05000373/FIN-2016007-03
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Inadequate Procedures for Containment Debris Management |
Description | The team identified a finding of very-low safety significance (Green) and an associated NCV of 10 CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, for the failure to establish procedures that were appropriate to manage containment debris consistent with the emergency core cooling system strainer debris loading design basis and supporting design information. Specifically, the procedures did not contain instructions for evaluating containment debris sources consistent with the associated analyses and other design documents. The licensee captured the team concerns in their CAP as AR 02663076 and AR 02656299. The immediate corrective actions included an operability evaluation that reasonably determined all of the affected emergency core cooling system strainers remained operable. The performance deficiency was determined to be more than minor because it was associated with the procedure quality attribute of the Mitigating Systems cornerstone, and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The finding screened as of very-low safety significance (Green) because it did not result in the loss of operability or functionality of mitigating systems. Specifically, the licensee performed an operability review and reasonably determined that only a portion of the unqualified coatings would be available for transport to the strainers and this quantity was bounded by the associated design basis analysis. In addition, this review reasonably determined that sufficient analytical margin existed to accommodate the quantities of the other debris types found during recent inspections. The team did not identify a cross-cutting aspect associated with this finding because it was not confirmed to reflect current performance due to the age of the performance deficiency. Specifically, the associated procedures were established more than 3 years ago. |
Site: | LaSalle |
---|---|
Report | IR 05000373/2016007 Section 1R21 |
Date counted | Jun 30, 2016 (2016Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | A Dahbur C Edwards D Reeser J Corujo-Sandin J Leivo M Jeffers N Feliz-Adorno |
Violation of: | 10 CFR 50 Appendix B Criterion V |
INPO aspect | |
' | |
Finding - LaSalle - IR 05000373/2016007 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (LaSalle) @ 2016Q2
Self-Identified List (LaSalle)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||