The objective of the Barrier Integrity cornerstone is to provide reasonable assurance that the physical design barriers protect the public from radionuclide releases caused by accidents. Licensees can reduce the effects of reactor accidents if they do occur by maintaining the integrity of the barriers. The barriers are the fuel cladding, reactor coolant system (RCS) boundary, and the containment.
ROP Process |
---|
| Site | Quarter | Title | Cross cutting aspect | Inspection procedure |
---|
05000387/FIN-2018011-01 | Susquehanna | 2018Q3 | Failure to conduct proper testing of 125 VDC molded case circuit breakers to confirm their design adequacy long-term | P.5 | IP 71152, Problem Identification and Resolution (PI&R) | 05000247/FIN-2018003-03 | Indian Point | 2018Q3 | Containment Fan Cooler 24 Through-Wall Service Water Leak Caused by Inadequate Application of Epoxy Coating Resulting in Corrosion and a Safety System Functional Failure of Containment | H.13 | IP 71152, Problem Identification and Resolution (PI&R) | 05000354/FIN-2018003-03 | Hope Creek | 2018Q3 | inadequate Procedures for Fuel Conditioning Results in Multiple Fuel Leaks | H.6 | IP 71153, Event Followup | 05000341/FIN-2018003-02 | Fermi | 2018Q3 | Failure to Ensure Electrolytic Capacitors Installed in the Plant Did Not Have Expired Shelf Lives | H.7 | IP 71153, Event Followup | 05000247/FIN-2018003-02 | Indian Point | 2018Q3 | Containment Fan Coolers 21 and 24 Motor Cooler Elbow Through-Wall Leaks Due to Excessive Service Water Flow Rates and Safety System Functional Failures of Containment | | IP 71152, Problem Identification and Resolution (PI&R) | 05000352/FIN-2018003-02 | Limerick | 2018Q3 | Failure to Correct Adverse Environmental Conditions Impacting Low Pressure Coolant Injection Outboard Primary Containment Isolation Valve | H.13 | IP 71153, Event Followup | 05000293/FIN-2018003-01 | Pilgrim | 2018Q3 | Failure to Identify an Adverse Condition Associated with Elevated Standby Gas Treatment System Accumulator Leakage | H.9 | IP 71111.19 | 05000247/FIN-2018003-01 | Indian Point | 2018Q3 | Inadequate Procedural Guidance for Spent Fuel Movement and Storage Requirements | H.3 | IP 71152, Problem Identification and Resolution (PI&R) | 05000263/FIN-2018012-01 | Monticello | 2018Q3 | Inboard Main Steam Isolation Valve Closure Time Test Acceptance Criteria Did Not Account for the Design Basis Accident Containment Back Pressure and Pneumatic Supply Operating Pressure | | IP 71111.21M, Design Bases Assurance Inspection | 05000410/FIN-2018002-01 | Nine Mile Point | 2018Q2 | Failure to Ensure Proper Control of the Standby Gas Treatment System Damper Valve, 2GTS*V2000B, Within Procedures, Materials, and Design Control Measures | P.1 | IP 71111.19 |
|
|