ENS 41663
From kanterella
Jump to navigation
Jump to search
ENS Event | |
---|---|
17:10 May 3, 2005 | |
Title | Appendix R Fire Scenario Involving Multiple High Impedance Faults |
Event Description | TMI Issue Report # 329440 identifies an issue associated with a previously unidentified/unanalyzed Appendix R fire scenario involving multiple high impedance faults. An engineering evaluation has determined that certain safety related power circuits are not protected against multiple high impedance faults, which in combination with a fire in the 305' elevation of the Control Building, could cause a loss of safe shutdown functions from the control room and the remote shutdown panel. An hourly fire-watch has been established in the affected fire zone in the 305' elevation of the Control Building as an interim compensatory measure.
The NRC Resident Inspector will be notified. |
Where | |
---|---|
Three Mile Island Pennsylvania (NRC Region 1) | |
Reporting | |
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
Time - Person (Reporting Time:+-2.63 h-0.11 days <br />-0.0157 weeks <br />-0.0036 months <br />) | |
Opened: | Adam Miller 14:32 May 3, 2005 |
NRC Officer: | Chauncey Gould |
Last Updated: | May 3, 2005 |
41663 - NRC Website | |
Unit 1 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
WEEKMONTHYEARENS 531062017-12-06T14:58:0006 December 2017 14:58:00
[Table view]10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Diesel Fuel Oil Tank Supply Non-Conforming with Licensing Basis for Tornado Generated Missiles ENS 501082014-05-12T14:20:00012 May 2014 14:20:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Postulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment ENS 500592014-04-25T15:13:00025 April 2014 15:13:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Postulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment ENS 472942011-09-26T19:00:00026 September 2011 19:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition New River Hydraulic Analysis Raises Maximum Flood Level ENS 431392007-02-02T18:50:0002 February 2007 18:50:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Low Pressure Injection (Lpi) Net Positive Suction Head Flow Requirements Not Met for Certain Accident Sequences ENS 425272006-04-25T17:30:00025 April 2006 17:30:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition - Control Logic Error ENS 416632005-05-03T17:10:0003 May 2005 17:10:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Appendix R Fire Scenario Involving Multiple High Impedance Faults ENS 414442005-02-16T01:55:00016 February 2005 01:55:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Possible Failure to Meet Design Basis Requirements of Positive Pressure in the Control Tower Envelope Following a Design Basis Accident. 2017-12-06T14:58:00 | |