ENS 48823
From kanterella
Jump to navigation
Jump to search
ENS Event | |
---|---|
23:00 Mar 14, 2013 | |
Title | Partial Loss of Offsite Communications |
Event Description | On 03/14/2013 at 1800 CDT, Browns Ferry Nuclear Plant experienced a partial loss of offsite communication to include the Emergency Notification System to the NRC and normal phone communication to offsite. This loss of communications appears to be the result of an unplanned degraded voltage condition on the 48VDC Telephone Battery supplying power to the communications network. Main Control Room indications and assessment capability were not affected. The Nextel cellular phone system, the satellite phones in the Control Rooms, and the Health Physics Radio Network were available onsite to communicate offsite. The plant radio system was also unaffected. Required corrective maintenance is being evaluated. Communication capability is being periodically restored during maintenance troubleshooting, but has not yet been permanently corrected. Operation of Unit 1, Unit 2, and Unit 3 was not affected by the event.
At 2145 CDT, the NRC Operations Center was notified of alternate contact numbers for [Browns Ferry] until the Telephone Battery is fully restored. The NRC Senior Resident Inspector has been notified. This event is reportable under 10CFR50.72(b)(3)(xiii).
A spare battery charger was aligned to the 48 VDC Telephone Battery and offsite communications was restored. The licensee notified the NRC Resident Inspector. Notified the R2DO (O'Donohue). |
Where | |
---|---|
Browns Ferry Alabama (NRC Region 2) | |
Reporting | |
10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness | |
Time - Person (Reporting Time:+2.8 h0.117 days <br />0.0167 weeks <br />0.00384 months <br />) | |
Opened: | Tim Taylor 01:48 Mar 15, 2013 |
NRC Officer: | Vince Klco |
Last Updated: | Mar 15, 2013 |
48823 - NRC Website | |
Unit 1 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
Unit 2 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (23 %) |
After | Power Operation (23 %) |
Unit 3 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
WEEKMONTHYEARENS 543822019-11-12T12:00:00012 November 2019 12:00:00
[Table view]10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Emergency Operations Facility Out of Service ENS 542782019-09-13T09:27:00013 September 2019 09:27:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness En Revision Imported Date 9/17/2019 ENS 520042016-06-13T22:33:00013 June 2016 22:33:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Alert Sirens Failed to Rotate ENS 494552013-10-19T22:05:00019 October 2013 22:05:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Partial Loss of Offsite Communications Due to a Blown Fuse ENS 488232013-03-14T23:00:00014 March 2013 23:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Partial Loss of Offsite Communications ENS 483272012-09-20T17:40:00020 September 2012 17:40:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Emergency Assessment Capability Due to Inoperable Seismic Monitoring Instrumentation ENS 471242011-08-04T13:35:0004 August 2011 13:35:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Power to Emergency Sirens Due to Weather ENS 469862011-06-25T21:15:00025 June 2011 21:15:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Meteorological Monitoring Instrumentation Inoperable Due to Loss of Power ENS 468792011-05-24T14:18:00024 May 2011 14:18:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Power to Thirty-Two Emergency Sirens ENS 467932011-04-27T22:01:00027 April 2011 22:01:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Notification of Unusual Event Due to Loss of Offsite Power ENS 444712008-09-07T22:20:0007 September 2008 22:20:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Partial Loss of Offsite Communication Capability Caused by an Unplanned Power Outage ENS 442322008-05-21T20:15:00021 May 2008 20:15:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Control Room Phone Communications 2019-09-13T09:27:00 | |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_48823&oldid=423248"