Notice of Violation from Insp on 850311-0810
ML20140D770
Person / Time
Site: River Bend Entergy icon.png
Issue date: 01/29/1986
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML20140D752 List:
References
50-458-85-09, 50-458-85-9, NUDOCS 8602030112
Download: ML20140D770 (2)


See also: IR 05000311/2008010

Text

,

APPENDIX A

NOTICE OF VIOLATION

Gulf States Utilities Docket: 50-458

River Bend Station Permit: CPPR-145

During NRC inspections conducted on March 11-15, April 1-5 and 22-23,

May 14-16 and 21-24, June 3-6, and August 6-10, 1985, four violations of NRC

requirements were identified. The violations involved design process for

seismic Category I cable tray and conduit supports. In accordance with the

" General Statement of Policy and Procedure for NRC Enforcement Actions,"

10 CFR Part 2, Appendix C (1985), the violations are listed below:

A. Failure to Adequately Check Calculations

10 CFR Part 50, Appendix B, Criterion III, requires checking the adequacy

of design.

Contrary to the above, four examples of inadequate checking of

calculations were identified. Specifically, the calculations involved are

analysis Case R3, calculation pp. E.S. 1483-ES.1494, the STRUD computer

analyses for the cable tray hold-down connection, and calculation

p. E.S.1358.

This is a Severity Level IV violation (Supplement I.D.) (50-458/8509-01).

B. Failure to Document and Verify Assumptions

10 CFR Part 50, Appendix B, Criterion V, requires that activities

affecting quality be accomplished in accordance with documented

instructions.

Section 4.2 of American National Standard N45.2.11 - 1974, " Quality

Assurance Requirements for the Design of Nuclear Power Plants," requires

that assumptions be documented and that those assumptions that must be

verified as the design proceeds be identified.

Contrary to the above, the comparison method of design for the cable tray

supports did not procedurally require that assumptions relative to

critical support parameters and criteria for conservatism be documented or

verified.

This is a Severity Level IV violation (Supplement I.D.)(50-458/8509-02).

C. Failure to Provide Basis for Design Input

10 CFR Part 50, Appendix B, Criterion V, requires that activities

affecting quality be accomplished in accordance with documented

instructions.

S

O

. . . . - - _ _ _ _ _ _ - _ _ _ - _ _ - _. _ - - _ _ _ - _ - _ ,

}

s' *

i

-2- t

3

i

Section 4.2 of American National Standard N 45.2.11 - 1974, " Quality

Assurance Requirements for the Design of Nuclear Power Plants," requires

l that procedures include requirements for the definition of design inputs

i and their sources,

j Contrary to the above, the basis for the 2D-3D factors applied to the two-

dimensional analyses to account for three-dimensional effects in support

systems were not procedurally required to be defined.

I This is a Severity Level IV violation (Supplement I.D.)(50-458/8509-03).

D. Failure to Provide Adequate Disposition of Construction Deviation

10 CFR Part 50, Appendix B, Criterion XV, requires that inadvertent use or

installation of components which do not conform requirements be prevented

j by established measures,

i

Contrary to the above, Engineering & Design Coordination Report C-24.199

and Nonconformance and Disposition Report 11957 were improperly i

i dispositioned and the subject components were allowed to be installed.

This is a Severity Level IV violation (Supplement I.D.) 50-458/8509-04).

Pursuant to the provisions of 10 CFR 2.201, Gulf States Utilities is hereby

i required to submit to this office within 30 days of the date of the letter

'

transmitting this Notice, a written statement or explanation in reply,

j including for each violation: (1) the reason for the violations if admitted,

(2) the corrective steps which have been taken and the results achieved,

!. (3) the corrective steps which will be taken to avoid further violations, and

! (4) the date when full compliance will be achieved. Where good cause is shown,

consideration will be given to extending the response time. l

,

l

Dated at Arlington, Texas,

this 29th day of January, 1986.