NRR-PMDAPEm Resource From: Lyon, Fred Sent: Friday, December 20, 2013 11:09 AM To: 'Elwood, Thomas B' (TElwood@ameren.com)

Cc: Maglio, Scott A (SMaglio@ameren.com)

Subject:

Question for TS 3.7.9 UHS LAR (TAC No. MF0378)

Staff has a question on the safety status of the setpoints for cooling tower fan speed control and cooling tower bypass valve automatic closure. Youve credited manual operator actions for these functions. If it is determined that these items are not safety-related, then we have less review to do. If they are safety-related, we need the calculations for each setpoint; a statement of whether each is, or is not, a limiting safety system setting (LSSS), and a TSTF-493 statement.

Thanks, Fred P.S. This is one that fell behind due to its priority versus Fukushima-related activities 1

Hearing Identifier: NRR_PMDA Email Number: 965 Mail Envelope Properties (Fred.Lyon@nrc.gov20131220110800)

Subject:

Question for TS 3.7.9 UHS LAR (TAC No. MF0378)

Sent Date: 12/20/2013 11:08:30 AM Received Date: 12/20/2013 11:08:00 AM From: Lyon, Fred Created By: Fred.Lyon@nrc.gov Recipients:

"Maglio, Scott A (SMaglio@ameren.com)" <SMaglio@ameren.com>

Tracking Status: None

"'Elwood, Thomas B' (TElwood@ameren.com)" <TElwood@ameren.com>

Tracking Status: None Post Office:

Files Size Date & Time MESSAGE 607 12/20/2013 11:08:00 AM Options Priority: Standard Return Notification: No Reply Requested: No Sensitivity: Normal Expiration Date:

Recipients Received: