NL-04-0871, Regarding Manual Reactor Trip Following Loss of Main Feedwater Pump Speed Control

From kanterella
(Redirected from 05000424/LER-2004-001)
Jump to navigation Jump to search
Regarding Manual Reactor Trip Following Loss of Main Feedwater Pump Speed Control
ML041470122
Person / Time
Site: Vogtle 
Issue date: 05/22/2004
From: Gasser J
Southern Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NL-04-0871 LER 04-001-00
Download: ML041470122 (5)


Text

Jeffrey T. Gasser Southern Nuclear Vice President Operating Company, Inc.

40 Inverness Center Parkway Post Office Box 1295 Birmingham, Alabama 35201 Tel 205.992.7721 Fax 205.992.0403 SOUTHERN May 22, 2004 COMPANY Energy to Serve Yo ur World Docket No.:

50-424 NL-04-0871 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Vogtle Electric Generating Plant Licensee Event Report 1-2004-001 Manual Reactor Trip Following Loss of Main Feedwater Pump Speed Control Ladies and Gentlemen:

In accordance with the requirements of 10 CFR 50.73, Southern Nuclear Operating Company hereby submits a Vogtle Electric Generating Plant licensee event report for a condition that occurred on March 27, 2004.

If you have any questions, please advise.

Sincerely, Jeffrey T. Gasser JTG/TDH/daj

Enclosures:

LER 1-2004-001 cc:

Southern Nuclear Operating Company Mr. J. B. Beasley, Jr., Executive Vice President Mr. W. F. Kitchens, General Manager - Plant Vogtle Mr. M. Sheibani, Engineering Supervisor - Plant Vogtle RType: CVC7000 U. S. Nuclear Regulatory Commission Mr. L. A. Reyes, Regional Administrator Mr. C. Gratton, NRR Project Manager - Vogtle Mr. J. Zeiler, Senior Resident Inspector - Vogtle

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB NO. 3150-0104 EXPIRES 713112004 (7-2001)

Estimated burden per response to comply with this mandatory Information collection request: 50 hrs. Reported lessons learned are incorporated Into LICENSEE EVENT REPORT (LER) the licensing process and fed back to Industry. Send comments regarding burden estimate to the Records Management Branch (T-6 E6), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by Internet e-(See reverse for required number of mail to bjsl(@nrc.gov, and to the Desk Officer, Office of Information and digits/characters for each block)

Regulatory Affairs, NEOB-10202 (3150-01041, Office of Management and Budget, Washington, DC 20503. If a means used to impose information collection does not display a currently valid OMB control number, the NRC l_

lmay not conduct or sponsor, and a person Is not required to respond to, E

1.

FACILITY NAME

2. DOCKET NUMBER
3. PAGE Vogtle Electric Generating Plant - Unit I J

05000-424 1 OF4

14. TITLE

.i Manual Reactor Trip Following Loss of Main Feedwater Pump Speed Control S. EVENT DATE

6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED MONTH DAY YEAR YEAR SEQUENTIAL REVISION MONTH DAY YEAR FACILITYNAME l

05000 INUMBER NUMBER 50 03 27 2004 2004 001 00 05 22 04 FACILITY NAME DOCKET NUMBER(S)

_ _ _0 5 (0 00 l9. OPERATING 1

1

_1.

THIS REPORIS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR §: {Check all that a I X

MODE 20.2201lb) 20.2203(a)(3)(ii) 50.73(a)(2)(ii)(B) 5 a

i

[0.POWER 3

_5 20.2201(d) 20.2203(a)(4) l 50.73(a)(2)(iii) 50.73(a)(2)(x)

LEVEL POW 20.2203(a)(1) 50.36(c(1l)(i)(A)

X 50.73(a)(2)(iv)(A) l73-71(a)(4) l--

=20.2203(a)(2)(i) l50.36(c)H1)(ii)(A) ll50.73(a)(2)(v)(A) l l73.71(a)(5)

{ -,=20-2203(a)(2)(ii) l50.36(c)(2) 50-73(a)(2)(v)(B) l lOTHER 20-2203(a)(2)(iii) 50.46(a)(3)(ii) l 50.73(a)(2)(v)(C)

Specify in Abstract below 20.2203(a)(2)(iv) 50.73(a)(2)(i)(A) l 50.73(a)(2)(v)(D) or In NRC Form 366A 20.2203(a)(2)(v) 50.73(a)(2)(i)(B) 50.73(a)(2)(vii)

-20.2203(a)(2)(vi) 50.73(a)(2)(i)(C) 50.73(a)(2)(viii)(A) 20.2203(a)(3)(i) 50.73(a)12)(ii)(A) l 50.73(a)(2)(viii)(B)

12. LICENSEE CONTACT FOR THIS LER l NAME lELEPHONE NUMBER (Incude Area Code)

Mehdi Sheibani, Nuclear Safety and Compliance l

(706) 826-3209 l

13. COMPLETE ONE LINE FOR EACH COMPONENT FAILURE DESCRIBED IN THIS REPORT CAUSE SYSTEM COMPONENT MANUFACTURER REPORTABLE CAUSE SYSTEM COMPONENT MANUFACTURER lREORTABLE A

SJ HCU G084 Y

14. SUPPLEMENTAL REPORT EXPECTED i 1,EXPECTED MONTH DAY YEAR YES SUNO SBMISSION (if_ yes com 5 E P C E (If yes, cmplete EXPECTED SUBMISSION DATE)

Jj lO DATE l 16. ABSTRACT (Umit to 1400 spaces, i.e., approximately 15 single-spaced typewritten lines)

On March 27, 2004, at 2110 EST, control room operators tied the generator to the grid. At 2150 EST, an operator observed steam flow/feed flow mismatch alarms and noticed that the speed of the inservice main feed pump, MFP B, was increasing. The feed pump speed control was switched from automatic to manual, but to no effect. Operators then changed speed control systems. This also had no effect on the increasing speed, and steam generator (SG) water levels began to fluctuate. Operators manually tripped the reactor at 2205 EST. The operators then tripped MFP B and the auxiliary feedwater system (AFW) actuated. The unit was stabilized in Mode 3 (Hot Standby) at 2209 EST.

The cause of this event was a control valve hydraulic operating cylinder sticking in the open position so that the speed of the feed pump turbine could not be controlled. The valve stuck open due to misalignment of the hydraulic cylinder shaft with bushings in the cylinder cover. The bushings were properly aligned, the feed pump returned to service, and the reactor returned to normal power operations.

NRC FORM 366A (1-2001)

NRC FORM 366A U.S. NUCLEAR REGULATORY COMMISSION (1-2001)

LICENSEE EVENT REPORT (LER)

TEXT CONTINUATION FACILITY NAME (1)

DOCKET LER NUMBER (6)

PAGE (3)

YEAR SEQUENTIAL RESION YEAR NUMBER Vogtle Electric Generating Plant - Unit 1 05000424 2004 001 00 2 OF 4 TEXT (If more space Is required, use additional copies of NRC Form 366A) ( 17 A. REQUIREMENT FOR REPORT This event is reportable per 10 CFR 50.73 (a)(2)(iv) because an unplanned reactor protection system actuation occurred.

B. UNIT STATUS AT TIME OF EVENT At the time of this event, Unit 1 was in power ascension in Mode 1 (power operations) at 35 percent of rated thermal power. The generator was tied to the grid and the Main Feedwater system was supplying water to all four steam generators. Other than that described herein, there was no inoperable equipment that contributed to the occurrence of this event.

C. DESCRIPTION OF EVENT On March 27, 2004, at 2110 EST, control room operators tied the generator to the grid. At 2150 EST, an operator observed steam flow / feed flow mismatch alarms and noticed that the speed of the inservice main feed pump, MFP B, was increasing. The feed pump speed control was switched from automatic to manual, but to no effect. Operators then changed speed control systems. This also had no effect on the increasing speed, and steam generator (SG) water levels began to fluctuate. Operators manually tripped the reactor at 2205 EST. The operators then tripped MFP B and the auxiliary feedwater system (AFW) actuated. The unit was stabilized in Mode 3 (Hot Standby) at 2209 EST.

D. CAUSE OF EVENT The cause of this event was a control valve hydraulic operating cylinder sticking in the open position so that the speed of the feed pump turbine could not be controlled. The valve stuck open due to misalignment of the hydraulic cylinder shaft with bushings in the cylinder cover. Discussions with vendor personnel determined that a technique exists to ensure the alignment of the upper and lower bushings on the hydraulic cylinder shaft following bushing installation. However, this technique was not utilized in the site instruction for rebuilding the valve. Previously, vendor personnel had been contracted to perform the valve rebuilding. The vendor considered the bushing alignment technique that was used to be a "skill-of-the-craft." More recently, site personnel had begun to perform the valve rebuilding, but the site instruction did not adequately address the necessity for using a bushing alignment technique.

NRC Form 3B6A (1-2001)

NRC FORM 366A U.S. NUCLEAR REGULATORY COMMISSION (1-2001)

LICENSEE EVENT REPORT (LER)

TEXT CONTINUATION FACILITY NAME (1)

DOCKET LER NUMBER (6)

PAGE (3)

YEAR SEQUENTIAL REVISION YEAR NUMBER Vogtle Electric Generating Plant - Unit 1 05000-424 2004 001 00 3 OF 4 TEXT (If more space is required, use additional copies of NRC Form 366A ( 17 A contributing cause of this event was the failure of control room personnel to recognize a higher-than-normal MFP B differential pressure prior to the start of the event. Had this been recognized, the control valve problem may have been diagnosed earlier and MFP B swapped for MFP A.

E. ANALYSIS OF EVENT As the steam flow / feed flow mismatch problem continued, control room personnel acted appropriately to trip the reactor and prevent a challenge to the automatic trip actuation circuitry.

They also performed appropriately in tripping MFP B, which initiated the auxiliary feedwater system actuation, as designed. Based on these considerations, there was no adverse effect on plant safety or on the health and safety of the public as a result of this event.

The event does not represent a safety system functional failure.

F. CORRECTIVE ACTIONS

1) The MFP B control valve hydraulic operating cylinder bushings were properly aligned, the control valve returned to service, and the reactor returned to normal power operations.
2) The valve rebuilding site instruction has been revised to incorporate the proper bushing alignment technique.
3) The Unit 2 MFP control valve hydraulic operating cylinders were assembled utilizing the proper bushing alignment technique. The Unit 1 MFP A control valve hydraulic operating cylinder will be inspected during the Spring 2005 refueling outage.
4) Maintenance and engineering personnel are evaluating the scope and extent of site instruction and procedure development for activities that were previously performed by turbine-generator vendor personnel. The key activities are expected to be identified by June 30, 2004, and a schedule for procedure changes will be developed by December 31, 2004.
5) Licensed operators will review this event in continuing training, emphasizing the importance of maintaining a questioning attitude when abnormal conditions or parameters are encountered.

NRC Form 366A (1-2001)

NRC FORM 366A

,(1-2001)

LICENSEE EVENT REPORT (LER)

TEXT CONTINUATION U.S. NUCLEAR REGULATORY COMMISSION Vogtle Electric Generating Plant - Unit 1 05000-424 11 TEXT (If more space Is required, use additional copies of NRC Form 366A) i17 G. ADDITIONAL INFORMATION

1) Failed Components:

Control valve hydraulic cylinder manufactured by General Electric Corporation, Type DEV631, 6 stage dual inlet turbine, secondary operating cylinder 501E431DY-63.

2) Previous Similar Events:

None

3) Energy Industry Identification System Code:

Main Feedwater System - SJ Auxiliary Feedwater System - BA NRC Fofm 366A 1 -2001)