ENS 47807
From kanterella
Jump to navigation
Jump to search
ENS Event | |
---|---|
22:35 Apr 4, 2012 | |
Title | Inoperable Accident Mitigation Equipment |
Event Description | On 4/4/2012 at 1517 EDT, the 'A' Emergency Diesel Generator (EDG) was declared inoperable for performance of a maintenance surveillance. At 1835 EDT on 4/4/2012 the 'B' Control Structure Chiller was declared inoperable due to an unrelated problem. [With] the 'B' Control Structure Chiller inoperable coincident with the 'A' EDG inoperable, the 'A' Control Structure Chiller would not be available to perform its design function on a loss of offsite power. This is a condition that, at the time of discovery, could have prevented fulfillment of a Safety Function and is reportable under 50.73(a)(2)(v) as an 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> notification. Note that Technical Specifications allows four hours to correct the condition before further actions are required, i.e. declare the features ('A' Control Structure Chiller) supported by the inoperable diesel inoperable. The 'A' EDG was restored to operable at 2200 which restored safety function capability for the 'A' Control Structure Chiller.
The licensee notified the NRC Resident Inspector. |
Where | |
---|---|
Susquehanna Pennsylvania (NRC Region 1) | |
Reporting | |
10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
LER: | 05000387/LER-2012-002 |
Time - Person (Reporting Time:+0.4 h0.0167 days <br />0.00238 weeks <br />5.4792e-4 months <br />) | |
Opened: | Ron Fry 22:59 Apr 4, 2012 |
NRC Officer: | Pete Snyder |
Last Updated: | Apr 4, 2012 |
47807 - NRC Website | |
Unit 2 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |