ENS 41551
From kanterella
Revision as of 22:21, 1 March 2018 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
ENS Event | |
---|---|
21:00 Mar 30, 2005 | |
Title | Identification of Design and Operating Procedure Deficiencies |
Event Description | The following information was provided by the licensee (licensee text in quotes):
On March 7, 2005, a condition assessment and resolution document was initiated to document several possible design and operating procedure deficiencies affecting Appendix R and Station Blackout (SBO) events. The deficiencies were identified during development of a proposed modification affecting existing Appendix R and SBO power supplies. On March 30, 2005, it was determined that the applicable Appendix R success criteria could not be assured under all of the postulated scenarios described in the Updated Final Safety Analysis Report (UFSAR). Specifically, during the scenarios where Combustion Turbine Generator (CTG) 11-1 (the dedicated Appendix R alternate power source) or other station CTGs are operating in parallel with the grid, availability of the alternate power source under Appendix R and SBO scenarios cannot be assured. Therefore, this event is being reported under 50.72(b)(3)(ii)(B). Actions to address the potentially affected Appendix R and SBO scenarios were put in place on March 7, 2005, when the deficiencies were identified. The NRC Resident Inspector has been notified. |
Where | |
---|---|
Fermi Michigan (NRC Region 3) | |
Reporting | |
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
LER: | 05000341/LER-2005-002 |
Time - Person (Reporting Time:+-2.78 h-0.116 days <br />-0.0165 weeks <br />-0.00381 months <br />) | |
Opened: | Jeff Yeager 18:13 Mar 30, 2005 |
NRC Officer: | Mark Abramovitz |
Last Updated: | Mar 30, 2005 |
41551 - NRC Website | |
Unit 2 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
WEEKMONTHYEARENS 552312021-05-03T13:30:0003 May 2021 13:30:00
[Table view]10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition ENS 537122018-11-01T04:00:0001 November 2018 04:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition En Revision Imported Date 12/31/2018 ENS 536742018-10-19T04:00:00019 October 2018 04:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Low Pressure Core Injection Pumps Incapable of Automatic Startup ENS 527242017-05-02T21:00:0002 May 2017 21:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition for Combustion Turbine Generator Configuration ENS 523422016-11-02T14:34:0002 November 2016 14:34:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition for Control Rod Drop Accident at Low Power ENS 522142016-08-31T23:50:00031 August 2016 23:50:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition with a Potential Tornado ENS 522022016-08-25T20:29:00025 August 2016 20:29:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Mechanical Draft Cooling Tower Declared Inoperable ENS 514402015-10-02T12:25:0002 October 2015 12:25:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Loose Safety Relief Valve Discharge Flange Bolts ENS 422242005-12-23T03:25:00023 December 2005 03:25:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Eecw Temperature Control Valve Not Fully Open ENS 418472005-07-18T02:31:00018 July 2005 02:31:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition of Maintenance Bus Tie Breakers ENS 418162005-06-30T23:31:00030 June 2005 23:31:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Related to the Standby Feedwater Pumps and Control Circuits ENS 417142005-05-18T22:50:00018 May 2005 22:50:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Identification of Design and Operating Procedure Deficiencies Related to Appendix R Events ENS 415512005-03-30T21:00:00030 March 2005 21:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Identification of Design and Operating Procedure Deficiencies 2021-05-03T13:30:00 | |