05000461/LER-2014-001

From kanterella
Jump to navigation Jump to search
LER-2014-001, Premature Failure Of Air Supply Solenoid Results In Isolation Of Fuel Building Ventilation System And Loss Of Secondary Containment Differential Pressure
Clinton Power Station, Unit 1
Event date: 01-22-2014
Report date: 03-20-2014
Reporting criterion: 10 CFR 50.73(a)(2)(v)(C), Loss of Safety Function - Release of Radioactive Material
Initial Reporting
ENS 49758 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material
4612014001R00 - NRC Website

12. LICENSEE CONTACT FOR THIS LER

LICENSEE CONTACT

Jeffrey E. Cunningham, Regulatory Assurance Manager TELEPHONE NUMBER (Include Area Code) (217) 937-3160 == 13. COMPLETE ONE LINE FOR EACH COMPONENT FAILURE DESCRIBED IN THIS REPORT ==

CAUSE SYSTEM COMPONENT MANU- FACTURER == REPORTABLE ==

TO EPIX CAUSE SYSTEM COMPONENT

MANU- == FACTURER ==

REPORTABLE

TO EPIX

X VG SOL A499 Y == 14. SUPPLEMENTAL REPORT EXPECTED ==

q YES (If yes, complete 15. EXPECTED SUBMISSION DATE) NO == 15. EXPECTED ==

SUBMISSION

DATE

MONTH DAY YEAR

On 1/22/14, the plant was at 97 percent reactor power and operators were placing Main Control Room Ventilation (VC) system Train B in service. While starting the VC Train B supply fan, operators received unexpected alarms caused by the trip of the in-service Fuel Building Ventilation system (VF) supply fan with the Fuel Building and Secondary Containment (SC) differential pressures (d/p) no longer being maintained negative, as required. In response to the loss of SC d/p, operators entered Emergency Operating Procedure (EOP) - 8, SC Control, declared SC inoperable, and entered the Technical Specification Actions. Troubleshooting and circuit analysis identified that the power source for VF inboard exhaust isolation damper also includes VC system supply air B zone isolation dampers and return air B dampers. During start of the VC system B train, the VC system dampers cycled and the VF system inboard exhaust isolation damper closed. The cause of this event was a prematurely degraded VF exhaust isolation damper air supply solenoid that responded to a minor perturbation of supply voltage or surge of current on the bus by dropping out during the VC Train B startup resulting in isolation of the VF system inboard exhaust isolation damper and a VF system trip.

The prematurely degraded solenoid has been replaced. The VF system damper failed closed, fulfilling its safety function.

Premature Failure Of Air Supply Solenoid Results In Isolation Of Fuel Building Ventilation System And Loss Of Secondary Containment Differential Pressure == A. Plant Operating Conditions Before the Event ==

Unit: 1 Event Date: 1/22/14 Mode: 1 Mode Name: Power Operation == B. DESCRIPTION OF EVENT ==

Event Time: 19:56 CST Reactor Power: 97 percent On 1/22/14, the plant was in Mode 1 at 97 percent reactor power and operators in the Main Control Room (MCR) were in the process of placing Train B of the Main Control Room Ventilation (VC) system [VI] into service. At 1956 hours, while starting the VC system Train B supply fan [FAN] OVCO3CB, operators received unexpected alarms [ALM] for trouble in the Fuel Building Ventilation (VF) system [VG] and high Fuel Building differential pressure (d/p).

Operators discovered the causes of the alarms were the trip of the in-service VF system supply fan 1VFO3CA and the Fuel Building [ND] and Secondary Containment differential pressures no longer being maintained negative, as required. Fuel Building d/p was plus 0.5 inches water column (inWC) and Secondary Containment d/p had risen to 0.0 inWC. Secondary Containment d/p is required to be less than or equal to a minus 0.25 inWC in accordance with Technical Specification Surveillance Requirement 3.6.4.1.1.

In response to the loss of secondary containment d/p, operators entered Emergency Operating Procedure (EOP) - 8, Secondary Containment Control. After several seconds the VF system exhaust fan (1VFO4CA) tripped and VF system exhaust fan 1VFO4CB automatically started and ran for several seconds before also tripping. Operators declared Secondary Containment inoperable due to secondary containment differential pressure being greater than minus 0.25 inWC, and entered Technical Specification (TS) 3.6.4.1, Action A.1 that requires secondary containment to be restored to an operable status within 4 hours.

At 1958 hours, operators in the MCR noticed VF system inboard exhaust isolation damper [DMP] 1VFO7Y change position from intermediate to open. Based on a review of computer point information, operators determined that at about 1956 hours isolation damper 1VFO7Y had travelled to the closed position. With the isolation damper closed (no flow path) the VF supply fan tripped as designed on either low flow or high Fuel Building d/p (greater than 0.0 inWC). The VF system exhaust fan is also designed to trip on low flow.

Therefore, the fan trips and subsequent loss of Secondary Containment negative d/p were expected system responses when the VF system inboard exhaust isolation damper 1VFO7Y closed.

At 2003 hours Fuel Building ventilation was restored, the inboard exhaust isolation damper was re-opened, the VF system was restarted, and Secondary Containment d/p was restored to normal. With the Fuel Building d/p and Secondary Containment d/p restored to normal values, operators exited the TS required action. At 2013 hours, operators exited EOP-8.

Troubleshooting of this event identified that VF system inboard exhaust isolation damper 1VFO7Y unexpectedly closed at almost exactly the same time as the start of VC system Train B supply fan OVCO3CB. Circuit analysis Clinton Power Station, Unit 1 05000461 identified that the power source for VF system damper 1VFO7Y also provides power to the VC system supply air B zone isolation dampers and return air B dampers. This review confirmed that the VF system inboard exhaust isolation damper 1VFO7Y closed during the cycling of the VC dampers during the start of the VC system B train. The trouble shooting team concluded that during the VC Train B startup, the air supply solenoid [SOL] on the VF system inboard exhaust isolation damper 1VFO7Y responded to a minor perturbation of the supply voltage or a surge of current on the bus by repositioning (dropping out) because the solenoid was weak or degraded, resulting in isolation of the VF system inboard exhaust isolation damper. The VF system inboard exhaust isolation damper failed closed, thus fulfilling its safety function.

This event is reportable under the provisions of 10 CFR 50.73(a)(2)(v)(C) as an event that could have prevented fulfillment of the Secondary Containment safety function needed to control the release of radioactive material. Event Notification Number 49758 was made to the NRC on 01/22/2014 at 2236 hours Central Standard Time.

This event was entered into the Clinton Power Station corrective action program under Issue Report 1611216.

C. CAUSE OF EVENT

The apparent cause of this event is the VF system inboard exhaust isolation damper 1VFO7Y air supply solenoid was prematurely degraded and caused the damper to isolate the VF system flow-path during the VC Train B startup, resulting in a VF system trip. This solenoid is currently replaced on an 8-year Preventive Maintenance frequency and was most recently replaced on 11/25/13. The cause of the premature failure of the solenoid is being evaluated by an independent laboratory.

D. SAFETY CONSEQUENCES

This event had no actual consequences. Operators entered EOP-8 for Secondary Containment d/p greater than minus 0.25 inWC and entered TS 3.6.4.1, Action A.1 to restore secondary containment to an operable status within 4 hours. Secondary Containment d/p was greater than minus 0.25 inWC for about 7 minutes. The VF system is the non-safety ventilation system which is normally in service to maintain secondary containment dip. The Standby Gas Treatment system (VG) [BH] is the safety-related system which is credited to perform this function in an accident condition. The VG system was fully operable at the time of the event and capable of performing the required safety function. The VG system was subsequently placed in service and demonstrated the ability to perform the safety function. Therefore, the ability of the Station to maintain secondary containment in an accident scenario was never jeopardized or challenged by the VF system exhaust isolation damper repositioning. An Engineering evaluation has concluded that the safety function of the VF system exhaust isolation damper is to close during the accident condition to ensure the Secondary Containment safety function can be met. Since the VF system exhaust isolation damper failed closed during this event, the damper safety function was met, and therefore this event is not being counted as a Safety System Functional Failure for the NRC performance indicator.

E. CORRECTIVE ACTIONS

The prematurely degraded solenoid has been replaced.

F. PREVIOUS OCCURRENCES

A review for previous occurrences did not identify a similar event at Clinton Power Station. The station reviewed Licensee Event Report 1987-009 that reported a manual actuation of the VG system that occurred due to a trip of the VF system exhaust fan resulting in Secondary Containment d/p greater than minus 0.25 inWC. The cause of the event was a random failure of the solenoid valve on the VF system supply outboard isolation damper. Engineering concluded that the solenoid valve failure mechanism described in LER 1987- 009 was different from the event described in this report (LER 2014-001).

G. COMPONENT FAILURE DATA

Component Description: Solenoid Valve; Type: 3 way; Size 3/8 inch; Material: Brass; Orfice: 9/32 inch Manufacturer: ASCO-Automatic Switch Co Model: NP8321A6E