ENS 49919
From kanterella
Jump to navigation
Jump to search
ENS Event | |
---|---|
16:02 Mar 15, 2014 | |
Title | Momentary Loss of Shutdown Cooling Due to a Loss of Offsite Power |
Event Description | [Unit] 1 experienced a loss of offsite power (LOOP). [Unit] 1 station aux transformers (SATs) tripped. 1A and 1B emergency diesel generators (EDGs) started and properly restored power to ESF [engineered safety feature] bus 141 and 142. Safe shutdown loads (1A/B SX [essential service water] pumps and 1A/B CC [component cooling] pumps) properly started when signaled by the EDG sequencers. The 1A residual heat removal pump was manually restarted at 1105 [CDT] to restore shutdown cooling. There was no impact to RCS temperature. Additionally, a containment isolation signal was actuated when containment radiation monitors which are powered from the ESF buses briefly lost power until restored by the EDGs. All related equipment realigned as expected except for the 0A VC [control room] chiller that didn't start when required on the EDG sequencer. The cause of the LOOP and the 0A VC chiller issue is under investigation. Fuel moves were in progress and stopped safely. All fuel bundles are in a safe location.
Unit 2 was not affected and remains in mode 1. The licensee has notified the NRC Resident Inspector. |
Where | |
---|---|
Byron Illinois (NRC Region 3) | |
Reporting | |
10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
Time - Person (Reporting Time:+-1.1 h-0.0458 days <br />-0.00655 weeks <br />-0.00151 months <br />) | |
Opened: | Blaine Peters 14:56 Mar 15, 2014 |
NRC Officer: | Dong Park |
Last Updated: | Mar 15, 2014 |
49919 - NRC Website | |
WEEKMONTHYEARENS 540202019-04-22T18:24:00022 April 2019 18:24:00
[Table view]10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Initiation of the Auxiliary Feedwater System in Response to a Loss of Feedwater ENS 534912018-07-06T05:00:0006 July 2018 05:00:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Transformer Failure Causes Loss of Offsite Power to Unit 2 ENS 522952016-10-12T18:38:00012 October 2016 18:38:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Spurious Feedwater Isolation ENS 508592015-03-03T17:01:0003 March 2015 17:01:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Main Power Transformer Bushing Short ENS 499192014-03-15T16:02:00015 March 2014 16:02:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Momentary Loss of Shutdown Cooling Due to a Loss of Offsite Power ENS 488382013-03-21T00:51:00021 March 2013 00:51:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Loss of Generator Stator Cooling Water ENS 477082012-02-28T23:31:00028 February 2012 23:31:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Due to Loss of Offsite Power ENS 476442012-02-06T23:19:0006 February 2012 23:19:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Rps Actuation Due to Turbine Trip ENS 476242012-01-30T16:01:00030 January 2012 16:01:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Unusual Event Due to Loss of Offsite Power Greater than 15 Minutes ENS 458672010-04-19T10:03:00019 April 2010 10:03:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Rps and Afw Actuation Signals While Shutdown in Mode 4 ENS 420632005-10-19T05:57:00019 October 2005 05:57:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Low 2 Steam Generator Water Level 2019-04-22T18:24:00 | |