Title | InadequateEvaluation of Spurious Valve Operation |
Description | The team identified a non-cited violation of License Condition 2.C.(5) for failure to implement and maintain in effect all provisions of the approved fire protection program. Specifically, the licensee failed to adequately evaluate the potential impacts on post-fire safe shutdown of two motor operated valves spuriously closing due to fire damage.The failure to adequately evaluate the impact of pressure operated relief valve block valves spuriously closing on post-fire safe shutdown was a performance deficiency. The performance deficiency was more than minor because it was associated with the protection against external events (fire) attribute of the Mitigating Systems cornerstone and it adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Because the finding affected the ability to reach and maintain safe shutdown conditions in case of a fire that led to control room evacuation and because the Phase 2 methodology of Inspection Manual Chapter 0609, Appendix F, was not appropriate for this finding, a senior reactor analyst performed a Phase 3 evaluation to determine the risk significance. The analyst determined this finding was of very low risk significance (Green). There is no cross-cutting aspect associated with this finding since the performance deficiency is not reflective of present performance (i.e., the performance deficiency occurred more than 3 years ago). |
Site: | Wolf Creek |
---|---|
Report | IR 05000482/2017008 Section 1R05 |
Date counted | Dec 31, 2017 (2017Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | J Mateychick B Correll G Pick S Makor G Werner |
Violation of: | License Condition |
INPO aspect | |
' | |
Finding - Wolf Creek - IR 05000482/2017008 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Wolf Creek) @ 2017Q4
Self-Identified List (Wolf Creek)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||