U-603676, Day Post-Outage Inservice Inspection (ISI) Summary Report

From kanterella
Jump to navigation Jump to search
Day Post-Outage Inservice Inspection (ISI) Summary Report
ML041590380
Person / Time
Site: Clinton Constellation icon.png
Issue date: 05/27/2004
From: Lliff W
AmerGen Energy Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
C1R09, U-603676
Download: ML041590380 (135)


Text

AmerGen An Exelon Company INSERVICE INSPECTION

SUMMARY

REPORT REPORT DATE: May 14, 2004 INSERVICE DATE: April 24,1987 REFUELING OUTAGE: C1 R09 CLINTON POWER STATION R.R.#3 Box 228, CLINTON, ILLINOIS 61727

Amergen.

An Exelon Company Clinton Power Station R. R.3, Box 228 Clinton, IL 61727 10 CFR 50.55a(g)

U-603676 May 27, 2004 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555-0001 Clinton Power Station, Unit 1 Facility Operating License No. NPF-62 NRC Docket No. 50-461

Subject:

90-Day Post-Outage Inservice Inspection (ISI) Summary Report In accordance with 10 CFR 50.55a, "Codes and standards," paragraph (g), "Inservice inspection requirements," AmerGen Energy Company (AmerGen), LLC is required to maintain an Inservice Inspection Program in accordance with the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code. Please find enclosed the Post-Outage (90-Day) ISI Summary Report for Clinton Power Station for examinations and repair/replacement activities performed between May 7, 2002 (i.e., the Spring 2002 refueling outage) and February 27, 2004 (i.e., the end of the most recent refueling outage).

This report is submitted in accordance with the requirements of ASME Section Xl, Article IWA-6200, Paragraph IWA-6230. This refueling outage was the first outage scheduled of the second inspection period of the second inspection interval. The second inspection interval is from January 1, 2000 to December 31, 2009.

Should you have any questions related to this information, please contact Mr. Jim Peterson at (217) 937-2810.

Respectfully, William S. Iliff Regulatory Assurance Manager.

Clinton Power Station JLP/bIf

  • &LO

U-603676 Page 2 of 2 cc: Regional Administrator - NRC Region III NRC Senior Resident Inspector- Clinton Power Station Office of Nuclear Facility Safety - IEMA Division of Nuclear Safety

INSERVICE INSPECTION

SUMMARY

REPORT CIR09 Prepared by:

_/

Reviewed by: -.' d. . /____- '/

Approved by: r/ D R) L ,/ 6/r o0-Concurred by:

1 .1 I

TABLE OF CONTENTS TITLE SECTION APPROVALS TABLE OF CONTENTS INTRODUCTION AND SCOPE ..................................................... 1 NIS-I CODE DATA REPORT ...................................................... 2 0 ABSTRACT OF EXAMINATIONS LISTING OF EXAMINATION AND TESTING PROCEDURES .................. 3 LISTING OF EXAMINATION AND TESTING PERSONNEL ..................... 4 LISTING OF EQUIPMENT AND MATERIALS ............................................. 5 REPAIR AND REPLACEMENT ...................................................... 6

° LISTING OF REPAIRS/REPLACEMENTS PERFORMED

° NIS-2 DATA REPORTS

Page 1 of 2 SECTION 1 INTRODUCTION AND SCOPE INTRODUCTION:

This Summary Report covers the Inservice Inspection performed at Clinton Power Station (CPS), between May 8, 2002 and February 25, 2004. This is the first inspection performed during the second inspection period of the second ten (1 0)-year interval.

During this Fuel Cycle, CPS experienced four forced outages (CIF37, CIF38, CIF39, and CIF40) and two planned outages(CIM13 and CIR09). All examinations, tests, repairs and replacements were performed in accordance with the CPS Inservice Examination Plan which complies with ASME Section XI, 1989 Edition.

The ASME Section XI examinations, tests and repairs/replacements were witnessed or verified by Authorized Nuclear Inservice Inspector M. Haydon of Hartford Steam Boiler of Connecticut. This summary report contains additional augmented (non-ASME Section XI) inspection results not required to be witnessed or verified by the ANTI.

In accordance with IWA-6220, the name and description of the components examined are listed on the NIS-1 Data Report and its attachments (Section 2). Further component information is obtainable through the reference number, or other information, for the specific item. The manufacturers' names for the components examined are also identified in Item 7 of the NIS-1 Data Report and their addresses are on file at CPS.

Documentation supporting this Summary Report is referenced in the Inservice Examination Plan, implementing procedures, or record files identified in the specific sections of this report.

Scope:

The scope of Inservice Inspection performed during this Fuel Cycle is summarized as follows:

Also, preservice examinations were performed on two (2) piping welds as a result of modification to the RCIC system during CIR09.

  • Scheduled Inservice Examinations - The NIS-I Data Report (Section 2) provides the listing of all examinations completed during CIR09. Conditions noted during ClRO9 and corrective measures taken are described in the NIS-1 Data Report.

Page 2of 2

  • Snubbers - There were 579 snubbers in the 1SI Program required by CPS Operational Requirements Manual (ORM). A representative sample of 59 snubbers (10% of each Type) was selected for functional testing. Two (2) snubbers which were identified in Cl R08 as degraded were also tested for Service Life Monitoring program.

As a result of two (2) snubber failures, additional snubbers were selected for testing.

Overall, there were nine (9) snubbers identified as not meeting the functional test acceptance criteria. A total of one hundred and sixteen (.16) snubbers were tested to meet the CPS ORM requirements. Attachment 2 discusses the details of failure analysis and corrective action taken to address these failures.

CPS implemented 4 modifications (MSFOI2, 341501, 341503, and 341504) eight (8) snubbers (I MS46001 Sj.l MS48003S, I MS48005S, IMS 10602S, I RT28006S, IRT28007S, IRT31004S , and IRT46001S ) were removed permanently from the program. The snubbers population afterthe CIR09 is now 571.

  • Component Supports - Thirty one (31) components supports (other than snubbers) and five (5) Class 3 integral attachments were scheduled for visual examination for Cl R09. All were found acceptable.
  • Pressure Tests - ASME Code Class l Components - A system leakage test and VT-2 inspection of ASME Code Class I components were successfully performed prior to plant startup.
  • Repairs and Replacements - During CIR09 no repairs and replacements were required as a result of scheduled examinations. Also during CIR09, there were several modifications performed. The modifications, as well as repairs and replacements which resulted from routine maintenance, are specifically detailed in Section 6 of this report.

FORM NIS-1 OWN'NER'S REPORT FOR INSERVICE INSPECTION ATTACHMENT I

1. Owner: Amergen Energy Co.. LLC, 965 Chesterbrook Blvd., Wayne. PA 19087
2. Plant: Clinton Power Station, RR3 Box 228. Clinton, IL 61727
3. Plant Unit: 1 4. Owner Certificate of Autherization: N/A
5. Commercial Service Date: 4-24-87 6. National Board Number for Unit: N/A
10. Abstract of Examination:

Listing of Examinations:

Table I lists scheduled examinations of components for CIRO9. The results column in the table provides further explanation for these examinations. Those items, which were examined, that require no further evaluation are identified as acceptable. Table 2 lists those items added to the Cl R09 scope for various reasons and examined. These items require no further evaluation and are identified as acceptable.

Table 3 lists scheduled visual examinations of component supports. The results column in the table provides further explanation for these examinations/tests. Those items, which were examined/tested, that require no further evaluation are identified as acceptable. The visual examination results of all supports were acceptable.:

Table 4 lists visual examinations and functional testing of snubbers. The results column in the table provides further explanation for these examinations/tests. Those items, which were examined/tested, that require no further evaluation are identified as acceptable. The visual examination results of snubbers are identified as acceptable. For those snubbers, which had unacceptable functional tests, the additional snubbers tested are included in this table and discussed further in attachment 2.

Table 5 lists scheduled pressure tests. The results column in the table provides further explanation for these tests.

Current Interval Status:

Currently CPS is in the Second Period of the Second Interval. CPS had two (2) refueling outages, CIR07 and CIR08 during the First Period. CPS will have two (2) refueling outages, CIRO9 and CIROIO, during the Second Period. CPS possibly will have one (1) refueling outage, CIROI 1,during the Third Period. With the exception of the examinations that may be deferred until the end of the inspection interval, the required examinations in each examination category were completed (Inspection Program B).

During the seventh refueling outage (CIR10) two (2) items were identified as requiring relief from NRC. These items are identified as N7 and RHR-A-2. During the eighth refueling outage (CI R08) ten (10) items were identified as requiring relief from NRC. These items are CH-C-2, RPV-C5, N2F, N2G, N3A, N3C, N4A, N4D, NSA, and N9A.

During the ninth refueling outage (CIROI I) one (I) item was identified as requiring relief from NRC. This item is identified as I-MS-A-7PR-WA.

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As Required by the Provisions of the ASME Code Rules

1. Owner Amergen Enervy Co., LLC, 965 Chesterbrook Blvd., Wayne, PA 19087
2. Plant Clinton Power Station, RR3 Box 228, Clinton,IL 61727
3. Plant Unit 1 4. Owner Certificate of Authorization (if required) N/A
5. Commercial Service Date 4/24/1987 6. National Board Number for Unit NIA
7. Components Inspected Component or Manufacturer Manufacturer State National Appurtenance or Installer or Installer Number Board No.

Serial No.

Reactor Vessel 1B13-D003 Chicago Bridge & Iron Co. B5225 B005056 4442 Recirculation Pump 1B33-C0011B- Binaham Willamette Co. 14217102 NIA NB-395 RHR Pump 1E12-C002A Bvron Jackson 741-S-1448 N/A N/A HPCS Pump 1E22-C001 Bvron Jackson 731-S-1186 N/A N/A LPCS Pump 1E21-C001 Bvron Jackson 741-S-1451 N/A N/A RCIC Pump 1E51-C001 Bincham Willamette Co. 16210287 N/A NB550 Valve 1B21-F1011A Anchor/Darling Valve Co. E-6214-154-1 N/A N/A Valve 1l21-F028A Atwood & Morrill Co. 5-562 N/A NIA Valve 1E21 -F007 Anchor/Darling Valve Co. E-6214-7-1 N/A N/A Pipinq Systems Illinois Power Co. See Note 1 N/A N/A Note 1: The piping components examined/tested are listed in Attachment 1 of this NIS-1 Data Report.

Note: Supplemental sheets inform of lists, sketches, or drawings may be used, provided (1) size is 8 1/2 in. x 11 in. (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As Required by the Provisions of the ASME Code Rules

1. Owner Amergen Energy Co., LLC, 965 Chesterbrook Blvd., Wayne, PA 19087
2. Plant Clinton Power Station, RR3 Box 228, Clinton,IL 61727
3. Plant Unit 1 4. Owner Certificate of Authorization (if required) N/A
5. Commercial Service Date 4/24/1987 6. National Board Number for Unit N/A
7. Components Inspected Component or Manufacturer Manufacturer State National Appurtenance or Installer or Installer Number Board No.

Serial No.

Valve 1B21-F028D Atwood &'Morrill Co. 8-562 N/A N/A Valve 1E12-F009 Anchor/Darlinq Valve Co. E-6214-122-1 N/A N/A Valve 1E12-FO41A Anchor/Darling Valve Co. E-6214-20-1 N/A *N/A k i Valve

- - --- A Anchor/uarling Valve Co.

A

- '1b21-t-Ub E-b214-19-1 NIA N/A Valve 1E51-F063 Anchor/Darlinq Valve Co. E-6214-5-1 N/A N/A Valve 1G33F001 Anchor/Darling Valve Co. E-6214-4-1 N/A N/A

FORM NIS-1 (Back)

8. Examination Dates 05/08/02 to 02/25/04 9. Inspection Interval from 01/01/00 to 12/31/09
10. Abstract of Examinations. Include a list of examinations and a statement concerning status of work required for current interval.

See Attachment 1.

.11. Abstract of Conditions Noted.

See Attachment 2.

12. Abstract of Corrective Measures Recommended and taken.

See Attachment 2.

We certify that the statements made in this report are correct and the examinations and corrective measures taken conform to the rules of the ASME Code, Section Xl.

Certificate of Authorization No. (if applicable) N/A Expiration Date N/A Date S;-1 -OL Signed Amergen EnercyCo.. LLC By gr Owner CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler of Connecticut have inspected the components described in this owner's report during the period 05/08/02 to 02/25/04, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this owner's Report in accordance with the inspection plan and as required by the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, Expressed Or implied, concerning the examinations and corrective measures described in Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any Manner for any personal injury or property damage or a loss of any kind arising from or th this inspection.

5 i inCommissions M /09I A 1e ri 1 Inspector's Signature National Board, state, province, and endorsements Date K)

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTION ATTACHIMENT I TABLE I

1. Owner: Amergen Co., LLC, 965 Chesterbrook Blvd., Wayne, PA 19087
2. Plant: Clinton Power Station, RR3 Box 228, Clinton, IL 61727
3. Plant Uni: 1 4. Owner Certificate of Autherization: N/A
5. Commercial Service Date: 4-24-87 6. National Board Number for Unit: N/A
10. Abstract of Examinations: Listing of Scheduled Examinations.

REFERENCE j ITEM EXAM CODE CODE CODE RESULTS NUMBER IDENTIFICATION TYPE ITEM CATEGORY CLASS 008100 VESSEL INTERIOR VT-3 3B13.10 B-N-I I ACCEPTABLE 008249 STEAM DRYR (TOP 1/2) VT-3 N/A N/A I ACCEPTABLE 008250 STEAM DRYR (BOT 1/2) VT-3 N/A N/A I SEE NOTE I &2 008252 SHROUD SUP ACC HOLE VT-3 N/A N/A I ACCEPTABLE 008253 STEAM SEP (1/2) VT-3 N/A N/A I lSEE NOTE 3 008451 CORESPRAY INT PIPING UT EVT-I N/A N/A I EE NOTE 4 008455 STM DRYR SUP BRCKTS EVT-I 3B13.21 B-N-2 i I CCEPTABLE SEE NOTE 5 008555 RPV SP BRCKT ATT. VT-I _B 13.20 B-N-2 I ACCEPTABLE SEE NOTE 6 008650 CORE SUP STRUC. ONLY VT-3 13B13.22 B-N-2 l_I __CCEPTABLE TOP GUIDE 008651 H9 UT N/A N/A I ACCEPTABLE 008711 ~ CORE SPRAY SPARGRS EVT-I N/A N/A I ACCEPTABLE 008712 IRMISRM (8) VT-I N/A N/A . ACCEPTABLE SEE NOTE 7 009200 CII-MC UT _ Bl.22 B-A I ACCEPTABLE 009250 CI-MD UT Bl.22 B-A I ACCEPTABLE 100260 1-MS-A-4/1-RI-04A UT-E RI.20 R-A I CCEPTABLE 100680 1-MS-A-7PR-WA PT 3B10.10 B-K-I I CCEPTABLE SEE NOTE 8 103020 I-MS-BSC-I-FB VT-I B7.50 B-G-2 l I ACCEPTABLE 106540 I-MS-D-6/DSC UT-E Rl.20 R-A I IACCEPTABLE 111700 I-FW-1-6QI UT-E RI.ll R-A I IACCEPTABLE 112460 1-FW-2-5-3 UT-E RI.] I R-A I [ACCEPTABLE 112840 I-FW-1-3-8 UT-E Rl.Il R-A I ACCEPTABLE 135200 -- RR-A-7/IRTOIEB4" UT-E __ Rl.20 R-A I ACCEPTABLE 135400 1-RR-A-10,'DRW UT-E _ Rl.20 R-A I IACCEPTABLE 137240 lI-RR-B-9/CRW UT-E RI.20 R-A I ACCEPTABLE 151060 Il-H1P-5-2-2 UT-E RI.20 R-A I ACCEPTABLE 180240 I-RI-13-8 UT-E _Rl.ll R-A I ACCEPTABLE 180260 1-MC42-A MT 3B10.10 B-K-I I ACCEPTABLE 180960 1-RI-144-2FB VT-I B7.50 B-G-2 I ACCEPTABLE 181040 I-RI-14-5-3QI UT-E RI.ll R-A I ACCEPTABLE 230040 IB21-FOIIA VT-I B7.70 B-G-2 I ACCEPTABLE 230160 IB21-F028A VT-I B7.70 B-G-2 I . I IACCEPTABLE 231000 1E21-F007 VT-I _ B7.70 B-G-2 I I IACCEPTABLE 560565 I-HPO3009RVA MT C3.20 l C-C 2 IACCEPTABLE 576760 1-RII-17-16 MT C3.20 C-C 2 ACCEPTABLE 582980 I-RH-09013R-U'A MT C3.20 C-C 2 lACCEPTABLE 594940 1-RH-14-13-2 UT-E RIl.I R-A 2 JACCEPTABLE 594960 RH1-R-14-23 UT-E RllRII R-A 2 lACCEPTABLE

FORM NIS-1 OWNER'S REPORT FOR INSERV'ICE INSPECTION ATTACHMENT I TABLE I

1. Owner: Amergen Co., LLC, 965 Chesterbrook Blvd., Wayne, PA 19087
2. Plant: Clinton Power Station, RR3 Box 228, Clinton, IL 61727
3. Plant Uni: 1 4. Owner Certificate of Autherization: N/A
5. Commercial Service Date: 4-24-87 6. National Board Number for Unit: N/A
10. Abstract of Examinations: Listing of Scheduled Examinations.

REFERENCE ITEM EXAM CODE CODE CODE RESULTS NUMBER IDENTIFICATION TYPE ITEM CATEGORY CLASS 595000 1-RII-14-30 MT C3.20 C-C 2 kCCEPTABLE 595020 I1-RI.-14-24 UT-E RI.11 R-A 2 JACCEPTABLE 800140 RHR-A-3 MT C6.10 C-G 2 ACCEPTABLE 801540 LPCS-3 MT C6.1 0 C-G 1 2 IACCEPTAB3LE 802540 HPCS-3 MT C6.10 C-G 2 ACCEPTABLE 803100 HRCSC-3 MT C6.10 C-G 2 ACCEPTABLE 803200 IRCIC-2 MT C6.10 C-G 2 ACCEPTABLE 942230 lRSX1400IA-WA VT-3 D2.20 D-B 3 ACCEPTABLE 942620 942745 JSX20002A-WA IISX20008A-WA VT-3 VT-3 D2.20 D2.20 I D-B D-B3 3

3 ACCEPTABLE 9432750 ISX2400A-WA VT-3 D2.20 D-B 3 A_____________

CCEPTABLE 943250 ISX24001 A-WA VT-3 D2.20 D-B . _3_IACCEPTABLE 945145 ISX22009A-WA VT-3 D2.20 D-B 3 IACCEPTABLE 950606 JP RI BR WELDED ATT (50%) EVT-I B13.20 B-N-2 _ I___CCEPTABLE 950607 JP RISER WELDS (50%) EVT-I N/A IN/A11ACCEPTABLE VARIOUS 950608 JP DIFFUSER WELDS 100% EVT-I N/A NCCEPTABLE N/A I 950609 JiP SENSING LINES (50%/O) VT-I N/A N/A I ACCEFTABLE 950660 ILPCI 3 WELDS EVT-I N/A N/A I ACCEPTABLE 951001 TVARIOUS CRDM VT-3 N/A N/A I [ACCEPTABLE

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTION ATTACHMENT I TABLE I Notes

1. Owner: Amergen Energy Co.. LLC. 965 Chesterbrook Blvd.. Wayne, PA 19087
2. Plant: Clinton Power Station, RR3 Box 228, Clinton, IL 61727
3. Plant Unit: I 4. Owner Certificate of Autherization: N/A
5. Commercial Service Date: 4-24-87 6. National Board Number for Unit: N/A
10. Abstract of Examinations: Listing of Scheduled Examinations Note 1:

Steam Dryer - The existing crack on the steam dryer channel #8 to the skirt was examined and determined that it has grown 1 1/8 inches in one cycle. This is not an ASME Section XI item. See attachment 2 for further discussion.

Note 2:

Steam Dryer -- The steam dryer was examined per GE SIL # 644, Supplement 1. During this examination of the dryer's lower guide at zero degrees, it was observed that the lower left horizontal stiffener was found with mechanical deformation. This is not an ASME Section XI item. See attachment 2 for further details.

Note 3:

Steam Separator - During the separator examination of the lower guide at zero degrees, it was observed that the lower left outside corners were found with mechanical deformation. This is not an ASME Section XI item. See attachment 2 for further details.

Note 4:

Core Spray Internal piping - In accordance with BWR VIP-I 8 document, Ultrasonic examinations were performed on the selected welds on Core Spray piping. Indications were recorded on three (3) of these welds (BP2, CP2, and DP2). This is not an ASME Section XI item.

See Attachment 2 for further discussion.

Note 5:

Steam Dryer Support Bracket - Several of the brackets appear to have Contact mark and some do not have any contact marks with the steam dryer. This is not an ASME Section XI item. See attachment 2 for further discussion.

Note 6:

Surveillance Specimen Brackets @ 003 and 177 degrees - During the examination of the surveillance specimen brackets ( 003 and 177 degrees, both lower tack welds on the attachment bracket were observed to be cracked. This is located outside the Section XI examination boundary.

See attachment 2 for further details.

Note 7:

IRM/SRM - The dry tubes (IRM/SRM) were examined per GE SIL: 409. During this examination dry tube 38-35, SRM 'D', linear indications were noted above the tube to primary pressure boundary fillet weld, on the non-pressure boundary side. The indications have both horizontal and vertical components. This is not an ASME Section XI item. See attachment 2 for details.

Note 8:

I-MS-A-7PR-WA (Reference Number 100680) -- Portions of weld 1-MS-A-7PR-WA were not examined due to interference with the component support (main steam guide support). A relief request will be submitted to request relief from examining 100% of the examination volume. This relief request will include all four (4) main steam guide supports, one on each of the four (4) main steam piping lines.

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTION ATTACIIN1ENT I TABLE 2

1. Owner: Amergen Co., LLC, 965 Chesterbrook Blvd., Wayne, PA 19087
2. Plant: Clinton Power Station, RR3 Box 228, Clinton, IL 61727
3. Plant Uni: 1 4. Owner Certificate ofAutherization: N/A
5. Commercial Service Date: 4-24-87 6. National Board Number for Unit: N/A
10. Abstract of Examinations: Listing of Substitited and Additional Examinations.

REFERENCE ITEM EXAM CODE CODE CODE RESULTS NUMBER IDENTIFICATION TYPE ITEM CATEGORY CLASS 200510 RR PUMP B'FLANGE VT-1 I B6.190 B-G-1 I ACCEPTABLE SURFACE 200620 RR PUMP 'B'PUMPCAS INT VT-3 lBI2.20l B-L-2 I IACCEPTABLE

_SURF 250220 IB21-FO28D VT-3 1Bl2.50 B-M-2 I CCEPTABLE 250740 1EI2-FOO9 VT-3 B12.50 B-M-2 I ACCEPTABLE 250840 IEI2-FO41A VT-3 B12.50 B-M-2 I ACCEPTABLE 250980 IE21-F006 VT-3 1Bl2.50 B-M-2 I ACCEPTABLE 251100 IE51-FO63 VT-3 B12.50 B-M-2 I ACCEPTABLE 251140 IG33-FOOI VT-3 I_ _B12.50 B-M2 I ACCEPTABLE

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTION ATTACIIMENT I TABLE 3

1. Owner: Amergen Co., LLC, 965 Chesterbrook Blvd., Wayne, PA 19087
2. Plant: Clinton Power Station, RR3 Box 228, Clinton, IL 61727
3. Plant Uni: 1 4. Owner Certificate of Autherization: N/A
5. Commercial Service Date: 4-24-87 6. National Board Number for Unit: N/A
10. Abstract of Examinations: Listing of Scheduled Examinations.

REFERENCE ITEM EXAM CODE CODE CODE RESULTS NUMBER IDENTIFICATION TYPE ITEM CATEGORY ICLASS 903710 IFWO2014G VT-3 FI.0 F-A I ACCEPTABLE 906140 II]PO3002R VT-3 FL.20 F-A l 2 ACCEPTABLE 908000 ILPOIO0IC VT-3 F.10 l F-A I (ACCEPTABLE 908305 I LPO4002X VT-3 F1.20 I F-A 2 IACCEPTABLE 909150 1HIO1C(A) VT-3 lFI.10 l F-A I [ACCEPTABLE 912200 1RIIO6007R VT-3 F1.10 F-A I IACCEPTABLE 913265 IRH07002X VT-3 FL.20 F-A [ 2 ACCEPTABLE 913525 IRHO7085C VT-3 FL.20 F-A 2 ACCEPTABLE 913898 IRH IIOO5R VT-3 FF.20 I F-A _2_ ACCEPTABLE 913975 I1RI109017V VT-3 FL.20 F-A I _2 ACCEPTABLE 914205 1RH109052X VT-3 FL.20 I F-A 2 ACCEPTABLE 916695 11RHO7068X VT-3 FL.20 F-A 2 [ACCEPTABLE 919005 IRIIO00OIA VT-3 FI. O F-A I JACCEPTABLE 919100 IIRIOIOOIC VT-3 FI.10 F-A I ACCEPTABLE 920270 1RIO8003R VT-3 F1.20 F-A 2 ACCEPTABLE 921330 ISD90-SPI3 VT-3 F1.20 F-A 2 ACCEPTABLE 922000 IB301A VT-3 F1.40 I F-A I ACCEPTABLE 922545 111356B VT-3 FII0 F-A 1I ACCEPTABLE 923030 IIRTOIO7R VT-3 FI.0 F-A I [ACCEPTABLE 940705 11SX01003R VT-3 Fl.30 F-A l3 ACCEPTABLE 941365 IISXOIO41X VT-3 FL.30 F-A l3 ACCEPTABLE 941750 IISXO2005R VT-3 FL.30 F-A 3 ACCEPTABLE 941770 ISX02006X VT-3 FL.30 F-A I 3 ACCEPTABLE 941910 11SX02013X VT-3 F.30 F-A 1 3 1ACCEPTABLE 942225 ;ISX14001A VT-3 FL.30 F-A 1 3 IACCEPTABLE 942615 lISX20002A VT-3 Fl.30 F-A I 3 IACCEPTABLE 942740 ISX20008A VT-3 Fl.30 F-A 3 IACCEPTABLE 942945 ISXI00O9X VT-3 Fl.30 F-A I 3 IACCEPTABLE 943245 ISX24001A VT-3 F1.30 F-A l3 A CCEPTABLE 944740 ISX16012R VT-3 FL.30 F-A !3 A CCEPTABLE 945140 1SX22009A VT-3 ___FI.30 F-A l 3 CCEPTABLE

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTION ATTACHMENT I TABLE 4

1. Owner: Amergen Co., LLC, 965 Chesterbrook Blvd., Wayne, PA 19087
2. Plant: Clinton Power Station, RR3 box 228, Clinton, IL 61727
3. Plant Uni: 1 4. Owner Certificate ofAutherization: N/A
5. Commercial Service Date: 4-24-87 6. National Board Number for Unit: N/A
10. Abstract of Examinations: Listing of Scheduled Examinations.

REFERENCE ITEM EXAM CODE CODE CODE RESULTS NUMBER IDENTIFICATION TYPE ITEM CATEGORY CLASS 903775 1FW0I006S VT-3 FT F1.10 F-A I ACCEPTABLE 903795 I FW0201OS VT-3 FT F1.10 F-A I ACCEPTABLE 909274 IMS05022S VT-3 FT NIA N/A I ACCEPTABLE 909281 IMS38005S VT-3 FT NIA N/A I ACCEPTABLE 906030 IMS38028S VT-3 FT /A N/A I FT UNACCEPTABLE 909282 IMS38097S VT-3 FT /A N/A I ACCEPTABLE 912110 1RHI04058S VT-3 FT Fl.10 F-A I ACCEPTABLE 919135 IRIOI008S VT-3 FT 1Fl.10 F-A I ACCEPTABLE 919155 IR10I012W VT-3 FT Fl.10 F-A I ACCEPTABLE 919280 1RI1 8002S VT-3 FT N/A N/A I ACCEPTABLE 922620 IIS369B VT-3 FT F1.10 F-A I ACCEPTABLE 922630 IS371B VT-3 FT F.10 F-A I ACCEPTABLE 922645 IIS374B VT-3 FT F1.0l F-A I I ACCEPTABLE 922650 ilS375B VT-3 FT F1.10 F-A I ACCEPTABLE 906640 l11-HP03013S-DN VT-3 FT N/A N/A 2 ACCEPTABLE 906660 l111-1P03013S-UP V-3 FT N/A N/A 2 ACCEPTABLE 906220 111 `P03029S VT-3 FT Fl.20 F-A 2 ACCEPTABLE 906680 ItIP03049S VT-3 FT N/A NIA 2 ACCEPTABLE 903888 111P04003S VT-3 FT N/A N/A 2 ACCEPTABLE 903890 IIOPW4016S-E VT-3 FT N/A N/A 2 ACCEPTABLE 903892 IH P04016S-W VT-3 FT N/A N/A 2 ACCEPTABLE 906260 111P08004S VT-3 FT N/A N/A 2 ACCEPTABLE 906702 IIS01007S VT-3 FT N/A I NIA 2 ACCEPTABLE 906704 IIS01009S VT-3 FT I/A I N/A 2 l ACCEPTABLE 906718 11S01014S VT-3 FT N/A f N/A 2 l ACCEPTABLE 906720 I[IS01016S VT-3 FT N/A NIA 2 ACCEPTABLE 906694 I[IS01020S VT-3 FT N/A NIA 2 ACCEPTABLE 906696 I1IS01022S VT-3 FT NIA N/A 2 ACCEPTABLE 906710 111S01027S VT-3 FT NIA N/A 2 ACCEPTABLE 906712 IIIS01029S VT-3 FT NIA N/A 2 ACCEPTABLE 906706 IIS01033S VT-3 FT /NA N/A 2 ACCEPTABLE 906700 11S01048S VT-3 FT N/A N/A 2 ACCEPTABLE 906716 111S01055S VT-3 FT N/A N/A 2 ACCEPTABLE 906746 IIS01074S VT-3 FT N/A N/A 2 ACCEPTABLE 906748 11S01075S VT-3 FT /A N/A 2 ACCEPTABLE 906754 I LP03015S VT-3 FT NlA N/A 2 ACCEPTABLE 906756 ILP03016S VT-3 FT VA/A NIA 2 ACCEPTABLE

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTION ATTACIIMENT I TABLE 4

1. Owner: Amergen Co., LLC, 965 Chesterbrook Blvd., Wayne, PA 19087
2. Plant: Clinton Power Station, RR3 box 228, Clinton, IL 61727
3. Plant Uni: 1 4. Owner Certificate of Autherization: N/A
5. Commercial Service Date: 4-24-87 6. National Board Number for Unit: N/A
10. Abstract of Examinations: Listing of Scheduled Examinations.

REFERENCE ITEM EXAM CODE CODE CODE RESULTS NUMBER IDENTIFICATION TYPE ITEM CATEGORY CLASS 909370 IMS38027S VT-3 FT N/A N/A 2 ACCEPTABLE 909394 IMS38072S VT-3 FT N/A N/A 2 ACCEPTABLE 909376 IMS38093S VT-3 FT N/A N/A 2 FT UNACCEPTABLE 909372 1IMS38094S VT-3 FT NIA N/A 2 ACCEPTABLE 909378 IMS38095S VT-3 FT N/A N/A 2 ACCEPTABLE 909374 IIMS38096S VT-3 FT N/A I N/A 2 ACCEPTABLE 909384 IMS46001S VT-3 FT lN/A N/A 2 ACCEPTABLE 909390 IMS48003S VT-3 FT /A N/A 2 ACCEPTABLE 909392 IMS48005S VT-3 FT N/A N/A 2 ACCEPTABLE 909358 I1RB21595S VT-3 FT N/A N/A 2 ACCEPTABLE 909338 IRB21596S VT-3 FT N/A N/A 2 FT UNACCEPTABLE 909334 IRB21599S VT-3 FT N/A N/A 2 ACCEPTABLE 909362 1RB24566S VT-3 FT N/A N/A 2 ACCEPTABLE 909366 1RB24568S VT-3 FT N/A NA 2 1 ACCEPTABLE 909368 IRB24575S VT-3 FT NIA N/A 2 FT UNACCEPTABLE 909342 IRB24576S VT-3 FT N/A I N/A 2 ACCEPTABLE 915555 lIRIIO8017S VT-3 FT FL.20 F-A 2 ACCEPTABLE 913355 IIRHO8024S VT-3 FT Fl.20 I F-A 2 ACCEPTABLE 914910 IRHO8047S VT-3 FT FL.20 F-A 2 ACCEPTABLE 914935 IRF108059S VT-3 FT 1F1.20 F-A 2 ACCEPTABLE 913635 1RHO8076S VT-3 FT 1Fl.20 F-A 2 ACCEPTABLE 916500 lIRH108098S VT-3 FT N/A N/A 2 ACCEPTABLE 914210 lRHO9053S VT-3 FT F1.20 F-A 2 ACCEPTABLE 914215 lIRIIO9054S VT-3 FT F1.20 F-A 2 ACCEPTABLE 914220 1RHO9055S VT-3 FT Fl.20 F-A 2 ACCEPTABLE 913906 IRI-1IOIIS VT-3 FT Fl.20 F-A 2 ACCEPTABLE 915940 IRH6201 IS VT-3 FT N/A N/A 2 ACCEPTABLE 917790 IRH173002S VT-3 FT N/A N/A 2 ACCEPTABLE 917780 1RH82002S VT-3 FT NA N/A 2 ACCEPTABLE 921025 1IR102008S VT-3 FT F1.20 F-A 2 ACCEPTABLE 921030 1IR02009S VT-3 FT 1.20 F-A 2 ACCEPTABLE 920400 R102016S VT-3 FT /A N/A 2 ACCEPTABLE 920460 1IR103013S VT-3 FT F.20 F-A 2 ACCEPTABLE 920950 1Rl21006S VT-3 FT N/A N/A 2 ACCEPTABLE 909410 ICCO7055S VT-3 FT N/A N/A 3 ACCEPTABLE 909520 IFC03076S-E VT-3 FT N/A N/A 3 ACCEPTABLE 909540 I FC03076S-W VT-3 FT IN/A N/A 3 l ACCEPTABLE

FORM NIS-1 ONNNER9S REPORT FOR INSERV'ICE INSPECTION ATTACIIMENT I TABLE 4

1. Owner: Amergen Co., LLC, 965 Chesterbrook Blvd., Wayne, PA 19087
2. Plant: Clinton Power Station, RR3 box 228, Clinton, IL 61727
3. Plant Uni: 1 4. Owner Certificate of Autherization: N/A
5. Commercial Service Date: 4-24-87 6. National Board Number for Unit: N/A
10. Abstract of Examinations: Listing of Scheduled Examinations.

REFERENCE ITEM EXAM CODE CODE CODE RESULTS NUMBER IDENTIFICATION TYPE ITEM CATEGORY CLASS 909560 1FC03081S VT-3 FT N/A N/A 3 FT UNACCEPTABLE 911280 IMS10705S VT-3 FT IN/A N/A 3 FT UNACCEPTABLE 911265 IMSIO808S VT-3 FT N/A N/A 3 FT UNACCEPTABLE 911290 IMSIO907S VT-3 FT N/A N/A 3 ACCEPTABLE 911295 IMS10909S VT-3 FT N/A N/A 3 FT UNACCEPTABLE 911300 IMSIO910S VT-3 FT N/A N/A 3 FT UNACCEPTABLE 911270 IMSIIIO6S VT-3 FT N/A N/A 3 1 ACCEPTABLE 911275 IMS11108S VT-3 FT N/A N/A 3 ACCEPTABLE 910540 IMS24010S VT-3 FT F1.30 I F-A 3 ACCEPTABLE 910170 IMS26009S VT-3 FT F1.30 F-A 3 ACCEPTABLE 910175 IMS26010S VT-3 FT F1.30 F-A 3 ACCEPTABLE 910930 IMS29007S VT-3 FT F1.30 I F-A 3 ACCEPTABLE 910940 jIMS29009S VT-3 FT F1.30 l F-A 3 ACCEPTABLE 911050 1IMS30001S VT-3 FT F1.30 I F-A 3 1 ACCEPTABLE 911110 lIMS30013S VT-3 FT F1.30 F-A 3 l ACCEPTABLE 909460 lIRHO9082S VT-3 FT N/A N/A 3 1 ACCEPTABLE 909480 jiRHO909OS-E VT-3 FT N/A N/A 3 ACCEPTABLE 909500 IIRHO9090S-W VT-3 FT NIA N/A 3 ACCEPTABLE 924060 11RT06018S VT-3 FT N/A N/A 3 ACCEPTABLE 941185 jISXOIO32S VT-3 FT F1.30 F-A 3 ACCEPTABLE 947200 IISXI7016S VT-3 FT N/A N/A 3 ACCEPTABLE 942785 I]SX20010S VT-3 FT F1.30 F-A 3 ACCEPTABLE 945095 !ISX22007S VT-3 FT F1.30 F-A I 3 ACCEPTABLE 945205 IISX22012S VT-3 FT F1.30 F-A 3 ACCEPTABLE 948160 IMS07012S VT-3 FT N/A N/A l D ACCEPTABLE 948200 IMSO7030S VT-3 FT N/A N/A D ACCEPTABLE 948940 IRHI5017S VT-3 FT N/A N/A D ACCEPTABLE 948920 IRIII8006S VT-3 FT N/A N/A D ACCEPTABLE 947540 IR1123018S VT-3 FT N/A N/A D ACCEPTABLE 903864 1DG04002S VT-3 FT N/A N/A 0 ACCEPTABLE 903866 IDG04OI7S VT-3 FT N/A N/A 0 ACCEPTABLE 949280 IVGOIOO5S VT-3 FT N/A N/A 0 ACCEPTABLE 949220 IVG02019S VT-3 FT N/A N/A 0 ACCEPTABLE 949240 IVGO2020S VT-3 FT /A N/A 0 ACCEPTABLE 948980 IVGO3002S VT-3 FT /A N/A 0 ACCEPTABLE 949060 IVGO3025S VT-3 FT JN/A N/A 0 ACCEPTABLE 949080 IVGI 1025S VT-3 FTJ N/A N/A 0 ACCEPTABLE

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTION AlTACHIMENT I TABLE 4

1. Owner: Amergen Co., LLC, 965 Chesterbrook Blvd., Wayne, PA 19087
2. Plant: Clinton Power Station, RR3 box 228, Clinton, IL 61727
3. Plant Uni: 1 4. Owner Certificate of Autherization: N/A
5. Commercial Service Date: 4-24-87 6. National Board Number for Unit: N/A
10. Abstract of Examinations: Listing of Scheduled Examinations.

REFERENCE ITEM EXAM CODE CODE CODE RESULTS NUMBER IDENTIFICATION TYPE ITEM CATEGORY CLASS 949260 IVG1 1041 S VT-3 F A N/A ____ ACCEPTABLE 949460 IVQ05032S VT-3 F IN/A N/A _ ACCEPTABLE 949480 IVRO4002S VT-3 F A J N/A 0 ACCEPTABLE 949500 IVRO4003S-N VT-3 A N/A 0 1 ACCEPTABLE 949520 IVRO4003S-S FN/A AVT-3 1N0 1 I ACCEPTABLE

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTION ATTACHMENT 1 TABLE 5

1. Owner: Amergen Energy Co., LLC, 965 Chesterbrook Blvd., Wayne, PA 19087
2. Plant: Clinton Power Station, RR3 Box 228, Clinton, IL 61727
3. Plant Unit: 1 4. Owner Certificate of Authorization: N/A
5. Commercial Service Date: 4-24-87 6. National Board Number for Unit: N/A
10. Abstract of Examinations: Listing of Scheduled Pressure Tests ITEM EXAM CODE CODE CODE RESULTS IDENTIFICATION TYPE ITEM CATEGORY CLASS ALL CLASS 1 COMPONENTS VT-2 B15.10,50,60,70 B-P 1 ACCEPTABLE, SEE NOTE 1

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTION ATTACHMENT I TABLE 5 Notes

1. Owner: Amergen Energy Co., LLC, 965 Chesterbrook Blvd., Wayne, PA 19087
2. Plant: Clinton Power Station, RR3 Box 228, Clinton, IL 61727
3. Plant Unit: I 4. Owner Certificate of Autherization: N/A
5. Commercial Service Date: 4-24-87 6. National Board Number for Unit: N/A
10. Abstract of Examinations: Listing of Scheduled Examinations Note 1: Pressure Tests Class I Components A system leakage test and VT-2 inspection of ASME Class I components was performed prior to Plant startup.

Condition noted: Only minor leakage from valve packing and bolted flanged connections was noted.

Corrective measures: Leakage was corrected to acceptable levels.

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTION ATTACHMENT 2

1. Owner: AmerGen Energy Co., LLC, 965 Chesterbrook Blvd., Wayne, PA 19087
2. Plant: Clinton Power Station, RR3 Box 228, Clinton, IL 61727
3. Plant Unit: 1 4. Owner Certificate of Authorization: N/A
5. Commercial Service Date: 4-24-87 6. National Board Number for Unit: N/A
10. Abstract of Examinations:

Examinations:

Steam Dryer -

Clinton Power station has examined the steam dryer in accordance with General Electric SIL Numbers 474 and 644, Supplement 1. During CIROl in 1989 a crack was identified in the drain channel number 8 to the skirt. The length of the crack was 7 5/8 inches. Clinton Power Station evaluated this crack for continued operation and has since been monitoring for additional crack growth. During ClR08 in 2002 the crack length was same 7 5/8 inches. The steam dryer is not addressed in ASME Section XI.

Condition Noted - During CIR09 inspection of this crack revealed that it had grown 1 1/8 inches in one cycle.

Corrective Measures - Clinton Power station repaired this crack in CIR09 by performing under water welding.

Also, during CIR09 it was observed that the lower left stiffener has mechanical deformation.

Clinton Power Station performed an engineering evaluation and concluded that the stiffener still performs its intended function. There are no visible cracks in the base material or the attachment welds.

Steam Separator -

Condition Noted - During CIR09 examination of the separator's lower guide at zero degrees, it was observed that the left outside corners have mechanical deformation.

Corrective Measures - Clinton Power Station has evaluated this deformation and justified continued operation. There are no apparent cracks or missing pieces.

Core Spray Internal Piping -

In accordance with the VIP-18, BWR Core Spray Internals Inspection and Evaluation Guidelines, Ultrasonic examinations were performed on the accessible areas of the selected welds on Core Spray Internal Piping.

Condition Noted -- Indications were identified on three (3) of these welds, BP2, CP2, and DP2.

Two (2) of these welds, BP2 and CP2, have indications previously identified in CIR07 (2000) and continued operation was justified.

Corrective Measures - The VIP-18 document requires Clinton to take the following steps:

Expansion of sample - CPS has scheduled inspection of all accessible welds on the Core Spray Internal Piping. Therefore, no sample expansion is required.

Crack Growth Analysis - Crack Growth analysis was performed to demonstrate the structural integrity of the internal piping for continued operation for two (2) cycles.

Leakage Rate Calculation - Separate leakage rate calculations were performed to demonstrate that the required amount of water can be transported to the core with the existing condition including crack growth.

Steam Dryer Support Brackets -

Condition noted - During Cl R09 outage examination of the steam dryer support brackets, some of the brackets appear to have contact marks and some do not have any contact marks with the steam dryer.

Corrective Measures -- Clinton Power Station has evaluated this and justified continued operation.

There are no apparent cracks or missing pieces.

RPV Surveillance Specimen Brackets -

Condition Noted - During the ClR09 outage examination of the Surveillance Specimen Brackets located at 003 deg. And 177 deg., both lower tack welds on the attachment brackets were observed cracked.

Corrective Measures - Clinton Power Station has evaluated this and justified continued operation.

These tack welds are outside the examination boundary.

SRM'D'-

Condition Noted - During the CIR09 outage examination of SRM 'D' per GE SIL 409, linear indications were noted above the tube to Primary Pressure Boundary fillet weld, on the non-pressure boundary side. The indications have both horizontal and vertical components.

Corrective Measures - Clinton Power Station has evaluated this and justified continued operation for at least one cycle.

Snubbers Functional testing -

An initial sample (10% of each type) of fifty-nine (59) snubbers was selected from the population of 579 snubbers. During the performance of initial sample testing, three (3) snubbers (two type 1 and one type 2) failed to meet the acceptance criteria. Type 1 snubbers consist of PSA-1/4 and PSA-1/2 and type 2 snubbers consist of PSA-1, PSA-3, and PSA-10.

. An additional ten (10) type 1 snubbers were selected for functional testing. More snubbers failed to meet the acceptance criteria and additional snubbers, 5% for each failure, were selected for testing. In total thirty-nine (39) additional type 1 snubbers were selected for testing.

. An additional sixteen (16) type 2 snubbers were selected for testing. No failures occurred in this additional sample.

Overall, there were one hundred and sixteen (116) snubbers tested during ClRO9.

Type 1 Snubbers -

A representative sample of ten (10) type 1 snubbers was selected for functional testing during CIR09. Two (2) snubbers failed to meet the acceptance criteria (IMS38093S and IRB21596S).

Two condition reports (Issue Reports 201408 and 200369) were initiated to address these failures.

These two snubbers were disassembled for evaluation. The following identified the results of the evaluation:

. lMS38093S - The evaluation identified that grease in the snubber had hardened and the rods of the guide rod and bearing assembly were bent.

. IRB21596S - The evaluation identified that the shaft of the torque carrier and shaft assembly was bent.

Ten (10) snubbers (5% for each failure or 5 for each failure) were selected for testing. Three (3) snubbers (IMS10705S, IMS10909S, and IMS38028S) failed the acceptance criteria. A condition report (Issue Report 201819) was initiated to address the issue. These failed snubbers were disassembled and evaluated as follows:

All three snubbers - The evaluation identified evidence of water and heavy corrosion throughout the snubbers. This condition is similar to the condition caused by operation in a harsh environment (high temperature and humidity). These snubbers are located in the Aux. Steam Tunnel.

Based on this evaluation, CPS concluded that all type 1 snubbers located in the Aux. Steam Tunnel were potentially degraded and the remaining type 1 snubbers located in the Aux. Steam tunnel should be functionally tested. The following snubbers were the remaining type 1 snubbers located in the Aux. Steam Tunnel at the time of testing:

. 1MS1091OS

  • IMS38005S

. lMS38027S

  • IMS38072S
  • IMS38094S

. IMS38096S

  • IMS46001S
  • IMS48003S These nine (9) snubbers were tested for extent of condition/condition monitoring purpose. This testing was in addition to the sample expansion criteria.

All of the above snubbers, except one (1), passed the testing criteria. One (1) snubber, IMS 1091OS, was found locked up and was not tested. A condition report (Issue Report # 202192) was initiated to address this issue. This snubber, IMS 10910S, was disassembled for evaluation. The results are as follows:

.1 MS 1091 OS - The evaluation identified that the bearing socket on the housing end of the carrier and shaft assembly was worn and the guide rods of the rod and bearing assembly exhibit wear marks.

No additional snubbers were selected due to the fact that the above snubbers were selected in addition to the expanded samples and for trending/life history purpose.

In addition to the nine (9) snubbers selected for trending purposes, fifteen (15) more type 1 snubbers (5 for each failure) were selected for testing. These snubbers were selected from other locations (other than Aux. Steam Tunnel). One snubber (IRB24575S) out of these fifteen (15) failed to meet the acceptance criteria. A condition report (Issue Report # 201885) was initiated to address the issue. This snubber, IRB24575S, was disassembled for evaluation. The following identified the results of the evaluation:

1RB24575S - The evaluation identified that the guide rods of the rod and bearing assembly were bent.

Five (5) more type 1 snubbers were selected for testing. These five (5) snubbers selected for testing are not located in the Aux. Steam tunnel. All five (5) passed the testing criteria.

Two (2) snubbers, IMS 10808S and IRI18002S, were identified in C1R08 as degraded and included in the CIR09 testing program for trending purposes. One (1) (lMS1080lS) of these two (2) snubbers failed to meet the acceptance criteria. A condition report (Issue Report 199563) was initiated to address this issue. This snubber was disassembled for evaluation. The results were:

  • IMS 10808S - The evaluation identified that the bearing socket of the torque carrier and shaft assembly on the housing end was damaged. There was grease on the capstan and capstan spring, while the amount of grease did not appear to be excessive, it may have been sufficient to cause the high activation rates. This condition is similar to conditions caused by harsh environment.

This snubber is also located in the Aux. Steam Tunnel.

In summary, fifty-one (51) type I snubbers were removed from various systems for testing purposes; this included all type I snubbers from the Aux. Steam Tunnel building. There were a total eight (8) snubbers that failed the acceptance criteria.

As required by the ORM, piping components on which these snubbers are installed were analyzed to ensure the integrity of the piping component. The results were satisfactory and documented in Engineering Change (EC) 347493.

Type 2 Snubbers -

A representative sample of thirty two (32) type 2 snubbers were selected for functional testing during CIR09. One (1) snubber, IFC03081S, failed to meet the functional testing criteria. A Condition Report (Issue Report 199563) was initiated to address this issue.

The snubber was disassembled for evaluation. This evaluation identified the cause of the snubber being frozen to be an excessive amount of grease in the ball nut assembly. This grease had hardened to the point that it restricted the movement of the recirculating ball bearings thus causing the frozen condition. Dried grease was also found throughout the snubber.

Sixteen (16) additional snubbers (5% for each failure) were selected for functional testing. All snubbers passed the functional testing criteria.

As required by the ORM, the piping components on which this snubber was installed analyzed to ensure the integrity of the piping components. The following describes the results:

The snubber failed in both tension and compression directions during a drag test but passed its functional test. The snubber was degraded due to dried grease. The grease had hardened to the point that it restricted the movement of the re-circulating ball bearing thus causing frozen condition.

Based on the support drawing, the snubber will experience a thermal movement of 1/16" in tension direction. The frozen snubber would be locked in the tension direction thus restraining the pipe thermal movement; this would result in a higher piping stress which may exceed the code stress limits. However, due to the fact the potential thermal movement is 1/16", which is negligible in terms of piping analysis, the pipe and pipe supports would have insignificant impact due to the snubber locked out. No further evaluation is required. This was evaluated in the Engineering Change (EC) 347493.

As a result of implementing 4 modifications (MSF012, 341501, 341503, and 341504) eight (8) snubbers (IMS46001S. IMS48003S, IMS48005S, IMS10602S, IRT28006S, IRT28007S, 1RT31004S , and IRT46001S ) were removed permanently. The snubber population after CIR09 is 579-8 = 571.

It should be noted that CPS also tested a 10% sampling of type 3, 4, and 6 snubbers with no failures.

~-j.

Page I of 2 SECTION 3 LISTING OF EXAMINATION AND TESTING PROCEDURES This section provides a listing of all examination and testing procedures utilized during this inspection period. This listing includes only the procedures required for the testing, examination, and associated calibration of equipment. The contractor procedure records are available and are located in the Document Record Center filed under record type 2E.220 or 3A.1 17 for the CIR08 outage.

Procedure Rev Title 386HA480 Rev. 18 Certification of Nondestructive Test Personnel Addendum Rev. 3 Addendum APPVII to GENE Written Practice 386HA480 Certification of APVII Nondestructive Test Personnel PT-EXLN- Rev. 0 Procedure for Liquid Penetrant Examination Using Fluorescent and Visible Dye 100V3 Liquid Penetrant Inspection Methods MT-EXLN- Rev. 0 Procedure for Magnetic Particle Examination (Dry Particle, Color Contrast or Wet 100V3 Particle, Fluorescent)

GE-VT-101 Ver. 1 Procedure for VT-1 Examination GE-VT-103 Ver. 2 Procedure for VT-3 Examination GE-VT-CLN- Rev. 0 Procedure for In-vessel Visual Inspection (IVVI) of BWR 6 RPV Internals 206 Ver. 5 GE-ADM- Ver. 3 Procedure for Performing Linearity Checks on Ultrasonic Instruments 1001 GE-ADM- Ver. 4 Procedure for Non-Destructive Examination Data Review and Analysis of Recorded 1002 Indications GE-ADM- Ver. 0 Procedure for Zero Reference and Data Recording for Nondestructive 1005 Examinations GE-ADM- Ver. 6 Procedure for Training and Qualification of Personnel For GE-NE Specialized NDE 1025 Applications GE-ADM- Ver. 0 Administrative Instruction for Establishing and Maintaining a Foreign Material 1029 Exclusion Area GE-ADM- Ver. 2 Procedure for Training of Personnel Per ASME Section Xi, Appendix VII, Appendix 1048 VIII, and USNRC Requirements GE-ADM- Ver. 0 Operational Guidelines for the Micro-Tomo Ultrasonic Data Acquisition System 1052 GE-ADM- V1 Operational Guidelines for the CSI Delivery System 1057 GE-ADM- VO Procedure for Installation and Removal of the CSI (RPV Internal) Core Spray 1058 Inspection Tool GE-ADM- Ver. 0 Administrative Procedure for Invessel Inspection (IVVI) 1061 GE-ADM- V1 Procedure for the Determination of the GERIS 2000 OD Data Acquisition System 2031 Liniarity GE-PDI-UT-1 Rev. 3 PDI Generic Procedure for the Ultrasonic Examination of Ferritic Pipe Welds GE-PDI-UT-2 Rev. 3 PDI Generic Procedure for the Ultrasonic Examination of Austenetic Pipe Welds GE-PDI-UT-3 Rev. 1 PDI Generic Procedure for Ultrasonic Through Wall Sizing in Piping Welds GE-UT-300 V8 Procedure for Manual Examination of Reactor Vessel Assembly Welds in Accordance with PDI

Page 2 of 2 Procedure Rev Title GE-UT-304 V6 Procedure for Manual Ultrasonic Planar Flaw Sizing in Vessel Materials GE-UT-511 V11 Procedure for the Automated Examination of Core Spray Piping Welds Contained within the Reactor Pressure Vessel GE-UT-605 V2 Procedure for the Performance of Straight Beam Examinations GE-UT-706 V2 Procedure for RPV Flaw Sizing with the GERIS 2000 OD System GE-UT-707 V5 Procedure for GERIS 2000 OD Ultrasonic Examination of the Shroud to RPV Attachment Welds ER-AA-335- Rev. 1 VT-1 Visual Examination 014 l ER-AA-335- Rev. 3 VT-2 Visual Examination 015 ER-AA-335- Rev. 1 VT-3 Visual Examination of Component Supports and Attachments 016 ER-AA-335- Rev.2 VT-3 Visual Examination of Pump and Valve Internals 017 MSS-002 Rev. E Procedure for Functional Testing of Hydraulic Snubbers MSS-004 Rev. H Procedure for Functional Testing of Pacific Scientific Mechanical Snubbers

Page I of 3 SECTION 4 LISTING OF EXAMINATION AND TESTING PERSONNEL This section identifies the contracted and company examination and testing personnel used to perform the inspections and tests during this period. These personnel have been qualified and certified in accordance with the Clinton Power Station ISI Plan and their employer's procedures and written practices.

Records and personnel qualification and certification are available and are located in the Document Record Center. Wyle Laboratories and General Electric Co. records are stored in file 2E.200 or 3A.1 17.

Name MT Lv PT Lv RT Lv UT Lv VT-1 VT-2 VT-3 Anderson, Paul IIl III II PDI Angelo, Arthur II-L* ll-L*

Armstrong, Michael IIlL* Ill L*

Amaud, Davi _l-L#

Awasom, Amanda, II I Bailey, Phil Ill Ill IlI Barrett, Charles iI 11 1IPDI Benicki, Lenin -I _ i Boiseclair, Roger II III I III Briggs, Jake III ill Il Brostrom, Bo L 1l-L* Il-L*

Burgess, Ronald 1i 1i iI II 11 Dubose, George Il IIll Ill PDI Dummer, Brad IIl ill Ill PDI Eiler, Lance 11 1I ll-L# I II II Eriksson, Mattids I_ Il-L* ll-L*

Fish, Karen I l-T i-L# POX Fish, Kevin l-T l-T Il-L#

Frakes, CE __

Garver, Jeremy _ll-L* _ I-L*

Gathrier, Clint I-T I-T _ IIl-L#

Gauthier, Shane II Ginder, Todd II II 1IPIDI i1 Goss, Edward II-L* 11-L*

Hanson, Michael iI 1i I III Holloway, Gary II-L* II-L*

Hrabik, Joseph Il-L 11-L*

Jackson, Michael II-L* ll-L*

Jasken, Richard II II IIP0DI.

Johnson, Paul _ _II PDI I Kalkbrenner, Marcie I I __ _ llLI

Page 2 of 3 Name MT Lv PT Lv RT Lv UT Lv VT-1 VT-2 VT-3 Kelly, Allen il 11PDI Kegel, Joel _l-L* Il-L*

Kemp, Michael 11 11 11PIDI III IIIl King, Douglas Il-L* Il-L*

Krueger, Michael IlI I11 III PIDI I I Kulkoski, Daniel __Il-L* 11L*

Laws, Jeff 1I L* l- L*

Lemmons, Eric Il-L* Il-L*

Michael, Dickey il il 11PDI .

Minor, Chris 1ll ill III PDI III Ill Montgomery, Kent 11PDI Neau, Steve _Il-L _ II__L*

Padgett, Edmond iI li -

Paillaman, Rudy ill ll III Paladino, Jason Il-L* 11L*

Petitte, Paul Il-L* Il-L*

Phillips, Alan Il-L* Il-L*

Powell, Paul Ilii Ill Price, James ii il il Rachal, Andre _ _ 11PIDI Reisewitz, Jack 11PDI Robideau, Kim i ll ilII li Scott, Timothy I I-T Il-L#

Seymore, Alan Il-L#

Sharrblin, Phil IIl III III PIDI_ II II III Simpson, Eugene i 11 I-L# I II II Strong, Robert I

  • Il- IIL*

Roe, Adam If III Thomas, Daniel III-L* 1-1L*

Tucker, David I I 11PDI Vinbald, John IL*1 11L*

Volt, Peter I11L* Il-L*

Walter, Donald . III PIDI __ _ _

Wilson, Matthew Il-L#

Winney, Ryan Il-L* 11L*

Anderson, Carl 11 11 il i i Anthony, Dave l Baig, Mirza l = = I _ _ _

Burke, Bill Carr, Dick 11 Coyle, Pat il Crothers, Patricia 11 Cummings, Joe il Dean, Robert _ il Eigenmann, Cory

Page 3 of 3 Name MT Lv PT Lv RT Lv UT Lv VT-1 VT-2 VT-3 Evans, Gary 11 I Glenn, Dave 11 Johnson, Arlton 11 Mahrt, Dan .

Procarione, Craig .

Rohrscheib, Randy _ _

Scott, Gary __

Slavens, Chris 11 VanFleet, Danny 11 Clark, Charles II li II 11 Thomas, Shawn 11 11 II 11 Touvavannas, Paul II 11 1I 11 Sebby, Mark 11 11 11 1I Miller, Jay 1 I Hall, Kevin Ill ll ll Ill IIl Suddick, Eric 11 II . 11 11 Greboniski, Mark Green, Jack , __

Miller, Michael 111 Windle, Clarance _ _

Pay, Steve III

  • ---- Limited to IVVI
  1. ---- Limited to thickness measurements

Page l of3 SECTION 5 LISTING OF EQUIPMENT AND MATERIALS This section provides a listing of all materials and equipment used to perform the examinations and inspections during this period. The materials and equipment records are available and are located in the Document Record Center filed under record type 2E. 180 or 3A. l 17 for the C I R09 outage.

DESCRIPTION SERIAL MANF SIZE FREQ ANGLE ITYPE GERIS SYSTEM GERIS4 GE _ __

GERIS Transducer 96-977 RTD 1.0 2.25 l0 GERIS Transducer 96-27 RTD 32x22 1.0 145 GERIS Transducer 00-1084 RTD 32x28 2.0 126 GERIS Transducer 98-868 RTD 132x22 1.0 145 i GERIS Transducer 01 -228 RTD 32x28 2.0 26 GERIS Transducer 01-229 RTD 32x28 2.0 126 Manual Transducer 22BC-03003 Sigma 2(1.1" X .62') 3.0 160 SDC3 Manual Transducer OOHRO6 KBA 0.375 2.25 145 COMP-G Manual Transducer 001 6HD KBA 3.5X1Omm 2.0 MSEB2E Manual Transducer 003R17 KBA 0.50" 1.5 ICOMP-G Manual Transducer 003W4V KBA 0.50" 2.25 COMP-G Manual Transducer 003W4W KBA o0.50" 2.25 lCOMP-G Manual Transducer 004NNO KBA 0.50"x1.0" 2.25 [ SWS Manual Transducer 0065PB KBA 1.0"x0.50" 1.0 ISWS Manual Transducer 00864 KBA 11mm 2.0 . MSEB Manual Transducer 008KY7 KBA 0.50"x1.0" 1.0 I GAMMA Manual Transducer 008KY9 KBA 0.50"x1.0" 1.0 IGAMMA Manual Transducer 008KYB KBA 0.50"x1.0" 1.0 SWS Manual Transducer 00CT38 KBA 0.375" 1.5 COMP-G Manual Transducer OOHRO5 KBA 0.375" 2.25 COMP-G Manual Transducer OOK9NV KBA 0.50"x1.0" 1.0 1SWS Manual Transducer OOKJCV KBA 0.50"x1.0" 2.25 10 lSWS Manual Transducer 00KV1H KBA 1.0" 2.25 145L 1113-262-043 Manual Transducer OOKV6D KBA 0.5"x1.0" 2.25 160L - SWS Manual Transducer 00KWBT KBA 0.50" 5.0 F-HP Manual Transducer OOL18C KBA 0.375 1.5 MSWQC IManual Transducer 00.217 KBA 1 2.25 [ , COMP-G IManual Transducer 00L2K7 KBA 10.50" 5.0 COMP-G Manual Transducer 00L325 KBA 0.50"x1.0' 1.0 IGAMMA IManual Transducer 00L327 KBA 0.5"X1.0" 1.0 iSWS lManual Transducer 00L48P KBA 0.5" 2.25 1113-242-591 UManual Transducer 00L48X KBA 0.25" 5.0 ICOMP-G Ianual Transducer OL4R4 KBA 0.5X1.0" 1.0 ISWS Manual Transducer 00L4YL KBA j0.25" 5.0 [COMP-G

Page 2 of 3 DESCRIPTION SERIAL MANF SIZE FREQ ANGLE TYPE Manual Transducer 00L700 KBA 0.375" 2.25 COMP-G Manual Transducer 00MPXC KBA 0.5" 1.5 COMP-G Manual Transducer OOMWR6 KBA 0.5" 2.25 COMP-G Manual Transducer OONOFD KBA 0.25" 1.5 COMP-G Manual Transducer 0ONOtH KBA 0.25" 1.5 COMP-G Manual Transducer OONOFL KBA 0.25" 1.5 COMP-G Manual Transducer OOPYB7 KBA 0.375" 5.0 COMP-G Manual Transducer OOPYB8 KBA 0.375" 5.0 COMP-G Manual Transducer 00T8J3 KBA 0.5"X1.0" 2.25 SWS Manual Transducer 00T8J4 KBA 0.5"X1.0" 2.25 SWS Manual Transducer 00V696 KBA 0.5" 2.25 COMP-G Manual Transducer 006VC KBA 0.5"X1.0" 1.0 113-891-600 Manual Transducer 006VD KBA 0.5"X1.0" 1.0 SWS Manual Transducer 0OX8CB KBA 0.5" 1.5 MSWQC Manual Transducer 00X9C8 KBA 0.5" 2.25 FDCP-XDCR Manual Transducer 0OX9HX KBA 0.375" 5.0 FDCP-XDCR Manual Transducer 00X9J3 KBA 0.25" 2.25 FDCP-XDCR Manual Transducer 0OX9TT KBA 0.25" 2.25 MSWQC Manual Transducer 00X9V1 KBA 0.25" 2.25 MSWQC Manual Transducer OOXB3L KBA 0.25" 5.0 COMP-G Manual Transducer 00XCD1 KBA 0.25" 2.25 COMP-G Manual Transducer OOXL6K KBA 0.5"X1.0" 2.25 SPFPA-

_ _SW4X8G2 Manual Transducer OOXL6N KBA 0.5"X1.0" 2.25 SPFPA-SW4X8G2 Manual Transducer OOXL6X KBA 0.5"X1.0" 2.25 SPFPA-SW4X8G2 Manual Transducer OOXLP5 KBA 0.375" 5.0 MSWQC Manual Transducer 00XN27 KBA 0.5" 5.0 MSWQC Manual Transducer 00XN2H KBA 0.5" 5.0 MSWQC Manual Transducer OOYR2D KBA 0.5"X1.0" 2.25 SWS Manual Transducer OOYR2F KBA 0.5"X1.0" 2.25 SWS Manual Transducer 00YXYJ KBA 0.25" 2.25 FDCP-XDCR Manual Transducer 0100NW KBA 0.5" 5.0 FDCP-XDCR Manual Transducer 01067N KBA 0.5" 2.25 FDCP-XDCR Manual Transducer 01ODYB KBA 0.5" 2.25 MSWQC Manual Transducer 010HB5 KBA 0.375" 5.0 FDCP-XDCR Manual Transducer 010HBF KBA 0.25" 5.0 FDCP-XDCR Manual Transducer 010HWB KBA 0.375" 2.25 MSWQC Manual Transducer 010HWK KBA 0.375" 1.5 .MSWQC Manual Transducer 01OHX8 KBA 0.5"X1.0" 1.0 SWS Manual Transducer 574628848 KBA 3.5X1Omm 4.0 MSEB4E Manual Transducer E09400 KBA 0.5"X1.0" 2.25 GAMMA Manual Transducer J29329 KBA 0.25" 5.0 Manual Transducer 92-893 RTD 2(10x18)mm 2.0 60 TRL2 THERMOMETERS 235024 PTC 12/3012004 Model 312F THERMOMETERS 235058 PTC 12/30/2004 Model 312F

Page 3 of 3 DESCRIPTION SERIAL IMANF SIZE FREQ !ANGLE TYPE THERMOMETERS 235096 (PTC 12/30/2004 i Model 312F THERMOMETERS 235098 PTC 12/30/2004 [ Model 312F THERMOMETERS 235112 PTC 12/30/2004 Model 312F THERMOMETERS 235121 PTC 12.30/2004 Model 312F THERMOMETERS 235130 PTC 12/30/2004 Model 312F THERMOMETERS 235142 IPTC 12/30/2004 _ Model 312F THERMOMETERS 235162 PTC 12/30/2004 Model 312F THERMOMETERS 235265 PTC 12/30/2004 Model 312F THERMOMETERS 235277 PTC 12/30/2004 . Model 312F THERMOMETERS 23528 PTC 12/30/2004 -- -- Model 312F THERMOMETERS 235280 PTC 12130/2004 Model 312F THERMOMETERS 235296 PTC 12/30/2004 Model 312F THERMOMETERS 235312 PTC 12/30/2004 _ __ Model 312F THERMOMETERS 235344 PTC 12/30/2004 j IModel 312F THERMOMETERS 235360 PTC .12/30/2004 Model 312F Ultragel II UT Cal Block 00325 CAL-10MT-001 Sonotech Parker Research CS j _ _. I..

Ultragel II UT Cal Block CAL-DPTH-59 S Ss SS Depth Cal UT Cal Block CAL-IIW2-018 GENE SS TYPE 2 UT Cal Block CAL-IIW2-028 Ray Check .

UT Cal Block CAL-ilW2-032 GENE CS i TYPE 2 UT Cal Block CAL-RHOM-037 . Rompas UT Cal Block CAL-RHOM-054 96-5538 CS Rompas UT Cal Block CAL-RHOM-066 SS  ! Rompas UT SCOPE 136P991A101224 Staveley 8/14/2004 _ . .__ Sonic 136P 9 UT SCOPE 136P1106B091353 Staveley 12/11/2004 Sonic 136P UT SCOPE 031570311 Panametrics 12/11/2004 ___ I EPOCH4 UT SCOPE 031574211 Panametrics 12/11/2004 EPOCH4 UT SCOPE 031540506 Panametrics 8/14/2004 EPOCH4

SECTION 6 REPAIR AND REPLACEMENT

SUMMARY

NIS-2 OWNER'S DATA REPORTS This section provides a listing of the 70 ASME Section XI repairs or replacements performed between May 8, 2002 and February 25,2004.

All repairs and replacements are of a routine nature. CPS did not identify any flaws during performance of any ISI examination which required a repair or replacement.

CPS utilized Code Case N-416-1 during this reporting period. This Code Case allows the elimination of the hydrostatic testing requirement following welded replacement, providing some additional NDE is performed and the 1992 Edition of Section III used for examination.

CPS installed a number of modifications including MSFO12 on MSIVs, M079 on ECCS testable check valves, and the changeout of numerous Dresser Relief Valves with Crosby replacements.

Following the listing of repairs and replacements are copies of NIS-2 Owner's Data Reports for all of the Class 1, 2, and MC repairs and replacements which CPS performed during this reporting period. Data reports for any components or parts used in support of those NIS-2's have not been included but are filed with Section XI repair and replacement records.

The records for all Section XI repairs and replacements are available and located in the Clinton Records Vault filed in the respective N-5 system under record 3A.1 17 entitled ASME System Data Reports.

SECTION 6 REPAIR AND REPLACEMENT

SUMMARY

NIS-2 Number Class Description RF-9-001 3 Replaced IDOOO1C and piping RF-9-002 3 Replaced Pump lG33-COOIB gland ring RF-9-003 3 Replaced Snubbers IRT06014S and IRT07009S and hanger bolting RF-9-004 2,3 Installed SX blind coupling per EC 333971 RF-9-005 3 Replaced SX piping and Tee fitting RF-9-006 3 Replaced channel to cover fasteners on RHR heat exchanger B RF-9-007 3 Replaced Coolers IVX14AA and IVX14AB RF-9-008 3 Replaced Valve I SX006C RF-9-009 3 Replaced Valve Disc on 1G33-F043C RF-9-010 2 Replaced Relief Valve I FC091 RF-9-011 3 Replaced Orifice Plate per EC 339985 RF-9-012 2/3 Replaced channel cover bolting on RHR heat exchanger B RF-9-013 I Weld repair of SRV # 160779 to rebuild seat cladding RF-9-014 I Weld repair of SRV # 160911 to rebuild seat cladding RF-9-015 I Weld repair of SRV # 160941 to rebuild seat cladding RF-9-016 I Weld repair of SRV # 160946 to rebuild seat cladding RF-9-017 I Weld repair of SRV # 160540 to rebuild seat cladding RF-9-018 I Modify Check Valve I E12-F104 A per EC 333697 RF-9-019 1,3 Replace SRV I1B21-F047C, bolting RF-9-020 1,3 Replace SRV I B21 -F051 G, bolting RF-9-021 1,3 Replaced SRV IB21-FO41D and bolting

SECTION 6 REPAIR AND REPLACEMENT

SUMMARY

NIS-2 Number Class Description RF-9-022 1,3 Replaced SRV IB21-F047A and bolting RF-9-023 1,3 Replaced SRV I B2 1-F041 C and bolting RF-9-024 1,3 Replaced SRV IB21-FO41F and bolting RF-9-025 1,3 Replaced SRV IB21-F0471 and bolting RF-9-026 1,3 Replaced SRV 1B21 -FO51 B and bolting RF-9-027 Install Modification MSFO 12 on I B21 --F0281 1

RF-9-028 Install Modification MSF012 on IB21-F028C

.1 RF-9-029 Install Modification MSF012 on IB21-F028D RF-9-030 2 Replaced Snubber IFC03081S RF-9-031 2 Replaced Snubber 1RT06018S RF-9-032 3 Replaced Snubbers 1MS10907S, IMS109IOS, IMS10909S RF-9-033 Replaced Snubbers IMS30013S, IMS38028S RF-9-034 3 Replaced Snubbers IMS10808S, IMS26010S, IMS38005S, IMS38027S, IMS05022S, IMS10705S, replaced load pin on IMS29007S RF-9-035 2 Replaced Snubbers IRH09082S, IRH09053S, IRH09055S, IRH09054S RF-9-036 2 Replaced Snubbers I RH08024S, I RH08076S, I RH08059S, I RH08047S, I RHO8017S RF-9-037 2 Replaced Snubbers IRHO909OSE, I RHO909OSW RF-9-038 3 Replaced piping in NSX06 RF-9-039 3 Replaced piping in NSX06

SECTION 6 REPAIR AND REPLACEMENT

SUMMARY

NIS-2 Number Class Description RF-9-040 3 Replaced piping in NSX07 RF-9-041 3 Replaced Valve Ball in IG36F030A RF-9-042 3 Replaced Valve I G33-F033 internals RF-9-043 3 Replaced piping in NSX08 RF-9-044 MC Replaced Drywell Head Eyebolt Assemblies RF-9-045 I Modified IE12-F009 per EC 339006 RF-9-046 I Modified IB21-FO16 per EC 34503.

RF-9-047 I Modified 1G33-FOO1 per EC 34504 RF-9-048 2 Replaced Valve I E51 1-F022 internals RF-9-049 3 Replaced Valve ISX032 Disc RF-9-050 3 Replacement of RHR B heat exchanger bolting and weld buildup RF-9-051 2 Install thermal relief valve I El2-F122A and piping per EC 330572 RF-9-052 3 Replaced line I CC58B-4 RF-9-053 I Replaced Reactor Recirculation Pump B seal assembly RF-9-054 2 Modified Relief Valve lE12-F025C discharge piping per EC 344836 RF-9-055 2 Replaced Relief Valve IE12-F017B per EC 344836 RF-9-056 I Replaced IC41-F004B trigger assembly RF-9-057 3 Replaced I G36-FO30B ball RF-9-058 3 Replaced IE12-F068A disc and performed weld buildup of guide ribs RF-9-059 2 Install thermal relief valve IE12-F1 12B and piping per EC 330706

SECTION 6 REPAIR AND REPLACEMENT

SUMMARY

NIS-2 Number Class Description RF-9-060 I Replaced I E5 1-F063 valve bonnet per EC 341502 RF-9-061, 3 Repaired IE12-FO14A guide ribs RF-9-062 2 Replaced IE12-F005 per EC 344836 RF-9-063 3 Replaced Relief Valve I SX208A per EC 344836 RF-9-064 I Replaced Reactor Recirculation Pump Back Pullout Assembly RF-9-065 I Replaced Reactor Water Cleanup components, piping, and CRDMs per EC 341501 RF-9-066 I Replaced 22 CRDMs and bolting RF-9-067 2 Replaced Relief Valve I C41 -F029A and piping per EC 344836 RF-9-068 I Modified 1E21 -F006 per Plant Modification M-079 RF-9-069 2 Replaced Reactor Core Isolation Cooling Piping per EC 341364 RF-9-070 2 Replaced Reactor Water Cleanup Decontamination Flange per EC 339013

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RP-9-004 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 09/19/2002 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station Name 00464032 & 464043 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A

- ZAA.. -

Expiration Date

4. Identification of System NSX06 I Code Class 2,3
5. (a) 1) Applicable Construction Code (Piping) Section III 1974 Edition, S74 Addenda, Code cases None (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases N-416-1
6. Identification of Components Repaired or Replaced and Replacement Components ASME National aCode Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Piping Illinois Power NSX06 NA NSX06 1986 Replacement Yes a .a. a - .i..k a

7. Description of Work Installed a blind coupling in line ISX88BB-30 and ISX93DB-31 in accordance with plant modification EC333971 at containment penetrations IMC204 and 1MC-205.
8. Tests Conducted:

Hydrostatic [ I Pneumatic [I Pressure N/A psi Test Temp. N/A *o Nominal Operating Pressure [X] Exempt E I Other I I

9. Remarks The 3" blind couplings were accepted on UTC2648253.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl. (repair or replacement)

Signed L t d Date / ,20 -:

Owner or ner's Designee, itle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by FMIC of Rhode Island have Inspected the components described In this Owner's Report during the period 0712212002 to 0911912002 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this

  • Inspection; (..../

________ Comm issions ____________

  • Inspector's Sig ture National Board, State, Province
  • Date 21 0 _,

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-010-

- .Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 07/09/2003 Address Sheet 1 of I Unit 1

2. Plant Clinton Power Station Name. 00319700 RR3 Box 228, Clinton, IL 61727 Repair organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date -

jAddress

4. Identification of System N7C0l .

Code Class 2

5. (a) 1) Applicable Construction Code (Piping) Section III 1974 Edition, 574 Addenda, Code cases NONE
2) Applicable Construction Code (Component-Valve) Section III 1977 Edition, No Addenda, Code cases NONE lb) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired , Code Name of Name of Manufacturer Board Other Year Replaced Stamped I . ..

Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve DRESSER - TM-99399 NA 1PC091 2003 Replacement Yes Piping ILLINOIS POWER PIPING SYSTEM NA NYCOl 1986 Replacement Yes

7. Description of Work Removed relief valve IFC091 for IST setpoint testing. A new replacement valve was reinstalled.
8. Tests Conducted:

Hydrostatic [ ] Pneumatic I I Pressure N/A psi Test Temp. N/A OF Nominal Operating Pressure [XI Exempt [ ] Other ( I

9. Remarks Replacement valve (Sn. TM-99399) was accepted on PO 35915, UTC2663896.

I CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and this Replacement conforms to the rules of the ASME Code, Section XI. (repair or replacement)

Sig Owner or Own0 s Desiglee, ale la /I

. Date 20-53 CERTIFICATE OF INSERVICE INSPECTION.

I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boller have inspected the components described In this Owner's Report during the period 10105/2001 to 07/09/2003, and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, nelthir the Inspector nor his employer shall be liable In any manner for any persona an or p amage or a loss of any kind arising from or connected with this Inspectl}/A Inspector's Signat re Commissions IL 1721 National Board, State, Province Date A)Ly 2

,20;

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi L 1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-012

. Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 07/18/2003 Address Sheet 1 of 1 Unit 1

2. Plant Clinton Power Station Name 00489886 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address
4. Identification of System NRH01 . Code Class 2/3
5. (a) 1) Applicable Construction Code (Component-Heat Exchanger) Section III 1974 Edition, W75 Addenda, Code cases NONE (b) Applicable Edition of Section XI Utilized for Repairs or Replacementsl989 Edition, No-Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME
NationalRepaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Heat Excha JOSEPH OAT 2318-B 1053 lE12BOOlB 1978 Replacement Yes

7. Description of Work Heat exchanger lE12BOOlB was disassembled for cleaning and eddy current testing. During-reassembly replaced all channel cover bolting..
8. Tests Conducted:

Hydrostatic l ] Pneumatic I 3 Pressure N/A psi Test Temp. N/A OF Nominal Operating Pressure C ] Exempt [X] Other I ]

9 Remarks Bolting was accepted as follows: Studs-UTC's 2101069, 2659881, 2110386, and 2106995; Nuts-UTCas2634643, 2117288, and2117782.

I CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler have inspected the components described in this Owner's Report during the period 0210612003 to 0711812003, and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or pro amage or a loss of any kind arising from or connected with this Inspe t

// Commissions IL. 1721 Inspector's Sig Uture National Board, State, Province Date Ii L .) 420.4

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi fw 1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-013 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 02/03/2004 Address Sheet 1 of I Unit 1

2. Plant Clinton Power Station

-Name -

350015-01 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date

- Address

4. Identification of System N/A - SPARE . - Code Class - 1
5. (a) 1) Applicable Construction Code (Component-See Remarks)

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements1989 Code Cases None

6. Identification of Components Repaired or Replaced and Replacement Components ASME National R epaired Code

-C> Name of Component Valve Namof f Manufacturer Dlkkers Manufacturer Serial No.

160779 Board N/A No.

Other Identification SPARE Year Replaced Built or Replacement 1978 Repair Stamped (Yes or No)

Yes

7. Description of Work Weld repair of Spare SRV, Serial number 160779, to rebuild seat cladding.
8. Tests Conducted:

.Hydrostatic I I Pneumatic I I Pressure N/A psi Test Temp. N/A OF Nominal Operating Pressure l I Exempt [XI Other [ ]repair non-pressure retaining

9. Remarks Valve built to ASME Section III, 1974, Summer 76 addenda

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this conforms to the rules of the ASME Code, Section Xl. (rep ir or replacement)

A Signed r ADate X _ __ L___ 200)i 1V lwnr ow~ner'9-Des g-ne-e-. ile CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed bv Hartford Steam Boiler Ofit.

have Inspected the components described In this Owner's Report during the period 4t r4 02103/2004 to 0210312004 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owneres Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither th/ Inspector nor his employer shall be liable In any manner for any personal Injury or prop a age or a loss of any kind arising from or connected with this InspectioI A"' Commissions IL 1721 Inspectors Si ature National Board, State, Province Date frQBAA 20

,0e II

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

1. Owner AmerGen Energy Co., LLC i Data Report No. RF-9-014 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03j02/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station Name 350015-07 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address

4. Identification of System NGE02 Code Class 1
5. (a) 1) Applicable Construction Code (Component-See Remarks)

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements I q S Code Cases AX//

6. Identification of Components Repaired or Replaced and Replacement Components ASMVE National Repaired Code Name of Name of Manufacturer Board Other Year Replaced . Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve Dikkers 160911 N/A SPARE 1978 Repair Yes 7 Description of Work Weld repair of SRV, serial number 160911, to rebuild seat cladding.

a8. Tests Conducted:

Hydrostatic I Pneumatic I ] Pressure N/A psi Test Temp. N/A OF Nominal Operating Pressure CJ Exempt E I Other [XI N/A S Remarks Valve built to ASME Section III, 1974, Summer 1976 Addenda

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this j conforms to the rules of the ASME Code, SectionXi. (repal or replacement)

Signed /t Date / - ,20 {7V ltnr r esl6nee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boller C>F /j have inspected the components described In this Owner's Report during the period t F JcJ 03/02J2004 to 03102J 200 4 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal in ury or pro ity damage or a loss of any kind arising from or connected with this Inspectid'n.A\ (

Commissions IL 1721 Inspector's Sigrature National Board, State, Province Date 3 20

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-015 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/02/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station name 350015-06 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address

4. Identification of System NGE02 Code Class 1
5. (a) 1) Applicable Construction Code (Component-See Remarks)

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Code Cases None

6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve DIkkers 160941 N/A SPARE 1978 Repair Yes

7. Description of Work Weld repair of spare SRV, Serial Number 160941, to rebuild seat cladding.
8. Tests Conducted:

Hydrostatic [ I Pneumatic C J Pressure N/A psi Test Temp. N/A OF Nominal Operating Pressure I ] Exempt [ ] Other [X]N/A 9 Remarks Valve built to ASME Section III 1974, Summer 1976 addenda

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this conforms to the rules of the ASME Code, Section Xl. 6repdir or replacement)

Signed _ie I Date 2 20L24 v~4ro wner's Designee, Ttie /

CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boller Cd' Cdi.

have Inspected the components described In this Owner's Report during the period his e 03/0212004 to 03/02/ 2004 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, n Ither the Inspector nor his employer shall be liable In any manner for any persona Injury or p rty damage or a loss of any kind arising from or connected with this Insptlo Commissions IL 1721 spector8Sltynature National Board, State, Province Date 20A

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-016 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/02/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station Name 3500i5-0/.g r41k 3t4g RR3 Box 228, Clinton, IL 61727 - - Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 6172!7 N/A Expiration Date Address

- 4. Identification of System NGE02 Code Class 1 S. (a) 1) Applicable Construction Code (Component-See Remarks)

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda

,Code Cases None

. . I

6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No),

Valve Dikkers 160946 N/A SPARE 78 Repair Yes

7. Description of Work Weld repair of spare SRV, serial number 160946. to rebuild seat cladding.
8. Tests Conducted:

Hydrostatic [ I Pneumatic 2 I Pressure N/A psi Test Temp. N/A F Nominal Operating Pressure E2 Exempt E I Other [X] N/A 9 Remarks Valve built to ASME Section III, 1974, Summer 1976 addenda

I CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and this conforms to the rules of the ASME Code, Section Xi.

P,- -

(repat or replacement)

Signed f- 4' Date X 20

/ ef e s Designed, Title er /

CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler nC (-T .

have Inspected the components described in this Owner's Report during the period C ,f 0310212004 to 0310212004 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property amage or a loss of any kind arising from or connected with this Inspectio D Inspector's Signat re Commissions IL 1721 National Board, State, Province Date , 20 ol

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-017 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/02/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station Name 00350015-04 RR3 Box 228, Clinton, IL 61727 Repair Organization P.o. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Power Station - N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address

4. Identification of System NGE02 Code Class I
5. (a) 1) Applicable Construction Code (Component-See Remarks)

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements1989 Edition, No Addenda Code Cases None

6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board - Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve Dikkers 160540 N/A SPARE 1978 Repair Yes

7. Description of Work Weld repair of Spare SRV, Serial Number 160540, to rebuild seat cladding.
8. Tests Conducted:

Hydrostatic C ] Pneumatic I I Pressure N/A psi Test Temp. N/A OF Nominal Operating Pressure [ I Exempt [ I Other [X] N/A 9 Remarks Valve built to ASME Section III, 1974, Summer 1976 addenda

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this c-.

conforms to the rules of the ASME Code, Section Xl. (repai or replacement)

Signed (' Date °J ,2012, f wne o Ow er-s-Designe , Title 'J CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler ^ _

have inspected the components described In this Owner's Report during the period 0310212004 to 0310212004, and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither he Inspector nor his employer shall be liable In any manner for any personal Injury or property d mage or a loss of any kind arising from or connected with this Inspect[ 1) te z Commissions IL 1721 Inspe tor's Signa#F- National Board, State, Province Date 3 M')A -' (. 20° J

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

1. Owner AmerGen Energy Co., LLC Data Report No. RP-9-018 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/02/2004 Address Sheet I of 1 Unit 1
2. Plant Clinton Power Station Name 00002645 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No." N/A RR.3 Box 228, Clinton, IL 61727 N/A Expiration Date ALddress
4. Identification of System NRH07 Code Class 1
5. (a) 1) Applicable Construction Code (Component-Valve) Section III 1974 Edition, S75 Addenda, Code cases 1516.1, 1567, 1622, 1635.1, 1677 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National epared Code Name of Name of Manufacturer Board Other Year. Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve ANCHOR DARLING E-6214-20-1 NA lE12FO41A 1979 Replacement Yes

7. Description of Work On valve lE12FO41A install modification M-079 per ECN 333697 to modify hinge pins and covers to convert valve from a testable check valve to a simple check. Replaced hingepin covers and cover studs.
8. Tests Conducted:

Hydrostatic f I Pneumatic [I Pressure N/A psi Test Temp. N/A F Nominal Operating Pressure [X] Exempt I I Other I I

9. Remarks Hinge pin covers received per UTC 2110681. Hinge pin cover studs received per UTC 2110681.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl. (repair or replacement)

Signed t.3j~ Date ') r Z7r 20 _

CERTIFICATE OF INSERVICE INSPECTION.

1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler 4(J have inspected the components described in this Owner's Report during the period , ;

03/14/2002 to 03/O2 / 2O 4nd state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or propety eamage or a loss of any kind arising from or connected with this inspect ttn Commissions IL 1721 Inspector's Signhture National Board, State, Province Date 3 /1 A(xC' 2021

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-019 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/03/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station AName 00529783 RR3 Box 228, Clinton, IL 61727 ,Repair-Organization P.O. No., Job No.

Address N/A Type Code Symbol St

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date AddressE

4. Identification of System NGE02 Code Class 1,3
5. (a) 1) Applicable Construction Code (Piping) SECTION III
  • 1974 Edition, S75 Addenda, Code cases *AND 1977, W77
2) Applicable Construction Code (Component-Valve) Section III 1974 Edition, S76 Addenda, Code cases NONE (b) Applicable Edition of Section XI Utilized for Repairs or Replacements1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME

. ~~National NainlRepaired AM Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve DIKKERS 160780 46 1B21F047C 1978 replaced Yes

7. Description of Work Replace valve 1B21F047C. Installed spare valve, serial # 160946, Inlet, Outlet, and Sub-Exhaust Bolting.
8. Tests Conducted:

Hydrostatic CI Pneumatic C I Pressure N/A psi Test Temp. N/A Nominal Operating Pressure [X] Exempt I ] Other [ I

9. Remarks Replacement Valve Serial # 160946, UTC 2567642 Replacement Bolting - Inlet Flange Studs UTC 2111768, 211033: Inlet Nuts - UTC 2684458 Outlet Flange Studs UTC 2684456, 2684458; Outlet Nuts - UTC 2684458 Sub Exhaust Flange Nuts - UTC 2640685 Valve built to 1974 S76 Addenda Data Report for replacement valve is located in N5 System NGE02, Supplement 1.

L CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Sections. (repair or replacement)

Signed - A(,I (' Date J/

l OwnerrOwner's lesignee, Titl`

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler e (C t have inspected the components described In this Owner's Report during the period pi 0511512003 to 0310312004 ,and state that to the best of my knowledge and belief the Owner has 71f1 performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or prope damage or a loss of any kind arising from or connected with this Inspection.

___ ' Commissions IL 1721 Inspector's inature National Board, State, Province Date , ° )IAVRC'k - ,2001

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-020 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/03/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station Name - 00529789 RR3 Box 226, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station

_ Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address

4. Identification of System NGEM 2 Code Class -I, ,l ]

t a)k e

5. (a) 1) Applicable Construction Code (Piping) SECTION III
  • 1974 Edition, S75 Addenda, sfv , . lt,.

Code cases *AND 1977, W77

2) Applicable Construction Code (Component-Valve) Section III 1974 Edition, S76 Addenda, Code cases NONE --

(b), Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None

6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve DIKKERS 160794 59 1B21F051G 1987 Replaced Yes

7. Description of Work Replaced Valve 1B21-FOSIG. Installed spare valve serial # 60949, Inlet, Outlet, R'vd Etb-gahauuI-Bolting.
8. Tests Conducted:

Hydrostatic C]Pneumatic ] Pressure N/A psi Test Temp. N/A O Nominal Operating Pressure [XI Exempt I I otherCI 9 Remarks Replacement valve serial # 160949, UTC 2610659 Inlet Studs -UTC 2111768 ,2110333 Inlet Nuts UTC 2640685 Outlet Flange Studs - UTC 2111962, 2111997, 2110841, 2102002, 2102019, 2112006 Valve built to 1974 S76 Addenda Data Report for replacement valve is located in N5 system NGE02, Supplement 1.

-I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this conforms to the rules of the ASME Code, Section X C'  ! e (rep ir or replacement)

Q2 Signed ;vKDate. /20 0i

{ wn or-6rrry sinee, Titl~

CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler { .-.

have Inspected the components described In this Owner's Report during the period ,(

03103/2004 to 0310312004, and state that to the best of my knowledge and belief the Owner has J1/ct performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neit r the Inspector nor his employer shall be liable In any manner for any personal Injury or p rt damage or a loss of any kind arising from or connected with this Inspe

_ _ _ _ _ _ Commissions IL 1721 Inspector's S nature National Board, State, Province Date __ _

_M _ _ _ 20

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-021 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/04/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station Name 00529778 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 6172i - N/A Exiration Date Address
4. Identification of System NGE02 l Code Class 14 ig. 3 jI/

(1/4Sf I lq,+,

5. (a) 1) Applicable Construction Code (Piping) SECTION III
  • 1974 Edition, S75 Addenda, Code cases -AND 1977, W77
2) Applicable Construction Code (Component-Valve) Section III 1974 Edition, S76 Addenda, Code cases none (b) Applicable Edition of Section XI Utilized for Repairs or Replacements1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve DIRKERS 160541 48 1B21FO41D 1978 Replaced Yes

7. Description of Work Replace valve 1B21FO41D. Installed spare valve, serial # 160540, Replaced inlet and outlet flange bolting.
8. Tests Conducted:

Hydrostatic 1 I Pneumatic l Pressure N/A psi Test Temp. N/A OF Nominal Operating Pressure [X] Exempt C I Other I 9 Remarks Replacement valve serial number 160540, UTC 2567649 Inlet studs - UTC 2111755, 2111768 Inlet nuts- UTC 2640685 Outlet studs - UTC 2684456 Outlet nuts - 2684458 Data Report for replacement valve is located in NS System NGE02, Supplement 1.

l CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xi. (repair or replacement)

Signed or Date 2/

20.

l wriner or Owner'sl-e'signee,litle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed bv Hartford Steam Boiler oft C have inspected the components described in this Owner's Report during the period  ?

05/2012003 to 0310412004, and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Repo~rt. Furthermore, neither the Ipspector nor his employer shall be liable In any manner for any personal Injury or property da a e or a loss of any kind arising from or connected with this Inspection, _ ___

Commissions IL 1721 Inspector's Signature National Board, State, Province Date l, 20 d

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-022 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/04/2004 Address Sheet 1 of l Unit 1
2. Plant Clinton Power Station Name 00529781 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address
4. Identification of System NGE02 Code Class 1,3

-a fbal7  ?

Aat(,I 1x1

5. (a) 1) Applicable Construction Code (Piping) SECTION III
  • 1974 Edition, S75 Addenda, Sft--

Code cases *AND 1977, W77

2) Applicable Construction Code (Component-Valve) Section III 1974 Edition, S76 Addenda, Code cases NONE (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National R epaired Code Name of Name of. Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve DIRRERS 160791 57 1B21F047A 1978 Replaced Yes 7 Description of Work Replace valve 1B21F047A. Installed spare valve 160792, inlet and outlet flange bolting.

8 Tests Conducted:

Hydrostatic C I Pneumatic l I Pressure N/A psi Test Temp. N/A -F Nominal Operating Pressure [XI Exempt I I Other C

9. Remarks Replacement valve, serial number 160792, UTC 2567639 Inlet studs - UTC 2110333, 2111761 Inlet nuts - UTC 2640685 Outlet studs - UTC 2111973, 2684456, 2112014 Outlet nuts - UTC 2684458 Data Report for replacement valve is located in N5 System NGE02, Supplement 1.

LII CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl. (repair or replacement)

Signed ill Date , 20i l CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler ' (of.

have inspected the components described in this Owner's Report during the period 0511512003 to 0310412004, and state that to the best of my knowledge and belief the Owner has 1141c performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection 7 \/

tCommissions

__________ _ IL 1721 Inspector s Sigrature National Board, State, Province Date I  % ,20iLf Vw

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. ' RF-9-023 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/09/2004 Address Sheet 1 of I Unit 1
2. Plant Clinton Power Station Name .00529777 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date

-Address

4. Identification of System NGEO2 Code Class (k,",

Nf*5 3 gave .

5. (a) 1) Applicable Construction Code (Piping) SECTION III
  • 1974 Edition, S75 Addenda, Code cases *AND 1977, W77
2) Applicable Construction Code (Component-Valve) Section III 1974 Edition,-S76 Addenda, Code cases none (b). Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and-Replacement Components ASME National RepaCred Code Name'of Name of Manufacturer Boird' - Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve DIyEERS 160788 205 1B21FO41C 1979 Replaced Yes

7. Description of Work Replace valve lB21FO41C. Installed spare valve serial # 160943. Replaced inlet and outlet fange bolting.

a8. Tests Conducted:

Hydrostatic C J Pneumatic I J Pressure N/A psi Test Temp. N/A F Nominal Operating Pressure [XI Exempt C I Other I I 9 Remarks Replacement valve serial # 160943, UTC # 2567651 Inlet Studs - UTC 2110813, 2110333, 2111755 Inlet Nuts - UTC 2640685 Outlet Studs - UTC 2102011, 2111982, 2102025 Outlet Nuts - UTC 2684458 Valve built to 1974 S76 addenda Data Report for replacement valve is located in N5 System NGE02, Supplement 1.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section XI. (repair or replacement)

V6 Signed C~ -

A, Dig I /e e AItII Date ,20 0'~

I 1 ~ wnle-r-orOwn-e-r's Dsilgn e, Tide CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler . . : r have inspected the components described In this Owner's Report during the period A /h7^4 0511512003 to 03/0912004 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or pro e amage or a loss of any kind arising from or connected with this Inspec c Commissions IL 1721 Inspector's Slgr ure National Board, State, Province Date . 20 ° 1

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-024 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/09/2004 Address Sheet 1 of I Unit 1
2. Plant Clinton Power Station 14ame 00529779 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address
4. Identification of System NGE02 Code Class 1t Ki049 3

_. - Io

5. (a) 1) Applicable Construction Code (Piping) SECTION III
  • 1974 Edition, S75 Addenda, r1_

Code cases *AND 1977, W77

2) Applicable Construction Code (Component-Valve) Section III 1974 Edition, S76 Addenda, Code cases NONE (b). Applicable Edition of Section XI Utilized for Repairs or Replacementsl989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve DIKEERS 160940 191 1B21P041F 1979 Replaced Yes

7. Description of Work Replaced valve 2B21FO41F. Installed spare valve serial # 160537. Replaced inlet and outlet bolting.
8. Tests Conducted:

Hydrostatic I I Pneumatic I I Pressure N/A psi Test Temp. N/A OF Nominal Operating Pressure [XI Exempt C I Other E I 9 Remarks Replacement valve serial # 160537, UTC 2558177 Inlet studs - UTC 2110819, 2110813 Inlet nuts - UTC 2640685 Outlet studs - UTC 2684456 Outlet nuts - UTC 2684458 Valve built to 1974 S76 addenda Data Report for replacement valve is located in N5 System NGE02, Supplement 1.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xi. (repair or replacement)

'p Signed c eiTne Date I /20" IOIIA wner's Designee', Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler r i '.

have inspected the components described in this Owner's Report during the period r '

0511512003 to 0310912004 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concer4 ing the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or propert dmage or a loss of any kind arising from or connected with this inspec ion

__I _ _ _ ___ _ Commissions IL 1721.

Inspector sSignae National Board, State, Province Date ()R20 40w

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-025 Name 965 Chesterbrook Blvd., Wayne, PA 19087 - Date 03/09/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station N ame 00529782 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address
4. Identification of System NGE02 Code Class l- M gilds3 3 I1M
5. (a) 1) Applicable Construction Code (Piping) SECTION III
  • 1974 Edition, S75 Addenda, 'Iwe:

Code cases *AND 1977, W77

2) Applicable Construction Code (Component-Valve) Section III 1974 Edition, S76 Addenda, Code cases none (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve DIKKERS 160790 62 1I21P047B 1978 Replaced Ye

7. Description of Work Replaced valve 1B211047B. Installed spare valve serial # 160911. Replaced inlet and outlet bolting.
8. Tests Conducted:

Hydrostatic C] Pneumatic C Pressure N/A psi Test Temp. N/A' Nominal Operating Pressure (XI Exempt CI Other CI 9i Remarks Replacement valve serial I 160911, UTC 2567641 Inlet studs - UTC 2111755, 2111768 Inlet nuts - UTC 2640685 Outlet studs - UTC 2684456 Outlet nuts - 2684458 Valve built to 1974 S76 addenda Data Report for replacement valve is located in N5 System NGE02, Supplement 1.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xi. (repair or replacement)

Signed (- Date , 20 e' netorOwner'sDesignee, Title /

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler have inspected the components described In this Owner's Report during the period 0511512003 to 03/0912004 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neith r the Inspector nor his employer shall be liable In any manner for any personal njury or pr915-C amage or a loss of any kind arising from or connected with this Inspection. l

_ Commissions IL 1721 Inspector's Signature National Board, State, Province Date /0 lA tA ,20 (7

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-026 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/09/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station

-Name 00529785 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Power Station N/A Authorization No. _

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address

4. Identification of System NGE02 Code Class lV-a%s4 A b"' J 1i&
5. (a) 1) Applicable Construction Code (Piping) SECTION III
  • 1974 Edition, S75 Addenda, Code cases *AND 1977, W77
2) Applicable Construction Code (Component-Valve) Section III 1974 Edition, S76 Addenda, Code cases NONE (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National aCode Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve DIKEERS 160785 56 1B21P051B 1978 Replaced Yes

7. Description of Work Replaced valve lB21F051B. Installed spare serial # 160783. Replaced inlet and outlet flange bolting.
8. Tests Conducted:

Hydrostatic CI Pneumatic I I Pressure N/A psi Test Temp. N/A eo Nominal Operating Pressure [X] Exempt [ I Other I I

9. Remarks Replacement valve serial # 160783, UTC 2558178 Inlet studs - UTC 211768, 2110333, 2111755 Inlet nuts - UTC 2640685 Outlet studs - UTC 2684456 Outlet nuts - UTC 2684458 Valve built to 1974 S76 addenda Data Report for replacement valve is located in N5 System NGE02, Supplement 1.

_ Il CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl. (repair or replacement)

(W1 Signed g L- 7' *, ' Date 7/9 ,2 4

{I ner otr Ons etgieTitle J I CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed bv Hartford Steam Boiler ' (-

have inspected the components described In this Owner's Report during the period 05/15/2003 to 03109/2004 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neithe, the Inspector nor his employer shall be liable In any manner for any personal injury or property 1 amage or a loss of any kind arising from or connected with this inspection I 97 Inspector's Signai Commissions IL 1 7 2 1 National Board, State, Province Date i 20aA (mWt)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RP-9-027 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/10/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station Name 00003672 RR3 Box 228, Clinton, IL 61727 Repair organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date I -Address
4. Identification of System NGE02 Code Class 1
5. (a) 1) Applicable Construction Code (Component-Valve) Section III 1974 Edition, None Addenda, Code cases 1622 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of - Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve ATWOOD MORRILL 6-S62 NA lB2lF028B 1976 Replacement Yes

7. Description of Work Install plant modification MSF012 on valve 1B21F028B in accordance with GE FDDR LHI-5846.
8. Tests Conducted:

Hydrostatic I I Pneumatic CI Pressure N/A psi Test Temp. N/A .F Nominal Operating Pressure [X] Exempt C I Other E I

9. Remarks MSIV Modification Kit received per UTC 2687044. All code parts received as part of Kit with the exception of poppet.

Poppet received per UTC 2106594.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl. (repair or replacement)

Signed ( rg /c ,O,( /ol Date I; /61'

/

,20 r-

  • Owner orwner's Designe4, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler of Cr.

have inspected the components described in this Owner's Report during the period PM 05/1212000 to 03/1012004 , and state that to the best of my knowledge and belief the Owner has j11,124 performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, ither the Inspector nor his employer shall be liable In any manner for any personal injury or p rty damage or a loss of any kind arising from or connected with this Inspectc /

-- l lCommissions-n IL 1721 Inspector's alture National Board, State, Province Date 3/1 2021

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

1. Owner AmerGen Energy Co., LLC
  • Data Report No. RF-9-028 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/10/2004 Address Sheet 1 of I Unit 1
2. Plant Clinton Power Station same 00003671 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date IAddress

4. Identification of System NGE02 Code Class I
5. (a) 1) Applicable Construction Code (Component-Valve) Section III 1974 Edition, None Addenda, Code cases 1622 . --  : -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements1989 Edition, No Addenda Code Cases None

6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Namebf - Name of Manufacturer . Board Other Year Replaced Stamped Component Manufacturer -Serial No. No. Identification Built or Replacement (Yes or No)

Valve ATWOOD a HORRILL 7-562 N/A 1B21F028C 1976 Replacement Yes Strt 3b1Pi

7. Description of Work Install plant modification MSP012 on valve lB21FO28C in accordance with design change documents GE FDDR LH1-5846.
8. Tests Conducted:

Hydrostatic l I Pneumatic I I Pressure N/A psi Test Temp. N/A OF Nominal Operating Pressure [XI Exempt [ I Other [I

9. Remarks MSIV modification kit received per UTC 2106594. All Code parts received as part of kit with the exception of poppet.

Poppet received per UTC 2687044.

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xi. (repair or replacement)

Signed .. /tr .// Date 3

,Z / ,20-'2T VOAnerior Owner's b signee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler - (r. ', .i./t have inspected the components described in this Owner's Report during the period 04/26/2000 to 03/10/2004 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neithe the Inspector nor his employer shall be liable In any manner for any personal injury or propertyy amage or a loss of any kind arising from or connected with this Inspecti \ /

6/  ;,Commissions IL 1721 Inspector's Si ature National Board, State, Province 4

Date __ ____ _ _c_ _ ,20 °_

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

1. Owner AmerGen Energy Co., LLC Data Report No. RP-9-029

- Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/10/2004 Address Sheet 1 of I Unit 1

2. Plant Clinton Power Station Name 00405236 RR3 Box 228, Clinton, IL 61727 -Repair Organization P.O. No., Job No..

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL.61727 N/A Expiration Date Address
4. Identification of System NGE02 Code Class 1
5. (a) 1) Applicable Construction Code (Component-Valve) Section III 1974 Edition, None Addenda, Code cases 1622 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, 'No Addenda Code Cases None -
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve ATWOOD/MORRELL 8-562 NA lB2IF028D 1976 replacement Yes

7. Description of Work Install plant modification MSF012 on valve 1B21F028D in accordance with GE FDDR LH1-5846. Perform weld buildup of seating area base metal to increase sectional thickness necessary to optimize overlay thickness. Installed hard facing overlay per welding.
8. Tests Conducted:

Hydrostatic I I Pneumatic CI Pressure N/A psi Test Temp. N/A Nominal Operating Pressure [X] Exempt CI Other CI

9. Remarks Valve modification kit received per UTC 2106619. All Code parts associated with modification contained in kit.

- - l CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl. (repair or replacement)

Signed / - I P-- Date 3 /I 4' 20 07L L /Ownro- ' e, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed bv Hartford Steam Boiler o C-have inspected the components described In this Owner's Report during the period 03114/2002 to 03/10/2004 ,and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither he Inspector nor his employer shall be liable In any manner for any personal injury or prope d mage or a loss of any kind arising from or connected with this inspec

__ Commissions IL 1721 InsptorSign ture National Board, State, Provincace Date 15 21Yo

_i

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RP-9-030 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/11/2004 Address Sheet 1 of I Unit 1
2. Plant Clinton Power Station

- Name 531246-14 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address
4. Identification of System NFC03 Code Class 2
5. (a) 1) Applicable Construction Code (Piping) Section III 74 Edition, S74 Addenda, Code cases None (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None --
6. Identification of Components Repaired or Replaced and Replacement Components-ASME National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Snubber Pacific Scientific 24487 N/A 1PCO3081S 85 replaced Yes

7. Description of Work Replaced snubber IPC03081S, PSA-l
8. Tests Conducted:

Pressure psi Test Temp. .F Hydrostatic [ I Pneumatic 1 I Nominal Operating Pressure I I Exempt I I Other l ]None

9. Remarks Replacement snubber received per UTC 2113583, Cat IDS 1151214, Serial # 24487

I CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl. (repair or replacement)

Signed / Ad (-a 1A-7if Date - //0 20 Ownenror Own er'i fee, n TitIeJ CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler '6(6t.

have inspected the components described in this Owner's Report during the period tkil ;/1>

0311112004 to 03/11/2004 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning (e examinations and corrective measures described In this Owner's Report. Furthermore, neither the spector nor his employer shall be liable In any manner for any personal injury or property~d a e or a loss of any kind arising from or connected with this inspection.

a Commissions IL 1721 Inspector's Signatur National Board, State, Province Date I

/ M A-R (-Vk 200'

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RP-9-031 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/11/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station Name 531246-35 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL.61727 N/A Expiration Date Address

4. Identification of System NRT06 Code Class 2
5. (a) 1) Applicable Construction Code,(Piping) Section III 1974 Edition, S74 Addenda, Code cases NONE (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Repiacement Components ASMVE National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Snubber Pacific Scientific 16745 N/A IRT06018S 85 Replaced No

7. Description of Work Replaced snubber lRT06018S, PSA 1/2
8. Tests Conducted:

Hydrostatic I I Pneumatic l I Pressure psi Test Temp. oF Nominal Operating Pressure I Exempt l] Other I ]None 9 Remarks Snubber received per UTC 2113229, Cat ID# 1151218, Serial # 16745

-L CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl. (repair or replacement)

Signed _ = m t e-i Date 20 0

)bvJerr ne'sDesig'ne-e, TRY~

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler ,4f At have inspected the components described in this Owner's Report during the period Rag 0311112004 to 03)1112004 ,and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the In pector nor his employer shall be liable in any manner for any personal innyly or property damag or a loss of any kind arising from or connected with this Inspection.</@7 Commissions IL 1721 Inspector's Signaore National Board, State, Province Date ,20 01

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RP-9-033 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/11/2004 Address Sheet 1 of I Unit 1
2. Plant Clinton Power Station Name 531246-17,33 RR3 Box 228, Clinton, IL 61727 Repair organization P.o. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL .61727 N/A Expiration Date Address

4. Identification of System NMS05 Code Class - 1
5. (a) 1) Applicable Construction Code (Piping) Section III 1974 Edition, S74 Addenda, Code cases (b). Applicable Edition of Section XI Utilized for Repairs or Replacements1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repared Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Snubber Pacific Scientific 11431 N/A 1MS30013S 86 Replaced Yes Snubber Pacific Scientific 16736 N/A IMS38028S 86 Replaced Yes 7 Description of Work Replaced Snubbers lMS30013S - PSA 31 IMS38028S - PSA 1/2

8. Tests Conducted:

Hydrostatic [ ] Pneumatic I j Pressure psi Test Temp. OF Nominal Operating Pressure 1 ] Exempt [ ] Other I ]None 93 Remarks Snubber Receipt Information:

IMS30013S - UTC 2112965, Cat ID # 1151222, Serial # 11431 IMS38028S - UTC2113206, Cat ID # 1151218, Serial II 16736

_ -L CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section X (repair or replacement)

Signed *0_/'k- Date // 20(2 ilwnerior wner's Designee; Title -J CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler a P 6 have inspected the components described in this Owner's Report during the period 478 _

03/1112004 to 0311112004 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither he Inspector nor his employer shall be liable in any manner for any personal Injury or prop age or a loss of any kind arising from or connected with this inspectio Commissions IL 1721 Inspector's Signature National Board, State, Province Date  ; m 2

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS -

As Required by the Provisions of the ASME Code Section Xi

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-035 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/12/2004 Address Sheet 1 of I Unit 1
2. Plant Clinton Power Station Name 531246-2,6,10,11 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., JolD No.

Address Type Code Symbol Stamp NI. A

3. Work Performed by: Clinton Power Station Authorization No. - . NI/A RR3 Box 228, Clinton, IL 61727 NI. /Al Expiration Date Address
4. Identification of System NRHO9 Code Class 2
5. (a) 1) Applicable Construction Code (Piping) Section III 1974 Edition, S74 Addenda, Code cases None (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Snubber Pacific Scientific 30344 N/A 1RH090825 1986 Replaced Yes Snubber Pacific Scientific 25823 N/A IRH090535 1986 Replaced Yes Snubber Pacific Scientific 15720 N/A IRH090555 1986 Replaced Yes Snubber Pacific Scientific 15881 N/A 1RH090545 1986 Replaced Yes t~~~ atIS"

7. Description of Work Replaced snubbers IRH09082S - PSA 3, 1RH090535 - PSA 3, 1RH09055S - PSA 10, IRH090545 - PSA 10
8. Tests Conducted:

Hydrostatic [ 1 Pneumatic I1 Pressure psi Test Temp. OF Nominal Operating Pressure [ 1 Exempt I I Other [ ]None

9. Remarks Snubber Receipt Information:

IRH09082S - UTC 2113345, Cat ID# 1151217, Serial # 30344 IRH09053S - UTC 2113569, Cat ID# 1151217, Serial # 25823 lRHO9055S - UTC 2108086, Cat ID# 1151215, Serial # 15720 IRH09054S - UTC 2108115, Cat ID# 1151215, Serial # 15881

l CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code Section Xi. (repair or replacement)

Signed i> ,k/ // k' c < Date i /Z 20l-O\-ifieror Owner's DesigneelTitle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed bv Hartford Steam Boiler '- .

have inspected the components described in this Owner's Report during the period i 03/1212004 to 03/1212004 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or prop, yamage or a loss of any kind arising from or connected with this InspectL

__ _ _ _ __ Commissions IL 1721 Inspector's Sig iure National Board, State, Province

-J Date M cv , 20 N)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

1. Owner AmerGen Energy Co., LLC Data Report No. RP-9-036 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/12/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station Name 532246-3,1/5,7,8,9 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Pow er Station Authorization No. N/A RR3 Box 228 , Clinton, IL 61727 N/A Expiration Date 4Address
4. Identification of System NRHO8 Code Class 2
5. (a) 1) Applicable Construction Code (Piping) Section III 1974 Edition, S1974 Addenda, Code cases None (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Snubber Pacific Scientific 17187 N/A IRH08024S 1986 Replaced Yes Snubber Pacific Scientific 28262 N/A IRH08076S 1986 Replaced Yes Snubber Pacific Scientific 25824 N/A IRH08059S 1986 Replaced Yes Snubber Pacific Scientific 29138 N/A 1RR080475 1986 Replaced Yes Snubber Pacific Scientific 28254 N/A .RH08017S 1986 Replaced Yes

7. Description of Work Replaced Snubbers - IRH08024S - PSA 10, IRH08076S - PSA 3, 1RH080595 - PSA 3, IRH080475 - PSA 3, IRH080175 - PSA 3
8. Tests Conducted:

Hydrostatic C] Pneumatic 1 I Pressure psi Test Temp. Op Nominal Operating Pressure 1 I Exempt cI Other [ ]None

9. Remarks Snubber Receipt Information:

IRH080245 - UTC 2108096, Cat ID # 1151215, Serial # 17187 IRH080765 - UTC 2113537, Cat ID # 1151217, Serial # 28262 lRH080595 - DUTC 2113486, Cat ID # 1151217, Serial # 25824 2RH080475 - UTC 2113561, Cat ID # 1151217, Serial # 29138 IRH080175 - UTC 2113485, Cat ID # 1151217, Serial # 28254

_ -L CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler ,' (7.

have inspected the components described in this Owner's Report during the period 0311212004 to 0311212004 , and state that to the best of my knowledge and belief the Owner has  ;,.

performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neith r the Inspector nor his employer shall be liable In any manner for any personapniry or pr p damage or a loss of any kind arising from or connected with this Inspection.

Commissions IL 1721 Inspector's SignaL National Board, State, Province Date ( 20 J

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-037 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/12/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station tName 531246-4 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address

4. Identification of System NRHO6 .

Code Class - 2

5. (a) 1) Applicable Construction Code (Piping) Section III 1974 Edition, 74S Addenda, Code cases None (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National aCode Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Snubber Pacific Scientific 29132 N/A 1RHO909OSE 1986 Replaced Yes Snubber Pacific Scientific 29702 N/A 1RHO909OSW 1986 Replaced Yes

7. Description of Work Replaced Snubber 1RH09090S. Snubber is a dual unit with east and west components. Snubbers are 3s.
8. Tests Conducted:

Hydrostatic I I Pneumatic [ I Pressure psi Test Temp.

Nominal Operating Pressure 1 I Exempt C] Other C ] None

9. Remarks Snubber Receipt Information 1RH0909OS-E - UTC 2113502, Cat ID # 1151217, Serial # 29132 IRHO909OS-W - UTC 2113553, Cat ID # 1151217, Serial # 29702

L CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xi. (repair or replacement)

Signed  ! -/7 ac ' Date i/ 2- , 20 f' 7wIerrLQ-fyeks-esig'nee, TiUe  !

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler x (r f; have inspected the components described in this Owner's Report during the period 03/12/2004 to 03/12/2004 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property dama or a loss of any kind arising from or connected with this Inspection.(

VX Inspector's Signat re Commissions IL 1721 National Board, State, Province Date / a /r)l4 .2 0 i

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-044 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/18/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station Name 540014 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address
4. Identification of System IWE/IWL Code Class MC
5. (a) 1) Applicable Construction Code (Component-See Remarks)

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1992 Edition , 1992 Addenda Code Cases None -  :

6. Identification of Components Repaired or Replaced and Replacement Components National Repaired ASME Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Vessel Illinois Power N/A N/A DRYWELL 1977 Replacement No

7. Description of Work Replacement of 6 Drywell Head Eyebolt assemblies, 1 Drywell Head Eyebolt
8. Tests Conducted:

Hydrostatic E] Pneumatic [ I Pressure N/A psi Test Temp. N/A Nominal Operating Pressure [ I Exempt [X] Other [ ] Flange bolting exempt 9 Remarks Receipt Information:

Eyebolt Assemblies - Cat ID # 1388929, UTC 2686290 Eyebolt - Cat ID # 1148022, UTC 2117819 CPS Drywell not code stamped. Drywell functions as a part of Primary Containment and is subject to replacement requirements of Class MC Components.

I CERTIFICATE OF COMPLIANCE We certify that the statements mode in this repojt are correct and this Replacement conforms to the rules of the ASME Code, SecV n Xi. (repair or replacement) 7 Signed ,sBA r G ie Date Signed- esnee, Tl CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressur Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler, C<A have inspected the components described in this Owner's Report during the period 03/18/2004 to O3 / 1 8/ 209,bnd state that to the best of my knowledge and belief the Owner has performed examinations and taken coriective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal ry or prop damage or a loss of any kind arising from or connected with this inspect I 1 Commissions IL 1721 Inspector's SIqature National Board, State, Province Date , 20 a

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

1. Owner AmerGen Energy Co., LLC Data Report No. RP-9-045 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/18/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station

- Name 489973 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address *
4. Identification of System NRH0f-Code Class 1
5. (a) 1) Applicable Construction Code (Component-Valve) Section III 1974 Edition, S75 Addenda, Code cases 1516.1, 1567, 1622, 1635.1, 1677 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements1989 Edition, No Addenda Code Cases None -
6. Identification of Components Repaired or Replaced and Replacement Components ASME

.NationalRepaired Code Name of Name of Manufcturer Board Other Year Replaced - Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve Anchor/Darling E-6214-122-1 NA IE12F009 1978 Replacement Yes

7. Description of Work Modified 1E12-F009 per EC 339006 to improve opening force of motor operator. Replaced Bonnet and Disc as a part of the modification.
8. Tests Conducted:

Hydrostatic I I Pneumatic t I Pressure N/A psi Test Temp. N/A OF Nominal Operating Pressure [X] Exempt [ ] Other CI

9. Remarks Code Parts Receipt Information:

Bonnet - Cat ID # 1387996, UTC 2686481 Disc - Cat ID # 1387997, UTC 2686479

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Sectio Xl. (repair or replacement)

Signed pPr I1-,

)ate 0 o r wner elignee, itle CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler r,( Ads have inspected the components described in this Owner's Report during the period 03/18/2004 to 03/' 8/20O nd state that to the best of my knowledge and belief the Owner has r/c' performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither t o Inspector nor his employer shall be liable In any manner for any personal i or rop rty age or a loss of any kind arising from or connected with this inspecti l( /

Commissions IL 1721 Inspe for's Signathj National Board, State, Province Date I 1 g ,220 i-

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl I 1. Owner AmerGen Energy Co., LLC Data Report No. RP-9-046 I</

v___~f^

Name -

It - Date 03/18/2004 Yn5 Chesternrook nBvo., Wayne, PA 19087 Address Sheet 1 of 1 Unit 1

2. Plant Clinton Power Station Name 00024713 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date -

Address

4. Identification of System NMS06 Code Class 1
5. (a) 1) Applicable Construction Code (Component-Valve) Section III 1974 Edition, S75 Addenda, Code cases 1516.1, 1567, 1622, 1635.1, 1677 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Cde eRepaired Name of Name of Manufacturer oard Other Year R lamped Component Manufacturer Serial No. . No. Identification Built or Replacement (Yes or No)

Valve ANCHOR DARLING E-6214-155-1 NA 1B21F016 1979 Replacement Yes

7. Description of Work Modified valve 1B21F016 to remove the valve leak-off line and replace the valve bonnet. The work performed IAW EC34503. Disc also replaced.
8. Tests Conducted:

Hydrostatic 1 1 Pneumatic [ Pressure N/A psi Test Temp. N/A Nominal Operating Pressure EX] Exempt 1 I Other 1

9. Remarks Code Parts Receipt Information:

Bonnet - Cat ID # 1388176, UTC 2685141 Disc - Cat ID # 1144968, UTC 2626134

--L CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this t.  !

conforms to the rules of the ASME Code, Section-XI. (reptair or replacement)

Signed a  ; I /.-11 Date .20

/wnerdr wner's Designee. Ttle CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler ; ( '

have inspected the components described In this Owner's Report during the period 02/22/2002 to 03 118 /2 00Abnd state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning tht examinations and corrective measures described in this Owner's Report. Furthermore, neither Ins ector nor his employer shall be liable in any manner for any personal injdoy'or property am g or a loss of any kind arising from or connected with this inspectio I Commissions IL 1721 V Inspector s Signature National Board, State, Province Date-/* { A(cs 2

.201

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-047 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/18/2004 Address Sheet 1 of I Unit 1
2. Plant Clinton Power Station Name 00470353 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Power Station N/A

_ Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date -

Address -

4. Identification of System NRT03 I Code Class 1
5. (a) 1) Applicable Construction Code (Component-Valve) Section III 1974 Edition, S75 Addenda, Code cases 1516.1, 1567, 1622, 1635.1, 1677 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None i- - - -
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer BoardOher. Year Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve ANCHOR DARLING E-6214-4-1 NA 1G33P001 1978 Replacement Yes

7. Description of Work Modified valve 1G33F001 to remove the valve leak-off line and replace the valve bonnet. Work performed IAW EC34504.
8. Tests Conducted:

Hydrostatic C] Pneumatic [] Pressure N/A psi Test Temp. N/A Nominal Operating Pressure [X] Exempt I I Other I I 9 Remarks Code Parts Receipt Information:

Bonnet - Cat ID # 1388173, UTC 2686288

---L CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Se tion Xi. (repair or replacement)

Signed .1 ,-!///2/'  ;- .- A Date 04 r 20l wner s Design, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler el Cr have inspected the components described in this Owner's Report during the period as 07/09/2003 to 03 l18/2 0 4rnd state that to the best of my knowledge and belief the Owner has 3Jef/r-performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither he Inspector nor his employer shall be liable in any manner for any personal injury or prop~rty amage or a loss of any kind arising from or connected with this Inspec ion.

d Inspector's Signam Commissions IL 1721 National Board, State, Province Date (\Cl A R' 20 fi

FORM N1S-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-048

-Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/18/2004 Address Sheet 1 of 1 Unit 1

2. Plant Clinton Power Station tame - -. -00576589 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station - Authorization No. N/A RR3 Box 228, Clinton, IL 6172'7 N/A Expiration Date

-- - Address'

4. Identification of System NRI01 I Code Class 2 S. (a) 1) Applicable Construction Code (Component-Valve) Section III 1974 Edition,5S75 Addenda, Code cases 1516.1, 1567, 1622, 1635.1, 1677 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASMVE NationalRepaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve ANCHOR DARLING E-6214-87-1 NA 1E51022 1978 Replacement Yes 7 Description of Work Replaced Disc and Stem of valve 1E51-F022

8. Tests Conducted:

Hydrostatic 1 I Pneumatic I Pressure N/A psi Test Temp. N/A *F Nominal Operating Pressure [XI Exempt I I Other 1I 9 Remarks Code Parts Receipt Information:

Disc and Stem Assembly - Cat ID # 1156567, UTC 2685222

--L CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Secti n Xl. (repair or replacement)

Signed t /> . ,ff~ Date o3 /P , 20{9 w ow-neiD signee, TifleJ) /

CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler of C' have Inspected the components described in this Owner's Report during the period 07

/17/ 2 003 to 0_l3/18/204bnd state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore. npither the Inspector nor his employer shall be liable in any manner for any personal injury or r arty damage or a loss of any kind arising from or connected with this inspe (

Commissions IL 1721 Inspector's gnature National Board, State, Province Date I ( A,Mc20C

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Owner AmerGen Energy Co., LLC Data Report No. RF-9-051 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/22/2004 Address Sheet 1 of I Unit 1

2. Plant Clinton Power Station Name 00319441 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Sitamp N/A

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address

4. Identification of System NRH01 Code Class 2
5. (a) 1) Applicable Construction Code (Piping) Section III 1974.Edition, S74 Addenda, Code cases None ,

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements1989 Edition, No Addenda Code Cases None

6. Identification of Components Repaired or Replaced and Replacement Components ASME National R dCode Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Piping ILLINOIS POWER PIPING SYSTEM N/A NRH01 1985 Replacement Yes

7. Description of Work Install a new thermal relief valve lE12l1l2A in accordance with Design Change Package EC 330572.

The design change adds the new valve and lines IRHI33AA-l" and lRH133BA-21 between IRH22AA-14" and IRH30BA-12" lines. The 1" inlet line and valve are exempt. This data report documents installation of the 2" discharge line.

8. Tests Conducted:

Hydrostatic EI Pneumatic EI Pressure N/A psi Test Temp. N/A .F Nominal Operating Pressure j I Exempt [XI Other [ Iline is open ended back to pool.

9. Remarks Code Parts Receipt Information:

2" Piping - Cat ID # 1153225, UTC 2110367 Outlet Flange Studs - Cat ID # 11501411, UTC 2686168 Outlet Flange Nuts - Cat ID # 1152013, UTC 2649961 Pipet 8 X 2 - Cat ID # 1146189, UTC 2118371 2" Flange - Cat ID # 1145915, UTC 2106911

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl. (repair or replacement)

Signed - U-,;6Z A r IDate - 03 /2 5 D, .

20 <n4

, _# I

- n rorO ne s6 esignee le CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler /) i(i-/

have inspected the components described in this Owner's Report during the period 2

12/11/2001 to O nd state that to the best of my knowledge and belief the Owner has 2L/ jhy performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or pro damage or a loss of any kind arising from or connected with this inspecti Commissions IL 1721 Inspector's Skfnature National Board, State, Province Date a* MAnu

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-053 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/22/2004 AddreBs Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station niame 477837 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A

.Expiration Date Address

4. Identification of System NGE01 I . Code Class 1 S. (a) 1) Applicable Construction Code (Component-Pump) Section III 1971 Edition, W73 Addenda, Code cases NONE (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Pump BINGHAM/WILLAMETTE 14217102 NB-395 1B33C001B 1977 Replacement Yes

77. Description of Work Replaced Reactor Recirculation Pump B seal assembly.

8B. Tests Conducted:

Hydrostatic [ I Pneumatic [ I Pressure N/A psi Test Temp. N/A *F Nominal Operating Pressure [X] Exempt [ I Other I

9. Remarks Replacement Code Parts Information:

Upper Gland - National Board # 1473 Seal Holder - National Board # 1274 Data Reports Attached for Replacement Parts.

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section Al. (repair or replacement)

Signed t{/

.Pw6owrieOLgnee, Vle G o, ,7 /) Date, 2L- .20 jL At CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler c {' (fr.

have inspected the components described in this Owner's Report during the period 03122/2004 to O3 / 2 2/ 2 Qt+nd state that to the best of my knowledge and belief the Owner has ,f-P performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither he Inspector nor his employer shall be liable In any manner for any personal injury or pro, e d mage or a loss of any kind arising from or connected with this inspectiqi . r Commissions IL 1721 V Inspector's Signa~ National Board, State, Province Date g,5 M 4 LZ1kA ,20(t

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-054

, .I .

Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/22/2004 Address Sheet 1 of I Unit 1

2. Plant Clinton Power Station Name 00572034 RR3 Box 228, Clinton, IL 61727 Repair Organization P.o. No., Job No.

Address N/A Type Code Symbol Stamp.

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date 1Address

4. ,Identification of System NR.H0l . . .

Code Class 2

5. (a) 1) Applicable Construction Code (Piping) Section III 1974 Edition, S74 Addenda, Code cases None (b) Applicable Edition of Section XI Utilized for Repairs or Replacementsl989 Edition, No Addenda
  • Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other . Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Piping ILLINOIS POWER PIPING SYSTEM N/A NRH01 1985 Replacement Yes 7 Description of Work Modify exempt relief valve IE12-F025C discharge piping per EC 344836.

8. Tests Conducted:

Hydrostatic I ] Pneumatic [ I Pressure N/A psi Test Temp. N/A Op Nominal Operating Pressure [ I Exempt [X] Other I ]open ended discharges to suppression pool.

9R Remarks Code Material Reciept Information:

1 1/2- piping - Cat ID II 1153243, UTC 2635920 1 1/20 flange - Cat ID # 1145951, UTC 2104640

I CERTIFICATE OF COMPLIANCE We certify that the statements mode in this report are correct and this - 1,t ,. '

conforms to the rules of the ASME Code, Section XI. (rep'airor replacement) '.-

Signed 1 -x i, A S Date () .'/ 20C'

.1 e'wrre1 Owner 's isignee Ti#e CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler H t have inspected the components described in this Owner's Report during the period 05/29/2003 to O3/ 22/ 2O094nd state that to the best of my knowledge and belief the Owner has {

performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable Inany manner for any personal injury or propertyd mage or a loss of any kind arising from or connected with this inspection"go/

Commissions IL 1721 nspector's 5 ature National Board, State, Province Date X lAh CY 20I

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-M5 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/22/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station

-Name 00571995 RR3 Box 228, Clinton, IL 61727 Repair organization P.O. No., job No. -

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date
Address s
4. Identification of System NRHO7 I I Code Class 2
5. (a) 1) Applicable Construction Code (Piping) Section III 1974 Edition, S74 Addenda, Code cases None
2) Applicable Construction Code (Component-Valve) Section III 1977 Edition, S77 Addenda, Code cases NONE (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases N-416-1
6. Identification of Components Repaired or Replaced and Replacement Components ASME \1 National Repaired Code Name of Name of Manufacturer Board Other YearReplaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve DRESSER TE-34459 N/A 1E12F017B 1982 Replacement Yes 7, Description of Work Replaced Relief Valve IE12-F017B. Installed Crosby Valve per EC 344836. Modified inlet and discharge piping per EC.

8. Tests Conducted:

Hydrostatic I I Pneumatic [ I Pressure N/A psi Test Temp. N/A F Nominal Operating Pressure [X] Exempt [ I Other [ IDischarge piping exempt 9 Remarks Code Part Receipt Information:

Crosby Valve - Cat ID # 1389505, UTC 2688771, Serial Number N99662-00-0003 1 1/2" piping - Cat ID t 1153243, UTC 2635920 2" piping - Cat ID # 1386894, UTC 2672625 1 1/2" flange - Cat ID # 1395070, UTC 2687432 2" flange - Cat ID # 1145915, UTC 2106911

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl (repair or replacement)

Signed -. (I Z ) ['K Date 6' &> ,20_2L

,,O¶ger r Owners Dgeignee, TiMW CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler have inspected the components described in this Owner's Report during the period 05/30/2003 to 0 3/ 2 2/2 0 94rnd state that to the best of my knowledge and belief the Owner has i1t performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or pro damage or a loss of any kind arising from or connected with this inspectionr) )

Commissions IL 1721 Inspector's nature National Board, State, Province Date'~> IA\LAA

'20C1

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-056 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/23/2004 Address - Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station Name 342373 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address
4. Identification of System NSCMM Code Class 1
5. (a) 1) Applicable Construction Code (Component-Valve) Section III 1977 Edition, S77 Addenda, Code cases NONE (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None
6. identification of Components Repaired or Replaced and Replacement Components' ASME National Repaired Code Name of Name of Manufacturer Board Other - Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve CONAX CORPORATION 70 N/A lC41FO04B 76 Replacement Yes

7. Description of Work Replace Trigger Assembly of SLC squib valve after firing.
8. Tests Conducted:

Hydrostatic [ I Pneumatic I ] Pressure N/A psi Test Temp. N/A 0F Nominal Operating Pressure [X] Exempt I I Other 1C

9. Remarks Code Replacement Parts Reciept Information:

Trigger Assembly - Cat ID # 1148279, UTC 2688486, Trigger Body - Serial Number 7065, Inlet Fitting -

Serial Number 7070

L CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section XI. (repair or replacement)

Signed! Ip ' '/ P/r Date 2 -i3 20 C bwneior bwnoe signee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler of ( 1 have inspected the components described in this Owner's Report during the period 03/23/2004 to 0312312 0 Q~bnd state that to the best of my knowledge and belief the Owner has X; '

performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or prope amage or a loss of any kind arising from or connected with this Inspection /\

U 1. A_ Commissions IL 1721 Inspector's Sifature National Board, State, Province Date _a_____1A,_ _ _ 20__

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-059 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/24/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station Name 00319442 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station

- Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date

.. Address

4. Identification of System NRH08 Code Class 2
5. (a) 1) Applicable Construction Code (Piping) Section III 1974 Edition, S1974 Addenda, Code cases None (b) Applicable Edition of Section XI Utilized for Repairs or Replacements1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Piping Illinois Power PIPING SYSTEM VA NRHO8 1985 Replacement Yee

7. Description of Work Install a new thermal relief valve 1E12F112B in accordance with Design Change Package EC330706. The design change adds the new valve and lines IRH132AB-1 and IRH132BB-20 between lRH22AB-140 and lRH30BB-12" lines. The 10 line and valve are exempt but are described for clarity. This data report documents installation of the 20 discharge piping, 1RH132BB-20, cont. Remarks
8. Tests Conducted:

Hydrostatic I I Pneumatic CI Pressure N/A psi Test Temp. N/A Nominal Operating Pressure I 1 Exempt [X] Other C ]Open-ended line

9. Remarks Code Parts Receipt Information:

Pipette, 36-8 X 2, Cat ID # 1146189, UTC 2118371 21 Piping - Cat ID # 1153225, 2110367 2W Flange - Cat ID # 1145915, UTC 2106911 Studs - Cat ID # 11501411, UTC 2686168 Nuts - Cat ID # 11520131, UTC 2649961 Desc. of Work Cont. - between relief valve 1E12-F112B and Line IRH30BB-12,

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Section Xi. (repair or replacement)

Signed kf2/' . v&, K. . Date () 12 , 20 L2 Owner orOwn-f's designee, Title /

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by- Hartford Steam Boiler of(-A have inspected the components described in this Owner's Report during the period 12/1112001 to 03/24/2004, and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither e Inspector nor his employer shall be liable In any manner for any personij orapro rt age or a loss of any kind arising from or connected with this inspects n.}

/ Commissions IL 1721 V Inspe~ctor's Signatu National Board, State, Province Date _____4 _ 20_

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-060 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/24/2004 Address Sheet 1 of I Unit 1
2. Plant Clinton Power Station Name 502184 -

RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date -

Address -

4. Identification of System NRI01 . Code Class 1
5. (a) 1) Applicable Construction Code (Component-Valve) Section III 1974 Edition, S75 Addenda, Code cases 1516.1, 1567, 1622, 1635.1, 1677 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve Anchor Darling E-6214-5-1 N/A 1E51P063 1979 Replacement No

7. Description of Work Valve 1E51-F063 modified per EC 341502 rev. 1 to remove stem leakoff line. Scope of modification includes replacement of bonnet.
8. Tests Conducted:

Hydrostatic [ I Pneumatic 1 3 Pressure N/A psi Test Temp. N/A F.

Nominal Operating Pressure [XI Exempt [ I Other [ I

9. Remarks Code Parts Receipt Information:

Bonnet - Cat ID # 1388175, UTC 2686392

-- L CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Sectio XI. (repair or replacement)

Signed I- I r P' Date 3 /0 2.

0 er n Dsignee, THI6 CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler of Ct have inspected the components described in this Owner's Report during the period 12/09/1903 to O3/24/20qbnd state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or prope da mge or a loss of any kind arising from or connected with this inspectito l a

)

Inspector's Signatur Commissions IL 1721 National Board, State, Province Date ?JL ( /k Ato 200S

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

1. 'Owner AmerGen Energy Co., LLC Data Report No. RF-9-062 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/24/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station game 00516591 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address N/A Type Code Symbol Stamp

3. Work Performed by: Clinton Power Station N/A Authorization No.

RR3 Box 228, Clinton, IL 61727 N/A Expiration Date -

Address

4. Identification of System NRH07 Code Class 2
5. (a) 1) Applicable Construction Code (Component-Valve) Section III 1977 Edition, S77 Addenda, Code cases NA (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases N-416-1
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification . Built or Replacement (Yes or No)

Valve DRESSER TE-34457 NA 1E12F005 1982 Replacement Yes Piping Illinois Power PIPING SYSTEM NA NRH07 1985 Replacement Yes

7. Description of Work Replaced relief valve 1E12-?005 with a Crosby model per EC 344836. Modified inlet and outlet piping to support valve fit per EC.
8. Tests Conducted:

Hydrostatic I] Pneumatic I I Pressure N/A psi Test Temp. N/A OF Nominal Operating Pressure [XI Exempt I I Other I I N-416-1 9 Remarks Code Parts Receipt Information:

1 1/20 piping - Cat ID # 1153243, UTC 2635920 2W piping - Cat ID # 1386894, UTC 2672625 1 1/2' flange - Cat ID # 1395070, -UTC 2687109 2' flange - Cat ID # 1145915, UTC 2105832 Valve - Cat ID # 1389503-1, UTC 2688807, serial Number N99659-00-0001

_ __I _ l CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this-- Replacement conforms to the rules of the ASME Code, Sec on XI. (repair or replacement)

Signed fJ/. i ' Date (25 ,20.Ll 0e4 els Designee, le CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler c°~ (i.

have inspected the components described in this Owner's Report during the period 47i 05/30/2003 to 0 3 / 24/ 2 0 9,4nd state that to the best of my knowledge and belief the Owner has his '

performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal inju or aage or a loss of any kind arising from or connected with this inspection.

Commissions IL 1721 Inspector's Signa National Board, State, Province Date -Sa6 M A-1Z-C-j .200g

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-064 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/26/2004 Address Sheet 1 of 1 Unit 1
2. 'Plant Clinton Power Station Name 489922 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp. N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address
4. Identification of System NGE01 Code Class 1
5. (a) 1) Applicable Construction Code (Component-Pump) Section III 1971 Edition, W73 Addenda, Code cases NONE -

Cb) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases None e a. Rn C m p

6. Identification of Components Repaired or Replaced and Replacement Components ASME

.Natonal Repaired Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Pump BINGHAM/WILLAMETTE 14217102 NB-395 IB33C001B 1977 Replacement Yes

7. Description of Work Replace pump stuffing box, lifting lugs received as part of pump back pullout assembly.

All other parts of assembly are one inch or less.

8. Tests Conducted:

Hydrostatic C I Pneumatic ] Pressure N/A psi Test Temp. N/A *F Nominal Operating Pressure [XI Exempt [ I Other II 9 Remarks Code Parts Receipt Information:

Pump back pullout assembly - Cat ID # 1393029, UTC 2688069

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Sectio6i Xi. (repair or replacement)

Signed ' ign r J Date G?-3 / 6 20 CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler at i have inspected the components described in this Owner's Report during the period 2

03/26/2004 to 036/ 600 nd state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty.

expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or prope damage or a loss of any kind arising from or connected with this inspectia n (i In*/ect - Commissions IL 1721 Inspector's Sig National Board, State, Province Date a (IARC\ .200t

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-065 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 03/30/2004 Address Sheet 1 of 1 Unit *1
2. Plant Clinton Power Station Name 00502187 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: . Clinton Power Station I Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date

- Address --

4. Identification of System NRT03 Code Class 2
5. (a) 1) Applicable Construction Code (Piping) Section III 1974 Edition, 574 Addenda, Code cases None (b).Applicable Edition of Section XI Utilized for Repairs or Replacements1989 Edition; No Addenda Code Cases n416-1 e , a
6. Identification of Components Repaired or Replaced and Replacement Components ASMVE National Repared Code Name of Name of Manufacturer Board Other Year Replaced - Stamped Component Manufacturer Serial No. -No. Identification Built or Replacement (Yes or No)

Valve ANCHOR/DARLING E-6214-1-1 NA 1G33F101 1978 Replacement -Yes Valve ANCHOR/DARLING E-6214-141-1 NA 1G33F103 1979 Replacement Yes Tank CB&I Co. B5225 4442 1B13D003 1978 Replacement Yes Piping. ILLINOIS POWER PIPING SYSTEM. NA NRT03. 1985 Replacement_ -Yes

7. Description of Work Performed the following work per EC 341501:

Replace valve 1G33F103 and downstream 30 piping Replaced bonnet on IG33P101 Replacement of CRDMs 24-25, 28-29 and bolting

8. Tests Conducted:

Hydrostatic [ ] Pneumatic ( ] Pressure N/A psi Test Temp. N/A OF Nominal Operating Pressure [XI Exempt I] Other [ IN416-1 9 Remarks 3" piping - Cat ID # 1389312, UTC 2675452 3" elbow - Cat ID # 1389620, UTC 2675556 3" Globe Valve - Cat ID # 1388180, UTC 2686308 3" Valve Bonnet - Cat ID # 1388170, UTC 2685139 Installed serial # A2168 at 24-25, A2308 at 28-29 CRD bolting - Cat ID # 1147766, UTC 2684461

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Sectio Xi. (repair or replacement)

Signed Date 23 /3A .20.l l n Onee einee, Ti6~

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressur Vessel Inspectors and the State or Province of Illinois and employed bv Hartford Steam Boiler q.7 s have inspected the components described in this Owner's Report during the period gile 06102/2003 to 0313012004 , and state that to the best of my knowledge and belief the Owner has Ie performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal IpjaM or property damrge or a loss of any kind arising from or connected with this Inspectio A/ Commissions IL 1721 Inspector's Si g 6 ture National Board, State, Province Date _ s____ _ ,_20__V

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-066 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 04/01/2004 Address Sheet 1 of v&'?

Unit 1 rAc

2. Plant Clinton Power Station Irki Name 00531347 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date Address
4. Identification of System NGE01 Code Class 1
5. (a) 1) Applicable Construction Code (Component-Tank) Section III11971 Edition, S73 Addenda, Code cases 1141, 1332, 1361-2, 1557-1, N207 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1985 Edition, No Addenda Code Cases None -
6. Identification of Components Repaired or Replaced and Replacement Components ASME NainlRepaired National -AM - Code Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Tank CB&I Co. B5225 4442 1B13D003 1978 Replacement Yes

- 4 Oh y = .

7. Description of Work Replace 22 control rod drive mechanisms and their associated flange capscrews. Page 3 of this data report contains a complete listing of all CRDMs , locations, and serial numbers..

S. Tests Conducted:

Hydrostatic [ I Pneumatic [ I Pressure N/A psi Test Temp. N/A Nominal Operating Pressure [X] Exempt l I Other I I

9. Remarks The replacement capscrews were received on Cat ID # 1147766, UTC 2684461.

-Code Data Reports for all replacement CRDM's in li5subsystem book NGE01

I

(- c F 3i CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, S ction Xl. (repair or replacement)

Signed V Lf Date / 2 0 6/Ai 04nOw Oelsignee~ttle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler af Cf have inspected the components described in this Owner's Report during the period 08101/2003 to 0410112004 , and state that to the best of my knowledge and belief the Owner has 4 performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neit er the Inspector nor his employer shall be liable In any manner for any personal injury or propert damage or a loss of any kind arising from or connected with this inspecti Fo

_ Commissions IL 1721 Inspector' ignature National Board, State, Province Date Avq, 201 '

Page 3 of 3 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Section 7 Description of work (continued)

WO Task Core Location Removed Serial Installed Serial Number Number 531347-01 08-17 8942 A2584/2156**

531347-05 ]2-13 A2698 A2584/2156 **

531347-06 12-21 A3383 A2369 531347-07 12-45 A3248 A2440 531347-08 12-49 A2451 A3288 531347-09 20-13 A3290 A3232 531347-10 24-33 8195 8967 531347-11 24-49 A2603 A2702 531347-12 28-05 A2456 A2632 531347-13 28-21 A3234 8935 531347-14 28-41 A3407 A2674 531347-15 32-09 A2484 A3222 531347-16 32-37 8557 9429 531347-17 32-49 8987 8508 531347-18 36-25 8638 A3110 531347-19 40-05 6763 A3376 531347-20 40-49 8445 8831 531347-21 44-45 A2734 A3225 531347-22 48-29 A2432 A3340 531347-23 52-21 A3211 A2729 531347-24 52-29 A5511 A3239 531347-25 32-49 8508 A3148 502187-32/41 24-25 A2674 A2168 502187-33/42 28-29 8508 A2308

  • installed per task 17-replaced after functional test failure
    • Issue Report 212402

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-067 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 04/01/2004 Address Sheet 1 of 1 Unit -1
2. Plant Clinton Power Station Zame 00448086 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date -

Address

4. Identification of System NSC01 Code Class
5. (a) 1) Applicable Construction Code (Piping) Section III 1974;Edition, S74 Addenda, Code cases NONE
2) Applicable Construction Code (Component-Valve) Section III 77 Edition, S77 Addenda,

-Code cases N/A (b) Applicable Edition of Section XI Utilized for Repairs or Replacements1989 Edition; No Addenda Code Cases None

6. Identification of Components.Repaired or Replaced and Replacement Components -

ASME National Repaired Code

.Name of Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Valve DRESSER TE-34455 N/A IC41P029A 1983 Replacement Yes Piping ILLINOIS POWER PIPING SYSTEM N/A NSC01 1986 Replacement Yes

7. Description of Work Replaced 1C41F029A with Crosby model per EC 344836. Inlet and outlet piping modified per EC to fit Crosby valve.
8. Tests Conducted:

Hydrostatic E I Pneumatic C I Pressure N/A psi Test Temp. N/A Nominal Operating Pressure [X] Exempt 1 ] Other I ]N-416-2

9. Remarks Code Parts Receipt Information:

Valve - Cat ID # 1389688, UTC 2688483, Serial # N99660-00-0003 Piping - 1 1/2" - Cat ID # 1394829, UTC 2686774 Piping - 2" - Cat ID # 1145891, UTC 2106835, 211404 Flange - 1 1/2" - Cat ID # 1394828, 2686570 Flange - 2" - Cat ID # 1394827, UTC 2686843 Elbow - 2" - Cat ID # 1145933, UTC 2115600

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Secqdn Xi. (repair or replacement)

Signed AZC Date ,200 2210(;

w gr esignee, tie /

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler of l have inspected the components described in this Owner's Report during the period yll 06/09/2003 to 04101/2004 , and state that to the best of my knowledge and belief the Owner has v/; f.

performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or prop rty damage or a loss of any kind arising from or connected with this inspeoeOrN V / Commissions IL 1721 Inseector's Signature National Board, State, Province Date ____ ___ 20c_

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co., LLC - - Data Report No. RP-9-068 K Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 05/06/2004 Address Sheet 1 of I Unit 1
2. Plant Clinton Power Station name 00002654 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A II.ddress Expiration Date
4. Identification of System NLP01 Code Class I
5. (a) 1) Applicable Construction Code (Component-Valve) Section III 1974 Edition, S75 Addenda, Code cases 1516.1, 1567, 1622, 1635.1, 1677 (b) Applicable Edition of Section XI Utilized-for Repairs or Replacements 1989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code NameoNameof Manufacturer ; Board Other Year Replaced Stamped Component Manufacturer Serial No. Identification Built or Replacement(YesorNo)

Valve ANCHOR/DARLING E-6214-19-1 NA lE2FlOO6 1979 REPLACEMENT Yes

7. Description of Work On valve 2E21F006 install modification M-079 per ECN 333700 to modify hinge pins and covers to convert valve from a testable check valve to a simple check.
8. Tests Conducted:

Hydrostatic [ ] Pneumatic [ I Pressure N/A psi Test Temp. N/A Nominal Operating Pressure [XI Exempt [ I Other [ I

9. Remarks Code Parts Installed:

Valve Modification Kit (Hinge Pin Covers, Hinge Pin Cover Studs) - UTC 2110677

____ ____ ____ ___I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Sec In Xi. (repair or replacement)

Signed r r/ Pu

.,efk Date _ 5)

! 0, e rwner's Designee, tie `---_7 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed bv Hartford Steam Boiler n' have inspected the components described in this Owner's Report during the period r 03/19/2002 to 05/0612004 , and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or propety damage or a loss of any kind arising from or connected with this Inspecti9 it,_

Commissions IL 1721 Inspector's gature National Board, State, Province Date 1 M A 2 00tY

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-069 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 05/06/2004 Address Sheet 1 of 1 Unit 1
2. Plant Clinton Power Station

-- Name 00553685 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 228, Clinton, IL 61727 N/A Expiration Date

- Address

4. Identification of System NRI01 Code Cli 2
5. (a) 1) Applicable Construction Code (Piping) Section III 74 Edition, S74 Addenda, Code cases NONE (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, No Addenda Code Cases N-416-1 - -  !-I
6. Identification of Components Repaired or Replaced'and Replacement Components ASME National ReardCode Nameof Name of Manufacturer Board Other Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Piping ILLINOIS POWER PIPING SYSTEM N/A NRI01 1986 REPLACEMENT Yes

7. Description of Work On line 1R104B-80 eliminate abandoned pipe by removal and insertion of a straight spool piece in accordance with EC341364
8. Tests Conducted:

Hydrostatic [ ] Pneumatic 1 ] Pressure N/A psi Test Temp. N/A OF Nominal Operating Pressure (X] Exempt I] Other ))Code Case N-416-1 9 Remarks Replacement Material:

Piping - 8" - Cat I.D. # 1154587-1, UTC 2688570

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, SectioXI. (repair or replacement)

Signed / o BDate 4 n, 25 206 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler A (^.

have inspected the components described In this Owner's Report during the period ax 06/1012003 to 05/06/2004 ,and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neitherihe Inspector nor his employer shall be liable In any manner for any personal injury or propert dWamage or a loss of any kind arising from or connected with this inspectiq . Go i

/_l_ _ _ Commissions IL 1721 Inspector's Sig ature National Board, State, Province Date , 20_

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

1. Owner AmerGen Energy Co., LLC Data Report No. RF-9-070 Name 965 Chesterbrook Blvd., Wayne, PA 19087 Date 05/14/2004 Address Sheet 1 of. 1 Unit 1
2. Plant Clinton Power Station Name 00489998 RR3 Box 228, Clinton, IL 61727 Repair Organization P.O. No., Job No.

Address Type Code Symbol Stamp N/A

3. Work Performed by: Clinton Power Station Authorization No. N/A RR3 Box 226, Clinton, IL 61727 N/A Expiration Date Address
4. Identification of System NRT05 Code Cli 2
5. (a) 1) Applicable Construction Code (Piping) Section III 1974 Edition, S74 Addenda, Code cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacementsl989 Edition, No Addenda Code Cases None
6. Identification of Components Repaired or Replaced and Replacement Components ASME National Repaired Code Name of Name of Manufacturer Board Other . Year Replaced Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)

Piping ILLINOIS POWER PIPING SYSTEM NA NRT05 1986 Replacement Yes

7. Description of Work On line lRT06D-40 replace existing blank flange on the decon connection with a new flange with test connections per EC 339013.
8. Tests Conducted:

Hydrostatic [ I Pneumatic j I Pressure N/A psi Test Temp. N/A Nominal Operating Pressure [X] Exempt [ I Other I I

9. Remarks 4 inch flange received per Cat I.D. V 1146185, UTC 2118539 Note: test connection valves and piping exempt per size <1".

I CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this Replacement conforms to the rules of the ASME Code, Secti Xl. (repair or replacement)

Signed 6 , ,,

oP Date ( 3 207/5 8 J~ - ~~ e, ilie CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boiler .' A,*

have inspected the components described in this Owner's Report during the period 0611912003 to 0511412004 , and state that to the best of my knowledge and belief the Owner has Y/

performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal iniu or property ma or a loss of any kind arising from or connected with this Inspectso o ()

Commissions IL 1721 Inspector's Signatuz~ National Board, State, Province Date / ,20 °I