ENS 51421
From kanterella
Jump to navigation
Jump to search
ENS Event | |
---|---|
02:00 Sep 24, 2015 | |
Title | High Pressure Coolant Injection Inoperable Due to Mgu Failure |
Event Description | During surveillance testing of the U2 HPCI [High Pressure Coolant Injection] system, the HPCI motor gear unit [MGU] was positioned from 100 percent to 75 percent demand to satisfy operability testing. The motor gear unit did not respond as system demand was returned to 100 percent. This indicated a failure of the MGU which requires declaration of inoperability of the HPCI System. This is a 14 day LCO. HPCI is a single train system and reportable under SAF 1.8 'Event or condition that could have prevented fulfillment of a safety function.'
The licensee will be notifying the NRC Resident Inspector. |
Where | |
---|---|
Dresden Illinois (NRC Region 3) | |
Reporting | |
10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
Time - Person (Reporting Time:+3.87 h0.161 days <br />0.023 weeks <br />0.0053 months <br />) | |
Opened: | Jeff Simpson 05:52 Sep 24, 2015 |
NRC Officer: | Jeff Rotton |
Last Updated: | Sep 24, 2015 |
51421 - NRC Website | |
Unit 2 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |