ENS 45162
ENS Event | |
---|---|
04:49 Jun 25, 2009 | |
Title | Discovery of an After-The-Fact Alert Due to Catastrophic Failure of Ccpd |
Event Description | A transitory ALERT [condition was determined to have existed] based on Emergency Action Level 7.D.2 - 'Onsite Explosion Affecting Plant Operation'. At time 0049 on 06/25/09 a catastrophic failure-explosion of the Constant Current Potential Device (CCPD) on 'J' Bus near Air Circuit Breaker (ACB) 34563 resulted in a loss of switchyard 345 KV Bus 'J'. This event de-energized Startup Transformer 01 which is a tie from offsite sources to the Unit 13.8 KV Busses. The unit entered [Technical Specification] LCO 3.8.1, Condition A [due to the loss of one offsite power source]. The Unit remains stable and in operation at 100% RTP [reactor thermal power]. A problem solving decision making team is working on [the] troubleshooting/repair/restoration activities. This event did not impact any plant safety systems or result in any release of radioactive material.
Failure of the CCPD caused automatic opening of the breakers on both sides of the 'J' bus which was configured as part of a switchyard ring bus at the time of the event. This resulted in the loss of one of the offsite power ties. However, startup Transformer 02 is still energized from offsite power and remains available for plant operations. Other than the de-energized startup transformer, onsite electrical configurations are normal including availability of emergency diesel generators. The licensee is in a 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> LCO per Tech Spec 3.8.1, Condition A, to restore the lost offsite power source. The licensee is inspecting the switchyard for collateral damage to other equipment from the failure of the CCPD. The licensee believes the CCPD failure is likely a result of equipment failure and not the result of any equipment tampering. The licensee stated that initially, the severity of the CCPD failure was not recognized because of the night time conditions and minimal lighting in the area. After daylight examination of the location of the event, it was determined that the failure of the CCPD should have been classified as an explosion affecting plant operation under EAL 7.D.2. Consequently, the licensee made the after-the-fact declaration. Licensee has notified the NRC Resident Inspector, and will be notifying State and local authorities. |
Where | |
---|---|
Davis Besse Ohio (NRC Region 3) | |
Reporting | |
Emergency class: | Alert |
10 CFR 50.72(a) (1) (i), Emergency Class Declaration | |
Time - Person (Reporting Time:+6.92 h0.288 days <br />0.0412 weeks <br />0.00948 months <br />) | |
Opened: | Eric Horvath 11:44 Jun 25, 2009 |
NRC Officer: | Bill Huffman |
Last Updated: | Jun 25, 2009 |
45162 - NRC Website | |
Unit 1 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
WEEKMONTHYEARENS 514832015-10-21T00:24:00021 October 2015 00:24:00
[Table view]10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Due to Suspicious Vehicle in Owner Controlled Area ENS 510612015-05-09T22:55:0009 May 2015 22:55:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to Steam Leak in the Turbine Building ENS 502632014-07-08T13:25:0008 July 2014 13:25:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Due to Smoke Alarm Inside Containment ENS 474432011-11-16T07:22:00016 November 2011 07:22:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Alert Due to Fire in Electrical Bus Affecting Safety Related Equipment ENS 465512011-01-19T07:32:00019 January 2011 07:32:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to a Fire and Explosions in the Protected Area ENS 451622009-06-25T04:49:00025 June 2009 04:49:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Discovery of an After-The-Fact Alert Due to Catastrophic Failure of Ccpd ENS 400702003-08-14T20:10:00014 August 2003 20:10:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to a Loss of Offsite Power. 2015-05-09T22:55:00 | |