 Entered dateEvent description
ENS 556843 January 2022 15:58:00The following information was provided by the licensee via email: At 1223 (EST) on 01/03/2022, Calvert Cliffs Unit 2 automatically tripped from 100 percent power due to loss of electrical load. The cause is under investigation. The site Senior Resident Inspector has been notified. The following additional information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance: All rods inserted and decay heat is being removed via the condenser. The plant is in a normal shutdown electrical lineup. There was no impact on Unit 1.
ENS 550203 December 2020 17:10:00At 0923 EST on December 3, 2020, with Unit 1 in Mode 1 at 100 percent power, an actuation of the Emergency AC Electrical Power System (Emergency Diesel Generator 1A) occurred during normal plant operations. The reason for Emergency Diesel Generator 1A auto start was due to Class 1E 4KV Bus 11 feeder breaker opening. The Emergency Diesel Generator 1A automatically started as designed when the loss of voltage signal on 4KV Bus 11 was received. This event is being reported in accordance with 10 CFR 50.72(b)(3)(iv)(A) as an event that resulted in a valid actuation of the Emergency AC Electrical Power System. There was no impact on the health and safety of the public or plant personnel. The NRC Resident Inspector has been notified. The cause of the 4KV Bus 11 Feeder Breaker opening is unknown at the present time and is under investigation.