BSEP-94-0103, Special Rept 1-SR-94-002:on 940226,fire Barrier Penetration Between EDG Bldg & Diesel Fuel Oil Day Storage Tank Room Opened.Fire Watch Stationed Prior to Opening Penetration & Remained in Place Until Penetration Fire Seal Operable

From kanterella
(Redirected from ML20064L038)
Jump to navigation Jump to search
Special Rept 1-SR-94-002:on 940226,fire Barrier Penetration Between EDG Bldg & Diesel Fuel Oil Day Storage Tank Room Opened.Fire Watch Stationed Prior to Opening Penetration & Remained in Place Until Penetration Fire Seal Operable
ML20064L038
Person / Time
Site: Brunswick  Duke energy icon.png
Issue date: 03/18/1994
From: Cowan J
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
1-SR-94-002, 1-SR-94-2, BSEP-94-0103, BSEP-94-103, NUDOCS 9403240090
Download: ML20064L038 (1)


Text

I j

l'

, turm.cfrMA10rABNamL*irtsrma

, Carohna 1%wer & Light Company nra m atammmeatwas Brunswick Nuclear Plant P. O. Box 10429 ,

Southport, N.C. 28461-0429 l MAR I 81994 FILE: B09-13510C t SERIAL: BSEP-94-0103 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555 BRUNSWICK ST3AM ELECTRIC PLANT UNIT 1 AND 2 [

DOCKET LO. 50-325 AND 50-324 LICENSE UO. DPR-71 AND DPR-62 SPECIAL REPORT PER TECHNICAL SPECIFICATION 3.7.8 AND PURSUANT TO TECH?QCAL SPECIFICATION 6.9.2 (1-SR-94-002)

Gent 1emeni l The following summarizes fire protection Limiting Conditions for Operation (LCO)

A2-94-F0093:

On February 26, 1994, a new fire barrier penetration between the Emergency Diesel Generator (EDO) Building and the #4 Diesel Fuel Oil 4 Day Storage Tank Room was opened. A fire watch had been stationed prior to opening the penetration and  ;

remained in place until the penetration fire seal was declared operable. The penetration (DG-1-142) was opened to support the installation of a 12"'. Service 4 Water pipe by Plant Modification 91-071 This was part of the initial mobilization of the EDG - Service Water piping' replacement project -that will ,

continue throughout the upcoming Unit 2 Refueling Outage. During the removal of ,

the forms used in applying the grout seal a void was identified. This resulted in the seal restoration being delayed beyond the 7 day Technical Specification' time limit. The seal was regrouted and declared operable on March 7, 1994.

l Very truly yours,

,Ak W. - - '

J. Cowan, Director of Site Operations (Acting)

Brunswick Nuclear Plant cca Mr. S. D. Ebneter Mr. P. D. Milano BSEP NRC Resident Office ,

9403240090 9403fB^~'N; PDR

' ADOCK 05000324 u

ap l D PDR  !  ;