10 CFR 36.27, Fire Protection

From kanterella
(Redirected from 10 CFR 36.27)
Jump to navigation Jump to search

Fire protection

a

(a) The radiation room at a panoramic irradiator must have heat and smoke detectors. The detectors must activate an audible alarm. The alarm must be capable of alerting a person who is prepared to summon assistance promptly. The sources must automatically become fully shielded if a fire is detected.

b

(b) The radiation room at a panoramic irradiator must be equipped with a fire extinguishing system capable of extinguishing a fire without the entry of personnel into the room. The system for the radiation room must have a shut-off valve to control flooding into unrestricted areas.


External Links

NRC website 10 CFR 36.27