BSEP-95-0590, Monthly Operating Repts for Oct 1995 for Brunswick Steam Electric Plant Units 1 & 2

From kanterella
(Redirected from ML20094L903)
Jump to navigation Jump to search
Monthly Operating Repts for Oct 1995 for Brunswick Steam Electric Plant Units 1 & 2
ML20094L903
Person / Time
Site: Brunswick  Duke energy icon.png
Issue date: 10/31/1995
From: Harrison F, Lopriore R
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
BSEP-95-0590, BSEP-95-590, NUDOCS 9511210174
Download: ML20094L903 (10)


Text

. .

l.  :**

l ., ' ..

l ,

.CP&L l

1

Carolina Power & Light Company j

! P. O. Box 10429 I Southport, NC 28461-0429

NOV 151995 l

FILE: B09-13510C l SERIAL: BSEP/95-0590 l

United States Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555 BRUNSWICK STEAM ELECTRIC PLANT UNITS 1 AND 2 DOCKET NOS. 50-325 AND 50-324 LICENSE NOS. DPR-71 AND DPR-62 MONTHLY OPERATING REPORT

! Gentlemen: i l-In accordance with Technical Specification 6.9.1.11 for the Brunswick Nuclear Plant, Units 1

and 2, Carolina Power & Light Company herewith submits the report of operating statistics l

! and shutdown experience for the month of October 1995. I f

If you have any questions regarding this report, please contact Ms. Frances Harrison at (910) 457-2756.

1 ry tr ly yours, l

R.Lopn Plant Manager Brunswick Nuclear. Plant FH/mcg MSC/93-8524 l Enclosures cc: Mr. S. D. Ebneter, Regional Administrator, Region 11 l

Mr. C. A. Patterson, NRC Senior Resident inspector - Brunswick Mr. D. C. Trimble, NRR Project Manager - Brunswick The Honorable H. Wells, Chairman - North Carolina Utilities Commission i

S) c

- n ,- ,,

  • UVg ,)

9511210174 951031 DR ADOCK 05000324 b I PDR

. . .-. - - . . ~ . - - . . - . . . . . . . _ - . . . - - . . . . - . . - - - - . . . - . .. . . . . . -

. (

l ENCLOSURE 1

BRUNSWICK STEAM ELECTRIC PLANT, UNITS NOS.1 AND 2  :

DOCKET NOS. 50-325 & 50-324-LICENSE NOS. DPR-71 & DPR-62 PLANT PERFORMANCE DATA SYSTEM OPERATING DATA REPORT  !

i l

l l

l l

i El-2

'CP&L 60 PLANT PERFORMMCE DATA SYSTEM. PAGE 1 1(UN DATE 11/07/95 APPENDIX B-- AVERAGE DAILY POWER LEVEL RPD39-000 RUN TIME 12:4,7:03 BRUNSi!!CK UNIT 1 DOCKET NO. 050-0325 COMPLETED BY FRANCES HARRISON TELEPHONE (910)457-2756 OCf03ER 1995 DAY AVG. DAILY POWER LEVEL DAY AVG. DAILY POWER LEVEL (MWE-NET) (MWE-NET) 1 -14 17 800 2 15 18 800 3 459 19 801 4 768 20 800 5 768 21 799 6 795 22 800 7 796 23 800 8 795 24 799 9 797 25 799 10 797 26 798

, 11 797 27 798 l

12 798 28 798

13 797 29 800 14 797 30 801 i

l 15 798- 31 802 l 16 800 o

1.16 - 8 i

A E

t

1

!.CP&$CO PLANT PERFORMANCE DATA SYSTEM PAGE 1 RUN DATE 11/07/95 OPERATING DATA REPORT RPD36-000 RUN TIME 12:4.7:04 BRUNSWICK UNIT 1 DOCKET NO. 050-0325 '

COMPLETED BY FRANCES HARRISON i OPERATING STATUS TELEPHONE (910)457-2756

1. UNIT NAME: BRUNSWICK UNIT 1 NOTES
2. REPORTING PERIOD: OCTOBER 95
3. LICENSED THERMAL POWER (MWT) : 2436  !
4. NAMEPLATE RATING (GROSS MWE) : 867.0
5. DESIGN ELECTRICAL RATING (NET MWE) : 821.0
6. MAX DEPENDABLE CAPACITY (GROSS MWE) : 791.0
7. MAX DEPENDABLE CAPACITY (NET MWE) : 767.0 -------------------------------  !
8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THRU 7) SINCE LAST REPORT, GIVE REASONS:
9. POWER LEVEL TO WHICH RESTRICTED IF ANY (NET MWE) :
10. REASONS FOR RESTRICTION IF ANY:

THIS YR TO CUMUL MONTH DATE ATIVE l

11. HOURS IN REPORTING PERIOD 745.00 7296.00 163248.00
12. NUMBER OF HOURS REACTOR CRITICAL 703.23 6057.42 101928.74 t
13. REACTOR RESERVE SHUTDOWN HRS .00 .00 1647.10 F
14. HOURS GENERATOR ON LINE 700.68 5930.18 97887.17
15. UNIT RESERVE SHUTDOWN HOURS .00 .00 .00  :
16. GROSS THERMAL ENERGY GEN. (MWH) 1681892.35 14272138.14 215807865.03
17. GROSS ELEC. ENERGY GEN. (MWH) 562265.00 4745080.00 70904805.00 i
18. WET ELEC. ENERGY GENERATED (MWH) 546993.00 4605891.00 68204930.00 ,
19. UNIT SERVICE FACTOR 94.05 81.28 59.96 l
20. UNIT AVAILABILITY FACTOR 94.05 81.28 59.96  ;
21. UNIT CAP. FACTOR (USING MDC NET) 95.73 82.31 53.29
22. U"IT CAP. FACTOR (USING DER NET) 89.43 76.89 50.89
23. UNIT FORCED OUTAGE RATE- 5.95 2.54 14.28
24. SHUTDOWNS SCHED. OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACd) :
25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF START UP: 1
26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION) : FORECAST ACHIEVED INITIAL CRITICALITY ---_---- --------

INITIAL ELECTRICITY -------- ------_-

COMMERCIAL OPERAT. TON -------- -----_--

1.16 - 9

  • CP&L CO PLANT PERFORMANCE DATA SYSTEM PAGE 2 RUN DATE 11/07/95 APPEifDIX B - AVERAGE DAILY POWER LEVEL RPD39-000 ,

RUN TIME 12:4.7:03 BRUNSWICK UNIT 2 DOCKET NO. 050-0324  ;

COMPLETED BY FRANCES HARRISON TELEPHONE (910)457-2756 OCTOBER 1995 DAY. AVG. DAILY POWER LEVEL DAY AVG. DAILY POWER LEVEL i (MWE-NET) (MWE-NET) 1 681 17 705 2 682 18 702 3 677 19 701 -

4 673 20 695 5 670 21 689 ,

6 642 22 689 7 327 23 688 8 524 24 684 9 635 25 681 10 667 26 679 11- 559 27 676 12 705 28 672 13 718 29 672 14 706 30 671 15 708 31 667 16 708 I

1.16 - 8

. . - -. . . - ~ - - - - - -- - . . . - . ., -

  • CP&L CO PIANT PERFORMANCE DATA SYSTEM PAGE 2 RUN DATE 11/07/95 OPERATING DATA REPORT RPD36-000 RUN TIME 12:4,7:04 BRUNSWICK UNIT 2 DOCKET NO. 050-0324 COMPLETED BY FRANCES HARRISON OPERATING STATUS TELEPHONE (910)457-2756
1. UNIT NAME: BRUNSWICK UNIT 2 NOTES-
2. REPORTING PERIOD: OCTOBER 95
3. LICENSED THERMAL POWER (MWT) : 2436
4. NAMEPLATE RATING (GROSS MWE) : 867.0
5. DESIGN ELECTRICAL RATING -(NET MWE) : 821.0
6. MAX DEPENDABLE CAPACITY (GROSS MWE) : 782.0
7. MAX DEPENDABLE CAPACITY (NET MWE) : 754.0 -------------------------------
8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THRU 7) SINCE LAST REPORT, GIVE REASONS:
9. POWER LEVEL TO WHICH RESTRICTED IF ANY (NET MWE) :
10. RFASONS FOR RESTRICTION IF ANY:  :

THIS YR TO COMUL MONTH DATE ATIVE

11. HOURS IN REPORTING PERIOD 745.00 7296.00 175272.00
12. WUMBER OF HOURS REACTOR CRITICAL 745.00 7296.00 111851.70
13. REACTOR RESERVE SHUTDOWN HRS .00 .00 .00
14. HOURS GENERATOR ON LINE 745.00 7296.00 106413.71
15. UNIT RESERVE SHUTDOWN HOURS .00 .00 .00
16. GROSS THERMAL ENERGY GEN. (MWH) 1597090.32 17127724.53. 229378061.03
17. GROSS ELEC. ENERGY GEN. (MWH) 512265.00 5508985.00 74158606.00
18. NET ELEC. ENERGY GENERATED (MWH) 493971.00 5339687.00 71172946.00
19. UNIT SERVICE FACTOR 100.00 100.00 60.71
20. UNIT AVAILABILITY FACTOR 100.00 100.00 60.71
21. UNIT CAP. FACTOR (USING MDC NET) 87.94 97.06 51.97
22. UNIT CAP. FACTOR (USING DER NET) 80.76 89.14 49.46
23. UNIT FORCED OUTAGE RATE .00 .00 11.34
24. SHUTDOWNS SCHED. OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH) :
25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF START UP:
26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION) : FORECAST ACHIEVED INITIAL CRITICALITY --- --- --_.____

INITIAL ELECTRICITY __------ - -----_

COMMERCIAL OPERATION ___-- _- -___----

1.16 - 9

_ _ . _ . . _ . . . . . . . . . . _ _ _ _ _ . . . . _ . _ _ . . _ . _ . _ . . . . _ . . . . . ._. . _ . .__ . m. _

.. ]

l- -

! ENCLOSURE 2 i BRUNSWICK STEAM ELECTRIC PLANT, UNITS NOS.1 AND 2

. DOCKET NOS. 50-325 & 50-324'  !

LICENSE NOS. DPR-71 & DPR-62 j i UNIT SHUTDOWN AND POWER REDUCTION ,

l REPORT - OCTOBER 1995 I

l l

l I .

i 1

i i

l

\ .~

1 i

E1-3

DOCKET NO. 050-0325 '

UNIT NAME Brunswick I DATE Novemter 1995 COMPLETED BY f rances Harrison TELEPHONE 910-457-2/56 UNIT SHLITDOWNS AND POWER REDUCTIONS REPORT MONTH October 1995 METHOD OF LICENSEE DURATION SHUTTING DOWN EVENT SYSTEM CODE COMPONENT CAUSE & CORRECTIVE ACTION TO NO. DATE TYPE (1) (HOURS) REASON (2) REACTOR (3) REPORT NO. (4) CODE (5) PREVENT RECURRENCE 95-044 950930 F 61.35 A 3 1-95-018 HH PUMPXX Rx Scram due to low vessel level caused by condensate system transient. The transient was a result of loss of condensate pump suction pressure caused by excessive air being admitted to the suction header of the condensate pump when a conductivity cell was being replaced during a schedule power reduction.95-046 95-1004 F 00 A 5 N/A RB CONROD Reduced power to 601 for Rod Improvement.

1: Tym 2: Reason 3: Method 4: Systam Code: 5. Componen+ Code F - Forced A- Equipment Failure 1- Manual Instructions for Instructions for S - Scheduled (explain) 2- Manual Scram preparation of data entry preparation of data B- Maintenance or test 3- Automatic scram sheets for Licensee Event entry sheets for LER C- Refueling 4- Continuations Report (LER) file from file from IEEE D- Regulatory 5- Load reductions IEEE Standard 805-1983. Standard 803A-1983.

restriction 6- Other per NUREG-1022. per NUREG-1022.

E- Operator Training & Section VI. Item 13.b Section VI Item 13.c License Examination F- Administrative G- Operational error (explain)

H- Other (explain)

+ .

DOCKET NO. 050-0324 '

UNIT NAME Brunswick 11 DATE Novemter 1995 COMPLETED BY Frances Harrison TELEPHONE 910-457-2756 -

UNIT SHUTlXMNS AND POWER REDUCTIONS REPORT K) NTH October 1995 METH00 0F LICENSEE DURATION SHUTTING DOWN EVENT SYSTEM CODE COMPONENT CAUSE & CORRECTIVE ACTION TO NO. DATE TYPE (1) (HOURS) REASON (2) REACTOR (3) REPORT NO. (4) CODE (5) PREVENT RECURRENCE <

95-052 950827 5 In H 5 N/A RC ZZ Core Coastdown.

prooress95-055 951006 5 00 B 5 N/A AD K) Reduced power to 25% for drywell entry to add oil to reactor recirculation pump.

95-0 % 951'J10 5 00 B 5 N/A RB CONROD Reduced power to 60% for rod improvement.

1: Tyre 2: Reason 3: Method 4: System Code. 5. Comoonent Coce F - Forced A- Equipment Failure 1- Manual Instructions for Instructions for 5 Scheduled (explain) 2- Manual Scram preparation of data entry preparation of data 3- Maintenance or test 3- Automatic scram sheets for Licensee Event entry sheets for LER C- Refueling 4- Continuations Report (LER) file from file from IEEE D- Regulatory 5- Load reductions IEEE Standard 805-1983. Standard 803A-1983.

restriction 6- Other per NUREG-1022. per NUREG-1022.

E- Operator Training & Section VI. Item 13.b Section VI. Item 13.c License Examination F- Administrative G- Operational error (explain)

H- Other (explain)

.. i

,+**.

I l

ENCLOSURE 3 i BRUNSWICK STEAM ELECTRIC PLANT, UNITS 1 AND 2 l NRC DOCKET NOS. 50-325 & 50-324 l OPERATING LICENSE NOS. DPR-71 & DPR-62 '

LIST OF REGULATORY COMMITMENTS  !

The following table identifies those actions committed to by Carolina Power &

Light Company in this document. Any other actions discussed in the submittal l represent intended or planned actions by Carolina Power & Light Company. They l are described to the NRC for the NRC's information and are not regulatory  !

commitments. Please notify the Manager - Regulatory Affairs at the Brunswick i Nuclear Plant of any questions regarding this document or any associated ,

regulatory commitments. l Commitment Committed date or  ;

outage

1. None j I

I E2-1 j