BSEP-85-0007, Special Rept 1-SR-84-6:on 841218,14-day Requirement of Limiting Conditions for Operation of Zone 14 Fire Detection Instruments Exceeded After 841204 Discovery That Control Room Annunciator Did Not Alarm During Performance Test

From kanterella
(Redirected from ML20101T749)
Jump to navigation Jump to search
Special Rept 1-SR-84-6:on 841218,14-day Requirement of Limiting Conditions for Operation of Zone 14 Fire Detection Instruments Exceeded After 841204 Discovery That Control Room Annunciator Did Not Alarm During Performance Test
ML20101T749
Person / Time
Site: Brunswick Duke energy icon.png
Issue date: 01/10/1985
From: Dietz C
CAROLINA POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
1-SR-84-6, BSEP-85-0007, BSEP-85-7, NUDOCS 8502060339
Download: ML20101T749 (1)


Text

CP&L Carolina Power & Ligpt Cppan BrunswickSNaI$'IsctricPlant ,

P. O. Box 10429 Southport, NC 28461-0429 January 10, 1985 FILE: B09-13510C SERIAL: BSEP/85-0007 Mr. James P. O'Reilly, Director U.S. Nuclear Regulatory Commission Suite 2900 101 Marietta Street, hV Atlanta, GA 30323 BRUNSWICK STEAM ELECTRIC PLAhT UNIT 1 DOCKET NO. 50-325 LICENSE NO. DPR-71 SPECIAL REPORT PER TECHNICAL SPECIFICATION 3.3.5.7 AND PURSUANT TO TECHNICAL SPECIFICATION 6.9.2 (1-SR-84-6)

Dear Mr. O'Reilly:

On December 4,1984, performance of the operability test of the nonsupervised circuitry between the fire detection panels and the Control Room annunicators, PT-35.17, revealed the Control Room annunciator associated with the Unit 1 Reactor Building 117-foot elevation zone 14 fire detection instrument group did not audibly alarm as required. On December 18, 1984, the specified 14-day time frame of the involveu LCO for zene 14 fire detection instruments was exceeded.

Troubleshooting revealed a defective logic card in the annunicator panel was preventing the annunciator from audibly alarming. On December 27, 1984, the subject logic card was replaced and the annunciator was satisfactorily tested for operation and returned to service.

Very truly yours, Id C. R. Dietz, General Manager Brunswick Steam Electric Plant MJP/ag/LETAG cc: Mr. R. C. DeYoung NRC Document Control Desk