NL-12-0662, Response to NRC Request for Additional Information (RAI) on License Amendment Request (LAR) for Technical Specification (TS) Table 3.3.1-1 in Response to Westinghouse NSAL 09-01, Rod Withdrawal at Power
| ML12093A138 | |
| Person / Time | |
|---|---|
| Site: | Farley |
| Issue date: | 03/30/2012 |
| From: | Ajluni M Southern Nuclear Operating Co |
| To: | Office of Nuclear Reactor Regulation, Document Control Desk |
| References | |
| NL-12-0662 | |
| Download: ML12093A138 (4) | |
Text
Mark J. Ajluni. P.E.
Southern Nuclear Nuclear Licensing Director Operating Company. Inc.
40 Inverness Center Parkway Pos t Office Box 1295 Birm ingham. Al abama 35201 Tel 205.992.7673 Fax 205.992.7885 March 30, 2012 SOUTHERN '\\'
COMPANY Docket Nos.: 50-348 NL-12-0662 50-364 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Joseph M. Farley Nuclear Plant Response to NRC Request for Additional Information (RAI) on License Amendment Request (LAR) for Technical Specification (TS) Table 3.3.1-1 in Response to Westinghouse NSAL 09-01, Rod Withdrawal at Power Ladies and Gentlemen:
By letter to the U.S. Nuclear Regulatory Commission (NRC) dated September 9, 2011 (Agencywide Documents Access and Management System (ADAMS),
Accession No. rvlL 112521438), Southern Nuclear Operating Company, Inc.,
(SNC) submitted a license amendment request for TS Table 3.3.1-1, "Reactor Trip System Instrumentation," Function 3, "Power Range Neutron Flux High Positive Rate." The change adds Surveillance Requirement 3.3.1.14 which requires verification that the response time is within limits every 18 months on a STAGGERED TEST BASIS.
On December 1, 2011, the NRC provided SNC with a Request for Additional Information (RAI) containing 4 questions regarding the LAR. By letter dated February 3, 2012, SNC responded to the RAI.
On March 8, 2012, the NRC provided SNC with an additional RAI containing one question regarding the LAR. The Enclosure to this letter contains SNC's response to this request.
This letter contains no NRC commitments. If you have any questions, please contact Jack Stringfellow at (205) 992-7037.
U.S. Nuclear Regulatory Commission NL-12-0662 Page 2 Mr. M. J. Ajluni states he is Nuclear Licensing Director of Southern Nuclear Operating Company, is authorized to execute this oath on behalf of Southern Nuclear Operating Company and, to the best of his knowledge and belief, the facts set forth in this letter are true.
Sworn to and subscribed before me this
-II.,
30 day of 01 a I(Ch
,2012.
4~tl.~~
Notary Public My commission expires: /1/s0/! 5 Respectfully submitted, M. J. Ajluni Nuclear Licensing Director MJNDWM/lac
Enclosure:
Response to NRC Request for Additional Information on License Amendment Request for Technical Specification Table 3.3.1-1 in Response to Westinghouse I\\JSAL 09-01, "Rod Withdrawal at Power" cc:
Southern Nuclear Operating Company Mr. S. E. Kuczynski, Chairman, President & CEO Mr. D. G. Bost, Executive Vice President & Chief Nuclear Officer Mr. T. A. Lynch, Vice President - Farley Mr. B. L. Ivey, Vice President - Regulatory Affairs Mr. B. J. Adams, Vice President - Fleet Operations RTYPE: CFA04.054 U. S. Nuclear Regulatory Commission Mr. V. M. McCree, Regional Administrator Mr. R. E. Martin, NRR Project Manager - Farley Mr. E. L. Crowe, Senior Resident Inspector - Farley Alabama Department of Public Health Dr. D. E. Williamson, State Health Officer
Joseph M. Farley Nuclear Plant Response to NRC Request for Additional Information on License Amendment Request for Technical Specification Table 3.3.1-1 in Response to Westinghouse NSAL 09-01, "Rod Withdrawal at Power" Enclosure
Joseph M. Farley Nuclear Plant Response to NRC Request for Additional Information on License Amendment Request for Technical Specification Table 3.3.1-1 in Response to Westinghouse NSAL 09-01, "Rod Withdrawal at Power" RAI1 The staff is requesting information about the bounding allocation time for the PFRT function for Farley, Units 1 and 2. Note that the WCAP-13632-P-A, Revision 2, "Elimination of Pressure Sensor Response Time Testing Requirements," allows users to estimate response time allocation times, using the specific channel card string for the protective function. Please indicate whether that is SNC's practice in this regard. If a different practice or approach is used to derive the allocation time, please include a specific explanation in your response.
SNC Response The allocation times (from WCAP 14036-P-A, Rev. 1 "Elimination of Periodic Channel Response Time Tests"), Table 8-1, are as follows:
NIS PR HIGH FLUX - LO SUM AMP + BISTABLE: 65ms Input + Logic + UV: 20ms NIS PR HIGH FLUX - HI SUM AMP + BISTABLE: 65ms Input + Logic + UV: 20ms These values were previously provided via email to the NRC staff reviewer.
E1-1