Semantic search

Jump to navigation Jump to search
 Start dateReporting criterionTitleEvent descriptionSystemLER
ENS 5265030 March 2017 13:22:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed ConditionUnanalyzed Condition Due to Potential Tornado Generated MissilesDuring the evaluation of tornado missile vulnerabilities and the potential impacts to safety-related plant equipment, it was concluded that the following structures are vulnerable to tornado generated missiles: All five of the Unit 1 and Unit 2 Emergency Diesel Generator (EDG) fuel oil storage tanks have ventilation pipe extending approximately 5 feet above grade. In the event that a tornado missile impact occurs on the aforementioned ventilation piping, there is a possibility that the vent lines could crimp. This could prevent the tanks from venting and inhibit the transfer of fuel oil from the main fuel oil storage tanks to the day tank. Ultimately, this causes the emergency diesels to be inoperable. These conditions are reportable per 10 CFR 50.72(b)(3)(ii)(B) and 10 CFR 50.72(b)(3)(v)(D) for any event or condition that results in the nuclear power plant being in an unanalyzed condition that significantly degrades plant safety and also an event or condition that could have prevented fulfillment of a safety function needed to mitigate the consequence of an accident. This issue is being addressed in accordance with EGM-15-002, Revision 1, Enforcement Discretion for Tornado-Generated Missile Protection Noncompliance. The NRC Resident Inspector has also been notified.Emergency Diesel Generator
ENS 525313 February 2017 19:58:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed ConditionUnanalyzed Condition - Appendix R Fire AnalysisIn preparation for transitioning the Plant Hatch Fire Protection Licensing Basis from 10CFR50.48(b) (Appendix R) to 10CFR50.48(c) (NFPA 805), a weak-link and operator manual action (OMA) analysis for Information Notice (IN) 92-18 type hot shorts on motor-operated valves (MOVs) was performed to support the Plant Hatch Appendix R Safe Shutdown Analysis. As a result of the analysis, it was identified that cable impacts can bypass valve limit and torque switches, resulting in physical damage to valves required for Safe Shutdown. This would prevent the valves from being operated locally or being operated from the remote shutdown panel. These cable failures could also cause the valve motors to fail. This updated analysis has identified circuit configuration deficiencies in Fire Areas 0024 A & C (Main Control Room & Cable Spread Room), 1203F (U1 Reactor Building SE), 1205F (U1 Reactor Building NE), and 2203F (U2 Reactor Building NE). Therefore, due to the identified deficient conditions, it was determined that in the event of a postulated fire in the affected fire areas, the paths of safe shutdown on the affected unit(s) could be compromised and impact the ability to achieve safe shutdown conditions. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions in these same fire areas. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded conditions can be repaired. CRs 10326399, 10326401, 10326402, 10326404 and 10326405 The licensee notified the NRC Resident Inspector. The unanalyzed condition is applicable to 10CFR50.48(b) Appendix R and not to 10CFR50.48(c) (NFPA 805).Remote shutdown
ENS 511204 June 2015 14:03:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed ConditionUnanalyzed Condition for a Postulated Fire

In preparation for transitioning the Plant Hatch Fire Protection Licensing Basis from 10 CFR 50.48(b) (Appendix R) to 10 CFR 50.48(c) (NFPA 805), an update to the Plant Hatch Appendix R Safe Shutdown Analysis has been performed for the Unit 1 and Unit 2 Reactor Buildings. This updated analysis has identified circuit configurations in four Fire Areas where an Appendix R postulated fire could impact the ability to achieve safe shutdown conditions. These are Category 1 barrier impairments. In the Unit 1 Safe Shutdown Analysis, RCIC (1E51C001) (Path 1) components are impacted by a fire in Fire Area 1203. The postulated failure described above impacts HPCI (1E41C001) (Path 2) operation. Therefore, in the updated analysis there is no safe shutdown method for high pressure injection that remains free of fire damage for an Appendix R postulated fire in Fire Area 1203. While this represents an unanalyzed condition for Appendix R, the described scenario is only possible given a fire has occurred in Fire Area 1203. In the Unit 1 Safe Shutdown Analysis, Path 2 components are impacted by a fire in Fire Area 1205. The postulated failure described above impacts the 1E 4160 Kv (1R22S005) emergency bus power to Path 1 components. Therefore, in the updated analysis there is no safe shutdown method that remains available for an Appendix R postulated fire in Fire Area 1205. While this represents an unanalyzed condition for Appendix R, the described scenario is only possible given a fire has occurred in Fire Area 1205. In the Unit 2 Safe Shutdown Analysis, Path 2 components are impacted by a fire in Fire Area 2205. The postulated failure described above impacts the 2E 4160 Kv (2R22S005) emergency bus power to Path 1 components. Therefore, in the updated analysis there is no safe shutdown method that remains available for an Appendix R postulated fire in Fire Area 2205. While this represents an unanalyzed condition for Appendix R, the described scenario is only possible given a fire has occurred in Fire Area 2205. In the updated post-fire safe shutdown model, both safe shutdown paths include the same three options for Torus Water Temperature indication (1T48R072, 1T47R611 or 1T47R612). Only one of these three components is required to succeed, however, all are impacted by the postulated fire. Thus, there is no Unit 1 Torus Water Temperature Indication available for a fire in Fire Area 1205. While this represents an unanalyzed condition for Appendix R, the described scenario is only possible given a fire has occurred in Fire Area 1205. Based on the updated Plant Hatch Appendix R Safe Shutdown analysis recommendations and the plant's Fire Hazard Analysis (FHA), compensatory measures have been taken and will remain in place until the conditions are resolved. The presence of the compensatory measures, in addition to portable fire protection equipment and installed fire protection and detection equipment, ensures the safe shutdown paths are preserved until the conditions are resolved. CR 10079009, 10079019, 10079022, 10079025 The licensee has notified the NRC Resident Inspector.

  • * * UPDATE FROM STANLEY STONE TO DONALD NORWOOD AT 1634 EDT ON 6/17/2015 * * *

In preparation for transitioning the Plant Hatch Fire Protection Licensing Basis from 10 CFR 50.48(b) (Appendix R) to 10 CFR 50.48(c) (NFPA 805), an update to the Plant Hatch Appendix R Safe Shutdown Analysis has been performed for the Unit 1 and Unit 2 Turbine Building. This updated analysis has identified circuit configurations in two Fire Areas where an Appendix R postulated fire could impact the ability to achieve safe shutdown conditions. These are Category 1 barrier impairments. 1) In the Unit 1 Safe Shutdown Analysis, Path 1 RCIC components are impacted by a fire in Fire Area 1105. The postulated failure would impact Path 2 (HPCI) operation. Therefore, in the current analysis for the credited safe shutdown method for high pressure injection may be affected for an Appendix R postulated fire in Fire Area 1105. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 1105. 2) In the updated post-fire safe shutdown model, both safe shutdown paths include the same two options for Torus Water Level Indication: 2T48-R622A and 2T48-R622B. Only one of these two components is required to succeed, however both would be impacted by a postulated fire in Fire Area 2104. Consequently, both credited paths of Unit 2 Torus Water Level Indication could potentially be affected due to a fire in Fire Area 2104. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 2104. Based on the updated Plant Hatch Appendix R Safe Shutdown analysis recommendations and the plant's Fire Hazard Analysis (FHA), compensatory measures have been taken and will remain in place until the conditions are resolved. The presence of the compensatory measures, in addition to portable fire protection equipment and installed fire protection and detection equipment, ensures the safe shutdown paths are preserved until the conditions are resolved. The analysis associated with the transition of the Plant Hatch Fire Protection Licensing Basis from Appendix R to NFPA 805 is continuing, and this and any subsequent similar conditions that meet reporting requirements will be in included in an ENS Update Report. CR 10084753, CR 10084757. The licensee notified the NRC Resident Inspector. Notified R2DO (HAAG).

  • * * UPDATE FROM SCOTT BRITT TO VINCE KLCO ON 6/24/15 AT 2114 EDT * * *

In preparation for transitioning the Plant Hatch Fire Protection Licensing Basis from 10 CFR 50.48(b) (Appendix R) to 10 CFR 50.48(c) (NFPA 805), an update to the Plant Hatch Appendix R Safe Shutdown Analysis has been performed for the Diesel Generator Building. This updated analysis has identified circuit configurations in five Fire Areas where an Appendix R postulated fire could impact the ability to achieve safe shutdown conditions. These are Category 1 barrier impairments. 1) An Appendix R postulated fire in Fire Area 1404 is assessed to impact a cable required for RHR Inboard Injection Valve A, 1E11-F015A, to open. This cable was not identified in the current Safe Shutdown Analysis Report (SSAR) for this component. This valve is normally closed and is required to open to support the operation of RHR Loop A in LPCI mode, which is the credited Low Pressure Injection system for Unit 1 in support of Inventory Control to the RPV for a fire in Fire Area 1404. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 1404. RHR Loop B is not available in this fire area due to fire impacts. 2) An Appendix R postulated fire in Fire Area 1408 is assessed to impact cables required for RHR Inboard Injection Valve B, 1E11-F015B, to open. These cables were not identified in the current Safe Shutdown Analysis Report (SSAR) for this component. This valve is normally closed and is required to open to support the operation of RHR Loop B in LPCI mode, which is the credited Low Pressure Injection system for Unit 1 in support of Inventory Control to the RPV for a fire in Fire Area 1408. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 1408. RHR Loop A is not available in this fire area due to fire impacts. 3) An Appendix R postulated fire in Fire Area 1412 is assessed to impact a cable required for RHR Inboard Injection Valve B, 1E11-F015B, to open. This cable was not identified in the current Safe Shutdown Analysis Report (SSAR) for this component. This valve is normally closed and is required to open to support the operation of RHR Loop B in LPCI mode, which is the credited Low Pressure Injection system for Unit 1 in support of Inventory Control to the RPV for a fire in Fire Area 1412. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 1412. RHR Loop A is not available in this fire area due to fire impacts. 4) An Appendix R postulated fire in Fire Area 2404 is assessed to impact a cable required for RHR Inboard Injection Valve B, 2E11-F015B, to open. This cable was not identified in the current Safe Shutdown Analysis Report (SSAR) for this component. This valve is normally closed and is required to open to support the operation of RHR Loop B in LPCI mode, which is the credited Low Pressure Injection system for Unit 2 in support of Inventory Control to the RPV for a fire in Fire Area 2404. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 2404. RHR Loop A is not available in this fire area due to fire impacts. 5) An Appendix R postulated fire in Fire Area 2408 is assessed to impact cables required for RHR Inboard Injection Valve B, 2E11-F015B, to open. These cables were not identified in the current Safe Shutdown Analysis Report (SSAR) for this component. This valve is normally closed and is required to open to support the operation of RHR Loop B in LPCI mode, which is the credited Low Pressure Injection system for Unit 2 in support of Inventory Control to the RPV for a fire in Fire Area 2408. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 2408. RHR Loop A is not available in this fire area due to fire impacts. Based on the updated Plant Hatch Appendix R Safe Shutdown analysis recommendations and the plant's Fire Hazard Analysis (FHA), compensatory measures have been taken and will remain in place until the conditions are resolved. The presence of the compensatory measures, in addition to portable fire protection equipment and installed fire protection and detection equipment, ensures the safe shutdown paths are preserved until the conditions are resolved. The analysis associated with the transition of the Plant Hatch Fire Protection Licensing Basis from Appendix R to NFPA 805 is continuing, and this and any subsequent similar conditions that meet reporting requirements will be in included in an ENS Update Report. CR 10088142 The licensee will notify the NRC Resident Inspector. Notified the R2DO (O'Donohue).

  • * * UPDATE AT 1739 EDT ON 08/13/15 FROM PAUL UNDERWOOD TO JEFF HERRERA * * *

In preparation for transitioning the Plant Hatch Fire Protection Licensing Basis from 10 CFR 50.48(b) (Appendix R) to 10 CFR 50.48(c) (NFPA 805), an update to the Plant Hatch Appendix R Safe Shutdown Analysis has been performed for the Control Building. This updated analysis has identified circuit configurations in a Fire Area where an Appendix R postulated fire could impact the ability to achieve safe shutdown conditions. This is a Category 1 barrier impairment. 1) An Appendix R postulated fire in Fire Area 0014 is assessed to impact a cable that is required for Diesel Building MCC 1C, 1R24-S027, to remain energized. Further analysis has shown that an inter-cable hot short between two conductors could cause the feeder breaker to this MCC to trip. This MCC is required to support the operation of Diesel Generator 1C, which is a credited power source in the Safe Shutdown analysis for both Unit 1 and Unit 2 in the event of a fire in this area. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 0014. Based on the updated Plant Hatch Appendix R Safe Shutdown analysis recommendations and the plant's Fire Hazard Analysis (FHA), compensatory measures have been taken and will remain in place until the conditions are resolved. The presence of the compensatory measures, in addition to portable fire protection equipment and installed fire protection and detection equipment, ensures the safe shutdown paths are preserved until the conditions are resolved. CR 10108999. The licensee notified the NRC Resident Inspector. Notified the R2DO (Nease).

  • * * UPDATE AT 1331 EDT ON 08/25/15 FROM JOHN MITCHELL TO JEFF HERRERA * * *

In preparation for transitioning the Plant Hatch Fire Protection Licensing Basis from 10 CFR 50.48(b) (Appendix R) to 10 CFR 50.48c (NFPA 805), an update to the Plant Hatch Appendix R Safe Shutdown Analysis has been performed for the Diesel Building. This updated analysis has identified circuit configurations in a Fire Area where an Appendix R postulated fire could impact the ability to achieve safe shutdown conditions. This is Category 1 barrier impairment. 1) An Appendix R postulated fire in Fire Area 1408 is assessed to impact a cable that is required for Station Battery Chargers 1D, 1E, and 1F to remain energized. These chargers support 125V DC Switchgear 1B which is the credited DC Switchgear for Unit 1 Path 2 Safe Shutdown in the event of a fire in this area. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 1408. 2) An Appendix R postulated fire in Fire Area 2408 is assessed to impact a cable that is required for Station Battery Chargers 2D, 2E, and 2F to remain energized. These chargers support 125V DC Switchgear 2B which is the credited DC Switchgear for Unit 2 Path 2 Safe Shutdown in the event of a fire in this area. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 2408. Based on the updated Plant Hatch Appendix R Safe Shutdown analysis recommendations and the plant's Fire Hazard Analysis (FHA), compensatory measures have been taken and will remain in place until the conditions are resolved. The presence of the compensatory measures, in addition to portable fire protection equipment and installed fire protection and detection equipment, ensures the safe shutdown paths are preserved until the conditions are resolved. The analysis associated with the transition of the Plant Hatch Fire Protection Licensing Basis from Appendix R to NFPA 805 is continuing, and this and any subsequent similar conditions that meet reporting requirements will be in included in an ENS Update Report.

CR 10113740, CR 10113745 The Licensee notified the NRC Resident Inspector. Notified the R2DO (Rose).

  • * * UPDATE FROM KENNY HUNTER TO DONALD NORWOOD AT 1717 EDT ON 8/28/2015 * * *

In preparation for transitioning the Plant Hatch Fire Protection Licensing Basis from 10 CFR 50.48(b) (Appendix R) to 10 CFR 50.48(c) (NFPA 805), an update to the Plant Hatch Appendix R Safe Shutdown Analysis has been performed for the Turbine Building. This updated analysis has identified circuit configurations in a Fire Area where an Appendix R postulated fire could impact the ability to achieve safe shutdown (SSD) conditions. This is a Category 1 barrier impairment. 1) An Appendix R postulated fire in Fire Area 1105 is assessed to impact cables which are required for HPCI Steam Supply Isolation MOV, 1E41-F002, to remain open. This valve is required open in support of HPCI (SSD Path 2), which is the credited form of high pressure injection in this fire area. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 1105. 2) An Appendix R postulated fire in Fire Area 1104 is assessed to impact a cable required for the RCIC Vacuum Breaker Isolation MOV, 1E51-F105, to remain open. This valve is required open to ensure operability of the RCIC turbine if RCIC is required to stop and restart. Failure of this valve to remain open could cause a siphon that would impact the operability of RCIC, and thus disable Safe Shutdown Path 1 High Pressure Injection. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 1104. In preparation for transitioning the Plant Hatch Fire Protection Licensing Basis from 10 CFR 50.48(b) (Appendix R) to 10 CFR 50.48(c) (NFPA 805), an update to the Plant Hatch Appendix R Safe Shutdown Analysis has been performed for the Reactor Building. This updated analysis has identified circuit configurations in a Fire Area where an Appendix R postulated fire could impact the ability to achieve safe shutdown conditions. This is a Category 1 barrier impairment. 1) An Appendix R postulated fire in Fire Area 1203 is assessed to impact a cable required for HPCI Steam Supply Isolation MOV, 1E41-F002, to remain open. This valve is required open to ensure steam flow to the HPCI turbine. Failure of this valve to remain open would isolate steam to the HPCI turbine, which would disable HPCI, and thus disable Safe Shutdown Path 2 High Pressure Injection. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 1203. 2) An Appendix R postulated fire in Fire Area 2203 is assessed to impact cables required for RHR Outboard Injection Valve B, 2E11-F017B, to remain open. This valve is required open to support RHR Loop B in LPCI mode, which is the credited lineup for Path 2 Safe Shutdown Decay Heat Removal. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 2203. 3) An Appendix R postulated fire in Fire Area 2203 is assessed to impact cables required for HPCI Vacuum Breaker Isolation Valve, 2E41-F104, to remain open. This valve is required open in support of Safe Shutdown Path 2 High Pressure Injection. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 2203. Based on the updated Plant Hatch Appendix R Safe Shutdown analysis recommendations and the plant's Fire Hazard Analysis (FHA), compensatory measures have been taken and will remain in place until the conditions are resolved. The presence of the compensatory measures, in addition to portable fire protection equipment and installed fire protection and detection equipment, ensures the safe shutdown paths are preserved until the conditions are resolved. The analysis associated with the transition of the Plant Hatch Fire Protection Licensing Basis from Appendix R to NFPA 805 is continuing, and this and any subsequent similar conditions that meet reporting requirements will be in included in an ENS Update Report. CR 10115432, CR10115473, CR10115436, CR10115446, CR10115444 The licensee will notify the NRC Resident Inspector. Notified R2DO (Rose).

  • * * UPDATE PROVIDED BY GUY GRIFFIS TO JEFF ROTTON AT 1815 EDT ON 09/04/2015 * * *

In preparation for transitioning the Plant Hatch Fire Protection Licensing Basis from 10 CFR 50.48(b) (Appendix R) to 10CFR50.48(c) (NFPA 805), an update to the Plant Hatch Appendix R Safe Shutdown Analysis has been performed for the Control Building and Reactor Building. This updated analysis has identified circuit configurations in Fire Area's where an Appendix R postulated fire could impact the ability to achieve safe shutdown (SSD) conditions. These are Category 1 barrier impairments. 1) An Appendix R postulated fire in Fire Area 0024 is assessed to impact a cable that is required for Torus Suction Valve, 1E11-F065B to remain open. This valve is required to remain open in support of LPCI train B which is credited for Unit 1 Safe Shutdown in the event that the RPV has spuriously depressurized and low pressure inventory control is performed from the remote shutdown panel. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 0024. 2) An Appendix R postulated fire in Fire Area 0024 is assessed to impact a cable required for Torus Suction Valve, 2E11-F065B to remain open. This valve is required to remain open in support of LPCI train B which is credited for Unit 2 Safe Shutdown in the event that the RPV has spuriously depressurized and low pressure inventory control is performed from the remote shutdown panel. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 0024. 3) An Appendix R postulated fire in Fire Area 0014 is assessed to impact all three Air Handling Units; 1Z41-B003A, 1Z41-B003B, and 1Z41-B003C. The fire impacts a cable required for MCC 1C, 1R23-S003 to remain energized. This MCC supports the operation of Air Handling Unit B, 1Z41-B003B which is required in support of Main Control Room HVAC. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 0014. 4) An Appendix R postulated fire in Fire Area 0031 is assessed to impact all three Air Handling Units; 1Z41-B003A, 1Z41-B003B, and 1Z41-B003C. These AHUs are required in support of MCR HVAC. MCR HVAC was not required in the current Safe Shutdown Analysis Report, and thus these failures were not evaluated in this fire area. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 0031. 5) An Appendix R postulated fire in Fire Area 2014 is assessed to impact a cable required for Station Battery Chargers 2A (2R42-S026) 2B (2R42-S027) and 2C (2R42-S028) to remain energized. These chargers support 125 VDC Switchgear 2A (2R22-S016), which is the credited DC Switchgear for Path 1 Safe Shutdown. Path 2 Safe Shutdown is not available in this fire area due to fire impacts. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 2014. 6) An Appendix R postulated fire in Fire Area 2014 is assessed to impact a cable required for 125 VDC Switchgear 2A (2R22-S016) to remain energized. This is the credited DC Switchgear for Path 1 Safe Shutdown. Path 2 Safe Shutdown is not available in this fire area due to fire impacts. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 2014. 7) An Appendix R postulated fire in Fire Area 0014 is assessed to impact cables required for Station Battery Chargers 1D (1R42-S029), 1E (1R42-S030), and 1F (1R42-S031) to remain energized. These chargers support 125VDC Switchgear 1B (1R22-S017) which is the credited DC Switchgear for Path 2 Safe Shutdown. Path 1 Safe Shutdown is not available in this fire area due to fire impacts. While this represents an unanalyzed condition for Appendix R, the described scenario presumes a fire has occurred in Fire Area 0014. Based on the updated Plant Hatch Appendix R Safe Shutdown analysis recommendations and the plant's Fire Hazard Analysis (FHA), compensatory measures have been taken and will remain in place until the conditions are resolved. The presence of the compensatory measures, in addition to portable fire protection equipment and installed fire protection and detection equipment, ensures the safe shutdown paths are preserved until the conditions are resolved. The analysis associated with the transition of the Plant Hatch Fire Protection Licensing Basis from Appendix R to NFPA 805 is continuing, and this and any subsequent similar conditions that meet reporting requirements will be in included in an ENS Update Report. CR 10118312, CR 10118328, CR10118333, CR10118338, CR10118345 The licensee will notify the NRC Resident Inspector. Notified R2DO (Seymour)

HVAC
Remote shutdown
Decay Heat Removal
ENS 5107014 May 2015 20:00:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed ConditionUnanalyzed Condition Due to Excessive Toxic Chemicals Onsite

On May 14, 2015, it was determined that the number of 55 gallon drums of 2-Butoxyethanol analyzed to be transported and stored within the owner-controlled area (OCA) at any one time had been exceeded. It was discovered that contrary to the toxic gas analysis performed, fourteen 55-gallon drums of 2-Butoxyethanol were transported and stored in the OCA to support the construction of a dome being built to provide storage for FLEX equipment. The number of drums exceeded the limitation specified in the toxic gas analysis performed as part of the design project for transportation and storage could potentially impact Control Room habitability, emergency diesel generator air intake and have an adverse impact on security personnel. Upon determination that an unanalyzed condition existed, Operations placed the control room ventilation system in the 'isolation mode' until the number of drums on-site was reduced within the analyzed number. A substantial covering had been placed over the drums which also decreased the likelihood that any of the drums would fail and would also limit the potential dispersion of chemicals should a breach occur. The excess number of drums of 2-Butoxyethanol being transported and stored on-site is considered an unanalyzed condition that significantly degraded plant safety and is reportable in accordance with 10CFR50.72(b)(3)(ii)(B). The allowed number of 55 gallon drums of 2-butoxyethanol allowed per the current toxic gas analysis is 4 drums. The number of drums has been reduced to 2 as of 2024 EDT. The licensee has notified the NRC Resident Inspector.

  • * * UPDATE FROM PAUL UNDERWOOD TO VINCE KLCO ON 7/8/2015 AT 1657 EDT * * *

Further investigation into the chemicals transported on-site (F183M, of which 2-Butoxyethanol is a component) revealed that an on-site spill of all fourteen 55-gallon drums will not adversely affect Main Control Room Habitability, Security Personnel, or the Emergency Diesel Generators (EDGs). The Control Room Habitability Determination flowchart in Attachment 3 of NMP-CH-002-002 establishes a 10 mmHg vapor pressure threshold for determining if chemicals need to be evaluated for impact on the Main Control Room. Chemicals with a vapor pressure less than 10 mmHg do not need to be evaluated for control room habitability. The basis for the threshold is found in Reg Guide 1.78 Revision 0 section C.5.a, 'For chemicals that are not gases at 100F and normal atmospheric pressure but are liquids with vapor pressures in excess of 10 torr (10 mmHg), consideration should be given to the rate of flashing and boil off to determine the rate of release to the atmosphere and the appropriate time duration of the release.' The individual chemical component (including 2-Butoxyethanol) vapor pressures are less than 10 mmHg. As their vaporization rate is too low to adversely affect Control Room Habitability, it is also too low to create a hazard for Security personnel or to adversely affect the Emergency Diesel Generators. Based on this information, the transportation and storage of these chemical barrels did NOT represent a condition that significantly degraded plant safety. As such, this condition has been determined to no longer meet reporting requirement 10CFR50.72(b)(3)(ii)(B) and is therefore NOT reportable. Based on this information the previous notification for Event 51070 is being retracted. The licensee notified the NRC Resident Inspector Notified the R2DO (McCoy).

Emergency Diesel Generator
ENS 506629 December 2014 23:25:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed ConditionNon-Functional Fire Barrier Discovered Affecting Both Safe Shutdown Paths

During an inspection of a fire penetration between Fire Area 1404, Switchgear Room 1G and Fire Area 1408, Switchgear Room 1F in the diesel generator building, the penetration was determined to be non-functional as a 3 hour fire barrier. In the event of a postulated fire in the affected areas, both safe shutdown paths on Unit 1 could be compromised. Given this information, the determination was made that this condition meets the reporting criteria of 10 CFR 50.72(b)(3)(ii)(B). Compensatory measures were established in accordance with the plant's Fire Hazard Analysis (FHA). The presence of the compensatory measures in addition to automatic fire detection in the fire areas ensure that the safe shutdown paths are preserved until the degraded condition can be repaired. (Condition report No.) CR904013 The licensee notified the NRC Resident Inspector

  • * * RETRACTION PROVIDED BY KENNY HUNTER TO JEFF ROTTON AT 0915 EST ON 12/30/2014 * * *

Further investigation revealed that after removing the outermost two inches of loose silicone foam material, and taking additional measurements there remained adequate silicone foam material to provide 10 inches of silicone foam sealing the penetration. Plant design shows that the wall in question is 18 inches thick and also that 9 inches of silicone foam is required in the penetration in order maintain a 3 hour fire rating for the wall/penetration. Since there is adequate foam in the penetration to maintain the 3 hour fire rating the penetration is fully functional. Based on this information, this penetration in its 'as found' state does NOT represent a condition that seriously degrades a principal safety barrier. As such this condition has been determined to no longer meet reporting requirement 10CFR50.72(b)(3) and is therefore NOT reportable. Based on this information the previous notification for Event 50662 is being retracted. The licensee notified the NRC Resident Inspector. Notified R2DO (Bartley)

ENS 5062919 November 2014 21:18:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed ConditionFire Penetration Not Meeting RequirementsDuring a fire inspection activity involving inspection of fire penetrations that serve as Appendix R barriers, degradation of a fire penetration was identified that was sufficient to prevent this penetration from meeting Appendix R requirements as a 3 hour fire barrier. In the event of a postulated fire in the affected areas both safe shutdown paths on Unit 1 and 2 could be compromised. Given this information the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B). Compensatory measures were put in place in accordance with the plant's Fire Hazard Analysis (FHA) for the degraded penetration in the affected fire areas. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded conditions can be corrected. The degraded fire penetration is located between the turbine deck and the main control room. The licensee has notified the NRC Resident Inspector.
ENS 5045513 September 2014 07:07:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed ConditionFire Penetration Did Not Meet Appendix R RequirementsA fire penetration on the Unit 1 reactor building 158 foot elevation was discovered to be degraded such that the associated wall would not meet Appendix R requirements as a 3-hour barrier. In the event of a postulated fire in either of the affected fire areas, separated by the affected penetration, both Unit 1 safe shutdown paths could be compromised. Given this information, the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B). Compensatory measures were established in accordance with the plant's Fire Hazard Analysis (FHA). The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition can be corrected. Condition Report: 865615 The NRC Resident Inspector has been informed.
ENS 503517 August 2014 21:07:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed ConditionUnanalyzed Condition Due to Discovery of Degraded Fire Barrier Walls

During a fire inspection activity involving inspection of fire walls that serve as Appendix R barriers, degradation of some fire walls was identified that was sufficient to prevent these walls from meeting Appendix R requirements as 3-hour fire barriers. In the event of a postulated fire in the affected areas, both safe shutdown paths on the affected unit could be compromised. Given this information, the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B). Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded penetrations in these same fire areas. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded conditions can be corrected. Condition Reports: 850802, 850819 In addition to automatic fire protection features, the licensee has posted fire watches as a compensatory measure. The licensee has notified the NRC Resident Inspector.

  • * * UPDATE FROM STANLEY STONE TO DONALD NORWOOD AT 1814 EST ON 11/24/2014 * * *

As part of the 'extent of condition' corrective action for the condition identified in EN 50351, an inspection activity is in progress to inspect the remaining fire walls for conditions similar to those reported on 8/7/2014. During this inspection, another condition was identified involving some degradation of the fire wall between Fire Area 1023 - RPS MG Set Room and Fire Area 1015 - Annunciator Room. In the event of a postulated fire in the affected areas both safe shutdown paths on Unit 1 could be compromised. Given this information, the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B). Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded penetrations in these same fire areas and will remain in place until the wall is repaired. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition is repaired. The inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS update report and will be documented in a revised LER at the end of the inspection activity. Condition Report: 898908. The licensee will notify the NRC Resident Inspector. Notified R2DO (Ehrhardt).

  • * * UPDATE FROM KENNY HUNTER TO DANIEL MILLS AT 1758 EST ON 11/25/2014 * * *

As part of the 'extent of condition' corrective action for the condition identified in EN 50351, an inspection activity is in progress to inspect the remaining fire walls for conditions similar to those reported on 8/7/2014. During this inspection, another condition was identified involving some degradation of the fire wall between Fire Area 1016 - 600 Volt Switchgear Room 1C and Fire Area 1017 - 600 Volt Switchgear Room 1D. In the event of a postulated fire in the affected areas, both safe shutdown paths on Unit 1 could be compromised. Given this information the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B). Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded penetrations in these same fire areas and will remain in place until the wall is repaired. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition is repaired. The inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS update report and will be documented in a revised LER at the end of the inspection activity. The licensee notified the NRC Resident Inspector. Notified R2DO (Ernstes).

  • * * UPDATE FROM SCOTT BRITT TO DONALD NORWOOD AT 1706 EST ON 12/4/2014 * * *

As part of the 'extent of condition' corrective action for the condition identified in EN 50351, an inspection activity is in progress to inspect the remaining fire walls for conditions similar to those reported on 8/7/2014. During this inspection, additional conditions were identified involving multiple fire barriers in the control building that affected both safe shutdown paths on Unit 1 and Unit 2 based on the respective inspection results. In the event of a postulated fire in the affected areas both safe shutdown paths on Unit 1 and 2 could be compromised. Given this information the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B). Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded penetrations in these same fire areas and will remain in place until the wall is repaired. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition is repaired. The inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS update report as required and will be documented in a revised LER at the end of the inspection activity. The licensee will notify the NRC Resident Inspector. Notified R2DO (Freeman).

  • * * UPDATE AT 1842 EST ON 12/12/2014 FROM G.S. GRIFFIS TO MARK ABRAMOVITZ * * *

As part of the 'extent of condition' corrective action for the condition identified in EN# 50351, an inspection activity is in progress to inspect the remaining fire walls and associated penetrations for conditions similar to those reported on 08/07/2014. During this inspection, nonconformances of multiple fire barriers were identified that bring into question the functionality of the affected fire barriers that can compromise safe shutdown paths on Unit 1 and 2 based on the respective inspection results. Since additional time is required to further evaluate each nonconformance to conclusively determine if the nonconformance is sufficient to consider the barrier nonfunctional, interim conservative fire actions were taken by considering these fire barriers as nonfunctional. Based on this conservative conclusion, in the event of a postulated fire in the affected areas both safe shutdown paths on Unit 1 and 2 could be compromised. Given this information the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B). Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded penetrations and fire walls in most of these same fire areas and will remain in place until the barrier(s) are repaired. Additional fire actions were taken as required to address the additional fire areas identified. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition is repaired. The inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report and will be documented in a revised LER at the end of the inspection activity. Unit 1 is entering a planned outage due to unrelated activities. Condition Report: 10000607 The licensee notified the NRC Resident Inspector. Notified the R2DO (Desai).

  • * * UPDATE FROM STANLEY STONE TO DONALD NORWOOD AT 2315 EST ON 1/15/2015 * * *

As part of the 'extent of condition' corrective action for the conditions identified in EN# 50351, an inspection activity was performed of a fire wall for conditions similar to those reported on 12/12/2014. During this inspection, another condition was identified involving some degradation of the fire wall between Fire Area 1008 - Unit 1 AC Inverter Room and Fire Area 0001 to consider the barrier nonfunctional. In the event of a postulated fire in the affected areas both safe shutdown paths on Unit 1 could be compromised. Given this information the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B). Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded fire barriers in these same fire areas and will remain in place until the wall is repaired. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition is repaired. The inspection activity is continuing and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report and will be documented in a revised LER at the end of the inspection activity. Condition Report: 10013077 The licensee notified the NRC Resident Inspector. Notified the R2DO (Musser).

  • * * UPDATE FROM JOHN MITCHELL TO JEFF HERRERA AT 2025 EST ON 1/21/2015 * * *

During review and closeout of fire barrier and penetration seals work orders and surveillance procedures performed as part of the 'extent of condition' inspection activity initially described in Event # 50351, the following conditions were identified that in the event of a postulated fire in the respective fire areas listed both safe shutdown paths could be compromised.

Unit 2 Control Bldg. el. 130', gap in the grout around conduit penetration between fire areas 2013 and 2015 Unit 1 Reactor Bldg. el. 130', open conduit between fire areas 1203C and 1105 Given this information the determination was made that this condition meets the reporting criteria of 10 CFR 50.72(b)(3)(ii)(B). Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded fire barriers in the Unit 2 fire area and will remain in place until the affected barrier areas are repaired. Compensatory measures were established for the Unit 1 areas and will remain in place until the affected barriers areas are repaired. The presence of the compensatory measures in addition to automatic fire detection in these fire areas ensure that the safe shutdown paths are preserved until the degraded condition is repaired. Subsequent similar condition(s) found when performing remaining inspections that meet the reporting requirements will be included in an ENS Update Report and will be documented in a revised LER at the end of the inspection activity.

Condition Report 10015417 Condition Report 10015437 The licensee notified the NRC Resident Inspector. Notified the R2DO (McCoy).

  • * * UPDATE FROM G.S. GRIFFIS TO HOWIE CROUCH AT 1714 EST ON 2/4/15 * * *

During the review of fire barrier surveillance procedures performed as part of the 'extent of condition' inspection activity for the event initially identified in EN# 50351, some degradation was observed on the east wall of fire area 2006. These nonconforming issues observed on the affected fire wall were identified as affecting both safe shutdown paths for Unit 2. Therefore, in the event of a postulated fire for the affected area, both safe shutdown paths on Unit 2 could be compromised. Given this information, the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B). Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire area and will remain in place until the wall is repaired. The presence of the compensatory measures, in addition to portable fire protection equipment located in adjacent areas, ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The extent of condition inspection activity is continuing, and this, and any subsequent similar condition(s) that meets the reporting requirements, will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10021623 Notified R2DO (HAAG).

  • * * UPDATE FROM JOHN MITCHELL TO DANIEL MILLS AT 1823 EST ON 2/18/15 * * *

During performance of work package closeouts to support the 'extent of condition' inspection activity for the event initially identified in EN# 50351, the following fire barriers were identified as failing to meet the procedure acceptance criteria: - Three penetrations separating Unit 1 Fire Areas 1013 and 0040 - A fire wall deficiency in the wall separating Unit 1 Fire Areas 1015 and 1013 These nonconforming issues observed on the affected penetrations and fire wall were identified as affecting both safe shutdown paths for Unit 1. Therefore, in the event of a postulated fire for the affected area, both safe shutdown paths on Unit 1 could be compromised. Given this information, the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B). Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire area and will remain in place until the wall is repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The extent of condition inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10028364 CR 10028366 The NRC Resident Inspector has been notified. Notified R2DO (Rose).

  • * * UPDATE AT 2035 EST ON 02/25/15 FROM SCOTT BRITT TO S. SANDIN * * *

During the review and closeout of a work package performed as part of the 'extent of condition' for the inspection activity initially described in EN #50351, a fire penetration seal was identified as failing to meet the procedure acceptance criteria. This penetration seal is located in the 2C Diesel Generator (DG) room and passes between Fire Area 2407 and 2408. The nonconforming issue observed on the affected penetration was identified as affecting both safe shutdown paths for Unit 2. Compensatory measures were established for the Unit 2 Areas and will remain in place until the affected barriers areas are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The extent of condition inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10032202 The licensee will inform the NRC Resident Inspector. Notified R2DO (Seymour).

  • * * UPDATE FROM SCOTT BRITT TO HOWIE CROUCH AT 2000 EST ON 3/4/15 * * *

During an expanded scope inspection, two deficiencies in the following areas were observed that caused the affected barriers to be considered nonfunctional: - Small imperfections and a hole through Penetration 1Z43-H116C that passes between Fire Area 1101G (Unit 1 Reactor Building Closed Cooling Water (RBCCW) Room) and Fire Area 1006 (Unit 1 Water Analysis Room), and - Gaps in a civil/architectural joint at the top of the south wall leading from Fire Area 1006 (Unit 1 Water Analysis Room) to Fire Area 0007A (East Corridor in the Control Bldg.). These nonconforming conditions observed for the affected penetration and fire barrier were identified as affecting both safe shutdown paths for Unit 1. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire area and will remain in place until the wall is repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS update report as required and will be documented in a revised LER at the end of the inspection activity. CR 10035730 The licensee will be notifying the NRC Resident Inspector. Notified R2DO (Sykes).

  • * * UPDATE FROM SCOTT BRITT TO DANIEL MILLS AT 2047 EDT ON 3/16/15 * * *

During an expanded scope inspection, deficiencies in the following areas were observed that caused the affected barriers to be considered nonfunctional: - Imperfections in three penetration seals (2Z43-H037C, 2Z43-H038C, and 2Z43-H177C) located in the 2A Battery Room separating Unit 2 Fire Areas 2004 and 2005 - Imperfections in fire penetration seal 2Z43-H644C located in the U2 Water Analysis Room separating Fire Area 2006 and 0007A - Imperfections in the grout between two tiers of concrete masonry wall and at the intersection of the walls in the upper northeast corner of the U2 Water Analysis Room separating Fire Areas 2006 and 0007A The nonconforming conditions observed for the affected penetrations and fire barriers were identified as affecting both safe shutdown paths for Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10041392, CR 10041394, and CR 10041397 The NRC Resident Inspector will be notified. Notified R2DO (Shaeffer)

  • * * UPDATE FROM JOHN MITCHELL TO HOWIE CROUCH AT 1619 EDT ON 3/17/15 * * *

During an expanded scope inspection, a fire penetration seal was observed to contain imperfections that did not meet acceptance criteria. Penetration seal 1Z43H542C is located between the U1 Corridor, Fire Area 0001, and the Unit 1 AC Inverter Room, Fire Area 1008, in the Unit 1 Control Building. The nonconforming issue observed on the affected penetration was identified as affecting both safe shutdown paths for Unit 1. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until all associated non-functional fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The extent of condition inspection activity is continuing and this, and any subsequent similar condition(s) that meets the reporting requirements, will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10041766 The licensee notified the NRC Resident Inspector. Notified R2DO (Desai).

  • * * UPDATE FROM GUY GRIFFIS TO HOWIE CROUCH AT 1648 EDT ON 3/18/15 * * *

During an expanded scope inspection, deficiencies in the following areas were observed that caused the affected barriers to be considered nonfunctional: - Gap in the concrete masonry wall at penetration seal 1Z43-H547C located between the Unit 1 AC Inverter Room (Fire Area 1008) and the Unit 1 Corridor (Fire Area 0001) - Gap in the annulus around the 2 inch continuous run penetration seal located between the Unit 1 AC Inverter Room (Fire Area 1008) and the Unit 1 Corridor (Fire Area 0001) - Gap in penetration seal 1Z43-H059C located between the Unit 1 AC Inverter Room (Fire Area 1008) and the Unit 1 Corridor (Fire Area 0001) The nonconforming conditions observed for the affected penetrations and barrier were identified as affecting both safe shutdown paths for Unit 1. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10042532; CR 10042530; CR 10042526 The licensee has notified the NRC Resident Inspector. Notified R2DO (Desai).

  • * * UPDATE FROM JOHN MITCHELL TO DANIEL MILLS AT 1814 EDT ON 3/31/15 * * *

During an expanded scope inspection, a fire wall was observed to contain a gap behind a 3 inch square plate attached to the thru-bolt anchor that did not meet acceptance criteria and caused the affected barrier to be considered nonfunctional. The affected fire barrier is located between the U2 RPS MG Set Room (Fire Area 2013) and the U2 Annunciator Room (Fire Area 2015). The nonconforming issue observed on the affected fire barrier was identified as affecting both safe shutdown paths for Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until all associated non-functional fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The extent of condition inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10048449 The licensee will notify the NRC Resident Inspector. Notified R2DO (Walker).

  • * * UPDATE FROM KEN HUNTER TO VINCE KLCO ON 4/13/15 AT 1722 EDT * * *

During an expanded scope inspection, deficiencies in the following areas were observed that caused the affected barriers to be considered nonfunctional: - Gap around penetration 1Z43H805D located between the Unit 1 East DC Switchgear Room 1D (Fire Area 1017) and the Unit 1 Transformer Room (Fire Area 1019). - Gaps in a fire barrier around a unistrut, below penetration 1Z43H012D, that are approximately 7 deep and into the CMU core located between the Unit 1 East DC Switchgear Room 1B (Fire Area 1020) and the Unit 1 130' Elevation Control Building Working Floor Hallway (Fire Area 0014K) - Gap in the top corner of the wall, above 1Z43H842D that protrudes into the CMU approximately 7 deep located between the Unit 1 East DC Switchgear Room 1B (Fire Area 1020) and the Unit 1 130' Elevation Control Building Working Floor Hallway (Fire Area 0014K) - Two anchor bolt holes east of penetration 1Z43H810D located between the Unit 1 East DC Switchgear Room 1B (Fire Area 1020) and the Unit 1 East DC Switchgear Room 1D (Fire Area 1017) The nonconforming conditions observed for the affected penetrations and fire barriers were identified as affecting both safe shutdown paths for Unit 1. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. The licensee will notify the NRC Resident Inspector. Notified the R2DO (Heissierer).

  • * * UPDATE FROM GUY GRIFFIS TO CHARLES TEAL ON 04/14/15 AT 1728 EDT * * *

During an expanded scope inspection, deficiencies in the following areas were observed that caused the affected barriers to be considered nonfunctional: - A 1/16" wide x 4" long x 5" deep gap was identified at the top of the wall, above penetration 1Z43H646D, in the west wall in Unit 1 East 600V Switchgear Room (separating Fire Area 1017 and Fire Area 1016). - A 1/16" wide x 4" long x 7" deep gap was identified at the top of the wall, above penetration 1Z43H646D, in the east wall in the Unit 1 West 600V Switchgear Room (separating Fire Area 1016 and Fire Area 1017). - A �" wide x 2" long x 7" deep gap was identified at the top of penetration 1Z43H522D located between the Unit 1 West 600 V Switchgear Room (Fire Area 1016) and U1 East 600 V Switchgear Room (Fire Area 1017). The nonconforming conditions observed for the affected penetrations and fire barriers were identified as affecting both safe shutdown paths for Unit 1. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10055316; CR 10055377 The licensee will notify the NRC Resident Inspector. Notified the R2DO (Bartley).

  • * * UPDATE FROM SCOTT BRITT TO JOHN SHOEMAKER AT 2000 EDT ON 4/16/15 * * *

During an expanded scope inspection, deficiencies in the following areas were observed that caused the affected barriers to be considered nonfunctional: - A 1" wide x 2" long x 7" deep gap was identified at the top of penetration 1Z43H622D in the west wall of the Unit 1 RPS MG Set Room (separating Fire Area 1013 and Fire Area 0014K). - A 1/4" wide x 1/4" long x 7" deep gap was identified near a ground wire, above penetration 1Z43H595D, at the top of the east wall of the Unit 1 East DC Switchgear Room (separating Fire Area 1020 and Fire Area 1104). - A 3" wide x 1/4" tall x 7" deep gap was identified at penetration 1Z43H617D on the south wall of the Unit 1 Working Floor (separating Fire Area 0014K and Fire Area 1013). The nonconforming conditions observed for the affected penetrations and fire barriers were identified as affecting both safe shutdown paths for Unit 1. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10056548; CR 10056555; CR 10056582 The licensee will notify the NRC Resident Inspector. Notified the R2DO (Bartley).

  • * * SEE EN #50998 FOR CONTINUATION OF UPDATES * * *
ENS 509987 August 2014 21:07:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed ConditionThis Is a Continuation of En #50351
  • * * UPDATE FROM STEVE BRUNSON TO CHARLES TEAL ON 4/20/15 AT 2126 EDT * * *

During an expanded scope inspection, deficiencies in the following areas were observed that caused the affected barriers to be considered nonfunctional: - A gap 1/4" wide, 1" tall, and 6" deep was found at penetration 1Z43H594D on the west wall of the U1 East Cableway (separating Fire Area 1104 and Fire Area 1020) - Near penetration 1Z43J837D, and approximately 12" south and above 1Z43H837D, gaps were observed in the mortar joint between CMU on the west wall of the U1 East Cableway (separating Fire Area 1104 and Fire Area 1020) - A triangular gap 1" wide, 1" tall and 6" deep was found at penetration 1Z43H592D on the west wall of the U1 East Cableway (separating Fire Area 1104 and Fire Area 1020) - A gap 4" tall and 3" wide was found behind Turn Box TB1-1272 which covers penetrations 1Z43H590D, 1Z43H589D, 1Z43H588, and 1Z43H587D on the west wall of the U1 East Cableway (separating Fire Area 1104 and Fire Area 1020) - At the architectural joint between the vertical wall to the horizontal floor/ceiling assembly above door 1C-22, above and to the south of 1Z43H1105D, a gap was observed approximately 1/4" tall, 3" wide, and 6" deep on the west wall of the U1 East Cableway Foyer (separating Fire Area 1105 and Fire Area 0014K) - Gap between the grout and the conduit of penetration 1Z43H778D approximately 1/4" tall x 1.5" wide x 6" deep on the east wall of the Unit 1 130' Elevation Control Building Working Floor Hallway (separating Fire Area 0014K and Fire Area 1105) The nonconforming conditions observed for the affected fire penetrations and fire barriers were identified as affecting both safe shutdown paths for Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensure the safe shutdown paths are preserved until the degraded conditions are repaired. CR 10058276; CR 10058278 The following deficiencies were also observed causing the affected penetrations to be considered nonfunctional: - A gap 1/4" wide, 1" tall, and 6" deep was located at penetration 1Z43H532D on the west wall of the U1 East Cableway (separating Fire Area 1104 and Fire Area 0014M) - A gap 1/8" wide, 1" tall and 6" deep was located at penetration 1Z43H780D on the west wall of the U1 East Cableway (separating Fire Area 1104 and Fire 0014M) - A gap 1/2" wide, 1" tall, and 6" deep was located at penetration 1Z43H781D on the west wall of the U1 East Cableway (separating Fire Area 1104 and Fire 0014M). A 1/4" x 1/2" defect was also identified at penetration 1Z43H781D on the east wall of the Men's Restroom in the Control Building (separating Fire Area 0014M and Fire Area 1104) The nonconforming conditions observed for the affected penetrations were identified as affecting both safe shutdown paths for Unit 1 and Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until degraded conditions are repaired. CR 10058277 The expanded scope inspection activity is continuing and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. The licensee has notified the NRC Resident Inspector. Notified R2DO (Blamey).

  • * * UPDATE FROM SCOTT BRITT TO DONG PARK ON 4/23/15 AT 1654 EDT * * *

During an expanded scope inspection, deficiencies in the following areas were observed that caused the affected barriers to be considered nonfunctional: - A gap 1/4" wide, 1" tall and 7" deep was found at penetration 1Z43H1138D on the east wall of the U1 RPS MG Set Room (separating Fire Area 1013 and Fire Area 0040). No seal material was seen between the sleeve and the cinderblock on the north side of penetration. - A void 1" tall, 1" wide, and 7" deep was found in the south upper corner under a concrete beam at column line T12 above penetration 1Z43H941D on the east wall of the U1 RPS MG Set Room (separating Fire Area 1013 and Fire Area 0040). - At penetration 1Z43H1139D, it appears that combustible neoprene insulation is used around the pipe within the plane of the west wall of the Vertical Cable Chase Room (separating Fire Area 0040 and Fire Area 1013). Combustible materials would not be part of a rated pen seal. - A gap 1" wide, 1" tall and 7" deep was observed at penetration 1Z43H1138D on the west wall of the Vertical Cable Chase Room (separating Fire Area 0040 and Fire Area 1013). The nonconforming conditions observed for the affected fire penetrations and fire barriers were identified as affecting both safe shutdown paths for Unit 1. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10060228 The licensee will notify the NRC Resident Inspector. Notified R2DO (Blamey).

  • * * UPDATE FROM STANLEY STONE TO DONG PARK ON 4/27/15 AT 2047 EDT * * *

During an expanded scope inspection, deficiencies in the following areas were observed that caused the affected barriers to be considered nonfunctional: -An opening in the grout 1/4" wide, 1/2" tall and over 7" deep was found between the wall and the outside sleeve for penetration 2Z43H028D on the west wall of the U2 Transformer Room (separating Fire Area 2019 and Fire Area 2016). -A 1/4" diameter hole in the grout approximately 2.5" deep was found above conduit 2MI2128 on the west wall of the U2 Transformer Room (separating Fire Area 2019 and Fire Area 2016). The nonconforming conditions observed for the affected penetration and fire barrier were identified as affecting both safe shutdown paths for Unit 1 and Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10061830 The licensee notified the NRC Resident Inspector. Notified R2DO (Blamey).

  • * * UPDATE FROM PAUL UNDERWOOD TO DONG PARK ON 4/28/15 AT 1640 EDT * * *

During an expanded scope inspection, deficiencies in the following areas were observed that caused the affected barriers in the Unit 2 Control Building 130' elevation to be considered nonfunctional and represented degraded conditions of penetrations through the wall separating the Unit 2 Switchgear Access Hallway - Fire Area 2014, from the U2 West 600 V Switchgear Room - Fire Area 2016. The following conditions were located on the south wall of the Unit 2 Switchgear Access Hallway (Fire Area 2014). 1. An opening between the conduit and the wall 1/4" wide, 2" long and probed to be at least 2 1/2" deep was identified for penetration 2Z43H668D. A similar condition exists for this penetration on the opposite side of the wall in Fire Area 2016. 2. An opening between the conduit and the wall 1/4" wide, 1/2" long and probed to be at least 3" deep was identified for penetration 2Z43H667D. A similar condition exists for this penetration on the opposite side of the wall in Fire Area 2016. The following conditions were located on the opposite side of the same wall. This is the north wall of the U2 West 600V Switchgear Room (Fire Area 2016): 3. An opening between the conduit and the wall 1/8" wide, 1" long and probed to be at least 4" deep was identified for penetration 2Z43H668D. 4. An opening between the conduit and the wall 1/8" wide, 1/2" long and probed to be at least 3" deep was identified for penetration 2Z43H667D. 5. An opening between the conduit and the wall 2 1/2" wide, 2 1/2" long and probed to be at least 4" deep was identified around the 2" continuous run conduit located above cable tray penetration 2Z43H031D. 6. An opening between the conduit and the wall 1/4" wide, 3/4" long and probed to be at least 6" deep was identified above a 3/4" continuous run conduit (first of three) located at the ceiling near column line TE. 7. An opening between the conduit and the wall 1/4" wide, 1/2" long and probed to be at least 6" deep was identified above a 3/4" continuous run conduit (second of three) located at the ceiling near column line TE. 8. An opening between the conduit and the wall 1/4" wide, 3/4" long and probed to be at least 5" deep was identified above a 3/4" continuous run conduit (third of three) located at the ceiling near column line TE. The nonconforming conditions observed for the affected penetration and fire barrier were identified as affecting both safe shutdown paths for Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10062254 The licensee notified the NRC Resident Inspector. Notified R2DO (Ehrhardt).

  • * * UPDATE FROM PAUL UNDERWOOD TO DANIEL MILLS ON 4/29/15 AT 1804 EDT * * *

During an expanded scope inspection, deficiencies in the Unit 2 Control Building 130 foot elevation were observed that caused the affected barriers to be considered nonfunctional and represented degraded conditions of penetrations through the wall separating the Unit 2 West DC Switchgear Room 2A (Fire Area 2018) and the Unit 2 Switchgear Access Hallway (Fire Area 2014). The following conditions were located on the west wall of the Unit 2 Switchgear Access Hallway (Fire Area 2014). 1. An opening between the conduit and the wall 1/4 inch wide, 1 inch long and probed to be greater than 2 inch deep, was identified for penetration 2Z43H673D. 2. There is insufficient masonry material to fill the full depth of the wall above the ductwork that passes through penetration 2Z43H032D. This deficiency affects a small area on the south side of the ductwork and penetrations 2Z43H789D, 2Z43H790D, and 2Z43H791D. 3. An opening between the conduit and the wall 1/4 inch wide, 1 inch long and probed to be 4 inch deep was identified for penetration 2Z43H671D. A similar condition exists for this penetration on the opposite side of the wall (see Item 5 below). The following conditions were located on the east wall of the Unit 2 West DC Switchgear Room 2A (Fire Area 2018). 4. There are openings between the conduits and the wall 1/2 inch wide and 1 inch long for penetrations 2Z43H789D, 2Z43H790D, and 2Z43H791D. These penetrations are affected in Item 2 above. 5. An opening between the conduit and the wall 1 inch wide, 1 inch long and probed to be greater than 6 inch deep, was identified for penetration 2Z43H671D. 6. An opening between the conduit and the wall 1/4 inch wide, 1 inch long and probed to be at least 2 inch deep, was identified for penetration 2Z43H673D. 7. An opening between the conduit and the wall 1/4 inch wide, 1 inch long and probed to be at least 2 1/2 inch deep, was identified for penetration 2Z43H676D. The nonconforming conditions observed for the affected penetrations were identified as affecting both safe shutdown paths for Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR10062955 The licensee notified the NRC Resident Inspector. Notified R2DO (Ehrhardt).

  • * * UPDATE FROM JOHN MITCHELL TO HOWIE CROUCH AT 2137 EDT * * *

During an expanded scope inspection, deficiencies in the Control Building 130' elevation were observed that caused the affected barriers to be considered nonfunctional and represented degraded conditions of the following penetrations through the wall separating the Unit 2 East Cableway (Fire Area 2104) and the Health Physics Hallway and Counting Room (Fire Areas 0014B and 0014G). - Penetration 2Z43H783D terminates open within a foot of the east wall of the Health Physics Counting Room (Fire Area 0014G) - Penetration 2Z43H603D contains no visible seal material and is located on the east wall of the Health Physics Hallway (Fire Area 0014B). The nonconforming conditions observed for the affected penetrations were identified as affecting both safe shutdown paths for Unit 1 and Unit 2. Deficiencies were also observed that caused the affected barriers to be considered nonfunctional and represented degraded condition of the wall separating the Unit 2 East Cableway (Fire Area 2104) from the common East Cableway Foyer (Fire Area 1105). - Gap near penetration 2Z43H170D between a conduit and the concrete masonry unit (CMU) wall located on the south wall of the Unit 2 East Cableway (Fire Area 2104).

The nonconforming conditions observed for the affected fire barriers were identified as affecting both safe shutdown paths for Unit 1. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas but were modified based on the nature of the degradations noted in the condition report and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR10063642 Notified R2DO (Ehrhardt).

  • * * UPDATE FROM JOHN MITCHELL TO JOHN SHOEMAKER AT 1638 EDT ON 5/7/15 * * *

During an expanded scope inspection, deficiencies in the Control Building 147' elevation were observed that caused the affected barriers to be considered nonfunctional. These deficiencies represented degraded conditions of the following penetrations through the wall separating the Unit 1 CO2 Tank Room (Fire Area 0025) and the Computer Room (Fire Areas 0024B) as well as a discrepancy in the affected wall.

   - In Fire Area 0024B, a small gap in the foam, approximately 6 (inch) deep was identified in Penetration 1Z43H592F.  The adjacent Fire Area is FA 0025.
   - In Fire Area 0024B, penetration 1Z43H325F was identified with no sealant for the penetration sleeve.  The adjacent Fire Area is FA 0025.
   - In Fire Area 0024B, foam sealant was missing in cable-tray, 1Z43H061F. The adjacent Fire Area is FA 0025
   - In Fire Area 0024B, a gap was identified in a concrete masonry unit (CMU) wall joint, directly above 1Z43H062F.

The nonconforming conditions observed for the affected fire barriers were identified as affecting both safe shutdown paths for Unit 1 and Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR10066678 The licensee has notified the NRC Resident Inspector. Notified the R2DO (Sandal).

  • * * UPDATE AT 2151 EDT ON 05/07/15 FROM SCOTT BRITT TO S. SANDIN * * *

During an expanded scope inspection, a deficiency in the Control Building 147 ft. elevation was observed that caused the affected barrier to be considered nonfunctional. This deficiency represented degraded conditions of the following fire barrier separating the Unit 1 CO2 Tank Room (Fire Area 0025) and the Cable Spreading Room (Fire Areas 0024A). - A 1/4 inch x 2 inch x approximately 4 inch deep gap in the east CMU wall of Unit 1 CO2 Tank Room above penetration 1Z43H046F. The nonconforming condition observed for the affected fire barrier was identified as affecting both safe shutdown paths for Unit 1 and Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR10066844 The licensee will inform the NRC Resident Inspector. Notified R2DO (Sandal).

  • * * UPDATE AT 2029 EDT ON 05/08/15 FROM SCOTT A. BRITT TO S. SANDIN * * *

During an expanded scope inspection, deficiencies in the Control Building 147 ft. elevation were observed that caused the affected barrier to be considered nonfunctional. These deficiencies represent degraded conditions of the following fire barrier separating the Cable Spreading Room (FA 0024A) and the CO2 Tank Room (FA 0025). - Multiple gaps in the caulk at the top of the ceiling of the west wall of the Cable Spreading Room (separating FA 0024A and FA 0025). The nonconforming condition observed for the affected fire barrier was identified as affecting both safe shutdown paths for Unit 1 and Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10067163 The licensee will inform the NRC Resident Inspector. Notified R2DO (Sandal).

  • * * UPDATE FROM PAUL UNDERWOOD TO DANIEL MILLS ON 5/11/15 AT 1711 EDT * * *

During an expanded scope inspection activity, multiple fire penetrations on the Control Building El. 130' elevation were identified that resulted in the affected barriers being considered NON-FUNCTIONAL. An issue was identified with the wall separating the Vertical Cable Chase, Fire Area 0040, from the Unit 2 RPS MG Set Room, Fire Area 2013. - A 1/4" wide x 1/2" long x approximately 6" deep gap in the grout of a 2" continuous run conduit, 6" away from 2Z43H581D was identified. - A 1/4" wide x 3" long x approximately 6" deep gap in the grout of penetration 2Z43H581D was identified. - A 1/2" wide x 2" long x approximately 6" deep gap in the grout of penetration 2Z43H580D was identified. The nonconforming condition observed for the affected fire barrier was identified as affecting both safe shutdown paths for Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10068138 The NRC Resident Inspector has been notified. Notified R2DO (Bonser).

  • * * UPDATE FROM GUY GRIFFIS TO DANIEL MILLS ON 5/12/15 AT 2151 EDT * * *

During an expanded scope inspection activity, a fire barrier on the Control Building El. 164' elevation was identified as being NON-FUNCTIONAL as follows; - A discrepancy was identified with the fire barrier separating the Unit 1 Turbine Building Main Floor Area, Fire Area 0101A from the Main Control Room, Fire Area 0024C. The condition consists of a small gap 1/4" wide, 3" long and probed to be greater than 6" deep between the wall and conduit at penetration 1Z43H605J on the Turbine Building side of the wall. The nonconforming condition observed for the affected fire barrier was identified as affecting both safe shutdown paths for Units 1 and 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10068842 The NRC Resident Inspector has been notified. Notified R2DO (Bonser).

  • * * UPDATE FROM GUY GRIFFIS TO VINCE KLCO ON 5/14/15 AT 2121 EDT * * *

During an expanded scope inspection, deficiencies in the Control Building 164' elevation were observed that caused the affected barrier to be considered nonfunctional: - A 1/4 inch x 1/2 inch x approximately 6 inch deep gap in the grout of the annulus of penetration 1Z43H602J was identified in the east wall of the Main Control Room (separating Fire Areas 0024C and 0101A). - A 1/4 inch wide x 8 inch long vertical crack, approximately 6 inch deep was identified in the CMU below penetration 1Z43H602J was identified in the east wall of the Main Control Room (separating Fire Areas 0024C and 0101A). - Three abandoned anchor holes, 1/2 inch in diameter and approximately 4 inch deep, were identified below penetration 1Z43H604J in the east wall of the Main Control Room (separating Fire Areas 0024C and 0101A). - A 1 inch diameter abandoned anchor hole, approximately 6 inch deep, was identified directly above a 1/4 inch pipe penetration in the east wall of the Main Control Room (separating Fire Areas 0024C and 0101A). - A 1/2 inch to 3/4 inch gap exists between the top of each of the 3 concrete block (CMU) walls enclosing the HVAC chase and the underside of the floor/ceiling assembly separating the Main Control Room (Fire Area 0024C) and the HVAC Room Chase (Fire Area 0014L). - A 1/2 inch diameter hole exists in the CMU at the upper right corner of penetration 1Z43H1184J separating the Main Control Room (Fire Area 0024C) and the HVAC Room Chase (Fire Area 0014L). The nonconforming condition observed for the affected fire barrier was identified as affecting both safe shutdown paths for Units 1 and 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10069898; CR 10069995 The licensee will notify NRC Resident Inspector. Notified the R2DO (Bonser).

  • * * UPDATE FROM R.S. STONE TO VINCE KLCO ON 5/15/15 AT 1807 EDT * * *

During an expanded scope inspection for penetration seals, the following discrepancies were identified with the wall separating the Unit 1 Working Floor, Fire Area 0001, from the Unit 1 AC Inverter Room, Fire Area 1008 that caused the affected barriers to be considered nonfunctional:

A 1/4 inch x 1 inch x approximately 2 inch deep gap in the grout of the annulus of penetration 1Z43H553C.

A 1/4 inch x 1 inch x approximately 2 inch deep gap in the grout of the annulus of penetration 1Z43H546C.

A 1/8 inch wide x 1/2 inch tall x approximately 6 inch deep gap in the foam block out, below penetration 1Z43H546C.

A 3 inch x 3 inch x 10 inch deep gap in the grout around a 2-1/2 inch continuous run conduit.

A 1/4 inch x 1 inch x 10 inch deep gap in the grout around 1-1/2 inch continuous run and 1-1/4 inch continuous run conduits.

2 inch deep gaps in the grout around 1-1/2 inch and 2-1/2 inch continuous run conduits.

A 1/4 inch hole x 1 inch deep gap in the grout around penetration 1Z43H060C.

A 1/4 inch x 1/4 inch x 2 inch deep gap around the annulus of a 1-1/4 inch continuous run and 2 inch continuous run conduits. The nonconforming condition observed for the affected fire barrier was identified as affecting both safe shutdown paths for Unit 1. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10070439 The licensee notified the NRC Resident Inspector. Notified the R2DO (Bonser).

  • * * UPDATE ON 1638 EDT ON 05/21/15 FROM GUY S. GRIFFIS TO JEFF HERRERA * * *

During an expanded scope inspection, the following discrepancies were identified in the Unit 1 Control Building 130(foot) elevation that caused the affected fire barrier to be considered nonfunctional: - Six 3(inch) x 3(inch) holes in the wall of the Men's Rest Room (separating Fire Areas 0014M and 1104). The nonconforming conditions observed for the affected barrier were identified as affecting both safe shutdown paths for Unit 1 and Unit 2. Deficiencies were also observed in the Diesel Generator Building 130(foot) elevation that caused the affected fire barrier to be considered nonfunctional: - Through-wall gap around the conduit that passes through penetration 2Y43H511D on the south wall of the U2 Diesel Generator Switchgear Room 2F (separating Fire Areas 2408 and 2409). The nonconforming condition observed for the affected fire barrier was identified as affecting both safe shutdown paths for Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR10073041; CR10073187 The licensee notified the NRC Resident Inspector. Notified the R2DO (Ernestes).

HVAC
ENS 510917 August 2014 21:07:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed ConditionThis Is a Continuation of En #50351 and En #50998
  • * * UPDATE ON 05/26/15 AT 1745 EDT FROM SCOTT BRITT TO JEFF HERRERA * * *

During an expanded scope inspection, deficiencies in the Control Building 147(foot) elevation were observed that caused the affected barrier to be considered nonfunctional: - Gaps were identified around cables in the foam cable tray penetration seal for penetration 1Z43H006F in the floor of the Cable Spreading Room (separating Fire Areas 0024A and 1104). The nonconforming condition observed for the affected fire barrier was identified as affecting both safe shutdown paths for Units 1 and 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10074859 The licensee will be notifying the NRC Resident Inspector.

  • * * UPDATE FROM STANLEY STONE TO JOHN SHOEMAKER AT 2017 EDT ON 6/1/15 * * *

During an expanded scope inspection for penetration seals, using more intrusive tools and methods, fire barriers in the Control Building El. 112 (foot) were found not to meet acceptance criteria. The fire protection engineering staff has examined the situations and recommends that these conditions be considered NON-FUNCTIONAL. - An issue was identified with the wall separating the el. 112 (foot) Control Building Working Floor, Fire Area (FA) 0001 from the Station Battery Room 1B, FA 1005. - An issue was identified with the wall separating the Station Battery Room 2A, Fire Area (FA) 2004 from the Station Battery Room 2B, FA 2005, on el. 112 (foot). The nonconforming conditions observed for the affected fire barriers were identified as affecting both safe shutdown paths for Units 1 and 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10077573 & 10077574. The licensee has notified the NRC Resident Inspector. Notified the R2DO(O'Donohue).

  • * * UPDATE FROM PAUL UNDERWOOD TO DONG PARK AT 1704 EDT ON 6/2/15 * * *

During an expanded scope inspection for penetration seals, using more intrusive tools and methods, fire barriers in the Control Building El. 112 (foot) were found not to meet acceptance criteria. The fire protection engineering staff has examined the situations and recommends that these conditions be considered NON-FUNCTIONAL: - Issues were identified with the wall separating the el. 112 (foot) Control Building Working Floor, Fire Area (FA) 0001 from the Unit 1 AC Inverter Room, FA 1008. The nonconforming conditions observed for the affected fire barriers were identified as affecting both safe shutdown paths for Unit 1. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10078011. The licensee has notified the NRC Resident Inspector. Notified the R2DO (Rose).

  • * * UPDATE FROM PAUL UNDERWOOD TO DONG PARK AT 1501 EDT ON 6/3/15 * * *

During an expanded scope inspection for penetration seals, using more intrusive tools and methods, fire barriers in the Control Building El. 112 (foot) were found not to meet acceptance criteria. The fire protection engineering staff has examined the situations and recommends that these conditions be considered NON-FUNCTIONAL: - Issues were identified with the wall separating the el. 112 (foot) Control Building U2 Water Analysis Room, Fire Area (FA) 2006 from the Control Building East Corridor, FA 0007 The nonconforming conditions observed for the affected fire barriers were identified as affecting both safe shutdown paths for Unit 2. Compensatory measures were already in place in accordance with the plant's Fire Hazard Analysis (FHA) as a result of previous conditions involving degraded barriers in the same fire areas and will remain in place until the fire barriers are repaired. The presence of the compensatory measures in addition to portable fire protection equipment located in adjacent areas ensures the safe shutdown paths are preserved until the degraded conditions are repaired. The expanded scope inspection activity is continuing, and this and any subsequent similar condition(s) that meets the reporting requirements will be included in an ENS Update Report as required and will be documented in a revised LER at the end of the inspection activity. CR 10078561. The licensee has notified the NRC Resident Inspector. Notified the R2DO (Rose).

ENS 5016030 May 2014 20:10:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed ConditionGrouting in Fire Penetrations Does Not Meet RequirementsConditions were identified in which grouting in some fire penetrations through hollow block walls on Units 1 and 2 do not comply with design drawings. While some grouting is present in the penetration, the determination has been made that the qualification of the amount and configuration of the grouting present does not meet Appendix R requirements. Further evaluation by Engineering concluded that this condition could compromise both safe shutdown paths on each unit in the event of a postulated fire. Given this information, the determination was made that this condition meets the reporting criteria of 10CFR50.72(b)(3)(ii)(B). Compensatory measures were established in accordance with the plant's Fire Hazard Analysis (FHA) to compensate for this condition to ensure that safe shutdown paths are preserved until the conditions can be corrected. The licensee has notified the NRC Resident Inspector.
ENS 4991514 March 2014 15:55:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed ConditionPostulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment

While evaluating IER 13-54, regarding the impact of unfused direct current (DC) circuits, a determination was made that the described condition is applicable to Edwin I. Hatch Units 1 and 2 for reactor protection system (RPS) battery/battery charger ammeter circuits. This results in an unanalyzed condition with respect to 10CFR50 Appendix R analysis requirements. In the postulated event, a fire induced hot short could adversely impact safe shutdown equipment. The Unit 1 and 2 RPS battery/battery charger ammeter indication circuits are routed from the affected components to the main control room. It is postulated that a fire in one fire area can damage the affected cables and cause short circuits without protection that would overheat the cable and possibly result in secondary fires in other fire areas where the cables are routed. The secondary fire could adversely affect safe shutdown equipment and potentially cause the loss of the ability to conduct a safe shutdown as required by 10CFR50 Appendix R. Interim compensatory measures (i.e., fire watches) have been implemented for the affected areas of the plant. This condition is being reported pursuant to 10CFR50.72(b)(3)(ii)(B).

The NRC Resident Inspector has been notified.

Reactor Protection System
ENS 496074 December 2013 20:40:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed Conditiona Potential Electrical Hot Short in the Rhr Shutdown Cooling Control Cable Could Result in an Inter-System LocaAs a result of questions raised by inspectors as part of the 2013 Triennial Fire Protection Inspection, a vulnerability from a postulated fire in the Unit 1 Cable Spreading Room was identified. This vulnerability involved the assumption of a fire occurring in Fire Area 0024A (Cable Spreading Room) which would create an inter-cable vulnerability that could result in an inter-system LOCA (Loss of Coolant Accident). Hatch's licensing basis included credit for the use of disconnect or remote shutdown panel 'Emergency' switches located on the respective remote shutdown panels to isolate the circuits in the cable spreading room thereby eliminating this vulnerability. However, the presence of these switches does not fully address this vulnerability. The Unit 1 RHR (Residual Heat Removal) shutdown cooling isolation valves 1E11-F008 and 1E11-F009 need to be de-energized in order to preclude the opening of these valves should this vulnerability occur on Unit 1. Since the Unit 2 RHR shutdown cooling isolation valves 2E11-F008 and 2E11-F009 are already closed and deactivated, they are not presently impacted by this additional vulnerability. Immediate actions were taken to de-energize the valves in the 'closed' position which removed the vulnerability. The postulated intersystem LOCA represents an unanalyzed condition that significantly degraded plant safety. The licensee notified the NRC Resident Inspector.Shutdown Cooling
Remote shutdown
ENS 4928515 August 2013 20:10:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed Conditiona Hot Short in the Rhr Shutdown Cooling Control Cable Could Result in an Inter-System LocaA condition was identified that resulted from an inter-cable circuit analysis as part of the safe shutdown analysis that identified a vulnerability associated with two Unit 2 valves with controls in Fire Area 2203. Specifically, during the postulated fire scenario, an inter-cable hot short could occur on the control cables for the RHR shutdown cooling suction valve 2E11-F008 valve and cause the valve to open in the event of a postulated fire in Fire Area 2203F which is in the vicinity of the Unit 2 remote shutdown panel. In addition, a spurious opening of RHR shutdown cooling suction valve 2E11-F009 valve could occur due to a hot short on the control cables. The fire is postulated while in Mode 1 which could cause both valves to open during power operation. This postulated event would expose the low pressure RHR-shutdown cooling suction line to normal operating pressures which would result in an inter-system LOCA. Immediate actions were taken to de-energize the valves in the 'closed' position which removed the vulnerability. When this condition was first discovered, the consequences of this postulated condition were evaluated and there was reasonable assurance that the condition did not represent an unanalyzed condition that significantly degrades/degraded plant safety. A review of the FSAR, design documents and regulatory requirements was performed to document the foundational logic for the engineering judgment to support the original conclusion that there was reasonable assurance that the inter-system LOCA did not represent an unanalyzed condition that significantly degraded plant safety and that this would not result in a loss of a safety function. Based on information learned in this review there was not sufficient information to make a conclusive determination. Since a conclusive determination cannot be made at this time and since there is some doubt regarding whether or not the report is needed, this report is being made in accordance with 10CFR50.72(b)(3)(ii). The licensee has notified the NRC Resident Inspector.Shutdown Cooling
Remote shutdown
ENS 4399218 February 2008 06:20:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed ConditionUnanalyzed Condition Due to #2 Turbine Bypass Valve Failure

Unit two reduced power to 90% to perform monthly turbine testing surveillance on 2/18/08. All tests were completed satisfactorily with the exception of the main turbine #2 Bypass Valve (BPV). At 0120 hours, the #2 BPV stroked fully open per procedure, but the last 10% of travel to full open did not yield the expected response of BPV fast open from 90% to 100%. The fast acting solenoid did indicate expected state change to 'energized' at 90% valve open, but the BPV did not indicate fast open. Therefore the Main Turbine Bypass System has been declared inoperable and associated actions of Tech Spec 3.7.7 have been invoked. This spec requires compliance with LCO 3 .2.2 MINIMUM CRITICAL POWER RATIO (MCPR) limits for an inoperable main turbine bypass system as specified in the COLR (Core Operating Limit Report), are made applicable (within 2 hours) or reduce THERMAL POWER to <24% RTP within the following 4 hours. The MCPR limits were calculated by reactor engineering and installed in the process computer at 0347 hours. A decrease in reactor power was not required once the MCPR limit was installed. The COLR (ref.: TRM Appendix A) states Unit Two can be operated with EITHER the End- of- Cycle Recirc Pump Trips (EOC-RPTs) out of service OR the Turbine Bypass Valves inoperable, but not both. The EOC-RPTs were already out of service as allowed for current conditions of the operating cycle. Upon discovery of the inoperable Bypass Valve, it was recognized that this placed Unit Two in an unanalyzed condition for fuel thermal limit. The shift crew took immediate actions to confirm the surveillance was current for EOC-RPTs and placed them in service per approved plant procedures. This was accomplished at 0315 hours, which returned the unit to an analyzed condition. The licensee notified the NRC Resident Inspector.

* * * UPDATE FROM J. ANDERSON TO P. SNYDER ON 3/20/08 AT 0943 * * * 

During the surveillance testing of the main turbine bypass valves, one of the three main turbine bypass valves did not function as expected. The function of the main turbine bypass system was degraded but not lost. Upon discovery the required action statement (RAS) in Technical Specifications 3.7.7 and 3.2.2 were properly entered, and the required actions were taken within the allowed out of service time of two hours. Based on the initial review of the condition and the fact that the core operating limits report (COLR) described operation in the condition with the EOC-RPT out of service concurrent with loss of the main turbine bypass capability as an unanalyzed condition, a notification was made in accordance with the following reporting requirement: '10 CFR 50.72 (b)(3)(ii)(B) The nuclear power plant being in an unanalyzed condition that significantly degrades plant safety.' The initial notification was a conservative action taken shortly after the condition was discovered. The condition was immediately identified during surveillance testing of the main turbine bypass valves, the required Technical Specifications RAS was entered and the actions completed within the allowed two hour time frame of 0120 - 0315 EST on 2/28/08. This prompt action prevented continued operation with EOC-RPT out of service and main turbine bypass inoperable and eliminated this potential to be in a condition where the design basis may not have been met. A more detailed review was subsequently performed which determined that the minimum critical power ratio thermal limit for having EOC-RPT out of service and main turbine bypass inoperable as calculated during the reload analysis was 1.42. At the time of the event the actual MCPR at that point in core life was 1.57. Even though prompt actions were taken as required, there was actual margin to the calculated MCPR limit of 1.42. Had a design basis transient occurred, the MCPR Safety Limit would not have been exceeded. Based on this information the determination has been made that the unit was not in an unanalyzed condition that significantly degraded plant safety. This notification serves to retract the previous event notification # 43992 made on 2/18/2008 at 0508 EST. The licensee notified the NRC Resident Inspector.

Main Turbine
ENS 4350318 July 2007 16:20:0010 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor
10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition
10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material
Unanalyzed Condition - Vent Space Less than Design Basis

During an inspection of the Unit 2 Reactor Building Steam Chase as a result of a similar situation being previously discovered on Unit 1, a storage gangbox was noted to be resting on one of the two hinged blowoff panels in the floor of the Steam Chase (elevation 130') and the hinged blowoff panels were determined to be restrained which would prevent their opening. The blowoff panels are designed to open to provide pressure and temperature relief between the torus room and 130 ft elevation of the reactor building for high energy steam line breaks. The 'as found' configuration of the blowoff panels hinder their capability to open, which constitutes a non-conforming and unanalyzed condition in that the vent area between the torus room and main steam chase in the reactor building is less than the area assumed in the analysis for a HPCI steam line break. As such, for a HPCl steam line break in the torus room, the short term pressure across the torus room ceiling would likely be greater than 2.3 psid, which is the maximum differential pressure stated in Chapter 15A of the Unit 2 FSAR. There is no known analyzed limit for the differential pressure between the torus room and the 130 ft elevation of the reactor building. The actual differential pressure given the 'as found' condition is not known at this time. Corrective actions have been taken to restore the assumed vent area between the torus room and the reactor building 130ft elevation. The gang box has been removed and both blow off panels no longer have restricted movement. The remaining 3' x 3' floor plug has also been removed, completely restoring the assumed vent area into compliance. Based on this information there is reasonable assurance that an adequate vent path currently exists such that the plant is no longer considered to be in a condition that significantly degrades plant safety. However, since the actual differential pressure given the 'as found' condition is not known at this time, the 'as found' condition as previously discussed is assumed to be an unanalyzed condition that represents a condition that significantly degraded plant safety; however, additional information is needed in order to more conclusively determine this. If more conclusive information is provided that indicates otherwise an update notification will follow. This was also reported under 10CFR50.72(b)(3)(v)(D). The licensee notified the NRC Resident Inspector.

  • * * RETRACTION FROM GORLEY TO HUFFMAN AT 1435 EDT ON 8/30/07 * * *

A review of the 'as found' configuration of the plant was performed to determine if this configuration would still be bounded by the calculations that support the HELB analysis in the Unit 2 FSAR. The 'as found' configuration consisted of having one torus plug in place rather than open and the two hinged torus ceiling blow-off panels bolted shut instead of being free to open. This engineering review concluded that if the torus ceiling blow-off panels do not open and with only one torus plug open, the torus pressures will not exceed the current FSAR pressures. Additionally, the torus pressures were found to be acceptable as a result of the modeling of friction in the HPCI pipe break mass and energy releases. This being the case, for a HPCI steam line break in the torus room, the short term pressure across the torus room ceiling would be 1.93 psid for the 'as found' condition which is less than the maximum differential pressure of 2.27 psid as stated in Chapter 15A of the Unit 2 FSAR. It should be noted that corrective actions were taken upon discovery and that the assumed vent area between the torus room and the reactor building 130 ft elevation was restored shortly following discovery. The gang box was removed, the restraint on the blow-off panels removed and both blow-off panels were confirmed to have full range of motion to open if the conditions were present that would warrant that movement. Based on this review of the design calculations while taking the 'as found' conditions into consideration, the conclusion reached is that the nonconforming 'as found' conditions did not represent a condition that significantly degraded plant safety. For this reason this condition that was initially reported under 10CFR50.72(b)(3)(ii)(B) is being retracted. The licensee will notify the NRC Resident Inspector. R2DO(Shaeffer) notified.

Main Steam
ENS 4349917 July 2007 12:00:0010 CFR 50.72(b)(3)(ii)(B), Unanalyzed ConditionUnanalyzed Condition - Vent Space Less than Design Basis

During a review of the temporary repair of the steam line drain bypass line in the Unit 1 Reactor Building Steam Chase, two storage gangboxes were noted to be on the grated opening in the floor of the Steam Chase (elevation 129 ft). These grated openings are designed to be open to provide pressure and temperature relief between the steam chase and the torus room for high energy steam line breaks. Appendix N to the Unit 1 FSAR credits the openings for venting the steam chase to the torus room through the openings for a main steam line break, and for venting the torus room to the steam chase for a HPCI steam line break in the torus room. The most limiting event is the HPCI steam line break in the torus room and the vent path associated with that event. Original assumptions used in the calculation for the vent opening did not adequately account for the grating itself and for louvers installed in a previous plant modification. As a result the vent area was further reduced. Upon further review of the above condition, it has been determined that a non-conforming and unanalyzed condition exists In that the vent area between the torus room and main steam chase in the reactor building is less than the area assumed in the analysis, even without gangboxes covering a portion of the grating. As such, for a HPCI steam line break in the torus room, the short term pressure between the torus room and the corner rooms (diagonals) is greater than 2 psid, which is the stated limit in Appendix N of the Unit 1 FSAR. The corner rooms contain ECCS components in the RHR and core spray systems. Based on engineering judgment there is reasonable assurance that the present nonconforming condition does not prevent safety systems and structures from fulfilling their safety function. This is based on the following information: Structural Steel floor elevation platforms do not appear to have been credited in the structural design capability of the walls. These platforms should act to help maintain the wall intact with increased pressure. The increased pressure transient is a very short term transient, approximately 2-3 seconds in duration, after which the pressure will return to within 2 psid. It is expected that the wall would withstand this transient without degrading the performance of the low pressure ECCS systems or other structures and components. Lastly, the probability of occurrence of a steam leak leading to an instantaneous line break is very small. There is currently no report of steam leaks from the HPCI line, and although a probability evaluation has not been performed, it is likely that the probability of occurrence of such a break is very small. Thus, there is no known immediate threat that would prevent safety systems from performing their safety function. More detailed review is continuing at this point. Short term corrective action will be required to increase the open 'vent' area between the torus room and the reactor building 130 ft elevation and restore at least the assumed vent path from the torus room. This can be accomplished by removing the gangboxes over the vent area in the steam chase and/or completing a floor plug evaluation of vent area needed between the torus room and the reactor building 130 ft elevation which will restore compliance with the 2 psid criteria. Analysis is currently underway to assess the pressure and temperature effects on the safety related structures and equipment by these short term actions. Regarding reportability, based on engineering judgment as previously discussed, the unanalyzed condition does not represent a condition that significantly degraded plant safety; however, additional information is needed in order to more conclusively determine this. For this reason this condition is being conservatively reported under 10CFR50.72(b)(3)(ii)(B) until such time as more conclusive information is provided to make the final determination. The licensee notified the NRC Resident Inspector.

  • * * RETRACTION FROM GORLEY TO HUFFMAN AT 1435 EDT ON 8/30/07 * * *

Upon further review of the above 'as found' conditions, it has been determined that there are existing conservatisms in the current analysis which bound the flow restriction caused by the gang boxes on the grating. The evaluation concluded that the gang boxes found on the grated opening in the floor of the steam chase would not increase the pressures in the Unit 1 reactor building as a result of HELB conditions. Thus the pressure between the torus room and the corner rooms (diagonals) which is limited to 2 psid as stated limit in Appendix N of the Unit 1 FSAR is not affected. In addition, an additional open floor plug (the 3 ft by 3 ft floor plugs between Elevation 130 and the torus room below found to be covered by a hinged metal plate) is acceptable since it causes less differential pressure across reactor building compartments during the HELB's evaluated. The results of this additional review confirmed the original engineering judgment that there was reasonable assurance that the as found nonconforming condition did not prevent safety systems and structures from fulfilling their safety function. Short term corrective actions were completed upon discovery of he 'as found' condition to further increase the open 'vent' area between the torus room and the reactor building 130 ft elevation and restore at least the assumed vent path from the torus room. This was accomplished by removing the gang boxes over the vent area in the steam chase. Based on this review of the design calculations white taking the 'as found' conditions into consideration, the conclusion reached is that the nonconforming 'as found' conditions did not represent a condition that significantly degraded plant safety. For this reason this condition that was initially reported under 10CFR50.72(b)(3)(ii)(B) is being retracted. The licensee will notify the NRC Resident Inspector. R2DO (Shaeffer) notified.

Core Spray
Main Steam Line
Main Steam