SAI 1BH 1.18 1.25 0.07 178 830 19 81 5.79 MAN 2BH

-2.58

-2.21 0.37 178 831 19 81 0.85 MAN 2BH

-0.79

-0.73 0.06 178 832 19 81 SAD 2BH

-3.32 178 833 19 81 1.18 SAN 2BH

-5.76

-5.73 0.03 178 834 19 81 0.43 MAI 1BH 1.21 1.27 0.06 178 835 19 81 3.71 MAN 1BH

-0.56

-0.21 0.35 178 836 19 81 SAD 1BH

-1.32 178 837 19 81 1.62 SAN 1BH

-3.76

-3.73 0.03 179 838 7

82 1.47 MAN 2BH

-0.86

-0.73 0.13 179 839 7

82 SAD 2BH

-3.52 179 840 7

82 0.90 MAI 1BH 1.14 1.27 0.13 179 841 7

82 SAD 1BH

-1.52 180 842 18 82 FPC 1BH 0.30 180 843 18 82 MAD 1BH

-0.91 180 844 18 82 0.38 MAN 2BH

-2.91

-2.76 0.15 180 845 18 82 0.91 MAI TRH 0.09 0.24 0.15 181 846 5

84 MAD 2BH

-3.00 181 847 5

84 1.00 SAN 2BH

-0.84

-0.71 0.13 181 848 5

84 MAD 1BH

-1.00 181 849 5

84 0.66 SAI 1BH 1.16 1.29 0.13 182 850 18 86 1.54 MAN 2BH

-0.67

-0.59 0.08 182 851 18 86 1.02 SAN 2BH

-5.74

-5.69 0.05 182 852 18 86 2.78 SAN 2BH

-3.29

-3.14 0.15 182 853 18 86 0.78 MAI 1BH 1.33 1.41 0.08 182 854 18 86 0.86 SAN 1BH

-3.74

-3.69 0.05 182 855 18 86 2.76 SAN 1BH

-1.29

-1.14 0.15 183 856 3

87 0.76 MAN 2BH

-0.62

-0.57 0.05 183 857 3

87 SAD 2BH

-3.31 183 858 3

87 SAD 1BH

-1.31 183 859 3

87 0.58 SAI 1BH 1.38 1.43 0.05 Page 146 of 169

TABLE 16 STEAM GENERATOR 22 - NEW F*2 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 17 14 MAD 2BH

-3.32 1

2 17 14 1.94 SAN 2BH

-0.58

-0.48 0.10 1

3 17 14 MAD 1BH

-1.32 1

4 17 14 0.64 SAI

1BH, 1.42 1.52 0.10 2

5 14 17 SAD 2BH

-3.32 2

6 14 17 3.28 SAN 2BH

-0.78

-0.71 0.07 2

7 14 17 SAD 1BH

-1.32 2

8 14 17 0.69 SAI 1BH 1.22 1.29 0.07 3

9 22 23 2.47 MAN 2BH

-3.51

-3.37 0.14 3

10 22 23 0.99 SAN 2BH

-0.77

-0.70 0.07 3

11 22 23 2.35 MAN 1BH

-1.51

-1.37 0.14 3

12 22 23 0.72 SAI 1BH 1.23 1.30 0.07 4

13 17 24 MAD 2BH

-2.92 4

14 17 24 0.77 SAN 2BH

-2.12

-2.02 0.10 4

15 17 24 MAD 1BH

-0.92 4

16 17 24 0.35 SAI 1BH

-0.12 0.02 0.14 5

17 5

25 FPC 1BH 0.30 5

18 5

25 SAD 1BH

-0.94 5

19 5

25 SAD 2BH

-2.94 5

20 5

25 0.42 SAI TRH 0.06 0.20 0.14 6

21 13 26 MAD 2BH

-2.85 6

22 13 26 1.16 MAN 2BH

-2.32

-1.94 0.38 6

23 13 26 MAD 1BH

-0.85 6

24 13 26 0.51 MAI 1BH

-0.32 0.06 0.38 7

25 14 27 3.61 MAN 2BH

-0.87

-0.68 0.19 7

26 14 27 SAD 2BH

-2.95 7

27 14 27 1.65 MAI 1BH 1.13 1.32 0.19 7

28 14 27 SAD 1BH

-0.95 8

29 28 27 MAD 2BH

-3.24 8

30 28 27 1.03 SAN 2BH

-0.70

-0.66 0.04 8

31 28 27 MAD 1BH

-1.24 8

32 28 27 0.63 SAI 1BH 1.30 1.34 0.04 9

33 19 29 SAD 2BH

-3.72 9

34 19 29 1.41 SAN 2BH

-0.87

-0.71 0.16 9

35 19 29 SAD 1BH

-1.72 9

36 19 29 0.93 SAI 1BH 1.13 1.29 0.16 10 37 1

30 MAD 2BH

-2.94 10 38 1

30 10.90 MAN 2BH

-0.78

-0.62 0.16 10 39 1

30 MAD 1BH

-0.94 10 40 1

30 0.68 SAI 1BH 1.22 1.38 0.16 11 41 16 31 FPC 1BH 0.30 11 42 16 31 SAD 1BH

-0.75 11 43 16 31 SAD 2BH

-2.75 11 44 16 31 0.55 SAI TRH 0.13 0.25 0.12 12 45 33 31 SAD 2BH

-3.32 12 46 33 31 1.11 SAN 2BH

-0.73

-0.64 0.09 12 47 33 31 SAD 1BH

-1.32 12 48 33 31 0.30 SAI 1BH 1.27 1.36 0.09 Page 147 of 169

TABLE 16 STEAM GENERATOR 22 - NEW F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 13 49 14 34 FPC 1BH 0.30 13 50 14 34 MAD 1BH

-0.82 13 51 14 34 MAD 2BH

-2.82 13 52 14 34 0.49 MAI TRH 0.07 0.18 0.11 14 53 15 34 FPC 1BH 0.30 14 54 15 34 SAD 1BH

-0.76 14 55 15 34 SAD 2BH

-2.76 14 56 15 34 0.48 SAI TRH 0.11 0.24 0.13 15 57 19 34 FPC 1BH 0.30 15 58 19 34 MAD 1BH

-0.80 15 59 19 34 MAD 2BH

-2.80 15 60 19 34 0.59 MAI TRH 0.10 0.20 0.10 16 61 20 34 FPC 1BH 0.30 16 62 20 34 MAD 1BH

-0.77 16 63 20 34 MAD 2BH

-2.77 16 64 20 34 0.39 MAI TRH 0.12 0.23 0.11 17 65 21 35 MAD 2BH

-3.00 17 66 21 35 0.63 SAN 2BH

-2.02

-1.94 0.08 17 67 21 35 MAD 1BH

-1.00 17 68 21 35 0.51 SAI 1BH

-0.02 0.06 0.08 18 69 18 36 FPC 1BH 0.30 18 70 18 36 SAD 1BH

-0.82 18 71 18 36 SAD 2BH

-2.82 18 72 18 36 0.44 SAI TRH 0.05 0.18 0.13 19 73 33 36 SAD 2BH

-3.23 19 74 33 36 0.97 SAN 2BH

-2.58

-2.39 0.19 19 75 33 36 1.47 SAN 2BH

-0.77

-0.65 0.12 19 76 33 36 SAD 1BH

-1.23 19 77 33 36 0.47 SAI 1BH 1.23 1.35 0.12 19 78 33 36 0.70 SAN 1BH

-0.58

-0.39 0.19 20 79 1

39 MAD 2BH

-3.55 20 80 1

39 4.83 MAN 2BH

-2.42

-1.80 0.62 20 81 1

39 MAD 1BH

-1.55 20 82 1

39 6.19 MAI 1BH

-0.42 0.20 0.62 21 83 1

40 MAD 2BH

-3.34 21 84 1

40 1.02 SAN 2BH

-0.82

-0.75 0.07 21 85 1

40 MAD 1BH

-1.34 21 86 1

40 0.55 SAI 1BH 1.18 1.25 0.07 22 87 7

40 FPC 1BH 0.30 22 88 7

40 SAD 1BH

-0.76 22 89 7

40 SAD 2BH

-2.89 22 90 7

40 0.40 SAI TRH 0.11 0.29 0.18 23 91 13 40 FPC 1BH 0.30 23 92 13 40 SAD 1BH

-0.76 23 93 13 40 SAD 2BH

-2.76 23 94 13 40 0.31 SAI TRH 0.14 0.24 0.10 24 95 1

41 MAD 2BH

-3.63 24 96 1

41 3.66 MAN 2BH

-5.75

-5.42 0.33 Page 148 of 169

TABLE 16 STEAM GENERATOR 22 - NEW F*2 TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 24 97 1

41 1.11 MAN 2BH

-0.69

-0.57 0.12 24 98 1

41 MAD 1BH

-1.63 24 99 1

41 0.35 MAI 1BH 1.31 1.43 0.12 24 100 1

41 4.63 MAN 1BH

-3.75

-3.42 0.33 25 101 1

42 SAD 2BH

-3.35 25 102 1

42 2.02 SAN 2BH

-5.75

-5.64 0.11 25 103 1

42 1.18 SAN 2BH

-0.75

-0.66 0.09 25 104 1

42 SAD 1BH

-1.35 25 105 1

42 0.36 SAI 1BH 1.25 1.34 0.09 25 106 1

42 2.67 SAN 1BH

-3.75

-3.64 0.11 26 107 16 42 FPC 1BH 0.30 26 108 16 42 MAD 1BH

-0.90 26 109 16 42 MAD 2BH

-2.90 26 110 16 42 0.38 MAI TRH 0.10 0.18 0.08 27 111 22 42 SAD 2BH

-3.49 27 112 22 42 0.55 SAN 2BH

-0.87

-0.78 0.09 27 113 22 42 SAD 1BH

-1.49 27 114 22 42 0.35 SAI 1BH 1.13 1.22 0.09 28 115 21 45 FPC 1BH 0.30 28 116 21 45 MAD 1BH

-0.88 28 117 21 45 MAD 2BH

-2.88 28 118 21 45 0.92 MAI TRH 0.02 0.12 0.10 29 119 21 46 FPC 1BH 0.30 29 120 21 46 MAD 1BH

-0.98 29 121 21 46 MAD 2BH

-2.98 29 122 21 46 0.40 MAI TRH

-0.02 0.10 0.12 30 123 11 48 2.08 MAN 2BH

-2.43

-1.92 0.51 30 124 11 48 SAD 2BH

-2.90 30 125 11 48 0.39 MAI 1BH

-0.57 0.08 0.65 30 126 11 48 SAD 1BH

-0.90 31 127 22 48 2.20 MAN 2BH

-0.83

-0.66 0.17 31 128 22 48 SAD 2BH

-3.52 31 129 22 48 1.27 MAI 1BH 1.17 1.34 0.17 31 130 22 48 SAD 1BH

-1.52 32 131 21 49 SAD 2BH

-2.86 32 132 21 49 2.24 SAN 2BH

-0.85

-0.75 0.10 32 133 21 49 SAD 1BH

-0.86 32 134 21 49 0.78 SAI 1BH 1.15 1.25 0.10 33 135 9

50 2.12 MAN 2BH

-5.57

-5.46 0.11 33 136 9

50 2.25 MAN 2BH

-3.16

-3.03 0.13 33 137 9

50 0.63 SAN 2BH

-0.77

-0.68 0.09 33 138 9

50 2.25 MAN 1BH

-3.57

-3.46 0.11 33 139 9

50 2.72 MAN 1BH

-1.16

-1.03 0.13 33 140 9

50 0.50 SAI 1BH 1.23 1.32 0.09 34 141 15 50 SAD 2BH

-3.20 34 142 15 50 0.99 SAN 2BH

-0.81

-0.78 0.03 34 143 15 50 SAD 1BH

-1.20 34 144 15 50 0.43 SAI 1BH 1.19 1.22 0.03 Page 149 of 169

TABLE 16 STEAM GENERATOR 22 - NEW F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 35 145 15 51 SAD 2BH

-3.09 35 146 15 51 1.05 SAN 2BH

-0.82

-0.76 0.06 35 147 15 51 SAD 1BH

-1.09 35 148 15 51 0.59 SAI 1BH 1.18 1.24 0.06 36 149 29 53 MAD 2BH

-3.53 36 150 29 53 1.22 MAN 2BH

-0.65

-0.58 0.07 36 151 29 53 1.01 SAN 2BH

-2.40

-2.34 0.06 36 152 29 53 MAD 1BH

-1.53 36 153 29 53 0.43 MAI 1BH 1.35 1.42 0.07 36 154 29 53 0.61 SAN 1BH

-0.40

-0.34 0.06 37 155 16 54 4.69 MAN 2BH

-2.64

-2.04 0.60 37 156 16 54 SAD 2BH

-3.29 37 157 16 54 0.85 SAN 2BH

-0.81

-0.72 0.09 37 158 16 54 8.66 MAN 1BH

-0.64

-0.04 0.60 37 159 16 54 SAD 1BH

-1.29 37 160 16 54 0.53 SAI 1BH 1.19 1.28 0.09 38 161 14 55 SAD 2BH

-3.20 38 162 14 55 2.60 SAN 2BH

-0.89

-0.80 0.09 38 163 14 55 SAD 1BH

-1.20 38 164 14 55 1.20 SAI IBH 1.11 1.20 0.09 39 165 21 55 MAD 2BH

-3.41 39 166 21 55 1.00 MAN 2BH

-0.88

-0.76 0.12 39 167 21 55 MAD 1BH

-1.41 39 168 21 55 0.68 MAI 1BH 1.12 1.24 0.12 40 169 22 55 1.99 MAN 2BH

-3.41

-3.25 0.16 40 170 22 55 0.94 SAN 2BH

-0.83

-0.76 0.07 40 171 22 55 1.92 MAN 1BH

-1.41

-1.25 0.16 40 172 22 55 0.66 SAI 1BH 1.17 1.24 0.07 41 173 4

56 3.74 MAN 2BH

-3.23

-3.12 0.11 41 174 4

56 3.64 SAN 2BH

-5.75

-5.68 0.07 41 175 4

56 1.08 SAN 2BH

-0.85

-0.81 0.04 41 176 4

56 4.12 MAN 1BH

-1.23

-1.12 0.11 41 177 4

56 0.46 SAI 1BH 1.15 1.19 0.04 41 178 4

56 0.83 SAN 1BH

-3.75

-3.68 0.07 42 179 16 57 SAD 2BH

-3.06 42 180 16 57 0.61 SAN 2BH

-0.86

-0.78 0.08 42 181 16 57 SAD 1BH

-1.06 42 182 16 57 0.31 SAI 1BH 1.14 1.22 0.08 43 183 18 58 MAD 2BH

-3.31 43 184 18 58 0.90 MAN 2BH

-0.89

-0.81 0.08 43 185 18 58 MAD 1BH

-1.31 43 186 18 58 0.64 MAI IBH 1.11 1.19 0.08 44 187 19 58 SAD 2BH

-2.98 44 188 19 58 0.84 SAN 2BH

-0.87

-0.80 0.07 44 189 19 58 SAD 1BH

-0.98 44 190 19 58 0.32 SAI 1BH 1.13 1.20 0.07 45 191 9

59 0.72 MAN 2BH

-0.87

-0.79 0.08 45 192 9

59 1 SAD 2BH

-3.30 Page 150 of 169

TABLE 16 STEAM GENERATOR 22 - NEW F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 45 193 9

59 0.71 MAI 1BH 1.13 1.21 0.08 45 194 9

59 SAD 1BH

-1.30 46 195 15 59 MAD 2BH

-3.34 46 196 15 59 5.26 SAN 2BH

-0.89

-0.70 0.19 46 197 15 59 MAD 1BH

-1.34 46 198 15 59 2.06 SAI 1BH 1.11 1.30 0.19 47 199 20 59 SAD 2BH

-3.43 47 200 20 59 0.75 SAN 2BH

-0.84

-0.76 0.08 47 201 20 59 SAD 1BH

-1.43 47 202 20 59 0.59 SAI 1BH 1.16 1.24 0.08 48 203 23 61 1.90 SAN 2BH

-3.44

-3.27 0.17 48 204 23 61 1.09 SAN 2BH

-0.81

-0.70 0.11 48 205 23 61 0.99 SAI 1BH 1.19 1.30 0.11 48 206 23 61 2.37 SAN 1BH

-1.44

-1.27 0.17 49 207 19 62 3.15 MAN 2BH

-3.26

-3.12 0.14 49 208 19 62 1.48 SAN 2BH

-0.85

-0.78 0.07 49 209 19 62 3.27 MAN 1BH

-1.26

-1.12 0.14 49 210 19 62 0.76 SAI 1BH 1.15 1.22 0.07 50 211 11 63 0.96 MAN 2BH

-0.80

-0.76 0.04 50 212 11 63 SAD 2BH

-3.30 50 213 11 63 0.59 MAI 1BH 1.20 1.24 0.04 50 214 11 63 SAD 1BH

-1.30 51 215 9

65 MAD 2BH

-3.00 51 216 9

65 1.78 SAN 2BH

-0.87

-0.73 0.14 51 217 9

65 MAD 1BH

-1.00 51 218 9

65 0.61 SAI 1BH 1.13 1.27 0.14 52 219 19 65 SAD 2BH

-3.29 52 220 19 65 1.40 SAN 2BH

-0.84

-0.77 0.07 52 221 19 65 SAD 11BH

-1.29 52 222 19 65 0.77 SAI 1BH 1.16 1.23 0.07 53 223 19 66 SAD 2BH

-3.00 53 224 19 66 0.88 SAN 2BH

-0.89

-0.79 0.10 53 225 19 66 SAD 1BH

-1.00 53 226 19 66 0.56 SAI 1BH 1.11 1.21 0.10 54 227 12 67 SAD 2BH

-3.02 54 228 12 67 0.65 SAN 2BH

-1.07

-1.01 0.06 54 229 12 67 SAD 1BH

-1.02 54 230 12 67 0.39 SAI 1BH 0.93 0.99 0.06 55 231 18 67 SAD 2BH

-2.98 55 232 18 67 0.78 SAN 2BH

-0.86

-0.80 0.06 55 233 18 67 SAD 1BH

-0.98 55 234 18 67 0.61 SAI 1BH 1.14 1.20 0.06 56 235 24 67 2.70 MAN 2BH

-3.35

-3.18 0.17 56 236 24 67 0.86 MAN 2BH

-0.82

-0.77 0.05 56 237 24 67 0.68 MAI 1BH 1.18 1.23 0.05 56 238 24 67 3.13 MAN 1BH

-1.35

-1.18 0.17 57 239 24 68 2.49 MAN 2BH

-3.45

-3.33 0.12 57 240 24 68 1.15 MAN 2BH

-0.96

-0.84 0.12 Page 151 of 169

TABLE 16 STEAM GENERATOR 22 - NEW F*2 TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 57 241 24 68 0.97 MAI 1BH 1.04 1.16 0.12 57 242 24 68 2.84 MAN 1BH

-1.45

-1.33 0.12 58 243 24 70 SAD 2BH

-3.57 58 244 24 70 1.24 SAN 2BH

-0.88

-0.82 0.06 58 245 24 70 SAD 1BH

-1.57 58 246 24 70 0.65 SAI 1BH 1.12 1.18 0.06 59 247 27 71 SAD 2BH

-2.90 59 248 27 71 0.43 SAN 2BH

-0.86

-0.80 0.06 59 249 27 71 SAD 1BH

-0.90 59 250 27 71 0.43 SAI 1BH 1.14 1.20 0.06 60 251 17 72 SAD 2BH

-3.26 60 252 17 72 0.93 SAN 2BH

-0.84

-0.80 0.04 60 253 17 72 SAD 1BH

-1.26 60 254 17 72 0.56 SAI 1BH 1.16 1.20 0.04 61 255 24 72 0.53 SAN 2BH

-3.49

-3.40 0.09 61 256 24 72 0.65 SAN 2BH

-2.46

-2.10 0.36 61 257 24 72 0.64 SAN 2BH

-0.92

-0.85 0.07 61 258 24 72 0.39 SAI 1BH 1.08 1.15 0.07 61 259 24 72 0.49 SAN 1BH

-1.49

-1.40 0.09 61 260 24 72 0.60 SAN 1BH

-0.46

-0.10 0.36 62 261 14 73 MAD 2BH

-3.13 62 262 14 73 0.59 SAN 2BH

-0.79

-0.75 0.04 62 263 14 73 MAD 1BH

-1.13 62 264 14 73 0.29 SAI 1BH 1.21 1.25 0.04 63 265 17 73 MAD 2BH

-3.30 63 266 17 73 1.19 MAN 2BH

-4.60

-4.47 0.13 63 267 17 73 0.53 MAN 2BH

-0.76

-0.70 0.06 63 268 17 73 MAD IBH

-1.30 63 269 17 73 0.47 MAI 1BH 1.24 1.30 0.06 63 270 17 73 1.18 MAN 1BH

-2.60

-2.47 0.13 64 271 6

75 SAD 1BH

-0.89 64 272 6

75 0.24 SAI 1BH 0.79 0.86 0.07 64 273 6

75 3.16 SAN 1BH

-3.69

-3.40 0.29 64 274 6

75 SAD 2BH

-2.89 64 275 6

75 SAD 2BH

-1.21 64 276 6

75 3.42 SAN 2BH

-5.69

-5.40 0.29 64 277 6

75 0.66 SAI TRH 0.11 0.23 0.12 64 278 6

75 4.02 SAN TRH

-2.69

-2.40 0.29 65 279 12 75 MAD 2BH

-3.22 65 280 12 75 SAD 2BH

-1.61 65 281 12 75 MAD 1BH

-1.22 65 282 12 75 0.12 SAI 1BH 0.39 0.47 0.08 66 283 17 77 MAD 2BH

-3.10 66 284 17 77 0.51 SAN 2BH

-0.78

-0.74 0.04 66 285 17 77 MAD 1BH

-1.10 66 286 17 77 0.35 SAI 1BH 1.22 1.26 0.04 67 287 22 78 SAD 2BH

-3.53 67 288 22 78 0.65 SAN 2BH

-0.62

-0.55 0.07 Page 152 of 169

TABLE 16 STEAM GENERATOR 22 - NEW F*2 TUBE#

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 67 289 22 78 SAD 1BH

-1.53 67 290 22 78 0.39 SAI 11BH 1.38 1.45 0.07 68 291 13 79 3.15 MAN 2BH

-5.72

-5.53 0.19 68 292 13 79 3.17 MAN 2BH

-3.16

-3.03 0.13 68 293 13 79 0.56 SAN 2BH

-0.64

-0.47 0.17 68 294 13 79 3.67 MAN 1BH

-3.72

-3.53 0.19 68 295 13 79 3.83 MAN 1BH

-1.16

-1.03 0.13 68 296 13 79 0.52 SAI 1BH 1.36 1.53 0.17 69 297 15 80 0.88 MAN 2BH

-0.74

-0.68 0.06 69 298 15 80 SAD 2BH

-3.32 69 299 15 80 0.75 MAI IBH 1.26 1.32 0.06 69 300 15 80 SAD 1BH

-1.32 70 301 22 83 SAD 2BH

-3.44 70 302 22 83 0.81 SAN 2BH

-5.70

-5.64 0.06 70 303 22 83 1.82 SAN 2BH

-0.98

-0.88 0.10 70 304 22 83 SAD 11BH

-1.44 70 305 22 83 1.19 SAI 1BH 1.02 1.12 0.10 70 306 22 83 0.60 SAN 1BH

-3.70

-3.64 0.06 Page 153 of 169

TABLE 17 STEAM GENERATOR 21 - NEW EF*

TUBE#

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 4

13 1.09 SAN EBH

-13.81

-13.69 0.12 1

2 4

13 1.03 SAN EBH

-11.63

-11.53 0.10 1

3 4

13 0.30 SAN EBH

-9.44

-9.41 0.03 1

4 4

13 0.36 SAI 2BH 1.19 1.22 0.03 1

5 4

13 1.21 SAN 2BH

-3.18

-3.06 0.12 1

6 4

13 1.29 SAN 2BH

-1.00

-0.90 0.10 2

7 6

14 4.53 MAN EBH

-16.34

-16.05 0.29 2

8 6

14 0.47 MAN EBH

-9.56

-9.48 0.08 2

9 6

14 SAD EBH

-13.93 2

10 6

14 1.11 SAN EBH

-13.70

-13.60 0.10 2

11 6

14 1.22 SAN EBH

-11.63

-11.52 0.11 2

12 6

14 0.42 MAI 2BH 1.07 1.15 0.08 2

13 6

14 4.97 MAN 21H

-5.71

-5.42 0.29 2

14 6

14 SAD 2BH

-3.30 2

15 6

14 1.44 SAN 2BH

-3.07

-2.97 0.10 2

16 6

14 1.28 SAN 2BH

-1.00

-0.89 0.11 3

17 8

30 2.66 MAN EBH

-16.56

-16.47 0.09 3

18 8

30 1.45 SAN EBH

-13.97

-13.84 0.13 3

19 8

30 1.43 SAN EBH

-11.57

-11.43 0.14 3

20 8

30 1.80 SAN EBH

-9.12

-8.91 0.21 3

21 8

30 1.68 MAN 2BH

-5.93

-5.84 0.09 3

22 8

30 1.48 SAI 2BH 1.51 1.72 0.21 3

23 8

30 1.66 SAN 2BH

-3.34

-3.21 0.13 3

24 8

30 1.54 SAN 2BH

-0.94

-0.80 0.14 4

25 8

33 2.94 MAN EBH

-13.93

-13.80 0.13 4

26 8

33 1.66 SAN EBH

-11.55

-11.45 0.10 4

27 8

33 0.76 SAN EBH

-9.48

-9.41 0.07 4

28 8

33 2.92 MAN 2BH

-3.30

-3.17 0.13 4

29 8

33 0.67 SAI 2BH 1.15 1.22 0.07 4

30 8

33 1.35 SAN 2BH

-0.92

-0.82 0.10 5

31 23 48 MAD EBH

-13.94 5

32 23 48 1.96 SAN EBH

-11.37

-11.30 0.07 5

33 23 48 0.40 SAN EBH

-9.43

-9.36 0.07 5

34 23 48 MAD 2BH

-3.31 5

35 23 48 0.53 SAI 2BH 1.20 1.27 0.07 5

36 23 48 1.99 SAN 2BH

-0.74

-0.67 0.07 6

37 21 54 MAD EBH

-13.85 6

38 21 54 0.52 MAN EBH

-9.52

-9.47 0.05 6

39 21 54 1.07 SAN EBH

-11.54

-11.47 0.07 6

40 21 54 MAD 2BH

-3.22 6

41 21 54 0.39 SAI 2BH 1.11 1.16 0.05 6

42 21 54 1.15 SAN 2BH

-0.91

-0.83 0.08 7

43 13 57 6.78 MAN EBH

-14.01

-13.52 0.49 7

44 13 57 1.22 MAN EBH

-11.54

-11.47 0.07 7

45 13 57 0.91 SAN EBH

-9.47

-9.41 0.06 7

46 13 57 6.99 MAN 2BH

-3.38

-2.89 0.49 7

47 13 57 1.46 MAN 2BH

-0.91

-0.84 0.07 7

48 13 57 0.84 SAI 2BH 1.16 1.22 0.06 Page 154 of 169

TABLE 17 STEAM GENERATOR 21 - NEW EF*

TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 8

49 23 57 2.09 MAN EBH

-13.86

-13.70 0.16 8

50 23 57 0.84 MAN EBH

-9.33

-9.26 0.07 8

51 23 57 1.99 SAN EBH

-16.38

-16.31 0.07 8

52 23 57 2.15 SAN EBH

-11.58

-11.45 0.13 8

53 23 57 0.89 MAI 2BH 1.30 1.37 0.07 8

54 23 57 2.35 MAN 2BH

-3.23

-3.07 0.16 8

55 23 57 2.41 SAN 2BH

-5.75

-5.68 0.07 8

56 23 57 1.99 SAN 2BH

-0.95

-0.82 0.13 9

57 11 59 3.45 MAN EBH

-13.94

-13.70 0.24 9

58 11 59 2.54 MAN EBH

-11.52

-11.37 0.15 9

59 11 59 1.49 SAN EBH

-9.44

-9.31 0.13 9

60 11 59 3.48 MAN 2BH

-3.31

-3.07 0.24 9

61 11 59 2.00 MAN 2BH

-0.89

-0.74 0.15 9

62 11 59 1.31 SAI 2BH 1.19 1.32 0.13 10 63 5

60 0.54 MAN EBH

-13.84

-13.74 0.10 10 64 5

60 2.56 MAN EBH

-11.52

-11.45 0.07 10 65 5

60 0.71 MAN EBH

-9.55

-9.46 0.09 10 66 5

60 0.73 MAI 2BH 1.08 1.17 0.09 10 67 5

60 0.56 MAN 2BH

-3.21

-3.11 0.10 10 68 5

60 2.71 MAN 2BH

-0.89

-0.76 0.13 11 69 29 60 MAD EBH

-13.90 11 70 29 60 1.37 SAN EBH

-16.38

-16.27 0.11 11 71 29 60 2.24 SAN EBH

-11.62

-11.48 0.14 11 72 29 60 0.52 SAN EBH

-9.46

-9.33 0.13 11 73 29 60 MAD 2BH

-3.27 11 74 29 60 0.53 SAI 2BH 1.17 1.30 0.13 11 75 29 60 1.28 SAN 2BH

-5.76

-5.65 0.11 11 76 29 60 2.20 SAN 2BH

-0.99

-0.85 0.14 12 77 9

61 1.12 MAN EBH

-13.99

-13.83 0.16 12 78 9

61 1.48 MAN EBH

-9.49

-9.37 0.12 12 79 9

61 2.12 SAN EBH

-11.61

-11.40 0.21 12 80 9

61 1.63 MAI 2BH 1.14 1.26 0.12 12 81 9

61 1.24 MAN 2BH

-3.36

-3.20 0.16 12 82 9

61 2.23 SAN 2BH

-0.98

-0.77 0.21 13 83 12 69 MAD EBH

-13.96 13 84 12 69 2.10 MAN EBH

-16.32

-16.18 0.14 13 85 12 69 2.11 MAN EBH

-11.42

-11.34 0.08 13 86 12 69 0.58 MAN EBH

-9.42

-9.26 0.16 13 87 12 69 MAD 2BH

-3.33 13 88 12 69 0.56 MAI 2BH 1.21 1.37 0.16 13 89 12 69 2.48 MAN 2BH

-5.69

-5.55 0.14 13 90 12 69 2.01 MAN 2BH

-0.79

-0.71 0.08 14 91 5

74 1.72 MAN EBH

-13.84

-13.73 0.11 14 92 5

74 1.44 SAN EBH

-16.44

-16.35 0.09 14 93 5

74 1.56 SAN EBH

-11.56

-11.41 0.15 14 94 5

74 0.28 SAN EBH

-9.45

-9.38 0.07 14 95 5

74 2.11 MAN 2BH

-3.27

-3.18 0.09 14 96 5

74 0.26 SAI 2BH 1.18 1.25 0.07 Page 155 of 169

TABLE 17 STEAM GENERATOR 21 - NEW EF*

TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 14 97 5

74 1.22 SAN 2BH

-5.81

-5.72 0.09 14 98 5

74 1.62 SAN 2BH

-0.93

-0.78 0.15 Page 156 of 169

TABLE 18 STEAM GENERATOR 22 - NEW EF*

TUBE#

IND# I ROW COL I VOLTS I PCT I LOCATION I ELEV-FROM I ELEV-TO I LENGTH None Installed During 2R27 Page 157 of 169

TABLE 19 STEAM GENERATOR 21 - NEW PLUGS TUBE #

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 1

10 MAD 2BH

-3.39 1

2 1

10 0.92 MAI 2BH 1.20 1.24 0.04 1

3 1

10 5.22 MAN 2BH

-5.76

-5.30 0.46 1

4 1

10 1.73 SAN 2BH

-0.87

-0.77 0.10 2

5 12 11 SAD 2BH

-2.99 2

6 12 11 0.75 SAI 2BH 1.02 1.08 0.06 2

7 12 11 0.89 SAN 2BH

-5.82

-5.78 0.04 2

8 12 11 0.39 SAN 2BH

-1.44

-1.15 0.29 3

9 12 16 MAD 2BH

-3.23 3

10 12 16 0.33 MAI 2BH 1.21 1.28 0.07 3

11 12 16 2.15 SAN 2BH

-5.73

-5.61 0.12 3

12 12 16 1.24 SAN 2BH

-0.89

-0.79 0.10 4

13 26 16 MAD 2BH

-3.40 4

14 26 16 0.84 MAI 2BH 1.38 1.48 0.10 4

15 26 16 2.86 MAN 2BH

-5.57

-5.51 0.06 4

16 26 16 3.01 SAN 2BH

-0.98

-0.81 0.17 5

17 4

17 1.03 MAI 2BH 1.18 1.27 0.09 5

18 4

17 5.73 MAN 2BH

-5.35

-5.24 0.11 5

19 4

17 SAD 2BH

-3.11 6

20 1

18 MAD 2BH

-3.21 6

21 1

18 0.65 MAI 2BH 1.40 1.45 0.05 6

22 1

18 5.41 MAN 2BH

-5.52

-5.40 0.12 6

23 1

18 1.05 SAN 2BH

-0.80

-0.69 0.11 7

24 19 18 1.00 MAI EBH

-0.06 0.10 0.16 7

25 19 18 0.59 MAN EBH

-13.50

-13.42 0.08 7

26 19 18 4.66 MAN EBH

-11.64

-11.25 0.39 7

27 19 18 SAD EBH

-13.90 7

28 19 18 1.40 SAN EBH

-16.42

-16.35 0.07 7

29 19 18 3.03 SAN EBH

-9.45

-9.38 0.07 8

30 27 18 0.80 MAI EBH 2.02 2.23 0.21 8

31 27 18 2.83 MAN EBH

-9.20

-9.10 0.10 8

32 27 18 SAD EBH

-14.13 8

33 27 18 1.48 SAN EBH

-16.21

-16.01 0.20 8

34 27 18 3.68 SAN EBH

-11.25

-10.98 0.27 8

35 27 18 0.71 SAN EBH

-0.25

-0.18 0.07 9

36 9

19 MAD 2BH

-3.20 9

37 9

19 0.99 MAI 2BH 1.08 1.21 0.13 9

38 9

19 3.60 SAN 2BH

-0.91

-0.72 0.19 10 39 25 19 MAD 2BH

-3.25 10 40 25 19 1.03 MAI 2BH 1.24 1.39 0.15 10 41 25 19 1.63 SAN 2BH

-0.87

-0.77 0.10 11 42 14 21 SAD 2BH

-3.28 11 43 14 21 0.78 SAI 2BH 1.11 1.20 0.09 11 44 14 21 5.68 SAN 2BH

-2.61

-2.05 0.56 11 45 14 21 2.59 SAN 2BH

-0.88

-0.74 0.14 12 46 24 21 2.84 MAN 2BH

-5.74

-5.47 0.27 12 47 24 21 3.37 MAN 2BH

-3.24

-3.11 0.13 12 48 24 21 1.21 SAI 2BH 1.16 1.28 0.12 Page 158 of 169

TABLE 19 STEAM GENERATOR 21 - NEW PLUGS TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 12 49 24 21 3.52 SAN 2BH

-0.92

-0.80 0.12 13 50 16 22 MAD 2BH

-3.33 13 51 16 22 0.71 SAI 2BH 1.15 1.25 0.10 13 52 16 22 4.22 SAN 2BH

-0.96

-0.63 0.33 14 53 16 23 1.47 MAN 2BH

-3.20

-3.07 0.13 14 54 16 23 1.30 SAI 2BH 1.15 1.22 0.07 14 55 16 23 0.89 SAN 2BH

-5.71

-5.67 0.04 14 56 16 23 1.67 SAN 2BH

-0.86

-0.79 0.07 15 57 19 23 1.74 MAI EBH

-0.30 0.11 0.41 15 58 19 23 1.44 MAN EBH

-13.86

-13.79 0.07 15 59 19 23 1.74 SAN EBH

-11.48

-11.41 0.07 15 60 19 23 0.95 SAN EBH

-9.21

-9.15 0.06 16 61 23 23 MAD 2BH

-3.22 16 62 23 23 0.37 SAI 2BH 1.11 1.17 0.06 16 63 23 23 1.73 SAN 2BH

-5.62

-5.51 0.11 16 64 23 23 1.67 SAN 2BH

-2.96

-2.90 0.06 16 65 23 23 3.45 SAN 2BH

-0.84

-0.74 0.10 17 66 31 23 1.96 MAN 2BH

-0.93

-0.66 0.27 17 67 31 23 SAD 2BH

-3.23 17 68 31 23 0.54 SAI 2BH 1.26 1.34 0.08 18 69 5

24 1.44 MAN 2BH

-3.31

-3.19 0.12 18 70 5

24 0.59 SAI 2BH 1.22 1.29 0.07 18 71 5

24 2.66 SAN 2BH

-5.67

-5.63 0.04 18 72 5

24 2.30 SAN 2BH

-0.79

-0.69 0.10 19 73 23 25 1.19 MAI 2BH 1.14 1.22 0.08 19 74 23 25 SAD 2BH

-3.21 19 75 23 25 1.85 SAN 2BH

-0.81

-0.71 0.10 20 76 12 27 MAD 2BH

-2.61 20 77 12 27 1.36 SAI 2BH 1.13 1.24 0.11 20 78 12 27 3.72 SAN 2BH

-0.73

-0.63 0.10 21 79 9

28 FPC EBH 0.30 21 80 9

28 0.31 MAN 2BH

-3.33

-3.23 0.10 21 81 9

28 1.46 MAN 2BH

-2.39

-2.04 0.35 21 82 9

28 0.32 MAN EBH

-13.96

-13.86 0.10 21 83 9

28 1.25 MAN EBH

-13.02

-12.67 0.35 21 84 9

28 1.94 SAI 2BH 1.23 1.33 0.10 21 85 9

28 0.75 SAN EBH

-16.19

-16.13 0.06 21 86 9

28 2.10 SAN EBH

-9.40

-9.30 0.10 22 87 16 28 0.38 MAI 2BH 1.52 1.61 0.09 22 88 16 28 1.94 MAN 2BH

-3.33

-3.18 0.15 22 89 16 28 1.64 SAN 2BH

-0.89

-0.75 0.14 23 90 23 28 1.25 MAI EBH

-0.11 0.02 0.13 23 91 23 28 0.15 MAI EBH 3.53 4.87 1.34 23 92 23 28 2.73 MAN EBH

-13.76

-13.62 0.14 23 93 23 28 2.16 MAN EBH

-11.50

-11.30 0.20 23 94 23 28 2.10 MAN EBH

-9.37

-9.20 0.17 24 95 18 29 2.81 MAN 2BH

-3.20

-3.06 0.14 24 96 18 29 5.53 MAN 2BH

-0.71

-0.68 0.03 Page 159 of 169

TABLE 19 STEAM GENERATOR 21 - NEW PLUGS TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 24 97 18 29 0.41 SAI 2BH 15.02 15.53 0.51 25 98 13 30 0.15 MAI EBH 4.56 5.00 0.44 25 99 13 30 SAD EBH

-13.71 25 100 13 30 0.09 SAI EBH 3.02 3.49 0.47 25 101 13 30 1.43 SAN EBH

-16.36

-16.21 0.15 26 102 18 30 0.40 MAI 2BH 1.48 1.57 0.09 26 103 18 30 SAD 2BH

-3.18 26 104 18 30 0.70 SAN 2BH

-5.84

-5.72 0.12 26 105 18 30 0.37 SAN 2BH

-2.13

-1.63 0.50 26 106 18 30 0.49 SAN 2BH

-1.04

-0.94 0.10 27 107 25 32 1.19 22 NV2 0.61 27 108 25 32 1.43 26 NV2 19.78 27 109 25 32 1.79 MAN 2BH

-5.67

-5.58 0.09 27 110 25 32 SAD 2BH

-3.26 27 111 25 32 0.35 SAI 2BH 1.29 1.35 0.06 27 112 25 32 1.17 SAN 2BH

-0.86

-0.74 0.12 28 113 3

33 2.42 MAN 2BH

-3.20

-3.04 0.16 28 114 3

33 1.80 MAN 2BH

-0.87

-0.77 0.10 28 115 3

33 0.55 SAI 2BH 1.39 1.46 0.07 29 116 10 34 1.59 MAI 2BH 1.25 1.44 0.19 29 117 10 34 3.52 MAN 2BH

-3.07

-2.91 0.16 29 118 10 34 1.13 SAN 2BH

-0.73

-0.62 0.11 30 119 27 34 SAD 2BH

-2.87 30 120 27 34 0.77 SAI 2BH 1.17 1.33 0.16 30 121 27 34 2.71 SAN 2BH

-0.85

-0.73 0.12 31 122 31 35 3.48 MAN 2BH

-0.95

-0.83 0.12 31 123 31 35 SAD 2BH

-3.36 31 124 31 35 0.52 SAI 2BH 1.23 1.31 0.08 32 125 5

36 2.10 MAN 2BH

-3.07

-2.97 0.10 32 126 5

36 6.40 MAN 2BH

-2.38

-1.87 0.51 32 127 5

36 0.71 SAI 2BH 1.07 1.16 0.09 33 128 7

36 SAD 2BH

-3.23 33 129 7

36 0.43 SAI 2BH 1.16 1.22 0.06 33 130 7

36 2.09 SAN 2BH

-0.82

-0.74 0.08 34 131 14 36 MAD 2BH

-3.00 34 132 14 36 0.93 SAI 2BH 1.13 1.21 0.08 34 133 14 36 0.12 SAI TSH 1.74 1.89 0.15 35 134 13 37 3.44 MAN 2BH

-3.20

-2.99 0.21 35 135 13 37 2.44 MAN 2BH

-0.82

-0.71 0.11 35 136 13 37 0.65 SAI 2BH 1.16 1.23 0.07 36 137 9

38 0.56 MAI 2BH 1.14 1.21 0.07 36 138 9

38 2.80 MAN 2BH

-3.11

-3.00 0.11 36 139 9

38 2,22 MAN 2BH

-0.84

-0.79 0.05 37 140 12 39 FPC EBH 0.30 37 141 12 39 0.52 SAI 2BH 1.16 1.27 0.11 37 142 12 39 2.59 SAN 2BH

-3.11

-2.93 0.18 37 143 12 39 1.39 SAN 2BH

-0.80

-0.74 0.06 37 144 12 39 2.19 SAN EBH

-13.74

-13.56 0.18 Page 160 of 169

TABLE 19 STEAM GENERATOR 21 - NEW PLUGS TUBE#

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 37 145 12 39 1.37 SAN EBH

-11.43

-11.37 0.06 37 146 12 39 0.50 SAN EBH

-9.47

-9.36 0.11 38 147 22 39 SAD 2BH

-3.28 38 148 22 39 0.56 SAI 2BH 1.21 1.28 0.07 38 149 22 39 2.67 SAN 2BH

-1.10

-0.78 0.32 39 150 12 40 MAD 2BH

-3.30 39 151 12 40 1.03 SAI 2BH 1.17 1.32 0.15 39 152 12 40 4.35 SAN 2BH

-0.79

-0.65 0.14 40 153 37 40 MAD 2BH

-3.14 40 154 37 40 0.60 SAI 2BH 1-1.24 1.28 0.04 40 155 37 40 0.17 SAI 2BH 14.53 14.71 0.18 40 156 37 40 2.19 SAN 2BH

-0.82

-0.71 0.11 41 157 21 42 1.44 MAN 2BH

-2.52

-2.25 0.27 41 158 21 42 SAD 2BH

-3.33 41 159 21 42 0.68 SAI 2BH 1.31 1.40 0.09 41 160 21 42 0.74 SAN 2BH

-0.90

-0.87 0.03 42 161 9

43 2.54 MAN 2BH

-3.23

-2.99 0.24 42 162 9

43 0.93 SAI 2BH 1.19 1.28 0.09 42 163 9

43 1.58 SAN 2BH

-0.81

-0.71 0.10 43 164 24 43 0.23 MAI 2BH 1-14.82 14.92 0.10 43 165 24 43 13.10 MAN 2BH

-3.37

-2.74 0.63 43 166 24 43 0.20 SAI 2BH 1-14.36 14.61 0.25 43 167 24 43 2.85 SAN 2BH

-0.84

-0.63 0.21 44 168 24 44 0.87 MAI 2BH 1-1.13 1.24 0.11 44 169 24 44 3.01 MAN 2BH

-3.18

-3.07 0.11 44 170 24 44 2.57 SAN 2BH

-0.90

-0.83 0.07 45 171 13 45 0.37 MAI 2BH

-0.32 0.02 0.34 45 172 13 45 9.71 MAN 2BH

-3.37

-2.81 0.56 45 173 13 45 1.26 MAN 2BH

-0.67

-0.60 0.07 46 174 30 45 3.78 MAN EBH

-9.14

-8.99 0.15 46 175 30 45 0.42 SAI EBH 2.08 2.14 0.06 46 176 30 45 0.28 SAN EBH

-13.65

-13.61 0.04 46 177 30 45 1.30 SAN EBH

-11.30

-11.26 0.04 47 178 16 46 MAD 2BH

-3.36 47 179 16 46 0.70 SAI 2BH 1-1.13 1.23 0.10 47 180 16 46 1.12 SAN 2BH

-5.74

-5.70 0.04 47 181 16 46 0.67 SAN 2BH

-0.74

-0.71 0.03 48 182 18 46 0.89 MAN 1BH

-0.35

-0.23 0.12 48 183 18 46 SAD 1BH

-1.24 48 184 18 46 0.09 SAI 1BH 17.01 17.12 0.11 48 185 18 46 1.32 SAN IBH

-3.74

-3.71 0.03 49 186 4

48 5.29 MAN 2BH

-3.20

-3.08 0.12 49 187 4

48 0.70 SAI 2BH 1.16 1.26 0.10 49 188 4

48 0.58 SAN 2BH

-0.77

-0.73 0.04 50 189 14 48 0.47 MAI 1BH

-0.56 0.19 0.75 50 190 14 48 0.26 MAI 1BH 0.63 1.00 0.37 50 191 14 48 0.19 MAI 2BH

-0.91

-0.87 0.04 50 192 14 48 0.27 MAI 2BH

-0.19

-0.11 0.08 Page 161 of 169

TABLE 19 STEAM GENERATOR 21 - NEW PLUGS TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 50 193 14 48 0.40 MAN 2BH

-2.56

-1.81 0.75 50 194 14 48 0.25 MAN 2BH

-1.37

-1.00 0.37 50 195 14 48 SAD 1BH

-0.95 50 196 14 48 SAD 2BH

-2.95 50 197 14 48 1.05 SAI TRH 0.05 0.10 0.05 50 198 14 48 0.14 SAI 2BH 1.58 1.67 0.09 51 199 15 49 MAD 2BH

-3.35 51 200 15 49 0.37 SAI 2BH 1.13 1.16 0.03 52 201 17 50 0.44 MAI EBH

-0.02 0.04 0.06 52 202 17 50 SAD EBH

-14.21 52 203 17 50 2.54 SAN EBH

-9.27

-9.20 0.07 53 204 35 52 0.47 MAI 2BH 1-1.13 1.25 0.12 53 205 35 52 SAD 2BH

-2.90 53 206 35 52 1.52 SAN 2BH 1-

-0.83

-0.80 0.03 54 207 10 55 3.53 MAN 2BH

-3.39

-3.01 0.38 54 208 10 55 1.21 SAI 2BH 1-1.18 1.28 0.10 54 209 10 55 2.26 SAN 2BH

-0.74

-0.64 0.10 55 210 11 55 MAD 2BH

-2.98 55 211 11 55 2.04 MAI 2BH 1.14 1.30 0.16 55 212 11 55 2.23 MAN 2BH

-0.66

-0.60 0.06 56 213 6

56 1.94 MAI 2BH 1.07 1.24 0.17 56 214 6

56 3.37 MAN 2BH

-3.28

-3.14 0.14 56 215 6

56 2.34 SAN 2BH

-0.89

-0.80 0.09 57 216 11 56 MAD EBH

-13.80 57 217 11 56 0.20 SAI EBH 3.93 4.78 0.85 57 218 11 56 1.24 SAN EBH

-11.37

-11.28 0.09 57 219 11 56 3.31 SAN EBH

-9.40

-9.32 0.08 58 220 1

57 1.38 MAN EBH

-9.15

-9.08 0.07 58 221 1

57 0.95 SAI EBH

-0.03 0.04 0.07 58 222 1

57 0.37 SAN EBH

-13.76

-13.71 0.05 58 223 1

57 0.72 SAN EBH

-11.42

-11.33 0.09 59 224 4

60 MAD EBH

-13.54 59 225 4

60 3.30 MAN EBH

-9.58

-9.36 0.22 59 226 4

60 1.19 SAI EBH 2.04 2.20 0.16 59 227 4

60 2.82 SAN EBH

-11.63

-11.50 0.13 60 228 7

61 MAD EBH

-13.42 60 229 7

61 0.84 MAI EBH 2.07 2.16 0.09 60 230 7

61 3.17 SAN EBH

-11.54

-11.22 0.32 60 231 7

61 3.64 SAN EBH

-9.62

-9.26 0.36 61 232 10 62 FPC EBH 0.30 61 233 10 62 MAD 2BH

-3.50 61 234 10 62 MAD EBH

-14.13 61 235 10 62 0.70 SAI 2BH 1.09 1.21 0.12 61 236 10 62 1.71 SAN 2BH

-0.95

-0.82 0.13 61 237 10 62 1.83 SAN EBH

-11.58

-11.45 0.13 61 238 10 62 0.72 SAN EBH

-9.54

-9.42 0.12 62 239 17 64 2.52 MAN EBH

-9.44

-9.30 0.14 62 240 17 64 0.25 SAI EBH 1.94 2.06 0.12 Page 162 of 169

TABLE 19 STEAM GENERATOR 21 - NEW PLUGS TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 62 241 17 64 0.21 SAN EBH

-13.91

-13.84 0.07 62 242 17 64 1.22 SAN EBH

-11.47

-11.40 0.07 63 243 3

71 0.84 MAI EBH 0.13 0.29 0.16 63 244 3

71 0.96 MAI EBH 2.12 2.24 0.12 63 245 3

71 0.70 MAN EBH

-13.75

-13.59 0.16 63 246 3

71 2.48 MAN EBH

-11.36

-11.23 0.13 63 247 3

71 1.69 SAN EBH

-8.97

-8.91 0.06 64 248 16 91 2.74 45 01C

-0.06 65 249 5

93 4.06 55 0iC

-0.06 Page 163 of 169

TABLE 20 STEAM GENERATOR 22 - NEW PLUGS TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1

1 29 13 0.78 13 01C 0.03 1

2 29 13 3.41 48 02C 0.00 2

3 25 14 12.60 MAI 2BH

-3.07

-1.94 1.13 2

4 25 14 SAD 2BH

-3.58 2

5 25 14 0.43 SAI 2BH 14.89 14.99 0.10 3

6 18 21 SAD 2BH

-3.55 3

7 18 21 SAD 2BH

-1.48 3

8 18 21 0.38 SAI 2BH 1_15 1.22 0.07 4

9 21 24 MAD 2BH

-3.31 4

10 21 24 0.65 MAI 2BH 1.23 1.30 0.07 4

11 21 24 6.68 MAN 2BH

-2.69

-1.84 0.85 5

12 25 24 MAD 2BH

-3.37 5

13 25 24 6.23 MAN 2BH

-2.53

-1.90 0.63 5

14 25 24 0.56 SAI 2BH 1.14 1.24 0.10 5

15 25 24 3.36 SCI 2BH

-2.03

-1.92 0.11 6

16 20 25 SAD 2BH

-2.96 6

17 20 25 2.68 SAI 2BH

-0.81

-0.71 0.10 6

18 20 25 0.62 SAI 2BH 1.16 1.26 0.10 7

19 9

28 SAD 2BH

-2.95 7

20 9

28 2.32 SAN 2BH

-2.75

-2.00 0.75 7

21 9

28 0.29 SAI TSH 0.07 0.45 0.38 8

22 12 28 0.19 SAI TSH 0.22 0.73 0.51 9

23 17 28 MAD 2BH

-3.19 9

24 17 28 SAD 2BH

-2.12 9

25 17 28 1.18 SAI 2BH 1.13 1.32 0.19 10 26 20 29 SAD 2BH

-3.16 10 27 20 29 0.79 SAI 2BH 1.14 1.30 0.16 11 28 11 33 0.20 SCI TRH 19.04 19.24 0.20 12 29 12 35 MAD 1BH

-1.21 12 30 12 35 0.15 SAI 1BH 16.93 17.36 0.43 13 31 13 35 1.71 MAN 2BH

-3.38

-3.01 0.37 13 32 13 35 0.86 MAN 2BH

-0.83

-0.79 0.04 13 33 13 35 0.12 SAI TSH 0.35 0.43 0.08 14 34 19 36 SAD 2BH

-3.32 14 35 19 36 0.70 SAI 2BH 1.15 1.31 0.16 15 36 14 40 SAD EBH

-14.25 15 37 14 40 0.40 SAI EBH 1.30 1.38 0.08 15 38 14 40 0.21 SAN EBH

-11.86

-11.64 0.22 15 39 14 40 2.54 SAN EBH

-9.57

-9.26 0.31 16 40 44 46 TBP 0.00 17 41 13 48 MAD 1BH

-1.06 17 42 13 48 0.23 SAI TSH 0.23 0.48 0.25 18 43 18 48 SAD 2BH

-2.96 18 44 18 48 0.77 SAI 2BH 1.02 1.13 0.11 19 45 21 57 0.09 MAN 2BH

-3.06

-2.91 0.15 19 46 21 57 3.09 MAN 2BH

-0.89

-0.63 0.26 19 47 21 57 0.42 SAI 2BH 1.12 1.23 0.11 20 48 43 57 0.50 24 o1C

-0.19 Page 164 of 169

TABLE 20 STEAM GENERATOR 22 - NEW PLUGS TUBE #

IND #

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 20 49 43 57 0.75 SAN IBH

-1.26

-1.19 0.07 20 50 43 57 2.26 40 NV3 0.00 20 51 43 57 0.62 18 NV4 0.00 21 52 12 66 MAD 2BH

-3.50 21 53 12 66 0.47 SAI 2BH 0.84 1.05 0.21 21 54 12 66 2.32 SAN 2BH

-0.81

-0.70 0.11 22 55 32 67 SAD 1BH

-1.22 22 56 32 67 1.22 23 NV1 0.06 22 57 32 67 1.42 26 NV2 28.54 22 58 32 67 2.35 39 NV2

-0.08 22 59 32 67 2.67 41 NV3

-0.08 22 60 32 67 1.15 24 NV4 0.00 23 61 16 72 SAD 2BH

-3.40 23 62 16 72 0.61 SAI 2BH 1.13 1.20 0.07 23 63 16 72 1.52 SAN 2BH

-0.75

-0.69 0.06 24 64 16 73 MAD 2BH

-3.43 24 65 16 73 5.46 MAN 2BH

-2.53

-1.88 0.65 24 66 16 73 0.38 SAI 2BH 1.19 1.22 0.03 25 67 19 73 0.38 MAI 2BH 1.15 1.29 0.14 25 68 19 73 SAD 2BH

-3.22 25 69 19 73 1.72 SAN 2BH

-0.85

-0.73 0.12 26 70 16 90 2.85 54 01C 0.00 Page 165 of 169

5. Number of tubes plugged or repaired during the inspection outage for each active degradation mechanism, Table 21 provides the number of tubes plugged and repaired during 2R27.

TABLE 21 REPAIRED PLUGGED ARI AR2 ARE MECHANISM SG 21 SG 22 SG 21 SG 22 SG 21 SG22 SG21 SG22 AVB Wear 0

2 0

0 0

0 0

0 Cold Leg Thinning 2

2 0

0 0

0 0

0 ODSCC 9

7*

0 0

0 1

0 0

PWSCC 54 15 146 1151 183 69 14 0

  • Tube R44C46 was classified as TBP for excessive tube noise in the tubesheet crevice region. The resultant noise exhibited itself as two linear ridges at 180 degrees.

The signals had a maximum voltage of 0.40 volts and were in the OD flaw phase plane on the +PointTM coil, but rotated backward (clockwise) with decreasing frequency and were not present in either the 0.115" or 0.080" pancake coils. The tube was treated as ODSCC for tube integrity considerations. The tube noise signal voltage was bounded by numerous previous insitu pressure tests for ODSCC type indications located within the tubesheet crevice, the sludge pile and the freespan.

6. Total number and percentage of tubes plugged or repaired to date, Table 22 provides the total number and percentage of tubes plugged and repaired to date.

TABLE 22 PLUG F*0 F*1 F*2 EF*

S/G SG 21 SG 22 SG 21 SG 22 SG 21 SG 22 SG 21 SG 22 SG 21 SG 22 TOTAL 386 316 174 171 1478 1153 469 236 48 10 PERCENT 11.39% 9.33% 5.14% 5.05% 43.62% 34.03%

13.84% 6.97% 1.42% 0.30%

Page 166 of 169

7. The results of condition monitoring, including the results of tube pulls and in-situ
testing, Condition monitoring and operational assessment evaluations of steam generator tubing at Prairie Island Unit 2 were performed without the need for tube pulls or in-situ pressure testing. The observed severity of degradation at the end of Cycle 26 was evaluated to determine if structural and leakage integrity requirements were maintained. The expected severity of tubing degradation at the end of Cycle 27 was projected to determine if required structural and leakage integrity margins will be maintained during the next cycle of operation. The scope of this evaluation included all forms of observed degradation.

The observed degradation at the EOC 26 outage was evaluated in a manner consistent with NEI 97-06 and EPRI guidance. Observed degradation did not present serious challenges to the deterministic (3AP or 1.4 SLB) structural margin requirement at the end of the previous cycle of operation or challenge required leakage integrity limits under postulated accident conditions. A conservative approach to operational assessment leads to a similar expectation for the next cycle of operation.

Condition monitoring structural and leakage integrity requirements were met for the previous cycle of operation. Operational assessments using both simplified and advanced techniques show that structural and leakage integrity requirements will be maintained over the next operating cycle. These analyses were performed for a cycle length of 1.5 EFPY. The projected steam line break (SLB) leakage at EOC 27 is entirely from degradation left in service according the F* and EF* alternate repair criterion. The projected SLB leakage is 0.42 gpm in SG 21 and 0.30 gpm in SG 22.

8. The effective plugging percentage for all plugging and tube repairs in each SG, There have been no repairs performed on these SGs that affect the heat transfer area; therefore the effective plugging percentage is equivalent to that reported in Table 22.
9. Repair method utilized and the number of tubes repaired by each repair method, and During 2R27 the Technical Specification (T.S.5.5.8.f.2.b) approved repair method of hardroll expanding non-sleeved portions of tubes in the (hot leg) tubesheet in order to apply the F* and EF* criteria was applied. Table 23 summarizes the number of tubes repaired at each elevation during 2R27.

TABLE 23 ELEVATION SG 21 SG 22 1st Repair Location 146 151 2 nd Repair Location 183 70 Elevated Repair Location 14 0

Page 167 of 169

10. The results of inspections performed under Specification 5.5.8. d. 3 for all tubes that have flaws below the F* or EF* distance, and were not plugged. The report shall include: a) identification of F* and EF* tubes, and b) location and extent of degradation.

The inspection results of tubes returned to service using the F* and EF* ARC's were provided in Tables 5 through 18 of item 4 above. Table 24 summarizes the current cumulative number of tubes with the F* and EF* ARC applied and returned to service.

TABLE 24 ELEVATION SG 21 SG 22 F*O 174 171 F*1 1478 1153 F*2 469 236 EF*

48 10 Total 2169 1570 64.02 46.34 Page 168 of 169

LEGEND OF FIELDS AND CODES FIELD TUBE#

IND#

ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH EXPLANATI ON Distinct ROW/COL combination within each Table Distinct ROW/COL/LOCATION combination within each Table Row number of tube location Column number of tube location Measured Voltage Measured percent or three digit code - see below Affected landmark - see below Measurement in inches from the centerline of the landmark to the center of the bobbin coil indication or the lower edge of the rotating coil indication Measurement in inches from the centerline of the landmark to the upper edge of the rotating coil indication Calculated Length (ELEV-TO - ELEV-FROM)

FIELD CODE PERCENT DNT DNI DSI DTI FPC INR IRR MAD MAI MAN MBM MCN MVN NQI PLP PSI SAD SAI SAN SCD SCI SVD SCN SVN TBP 0-100 EXPLANATION Dent Dent with Indication Distorted Support signal with Indication Distorted Tubesheet signal with Indication Failed Profilometry Criteria Indication Not Reportable Inadvertent ReRoll Multiple Axial indications not Detectable Multiple Axial Indications Multiple Axial indications No change Manufacturing Burnish Mark Multiple Circumferential indications No change Multiple Volumetric indications No change Non-Quantifiable Indication Possible Loose Part Possible Support Indication Single Axial indication not Detectable Single Axial Indication Single Axial indications No change Single Circumferential indication not Detectable Single Circumferential Indication Single Volumetric indication not Detectable Single Circumferential indication No change Single Volumetric indication No change To Be Plugged As measured percent through wall LOCATION TEH TRH 1BH 2BH EBH TSH 0?H NV?

0?C TSC TEC Tube end hot (primary face) original Tube Roll Hot leg 1 st additional reroll Bottom roll transition Hot leg 2nd additional reroll Bottom roll transition Hot leg Elevated reroll Bottom roll transition Hot leg Tube sheet hot (secondary face)

? = First through Seventh tube support plate on hot leg side

? = First through Fourth anti-vibration bar

? = First through Seventh tube support plate on cold leg side Tube sheet cold (secondary face)

Tube end cold (primary face)

Page 169 of 169