Control & Block Diagram.Sheet 14 2D
ML17312A042
Person / Time
Site: Saint Lucie NextEra Energy icon.png
Issue date: 01/04/1995
From:
EBASCO SERVICES, INC.
To:
Shared Package
ML17312A008 List:
References
Download: ML17312A042 (1)


Text

CCW PUMP 1C CS-209 106 CONT SW SEQUENCE OF EVENTS REC.AFTER START AFTER STOP STOP PULL TO LOCK OR OR N 0 COMPONENT CLG WATER PUMP 1C RUN STOP R 106 LOCAL PB STATION G 106 STOP OR SWITCHGEAR 1AB BUS UNDERVOLTAGE ELECTRICAL FAULT CONTROL RM ISOL SW CUB IQI2 SWGR 1AB NORMAL ISOLATE H 0 OR A 106(S-33)106 (S-53)CONT SW-SWGR CLOSE TRIP CONTAINMENT ISOLATION SIAS CHNL A ON CONTAINMENT ISOLATION SIAS CHNL B ON BUS TIE 1A3 TO 1AB CL DIESEL GEN 1A ON OR 6 SEC 4-2 OR OR OR NOTE'.FOR ELECTRICAL FAULT AND PERMISSIVE CIRCUITS SEE CWD'S REFERENCE DYfGS: CONTROL WIRING DIAGRAM 8770-B-327 SH.209 FLOW DIAGRAM 8770-G-083 INSTRUMENT UST 8770-B-270 3 I I<If NUCLF>R RECORDENI'gag g)ASTROL CEN'US TIE 1B3 TO 1AB CL DIESEL GEN 1B ON CCWP 1C MTR INBD BRG TIS-1 4-1 C2 TEMP'HIGH 6 SEC 106 OR A (S 43)OR 4-2 COMPONENT COOLING V/ATER PUMP 1 C R4-REVISED Bc REDRAWN PER PCM 182-193 FOR REFERENCE ONLY NUCLEAR SAFETY RELATED CCWP 1C MTR OUTBD BRG TIS-14-1C I TEMP HIGH REV DATE BY CHK APPROVED DIV: IAC DR: AZ CH: CA DATE;DEC 14, 1971 APPROVAL R.C.HAEKLER FLORIDA POWER 8c LIGHT CO.ST.LUCIE PLANT-UNIT No.1 CONTROL 8c BLOCK DIAGRAM 8770-8-276 SHEET 14.2D USE00216.DWG