Special Rept 1-SR-84-7:on 840924,fire Barrier Limiting Condition Initiated for Fire Door in Emergency Ac Diesel Generator Bldg.Caused by Failure of Door to Open & Close as Result of Differential Pressure Conditions
ML20108B683
Person / Time
Site: Brunswick Duke energy icon.png
Issue date: 10/31/1984
From: Dietz C
CAROLINA POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
1-SR-84-7, BSEP-84-2282, NUDOCS 8411160144
Download: ML20108B683 (1)


Text

4 CP&L E ce Carolina Power & Light Company .

34 NOV g NO : 24 Brunswick Steam Electric Plant P. O. Box 10429 Southport, NC 28461-0429

~

October 31, 1984 FILE: B09-13510C SERIAL: BSEP/84-2282 Mr. James P. O'Reilly, Administrator U.S. Nuclear Regulatory Commission Region II, Suite 3100 101 Marietta Street N.W.

Atlanta, GA 30323 BRUNSWICK STEAM ELECTRIC PLyiT UNIT 1 DOCKET NO. 50-325/

LICENSE NO. DPR-71 SPECIAL REPORT PER TECHNICAL SPECIFICATION 3.7.8 AND PURSUANT TO TECHNICAL SPECIFICATION 6.9.2 (1-SR-84-7)

Dear Mr. O'Reilly:

During Unit 1 power operation, concurrent with Unit 2 preoperational testing following a unit refueling / maintenance outage, a Unit 1 fire barrier LCO was initiated on September 24, 1984, for a fire door in the units' common Emergency AC Diesel Generator Building.

The subject fire door, No. 214, is located at fire barrier penetration seal No. DG-3-400 on the 50-foot north elevation of the building. Door No. 214 provides personnel access to the elevation from the northern stairwell of the building. The involved LCO was initiated due to the inability of the door to properly open and close as a result of excessive differential pressure -

conditions at the door. On October 1, 1984, the specified seven-day time frame of the LCO was exceeded. Until resolution of the excessive differential pressure condition affecting fire door No. 214, the involved LCO and appropriately stationed fire watches will remain in effect.

Very truly yours, C. R. Dietz, General Manager Brunswick Steam Electric Plant MJP/mcg/LETCG2 cc: Mr. R. C. DeYoung NRC Document Control Desk Ot:FICIAL COPY 60144 841031 ADOCK 05000 gLL IO

-