ENS 5541618 August 2021 13:51:00At 1036 CDT on 8/18/2021, Wolf Creek experienced a reactor trip due to low level in B Steam Generator. Auxiliary feedwater system actuated as designed. All systems actuated as expected. Decay heat is currently being removed by the auxiliary feedwater system. The NRC Senior Resident Inspector has been informed. All control rods fully inserted, and offsite power remained available.