Forwards Copy of Amend to Util Npdes,Wastewater Discharge Permit CO-0001121,which Clarifies That Monitoring of Farm Pond Outlet Required When Industrial Wastewater Being Discharged Through Upstream Goosequill Ditch
ML20135D953
Person / Time
Site: Fort Saint Vrain Xcel Energy icon.png
Issue date: 02/27/1997
From: Borst F
PUBLIC SERVICE CO. OF COLORADO
To: Jim Hickey
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM), NRC OFFICE OF NUCLEAR MATERIAL SAFETY & SAFEGUARDS (NMSS)
References
P-97010, NUDOCS 9703060136
Download: ML20135D953 (6)


Text

_ _ .. .. - .

hPublic 16805 WCR Service

  • 80651 191/2; Platteville, Colorado r#lL February 27,1997

. Fort St. Vrain P-97010 U. S. Nuclear Regulatory Commission ATIN: Document Control Desk Washington, D. C. 20555 Attention: Mr. John W. Hickey, Chief Decommissioning and Regulatory Issues Branch

! Docket No. 50-267 i

REFERENCE:

PSCO Ixtter, Borst to Weber, dated October 4,1996 (P-96086)

" Forthcoming Change to Fort St. Vrain NPDES Permit" 4

j

SUBJECT:

Amendment to Fort St. Vrain NPDES Permit

Dear Mr. Hickey:

)

Attached for your information is a copy of an amendment to the Fort St. Vrain (FSV)

National Pollutant Discharge Elimination System (NPDES) Permit, Wastewater Discharge Permit No. CO-0001121. This amendment clarifies that monitoring of the i farm pond outlet is only required when industrial wastewater is being discharged through  ;

the upstream Goosequill ditch and/or Jay Thomas ditch, as described in the referenced i letter. The Colorado Department of Public Health and Environment approved this amendment as a minor modification, which became effective on October 18,1996. A correction to the legal and facility contacts, dated R amber 12,1996, is also included.

The attached amendment to the FSV NPDES Perrait is provided to the NRC in accordance with Section 3.2.c of the FSV Non-Radio!ogical Technical Specifications, Appendix B to Facility Operating License No. DPR-34. Public Service Company of .

Colorado regrets that, due to an oversight, this amendment was not provided within 30 l days as required. If you have any questions reganimg this information, please contact  ;

Mr. M. H. Holmes at (303) 571-7633.

Sincerely, j hdlAtb Frederic J.

51--

rst /

l_ l 0 , l Decomnu oning Program Director  ;

9703060136 970227 PDR ADOCK 05000267 W PDR

@.NE .E.k

)

P-97010 February 27,1997 Page 2 Attachment FJB/SWC cc: Regional Administrator, Region IV Mr. Robert M. Quillin, Director Radiation Control Division Colorado Department of Public Health and Environment

. -~ .. . - . - . = _ - _ _ - _ - . - - - _- - .- -- . . -.

. .. COLORADO DISCHARGE PERMIT SYSTEM (CDPS) \

AMENDMENT NO. 6 - RATIONALE I PilBLIC SERVICE COMPANY OF COLORADO FORT ST. VRAIN STATION PERMITNO. CO 000!!21, WELD COUNTY l 1.

l'YPE OF PERMIT:

Industrial- Minor Modspcation i

11.

FACILITY INFORMATION:

A. Facility Type I and Fee Category: Category 8. Subcategory 4 - Power Plants: Process Waterfrom 1.0 to l

4.999 MGD - Currentfee $4568 per yearfor the process related permit:

} and Category 24. Subcategory 2 -IndividualIndustrialStorm Water

} Permits: Ten Acres or More - Currentfee $300/ year per CRS 25-8-502.

4 Totalfee = $4868/ year.

l B. SIC No.:

4911 (Electruc Services)

C. Legal Contaa:

A. Clegg Crawford

( V.P. Engineering & Operations Support Public Serke Conymny of Colorado \

P.O. Box 840 \

I Denver, CO 80201-0840 (303)+571-7000 4

D.

  • Faahty Contaas:  !

! Ted Borst, Decommbsioning Program Director Public Service Company of Colorado i'

Fort St. Vrain Station

\

i I6805 Weld County Road I9 I/2 Platteville, CO 80651 \

{ (303)+620-1000

\

E. Faakty Location:

i ne Public Service Company Fort Saint Vrain Station is located apprazunately 3.5 miles nonhnest of Platteville, Colorado in Section 3 T3N, R67W: and Sections 34 and 35 T4N, R67W: 6th Prmapal Meruitan, as shown inpgure I and 2 of the pernut.

F. Discherte Points:

See renewal rationalefor thisfacilityfor description of all he outfalls (discharge ponnes 001A, 001B, 002, 003, 004, 005, 006, 007, and monstorsag point 008) at thisfacility. \

Outfall 001A - the outfall 001 overfowfrom thefarm pond at the l

Parshallfume, which is prior to entering the South Place River, as 1 shown infgure 3 of the permit.

G. Faality Rows:  ;

nefollowingpowsfor 001A are unchangedfrom the prmus rationale.

001A =

2.0t]5 MGD (averagefacilityflow)

=

3. 7 MGD (mazunum/ow) 00lA 30-Day Average Flow Range: 1.03 - 2.88 MGD 001A Daily Mazunum Flow Range: 1.280 - 5.250 MGD (from Discharge Monitoring Reportsfrom 1-1-94 through 6 301995)

See previous renenel rationalefor the other dischargefows.

Corrected: 11//2/96

COLORADO Rationgig, Amendment DEPARTMENT No. 6 Page 2 0F PUBLICltEALTH AND ENVIRONMENT, Water Quality Cont Permit No. CO-000ll21

' 'lf.,

l RECEIVING STREAM:

Outfalls 001A and 003 go to the South Platte River (segment 1. Middle South Platte River su located in the Goosequiu Ditch Stub, which then goes to Gocsequiu Ditch, which is tributary River (Goosequiu Ditch is in segment 3. Middle South Platte River subbasin); and out St. Vrain Creek (segment 3. St. Vrain Creek subbasin). Outfans 006 and 007 are internal d do not discharge directly to any surface waters. Dese two internal outfaus eventuaHy c 001A, 001B, and/or 002. See the previous renewal rationale (February 8,1993) forfunher details.-

IV, PURPOSE OF AMENDMENT:

This amendment includes a claripcation of when monitoring at outfall 001A is required. Monito1 parameters at cutfall 001A is only required 'vhen there are industrial wastewater discharges entering th i Goosequin Ditch Stub and/or the Jay nomas Ditch via outfau 001B (orfrom any other industrial wastewa discharge sources). De basisfor this change isfunher discussed in thefollowing section.

- V, DISCUSSION OF AMENDMENT: 1 i

in a telephone call and then in a subsequentfollow-up letter dated September 23,1996, Public Service Company of Colorado (PSC) submitted a request regarding a claripcationfrom the Division for when sampling at from the Farm Pondis required. l As indicated in the PSC letter of September 23,1996, the pnmary industrial wastewater discharge point t Goosequill Ditch Stub is identiped as outfall 0018. Industrial wastewater discharge to the Gooseq'uill }D .

currently includes turbine building drain (internal discharge point idennped as outfall 006), treated domestic wastewater (internal discharge point identiped as outfan 007), service water cooling tower blowdown, bypal '

water, and stormwater runoffrom the nonk and south yard drains. Wastenter dischargefrom the prestressed <

concrete reactor vessel (PCRV) and the reactor building sump have been discontinued. De combmation of wastewaterfrom the Goosequill Ditch Stub, the Jay Domas Ditch (inigation waterfrom the South Platte River), l and agricultural irrigation returnflows into the Farm Pond. Overflowfrom the Farm Pond to the South Platte '

River is idennped as outfan 001A in the PSC Fon St. Vrain wastewater discharge permit.

When the Goosequal Ditch Stub requires maintenance, allindustrial wastewater discharm from the PSC Fort St.

Vrainfacility are divened to the St. Vrain Creek, through the drainage slough (outfan OW). When outfall 00 used, only irrigation waterfrom the Jay Thomas Ditch and irrigation return pows enter thefann pond and overflow through outfan 001A.

Monitoring requirements for outfau 001A when industrial wastewater is discharged through the alternate disc path (outfan 002) were discussed between the Division and PSCin a phone call on September 18,1996. From this telephone conversation, it was concluded that when there are no industrial wastewater discharges to thefarm p through outfan 001B, monitoring of the parameters at outfaN 001A would not be required.

'Ihus, on page li of the permit, the Division made thefollowing addition to the monitoring requirements for outfall 001A for the dischargefrom the Farm Pond:

i "Monitoringfor the above parameters is only required at outfan 001A when there are industrial wastewater discharges entering the Goosequill Ditch Stub and/or the Jay Domas Ditch via outfall 001B (orfrom any other industrial wastenter discharge sources). If, during the discharge monitoring repon period, there are i no industrial mstewater discharges entering the Goosequill Ditch Stub and/or the Jay Thomas Ditch via outfan 001B, then this should be indicated on the discharge monitoring repon. '

-_ - __ -_ _ _ . _ . _ _ __ _ n _. - _ _ - 1

COLORAT)O DEPARTMENTOF PUBLIC HEALTH AND ENVIRONMENT, Water Quality Ctatrol Division Rationale. Amendment No. 6 Page 3 Permit No. CO-0001121

~

V.

DISCUSSION OF AMENDMENT: (Cont.)

Since there have been no signifcant major modifications to the permit, public notice requirements are not applicablefor this Division-initiated amendment.

Don Holmer October 15,1995 i

)

1 PART I

.. " Pags li of 19 l

.." Permit No. CO-00C;1121 i 9

B. MONITORING REQUIREMENTS

1. Freauency and-Samole Tvoe - Discharge Point 001A l

In order to obtain an indication of the probable compliance or non- 1 compliance with the effluent limitations specified in Section A, the permittee frequencies:shall monitor all effluent parameters at the following Effluent Parameter Measurement Frecuency g/ Samole Tvoe g/

Flow, MGD Weekly oil and Grease, mg/l 1/ Weekly Instantaneous Temperature, degrees F Weekly Visual Total Residual Chlorine, mg/l Weekly In-Situ Grab Sampling by the permittee for compliance with the monitoring requirements specified above shall be performed at outfall 001A, the overflow from the farm pond at the Parshall fiume, which is prior to entering the South Platte River, as shown in figure 3.

Monitoring for the above parameters is only required at outfall 001A when there are industrial wastewater discharges entering the Goosequill Ditch Stub and/or the Jay Thomas Ditch via outfall 001B (or from any other industrial wastewater discharge sources). If, during the discharge monitoring report period, there are no industrial wastewater discharges entering001B, outfall the Goosequill Ditch Stub and/or the Jay Thomas Ditch via  !

report. then this should be indicated on the discharge monitoring See Part I.C. for Footnotes Amended 12/14/94 Effective 02/01/95 Amended DrT 1 R -100.C

. . . Effective 4 o enne A. t.' T. iw . , ,v Code: 1 - 3a Date: 1-84, revised 2-87, revised 12-88

_,_ _ - _ _ _ . - - - - - - - - - - - -