ENS 5471013 May 2020 18:01:00At 1000 CDT on May 13, 2020, the Byron Station Technical Support Center (TSC) emergency ventilation system inlet isolation damper would not open as required to support system operation. This failure affected the ability of the TSC ventilation system to maintain adequate radiological habitability in the event of an emergency with an airborne radiological release. All other capabilities of the TSC were unaffected by this condition. If an emergency was declared requiring TSC activation during this period, the TSC would be staffed and activated using existing emergency planning procedures. If the TSC became uninhabitable, the Station Emergency Director would relocate the TSC staff to an alternate TSC location in accordance with applicable procedures. The TSC emergency ventilation system inlet isolation damper has been repaired and is now functional. This event is reportable in accordance with 10 CFR 50.72(b)(3)(xiii) because the discovered condition affected the functionality of an emergency response facility. The NRC Resident Inspector has been notified.