Title | Secondary Containment Inoperable |
Event Description | At 0910 [CST] on January 30, 2019, the Dresden Station Heater Boiler 'B' tripped while placing the station Heater Boiler 'A' in service. With colder temperatures, the density of the supply air increased and contributed to a greater quantity of air entering the Reactor Building than what was previously being supplied with heating steam in service. The Reactor Building differential pressure (DP) degraded and dropped below 0.25 inches water column vacuum. This condition represents a failure to meet Technical Specification (TS) Surveillance Requirement 3.6.4.1.1. Entry into TS 3.6.4.1 Condition A was made due to Secondary Containment becoming inoperable.
Standby Gas Treatment System was initiated to assist with Reactor Building DP control. Reactor Building DP was restored to greater than 0.25 inches water column vacuum. TS 3.6.4.1 Condition A was exited. This event is being reported under 10 CFR 50.72(b)(3)(v)(C), 'Any event or condition that at the time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to ... control the release of radioactive material.' The NRC Resident Inspector has been notified." |
Where | |
---|---|
Dresden Illinois (NRC Region 3) | |
Reporting | |
10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material | |
Time - Person (Reporting Time:+2.52 h0.105 days <br />0.015 weeks <br />0.00345 months <br />) | |
Opened: | Michael Franzen 17:41 Jan 30, 2019 |
NRC Officer: | Brian P. Smith |
Last Updated: | Jan 30, 2019 |
53851 - NRC Website | |
Unit 2 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
Unit 3 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
WEEKMONTHYEARENS 538512019-01-30T15:10:00030 January 2019 15:10:00
[Table view]10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Secondary Containment Inoperable ENS 525822017-03-01T00:25:0001 March 2017 00:25:00 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Short Duration Loss of Secondary Containment Due to Severe Weather ENS 523552016-11-08T11:10:0008 November 2016 11:10:00 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Reactor Building to Atmosphere Differential Pressure Out of Specifications ENS 517212016-02-10T03:42:00010 February 2016 03:42:00 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Secondary Containment Inoperable ENS 513742015-09-05T15:10:0005 September 2015 15:10:00 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Secondary Containment Inoperable Due to Loss of Vacuum from Open Inspection Hatch ENS 513712015-09-04T13:10:0004 September 2015 13:10:00 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Secondary Containment Inoperable Due to Both Airlock Doors Being Open Simultaneously ENS 499632014-03-27T06:51:00027 March 2014 06:51:00 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Failure of Secondary Containment Door Interlock ENS 495902013-11-28T08:58:00028 November 2013 08:58:00 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Secondary Containment Declared Inoperable While Two Secondary Containment Doors Were Simultaneously Open ENS 495432013-11-16T16:19:00016 November 2013 16:19:00 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Failure of Secondary Containment Interlock Mechanism ENS 495032013-11-05T14:42:0005 November 2013 14:42:00 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Secondary Containment Declared Inoperable Due to Failure of Interlock Mechanism ENS 493792013-09-23T21:55:00023 September 2013 21:55:00 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Both Secondary Containment Access Doors Opened Simultaneously ENS 491532013-06-28T12:49:00028 June 2013 12:49:00 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Door Interlock Malfunction Resulted in Brief Loss of Secondary Containment ENS 475402011-12-21T06:46:00021 December 2011 06:46:00 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Both Unit Two Secondary Containment Doors Were Inadvertently Left Open 2019-01-30T15:10:00 | |