ENS 51604
ENS Event | |
---|---|
05:29 Oct 21, 2015 | |
Title | Diesel Generator Start Due to Invalid Signal |
Event Description | This report is being made per paragraphs 50.73(a)(1) and 50.73(a)(2)(iv)(A) to address an actuation of Emergency Diesel Generator 'A' on October 21, 2015, during the performance of a Diesel Generator Load and Safeguard Sequence Test. The Emergency AC Electrical Power system, including Diesel Generators is a system named in 50.73(a)(2)(iv)(B).
During the performance of the Diesel Generator Load and Safeguard Sequence Test restoration steps a human performance error, while taking resistance readings on a relay, resulted in the unintentional start of the 'A' Emergency Diesel Generator. The testing was aborted and the affected Diesel Generator was restored to standby service in accordance with plant procedures. This is defined as an 'invalid signal' in that the 'A' Diesel Generator did not start as the result of an actual initiating condition. The start signal is considered an INVALID signal with respect to 50.73(a)(2)(iv)(A), however the system was not fully removed from service. The 'B' train was not affected by this event. The actuation signal was considered complete since all necessary components responded as would have been expected if there had been a valid signal. The NRC Resident Inspector was notified. The licensee has determined that shorter test probe tips, when taking resistance readings, are necessary to prevent reoccurrence of this event. |
Where | |
---|---|
Ginna New York (NRC Region 1) | |
Reporting | |
10 CFR 50.73(a)(1), Submit an LER, Invalid Actuation | |
Time - Person (Reporting Time:+1304.05 h54.335 days <br />7.762 weeks <br />1.786 months <br />) | |
Opened: | Thomas Joachimczyk 14:32 Dec 14, 2015 |
NRC Officer: | John Shoemaker |
Last Updated: | Dec 14, 2015 |
51604 - NRC Website | |
Unit 1 | |
---|---|
Reactor critical | Not Critical |
Scram | No |
Before | Cold Shutdown (0 %) |
After | Cold Shutdown (0 %) |
WEEKMONTHYEARENS 556092021-10-17T18:58:00017 October 2021 18:58:00
[Table view]10 CFR 50.73(a)(1), Submit an LER 60 Day Optional Telephonic Notification for Invalid Specified Actuation of Containment Isolation Train ENS 516042015-10-21T05:29:00021 October 2015 05:29:00 10 CFR 50.73(a)(1), Submit an LER Diesel Generator Start Due to Invalid Signal ENS 502312014-05-08T17:20:0008 May 2014 17:20:00 10 CFR 50.73(a)(1), Submit an LER 60-Day Telephonic Notification of Invalid Specified System Actuation ENS 470942011-06-03T04:39:0003 June 2011 04:39:00 10 CFR 50.73(a)(1), Submit an LER Invalid Actuation of Emergency Diesel Generator ENS 469662011-04-25T01:44:00025 April 2011 01:44:00 10 CFR 50.73(a)(1), Submit an LER 60 Day Optional Notification of Invalid Start of Emergency Diesel Generator. ENS 466242010-12-29T05:00:00029 December 2010 05:00:00 10 CFR 50.73(a)(1), Submit an LER Invalid System Actuation Due to Operator Error ENS 443202008-05-10T01:32:00010 May 2008 01:32:00 10 CFR 50.73(a)(1), Submit an LER Invalid Auxiliary Feedwater System Actuation ENS 403322003-10-08T07:16:0008 October 2003 07:16:00 10 CFR 50.73(a)(1), Submit an LER Invalid Safety Injection Signal During Surveillance Testing at Ginna ENS 403312003-09-27T20:44:00027 September 2003 20:44:00 10 CFR 50.73(a)(1), Submit an LER Invalid Partial Safety Injection Signal During Surveillance Testing at Ginna 2021-10-17T18:58:00 | |