NL-10-1021, Unit 1 & 2, Request to Implement Subsequent Edition of ASME OM Code for Class 1 Safety Relief Valves with Auxiliary Actuating Devices

From kanterella
(Redirected from ML103090168)
Jump to navigation Jump to search

Unit 1 & 2, Request to Implement Subsequent Edition of ASME OM Code for Class 1 Safety Relief Valves with Auxiliary Actuating Devices
ML103090168
Person / Time
Site: Hatch  
Issue date: 10/29/2010
From: Ajluni M
Southern Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NL-10-1021
Download: ML103090168 (4)


Text

Mark J. Ajiluni, P.E.

Southern Nuclear Nuclear Licensing Director Operating Company, Inc.

40 Inverness Center Parkway Post Office Box 1295 Birmingham, Alabama 35201 Tel 205.992.7673 Fax 205.992.7885 October 29, 2010 SOUTHERN ZZ COMPANY Docket Nos.: 50-321 NL-10-1021 50-366 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Edwin I. Hatch Nuclear Plant - Unit 1 and Unit 2 Request to Implement Subsequent Edition of ASME OM Code for Class 1 Safety Relief Valves with Auxiliary Actuating Devices Ladies and Gentlemen:

In accordance with 10 CFR 50.55a, "Codes and Standards," paragraph (f)(4)(iv) and the guidance provided in Reference 1, Southern Nuclear Operating Company (SNC) requests NRC approval to use portions of a later edition and addenda of the American Society of Mechanical Engineers (ASME) Code for Operation and Maintenance of Nuclear Power Plants (OM Code) for the Edwin I.

Hatch Nuclear Plant - Unit 1 and Unit 2 (HNP) Inservice Testing (IST) Program.

Specifically, SNC requests approval to use ASME OM Code 2004 Edition, "Inservice Testing of Pressure Relief Devices in Light-Water Reactor Nuclear Power Plants" as part of the Edwin I. Hatch Nuclear Plant - Unit 1 and Unit 2 IST Program for testing of Class 1 Safety Relief Valves with Auxiliary Actuating Devices. The 2004 Edition of the ASME OM Code was incorporated by Reference 2 into 10 CFR 50.55a(b)(3), with no new modifications or limitations.

For HNP, the current code of record is the 2001 ASME OM Code Edition through 2003 Addenda. Table 1 (attached) evaluates the sections that changed between the ASME OM Code 2004 Edition, Mandatory Appendix I and the ASME OM Code 2001 Edition through 2003 Addenda, Mandatory Appendix I for applicability and impact to the Class 1 Safety Relief Valves with Auxiliary Actuating Devices Inservice Testing Program.

The use of the later edition and addenda of the ASME OM Code is requested for the remainder of the fourth 10-year IST interval, which began January 1 st, 2006 and is scheduled to end on December 3 1st, 2015.

-AWU4

U.S. Nuclear Regulatory Commission NL-10-1021 Page 2 The NRC has recently approved similar requests to adopt later editions of the ASME OM Code for IST Programs. These approvals are documented in ADAMS Accession Numbers ML060590178 and ML090770014.

Approval of this proposed revision to the code of record for the Class 1 safety relief valves with auxiliary actuating devises is requested by September 7, 2012.

If you have any questions, please contact Jack Stringfellow at (205)-992-7037.

Respectfully submitted, M. J. Ajiuni Nuclear Licensing Director MJA/PAH/lac

Enclosure:

Mandatory Appendix I Changes from ASME OM Code 2001 Edition with 2003 Addenda and ASME OM Code 2004 Edition for Class 1 Safety Relief Valves with Auxiliary Actuating Devices

References:

1. NRC Regulatory Issue Summary (RIS) 2004-12, "Clarification on Use of Later Editions and Addenda to the ASME OM Code and Section XI,"

dated July 28, 2004

2. Federal Register, 73 FR 52729, dated September 10, 2008 cc:

Southern Nuclear Operatingq Company Mr. J. T. Gasser, Executive Vice President Mr. D. R. Madison, Vice President - Edwin I. Hatch Nuclear Plant Ms. P. M. Marino, Vice President - Engineering RTYPE: CHA02.004 U. S. Nuclear Regqulatory Commission Mr. L. A. Reyes, Regional Administrator Mr. R. E. Martin, NRR Project Manager-Edwin I. Hatch Nuclear Plant Mr. E.D. Morris, Senior Resident Inspector - Edwin I. Hatch Nuclear Plant Mr. P.G. Boyle, NRR Project Manager

Edwin I. Hatch Nuclear Plant - Units 1 and 2 Request to Implement Subsequent Edition of ASME OM Code for Class 1 Safety Relief Valves with Auxiliary Actuating Devices Mandatory Appendix I Changes from ASME OM Code 2001 Edition with 2003 Addenda and ASME OM Code 2004 Edition for Class 1 Safety Relief Valves with Auxiliary Actuating Devices

Table 1 Mandatory Appendix I Changes from ASME OM Code 2001 Edition with 2003 Addenda and ASME OM Code 2004 Edition for Class I Safety Relief Valves with Auxiliary Actuating Devices Section in Mandatory Appendix I with Applicability to Class I Safety Relief Impact to IST Program for Class I Safety Changes between ASME OM Code 2004 Valves with Auxiliary Actuating Relief Valves with Auxiliary Actuating Edition and ASME OM Code 2001 Edition Devices.

Devices.

1-3300 Periodic Testing Not Applicable None 1-3360 Classes 2 and 3 Nonreclosing Pressure Not Applicable None Relief Devices Main disc movement and set-pressure 1-3410 Class 1 Main Steam PRV with Auxiliary Applicable verification are not required following removal Actuating Devices for maintenance.

1-3460 Classes 2 and 3 Nonreclosing Pressure Not Applicable Relief Devices 1-4120 Compressible Fluid Services other than Not Applicable None Steam 1-7370 Classes 2 and 3 Nonreclosing Pressure Not Applicable None Relief Devices